Security Control Panel Assembly
Mounted in a 16 in. x 16 in. Enclosure                                                                                    Part No. 24-10613-4, Rev. C
                                                                                                                                      Issued December 2017
Installation Instructions
SPA10000-1A10, SPA1B100-1A10, SPB10000-1A10, SPC10000-1A10

                                                                  Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications                                                                        Parts Included
The 16 in. x 16 in. Security Control Panel is a pre-wired,                          •   16 in. x 16 in. (40.6 cm x 40.6 cm) enclosure, Type 1 with keyed
preassembled standard control panel and enclosure that contains an                      lock, door tamper switch, and battery support brackets
S321-IP or CK721-A network controller and/or S300-DIN-RDR2SA                        •   S321-IP or CK721-A network controller and/or RDR2S-A two-door
(also called RDR2S-A) modules. The control panel is shipped                             interface module
complete, mounted in a steel enclosure. The panel is equipped with                  •   S300-DIN-L-PS 24 VDC, 5 A power supply
the required number of 120 VAC/24 VDC power supplies. The power
supply has Uninterruptible Power Supply (UPS) capability with the
addition of factory-wired gel cell batteries (S300-BAT), which are sold
separately. These enclosures are designed specifically for security
control requirements, with battery brackets that do not need to be
removed to install the batteries, a lift-off door, a pre-wired door tamper
switch, and a lockable door with key. Space is reserved on specific
models for the addition of future components.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. Contact Global Security
Solutions Technical Support at (866) 893-0423 or (414) 524-1214, or
by email at support.globalsecuritysolutions@jci.com. End users can
contact their local branch or authorized dealer. For the nearest office,
visit http://www.johnsoncontrols.com/location-finder.                                               Figure 1: Security Control Panel Mounted in a
                                                                                                               16 in. x 16 in. Enclosure
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately.
Cable Requirements
 Description                             Recommended Cable Type1, 2                                      Maximum Segment Length
 CK721-A: RS485A, RS485B                 Listed, 22 AWG, stranded, copper, hook-up wire                  Limited to within cabinet.
 RDR2S-A: RS485+/-
 S321-IP: N/A                            Listed, 18 AWG, 3-conductor, stranded, shielded, copper         4,000 ft (1,219 m) maximum

 CK721-A: ICOM1, ICOM2                   Belden® 8442, 22 AWG, 1 twisted pair, stranded,                 500 ft (152 m)
 RDR2S-A: Door Contact                   unshielded, copper
 S321-IP: Door Contact, Input Point
 CK721-A: OUT1                           Belden 9740, 18 AWG, 1 twisted pair, stranded,                  Depends on power requirements of the device. Voltage to
 RDR2S-A: Door Strike, Shunt;            unshielded, copper                                              the device must not be reduced more than 10% over the
 S321-IP: Door Strike, Shunt                                                                             18 AWG wire, measured when energized.
 Request to Exit                         Belden 8442, 22 AWG, 1 twisted pair, stranded,                  500 ft (152 m)
 RDR2S-A and S321-IP only)               unshielded, copper
 Reader Power                            Belden 9740, 18 AWG, 1 twisted pair, stranded,                  Refer to reader manufacturer’s specification for power
 (RDR2S-A and S321-IP only)              unshielded, copper                                              requirements.
 Reader Data0/Data1                      Belden 9744, 22 AWG, 2 twisted pairs, stranded,                 500 ft (152 m). Refer to reader manufacturer’s
 (RDR2S-A and S321-IP only)              unshielded, copper                                              specification for data requirements.
 RS232 A, RS232 B                        Listed DB9 F/F AT Null Modem cable                              25 ft (7 m). Cable must remain in the same room as the
                                                                                                         CK721-A.
 Ethernet                                Listed, Category 5, 24 AWG, solid, 2 pair or 4 pair type        354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
                                                                                                         tool to be supplied by customer.

1.   All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
     strike cables, such as strike voltage greater than 42 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
     with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2.   Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.

UL 294 Performance Levels
                                         Destructive Attack             Line Security                 Endurance                  Standby Power
 SPA10000-1A10                           Level I                        Level II                      Level IV                   Level II
 SPA1B100-1A10                           Level I                        Level II                      Level IV                   Level II
 SPB10000-1A10                           Level I                        Level I                       Level IV                   Level II
 SPC10000-1A10                           Level I                        Level II                      Level IV                   Level II

                           Security Control Panel Assembly Mounted in a 16 in. x 16 in. Enclosure Installation Instructions                                        1
Mounting and Connecting the Panels                                                Technical Specifications
•    Mount the panel on a wall or other mounting surface located in a             Security Control Panel Assembly Mounted in a 16 in. x 16 in.
     restricted-access area.
                                                                                  Enclosure
•    The horizontal distance between the mounting holes is 11 in. (28
     cm); the vertical distance is 13.88 in. (35.3 cm). Mounting hole             Electrical Rating   SPA10000-1A10: 120 VAC, 1.8 A, 50/60 Hz
     diameter is 0.31 in. (0.8 cm).                                                                   SPA1B100-1A10: 120 VAC, 1.8 A, 50/60 Hz
•    Ensure the door can swing fully open.                                                            SPB10000-1A10: 120 VAC, 1.8 A, 50/60 Hz
•    Mount the panel in a location where airflow is uninhibited over the                              SPC10000-1A10: 120 VAC, 1.8 A, 50/60 Hz
     exposed surfaces.
                                                                                  Enclosure Rating    NEMA Type 1
•    Remove the back plate before securing the panel to the mounting
     surface and reinstall it when mounting is complete.                          Ambient Operating   32 to 122°F (0 to 50°C), 10 to 85% RH,
                                                                                  Condition           noncondensing
AC Power Connection
                                                                                  Dimensions (Width   16 in. x 16 in. x 6.62 in.
•    Put the AC                                            Wired at               x Height x Depth)   (40.6 cm x 40.6 cm x 16.8 cm)
     power wiring
                       To AC power
                                                           the factory
                                             BLU
                               G
     through a              N
                                                                                  Ambient Storage     -4 to 158°F (-20 to 70°C), 5 to 95% RH,
                                                   BRN
                               BLU                                                Condition           noncondensing
     knockout.              L                       N L     L = Line
                       source
                               BRN
•    Connect the AC                                         N = Neutral           Compliance          United States:
     power wiring to          TB-1           Power supply G = Ground                                  UL Listed under UL 1076 for Proprietary Burglar
     terminal block                                                                                   Alarm Units and Systems, and under UL 294 for
     TB-1.                                                                                            Access Control Systems Units;
•    Do not connect the DC power cable to the module until all wiring is                              This equipment has been tested and found to
     complete                                                                                         comply with the limits for a Class B digital device,
                                                                                                      pursuant to Part 15 of the FCC rules. These limits
                                                                                                      are designed to provide reasonable protection
                 WARNING: Risk of Electric Shock.
                                                                                                      against harmful interference in a residential

        !
                 Disconnect the power supply before making                                            installation. This equipment generates, uses and
                 electrical connections. Contact with components                                      can radiate radio frequency energy and, if not
                 carrying hazardous voltage can cause electric shock                                  installed and used in accordance with the
                                                                                                      instructions, may cause harmful interference to
                 and may result in severe personal injury or death.
                                                                                                      radio communications. However, there is no
                                                                                                      guarantee that interference will not occur in a
S300-BAT Battery Connection                                                                           particular installation. If this equipment does cause
                                                                                                      harmful interference to radio or television reception,
The optional S300-BAT                                                                                 which can be determined by turning the equipment
                                       RED
feature uses two PowerSonic,           WHT      BLK
                                                                                                      off and on, the user is encouraged to try to correct
Model PS-1270, 12 VDC, 7                                                                              the interference by one or more of the following
Ah, sealed lead acid batteries   + -       + -      + - + - GNL
                                                                     DC                               measures:
                                                               BAT
                                                                           HIGH
per power supply.                 B-1A     B-1B                      OUT   VOLT
                                                                                                      • Reorient or relocate the receiving antenna.
The batteries should be                                                    AGE

replaced every three years to                            PS-1                                         • Increase the separation between the equipment
ensure proper operation.                                                                                 and receiver.
                                                                                                      • Connect the equipment into an outlet on a circuit
The RED (+), BLK (-), and WHT cables are provided with the
                                                                                                         different from that to which the receiver is
enclosure.
                                                                                                         connected.
Replace the batteries whether or not they have been placed into use                                   • Consult the dealer or an experienced radio/TV
by an AC power failure. Observe the polarity when connecting the                                         technician for help.
batteries.                                                                                            The user is cautioned that changes and
                                                                                                      modifications made to the equipment without
Field Devices                                                                                         approval of the manufacturer could void the user's
                                                                                                      authority to operate this equipment.
For information on wiring the CK721-A controller, S321-IP controller,
or the RDR2S-A module, refer to the documentation provided with                                       Canada:
these devices.                                                                                        CAN ICES-3 (B)/NMB-3(B);
Use a separate Class 2 transformer or power supply for door strike                                    cUL Listed under ULC/ORD-C1076 Proprietary
power. Under no circumstances connect a door strike to the                                            Burglar Alarm Units and Systems
enclosure power supply.
                                                                                                      Europe:
Selection Chart                                                                                       CE Mark – Johnson Controls, declares that this
                                                                                                      product is in compliance with the EMC Directive and
    Product Code           Description                                                                the Low Voltage Directive.
    Number
    SPA10000-1A10          16 in. x 16 in. (40.6 cm x 40.6 cm) security control
                           panel with CK721-A controller and power supply
    SPA1B100-1A10          16 in. x 16 in. (40.6 cm x 40.6 cm) security control
                           panel with CK721-A controller, RDR2S-A module,
                           and power supply
    SPB10000-1A10          16 in. x 16 in. (40.6 cm x 40.6 cm) security control
                           panel with RDR2S-A module and power supply
    SPC10000-1A10          16 in. x 16 in. (40.6 cm x 40.6 cm) security control
                           panel with S321-IP controller and power supply

                                                                                                          Building Technologies & Solutions
                                                                                                  507 E. Michigan Street, Milwaukee, WI 53202
                                                            Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
                                                   All other marks herein are the marks of their respective owners. © 2017 Johnson Controls

2         Security Control Panel Assembly Mounted in a 16 in. x 16 in. Enclosure Installation Instructions

Published in U.S.A.                                                                                                       www.johnsoncontrols.com