Security Control Panel Assembly
Mounted in a 16 in. x 16 in. Enclosure Part No. 24-10613-4, Rev. C
Issued December 2017
Installation Instructions
SPA10000-1A10, SPA1B100-1A10, SPB10000-1A10, SPC10000-1A10
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications Parts Included
The 16 in. x 16 in. Security Control Panel is a pre-wired, • 16 in. x 16 in. (40.6 cm x 40.6 cm) enclosure, Type 1 with keyed
preassembled standard control panel and enclosure that contains an lock, door tamper switch, and battery support brackets
S321-IP or CK721-A network controller and/or S300-DIN-RDR2SA • S321-IP or CK721-A network controller and/or RDR2S-A two-door
(also called RDR2S-A) modules. The control panel is shipped interface module
complete, mounted in a steel enclosure. The panel is equipped with • S300-DIN-L-PS 24 VDC, 5 A power supply
the required number of 120 VAC/24 VDC power supplies. The power
supply has Uninterruptible Power Supply (UPS) capability with the
addition of factory-wired gel cell batteries (S300-BAT), which are sold
separately. These enclosures are designed specifically for security
control requirements, with battery brackets that do not need to be
removed to install the batteries, a lift-off door, a pre-wired door tamper
switch, and a lockable door with key. Space is reserved on specific
models for the addition of future components.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. Contact Global Security
Solutions Technical Support at (866) 893-0423 or (414) 524-1214, or
by email at support.globalsecuritysolutions@jci.com. End users can
contact their local branch or authorized dealer. For the nearest office,
visit http://www.johnsoncontrols.com/location-finder. Figure 1: Security Control Panel Mounted in a
16 in. x 16 in. Enclosure
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately.
Cable Requirements
Description Recommended Cable Type1, 2 Maximum Segment Length
CK721-A: RS485A, RS485B Listed, 22 AWG, stranded, copper, hook-up wire Limited to within cabinet.
RDR2S-A: RS485+/-
S321-IP: N/A Listed, 18 AWG, 3-conductor, stranded, shielded, copper 4,000 ft (1,219 m) maximum
CK721-A: ICOM1, ICOM2 Belden® 8442, 22 AWG, 1 twisted pair, stranded, 500 ft (152 m)
RDR2S-A: Door Contact unshielded, copper
S321-IP: Door Contact, Input Point
CK721-A: OUT1 Belden 9740, 18 AWG, 1 twisted pair, stranded, Depends on power requirements of the device. Voltage to
RDR2S-A: Door Strike, Shunt; unshielded, copper the device must not be reduced more than 10% over the
S321-IP: Door Strike, Shunt 18 AWG wire, measured when energized.
Request to Exit Belden 8442, 22 AWG, 1 twisted pair, stranded, 500 ft (152 m)
RDR2S-A and S321-IP only) unshielded, copper
Reader Power Belden 9740, 18 AWG, 1 twisted pair, stranded, Refer to reader manufacturer’s specification for power
(RDR2S-A and S321-IP only) unshielded, copper requirements.
Reader Data0/Data1 Belden 9744, 22 AWG, 2 twisted pairs, stranded, 500 ft (152 m). Refer to reader manufacturer’s
(RDR2S-A and S321-IP only) unshielded, copper specification for data requirements.
RS232 A, RS232 B Listed DB9 F/F AT Null Modem cable 25 ft (7 m). Cable must remain in the same room as the
CK721-A.
Ethernet Listed, Category 5, 24 AWG, solid, 2 pair or 4 pair type 354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
tool to be supplied by customer.
1. All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
strike cables, such as strike voltage greater than 42 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2. Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.
UL 294 Performance Levels
Destructive Attack Line Security Endurance Standby Power
SPA10000-1A10 Level I Level II Level IV Level II
SPA1B100-1A10 Level I Level II Level IV Level II
SPB10000-1A10 Level I Level I Level IV Level II
SPC10000-1A10 Level I Level II Level IV Level II
Security Control Panel Assembly Mounted in a 16 in. x 16 in. Enclosure Installation Instructions 1
Mounting and Connecting the Panels Technical Specifications
• Mount the panel on a wall or other mounting surface located in a Security Control Panel Assembly Mounted in a 16 in. x 16 in.
restricted-access area.
Enclosure
• The horizontal distance between the mounting holes is 11 in. (28
cm); the vertical distance is 13.88 in. (35.3 cm). Mounting hole Electrical Rating SPA10000-1A10: 120 VAC, 1.8 A, 50/60 Hz
diameter is 0.31 in. (0.8 cm). SPA1B100-1A10: 120 VAC, 1.8 A, 50/60 Hz
• Ensure the door can swing fully open. SPB10000-1A10: 120 VAC, 1.8 A, 50/60 Hz
• Mount the panel in a location where airflow is uninhibited over the SPC10000-1A10: 120 VAC, 1.8 A, 50/60 Hz
exposed surfaces.
Enclosure Rating NEMA Type 1
• Remove the back plate before securing the panel to the mounting
surface and reinstall it when mounting is complete. Ambient Operating 32 to 122°F (0 to 50°C), 10 to 85% RH,
Condition noncondensing
AC Power Connection
Dimensions (Width 16 in. x 16 in. x 6.62 in.
• Put the AC Wired at x Height x Depth) (40.6 cm x 40.6 cm x 16.8 cm)
power wiring
To AC power
the factory
BLU
G
through a N
Ambient Storage -4 to 158°F (-20 to 70°C), 5 to 95% RH,
BRN
BLU Condition noncondensing
knockout. L N L L = Line
source
BRN
• Connect the AC N = Neutral Compliance United States:
power wiring to TB-1 Power supply G = Ground UL Listed under UL 1076 for Proprietary Burglar
terminal block Alarm Units and Systems, and under UL 294 for
TB-1. Access Control Systems Units;
• Do not connect the DC power cable to the module until all wiring is This equipment has been tested and found to
complete comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC rules. These limits
are designed to provide reasonable protection
WARNING: Risk of Electric Shock.
against harmful interference in a residential
!
Disconnect the power supply before making installation. This equipment generates, uses and
electrical connections. Contact with components can radiate radio frequency energy and, if not
carrying hazardous voltage can cause electric shock installed and used in accordance with the
instructions, may cause harmful interference to
and may result in severe personal injury or death.
radio communications. However, there is no
guarantee that interference will not occur in a
S300-BAT Battery Connection particular installation. If this equipment does cause
harmful interference to radio or television reception,
The optional S300-BAT which can be determined by turning the equipment
RED
feature uses two PowerSonic, WHT BLK
off and on, the user is encouraged to try to correct
Model PS-1270, 12 VDC, 7 the interference by one or more of the following
Ah, sealed lead acid batteries + - + - + - + - GNL
DC measures:
BAT
HIGH
per power supply. B-1A B-1B OUT VOLT
• Reorient or relocate the receiving antenna.
The batteries should be AGE
replaced every three years to PS-1 • Increase the separation between the equipment
ensure proper operation. and receiver.
• Connect the equipment into an outlet on a circuit
The RED (+), BLK (-), and WHT cables are provided with the
different from that to which the receiver is
enclosure.
connected.
Replace the batteries whether or not they have been placed into use • Consult the dealer or an experienced radio/TV
by an AC power failure. Observe the polarity when connecting the technician for help.
batteries. The user is cautioned that changes and
modifications made to the equipment without
Field Devices approval of the manufacturer could void the user's
authority to operate this equipment.
For information on wiring the CK721-A controller, S321-IP controller,
or the RDR2S-A module, refer to the documentation provided with Canada:
these devices. CAN ICES-3 (B)/NMB-3(B);
Use a separate Class 2 transformer or power supply for door strike cUL Listed under ULC/ORD-C1076 Proprietary
power. Under no circumstances connect a door strike to the Burglar Alarm Units and Systems
enclosure power supply.
Europe:
Selection Chart CE Mark – Johnson Controls, declares that this
product is in compliance with the EMC Directive and
Product Code Description the Low Voltage Directive.
Number
SPA10000-1A10 16 in. x 16 in. (40.6 cm x 40.6 cm) security control
panel with CK721-A controller and power supply
SPA1B100-1A10 16 in. x 16 in. (40.6 cm x 40.6 cm) security control
panel with CK721-A controller, RDR2S-A module,
and power supply
SPB10000-1A10 16 in. x 16 in. (40.6 cm x 40.6 cm) security control
panel with RDR2S-A module and power supply
SPC10000-1A10 16 in. x 16 in. (40.6 cm x 40.6 cm) security control
panel with S321-IP controller and power supply
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls
All other marks herein are the marks of their respective owners. © 2017 Johnson Controls
2 Security Control Panel Assembly Mounted in a 16 in. x 16 in. Enclosure Installation Instructions
Published in U.S.A. www.johnsoncontrols.comПозиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.