FANs 121, 125, 1628.3
                                                                                          Product/Technical Bulletin S66
                                                                                                        Issue Date 0921

                       S66 Series Electronic Fan Speed Control

The S66 Series Electronic Fan Speed Control is
designed to modulate the speed of single-phase,
permanent split-capacitor motors that have been
approved for speed control by the motor manufacturer.
The S66 permits variable speed control of ventilation
fans in response to a DC input signal. Compatibility
with various VAV Box controllers allows for fan speed
adjustment to meet cfm requirements.

                                                                    Figure 1: S66 Electronic Fan Speed Control

                                               Features and Benefits
                        120-480 VAC, 50 or 60 Hz        Allows for use on a wide range of voltage
                        Motor Control                   applications

                        Built-in Radio Frequency        Insulates the S66 from interference from other
                        Interference (RFI)              devices, and deters the S66 from interfering with
                        Suppression                     other equipment

                        Internal Isolation              Allows the input signal and low voltage power
                        Transformer (S66AA Model)       supply to utilize the same common

                        Built-in Transient Protection   Exceeds IEEE 587 Standards

                        Hard Start of Motor             Applies 90 to 100% of the line voltage to the
                        (S66AA Model)                   motor for a period of 7+3 seconds

© 2021 Johnson Controls                                                                                                    1
  Part No. 24-8374-8, Rev. E
  Code No. LIT-121605
O peration
The S66 operates as follows:

                                       Figure 2: S66 Operation Flowchart

2 S66 Series Electronic Fan Speed Control Product/Technical Bulletin
                                                                 !
                                                                         CAUTION: Equipment Damage Hazard.
                                                                                  Because the S66 is a single
                                                                                  phase control, it may be used
                                                                                  only with single-phase motors
                                                                                  approved by the manufacturer for
                                                                                  speed control applications.

                                                             Mounting
                                                             •       Mount the S66 control with the cooling fins in a
                                                                     vertical position, making sure that there are no
                                                                     obstructions restricting or preventing the air flow
                                                                     through the cooling fins. Maintaining operating
                                                                     temperatures within the listed specifications is
                                                                     necessary for proper operation.
                                                                     Note:   For maximum heat dissipation, locate the
                                                                             S66 where a large amount of air passes
                                                                             through the cooling fins. For maximum
                                                                             ambient temperature ratings, refer to the
                                                                             Specifications table.
                                                             •       Do not mount the S66 in an area where the control
           Figure 3: S66AA Input vs. Output Curve                    is exposed to excessive heat.
                                                             •       Mount the S66 where it can be conveniently wired

I nstallation                                                        to the power supply and the motor.

The S66 controls may be used with motors that are            Adjustments
approved by the manufacturer for speed control
applications and meet the following requirements:            All S66 Series Controls come factory set. There are
                                                             no field adjustments available.
•       Ball-bearing construction
•       Service factor of 1.25 or greater
•       Low heat rise
•       Power factor of 0.7 or greater

    !
           WARNING: Personal Injury Hazard. All S66
                    Series Controls are designed for
                    use only as operating controls.
                    Where an operating control
                    failure would result in personal
                    injury or loss of property, it is the
                    responsibility of the installer to
                    add devices (safety, limit controls)
                    or systems (alarm, supervisory
                    systems) that protect against, or
                    warn of, control failure.

                                                 S66 Series Electronic Fan Speed Control Product/Technical Bulletin 3
Wiring
See Figure 5 and Figure 6 for wiring diagrams.                   W iring Diagrams
    !
            WARNING: Personal Injury Hazard. To
                     avoid possible electrical shock
                     or damage to equipment,
                     disconnect power supply before
                     wiring any connections.

    !
            CAUTION: Equipment Damage Hazard.
                     To ensure proper operation, the
                     S66 must be connected to a
                     suitable earth ground.

•       Make all wiring connections using copper
        conductors only.
•       Install all wiring to conform to the National Electric
        Code and local regulations.
Note:       For maximum electrical ratings of the control,
            see the Specifications table.

                                                                 Figure 5: Permanent Split-capacitor Connections to
                                                                            the S66AA Fan Speed Control

4 S66 Series Electronic Fan Speed Control Product/Technical Bulletin
Figure 6: Permanent Split-capacitor Single Phase Connections to the S66AA Fan Speed Control when used on
           Three-phase Systems. The S66 and the Single Phase Motor Must be on the Same Phase.

C heckout Procedure                                                       R epairs and Replacement
Note:    Before applying power, make sure                                 Field repairs must not be made. Replacement
         installation and wiring connections are                          controls are available through local Johnson
         according to job specifications.                                 Controls/PENN distributors and the original
                                                                          equipment manufacturer.
After necessary adjustments and electrical
connections have been made, put the system in
operation and observe at least three complete
operating cycles before leaving the installation.

O rdering Information
Table 1: Ordering Information
 Product Code Number                        Description
 S66AA-1C                                   Motor Controller with Hard Start Feature
                                            Line Voltage Range: 120-277 VAC, 60 Hz,
                                            1-10 VDC Input Signal, Start Voltage: 50% of Line Voltage if Hard Start is not Initiated
                                            See Specifications table for output current ratings.

An S66 with selectable hard start (enable or disable), or models with different start voltages, are also available. For more information,
contact Refrigeration Application Engineering at (414)-274-5535.

                                                       S66 Series Electronic Fan Speed Control Product/Technical Bulletin 5
D imensions

                                       Figure 7: S66 Dimensions, in./mm

6 S66 Series Electronic Fan Speed Control Product/Technical Bulletin
S pecifications
                          Product      S66 Electronic Fan Speed Control
            Line Voltage Range         120-480 VAC at 50-60 Hz
        Output Current Ratings              120 VAC               208 VAC                240 VAC                277 VAC               480 VAC
  S66AA Full Load Amperes                      9.8                    9.3                   8.0                    6.9
        Locked Rotor Amperes                   24                     24                     24                    24
      Start Voltage :       S66AA      40% to 60% of Line Voltage (Factory Set), see Figure 3
             Ambient Operating
                 Temperature:               120 VAC               208 VAC                240 VAC                277 VAC               480 VAC
               S66AA Maximum              131°F/55°C             140°F/60°C            140°F/60°C             140°F/60°C
                         Minimum          -40°F/-40°C            -40°F/-40°C           -40°F/-40°C            -40°F/-40°C
                Ambient Storage
                   Temperature         -40°F to 185°F / -40°C to 85°C
              Ambient Humidity         0 to 95% RH Non-condensing; Maximum Dew Point: 85°F/29°C
          Control Case Material        Cold Rolled Steel
                        Enclosure      NEMA 1
            Wiring Connections                                S66AA
                     Input Signal                    1/4 in. Quick Connects
                     Low Voltage                     1/4 in. Quick Connects
                     Line Voltage          Terminal Strip (14 AWG Wire Maximum)
                        Mounting       Vertical Only, Four Holes for No. 10 Screw
       Signal Input Impedance          10,000 ohms
           Input Signal Voltage                        S66AA: 1-10 VDC
           Transient Protection        320 V Surge Suppression; Exceeds IEEE 587 Standards
              Low Voltage Input        20-30 VAC, Class 2
       Dimensions (H x W x D)          5.26 in. x 4.40 in. x 2.87 in./134 mm x 112 mm x 73 mm
                Shipping Weight        1.875 lb/0.850 kg
                Agency Listing :       UL recognized (US): File SA516, Guide SDFY2
                                       UL recognized (Canada): File SA516, Guide SDFY8
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications,
consult Johnson Controls/PENN Application Engineering at (414) 274-5535. Johnson Controls shall not be liable for damages resulting from
misapplication or misuse of its products.

                                                                                                                             www.penncontrols.com

                                                                   ® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
                                                      United States of America and/or other countries. All other trademarks used herein are the property
                                                                  of their respective owners. © Copyright 2021 by Johnson Controls. All rights reserved.

                                                            S66 Series Electronic Fan Speed Control Product/Technical Bulletin 7

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.