The VA-7150 series synchronous motor driven actuator provides floating or proportional control of valves with up to 19 mm stroke in heating, ventilation and air conditioning applications. This compact, non-spring return actuator has 500 N nominal force and responds to a variety of input signals. It can be field mounted or ordered factory coupled ("+M") to VG7000 and VBF series valves.
Ключові дані
| Actuator force | 500 N ± 20% |
|---|---|
| Stroke | 20 mm maximum |
| Supply voltage | 24 V ± 15% / 230 V ±15%, 50/60 Hz |
| Control signal (proportional) | 0…10 VDC (jumper selectable 0-5 / 5-10) |
| Nominal speed at 50 Hz | 10 s/mm (8.5 s/mm at 60 Hz) |
| Enclosure protection | IP 40 (IEC 60529) |
| Ambient operating condition | -5 to +55° C, non condensing |
| Net weight | 0.8 kg |
Застосування
- Floating or proportional control of valves in heating, ventilation and air conditioning applications
- Valve ranges: VG7000 and VG7010 series (VG7T all body types DN 15…50); VBF series PN6 and PN10 (all body types DN 15…40)
Особливості
- 500N force output in a compact unit — covers a wide range of applications with one actuator
- Magnetic clutch — constant output force for closeoff of valves, protects motor in stall conditions
- Unique yoke design — easy field mounting reduces installation and stroke adjustment time
- Positioner with adjustable starting point and span, reverse and direct action modes
- "Signal fail" safe position — safety position (up/down) selectable in-situ after control signal failure
- Maintains shutoff force even if power is removed; compensates for seat wear
Технічні дані
| Parameter | Value |
|---|---|
| Models | Floating: VA-7150; Proportional: VA-7152 |
| Action / control | Floating: optional 2 kΩ feedback, optional 1 aux. switch; Proportional: 0…10 VDC |
| Type of motor | Synchronous / reversible |
| Supply voltage (50/60 Hz) | Floating 230V: 230 V ±15%; Floating 24V: 24 V ± 15%; Proportional: 24 V ± 15% |
| Motor ratings | 2.7 VA (floating), 2.7 VA + electronic positioner 2 VA (proportional) |
| Electronic positioner ratings | 100 kΩ input impedance |
| Actuator force | 500 N ± 20% |
| Stroke | 20 mm maximum |
| Nominal speed at 50 Hz (60 Hz) | 10 (8,5) s/mm |
| Enclosure protection | IP 40 (IEC 60529) |
| Enclosure material | Self extinguishing VO-UL 94 ABS + PC |
| Yoke material | Die cast aluminium |
| Ambient operating condition | -5 to +55° C, non condensing |
| Ambient storage condition | -20 to +65 °C, non condensing |
| Electrical connections | 2.5 mm² (floating), 1.5 mm² (proportional) |
| Optional PCBs connections | 1.5 mm² |
| Net weight | 0.8 kg |
Варіанти замовлення
Ordering code structure: VA-715 - 0
- Voltage supply:
1= 24 VAC, 50/60 Hz;3= 230 VAC, 50/60 Hz (only for floating models) - Valve type:
10= threaded valves VG7000;82= flanged valves VBF - Control type:
0= floating;2= proportional 0…10V - Note: floating models with 2KΩ feedback, 0…10V feedback and auxiliary switches are available on request
- Factory fitted valve-actuator combination: add "+M" to the end of the actuator ordering code (e.g. VA-7152-1001+M with VG7203AT valve body)
Допуски та стандарти
- EMC (89/336 EEC) according to standard EN 50081-1 and EN 50082-1
- LVD (73/23/EEC) according to standard EN 60335
Текст документа
European Electronic Controls Catalogue
Section E
Product Bulletin VA-7150
Issue Date 03 2000
VA-7150
Electric Valve Actuator
I ntroduction
The VA-7150 series synchronous motor driven
actuator provides floating or proportional control of
valves with up to 19mm stroke in heating,
ventilation and air conditioning applications.
This compact, non-spring return actuator has
500N nominal force and responds to a variety of
input signals.
The VA-7150 series can be easily field mounted or
ordered factory coupled to VG7000 and VBF
series valves in accordance with the specified
maximum close-off pressure ratings (see pertinent
valve bulletins)
VA-7150 valve actuator
Features and Benefits
G 500N force output in a compact unit Covers a wide range of applications with one actuator
G Magnetic clutch Provides constant output force for closeoff of valves,
and protects motor in stall conditions
G Unique Yoke Design Easy field mounting to valves reduces installation and
stroke adjustment time
G Positioner with adjustable starting point and Easy setup and installation and allows sequence
span, reverse and direct action modes control
G “Signal fail” safe position Valve safety position after control signal failure, the
safety position, up / down, is selectable in-situ
© 2000 Johnson Controls, Inc. E 14
Order No. 10.736 E
2 VA-7150
O rdering data
VA-715 - 0
Voltage supply
1 24 VAC, 50 / 60 Hz
3 230 VAC, 50 / 60 Hz (only for floating models)
Valve type
10 Threaded valves: VG7000
82 Flanged valves: VBF
Control Type
0 Floating
2 Proportional 0…10V
Note: floating models with 2KΩ feedback, 0…10V feedback and auxiliary switches
are available on request
O rdering procedure
The actuator can be ordered as a separate unit or
a factory fitted valve-actuator combination. Should
the latter be requested, please just add “+M” to the VBF series, PN6 and PN10
end of the actuator ordering code. VBF- -5200 All body types DN 15…40
For example:
Item 1 VG7203AT (valve body) For complete ordering information, please refer to
the relevant product bulletin
Item 2 VA-7152-1001 (actuator)
Alternatively, to order a factory fitted combination. O peration
Item 1 VG7203AT (valve body) The VA-715x Series actuators use a reversible
Item 2 VA-7152-1001+M (actuator) synchronous motor and magnetic clutch to
accurately position the valve. The combination can
reliably generate 500 N of force in either direction.
R epair Information
The actuator maintains the shutoff force even if
power to the actuator is removed. When the
controller provides a signal for actuator to move in
Field repairs must not be made. For a replacement
the opposite direction, the shutoff force is reduced
actuator, contact the nearest Johnson Controls
and the valve modulates.
representative.
The magnetic clutch maintains a constant load at
the end of travel, which ensures tight valve shutoff
and compensates for seat wear.
A ctuator / valve combinations
The VA-7150 can be combined with the following
valve ranges:
VG7000 and VG7010 series
VG7 T All body types DN 15…50
E 14
VA-7150 3
Floating Control VA-7150
A controller provides 24 VAC to the up, Down, and M ounting instructions
Common terminals depending upon the desired When mounting the actuator on a valve, please
movement of the valve stem. The signal causes follow the instructions below:
the motor to rotate in the proper direction. The
gear train and drive screw move the valve stem up
or down. • It is recommended that the valves be mounted
When the controller stops sending a signal, the upright in an easily accessible location.
valve stem is held in place and remains in position
until the next control signal is sent.
Note: In incremental application, there is no direct
correlation between valve position and
controller output (0 to 100 %). If correlation OK
is important, use proportional control or
actuators that provide position feedback.
Proportional Control VA-7152
The VA-7152 provides a proportional stroke in OK
relation to the input control signal of 0 to 10, 0 to 5,
or 5 to 10 VDC jumper selectable input control • The actuator must be protected against
signal. It also features stroke selection and Direct dripping water, which could enter the housing
Acting (DA) or Reverse Acting (RA) jumpers. and damage the mechanism or motor.
An electronic controller provides the proportional • Do not cover with insulating material.
input signal to the VA-7152. The signal is • Sufficient clearance must be allowed for
compared to the actual valve position via internal actuator removal (refer to the “Dimension”
feedback potentiometer. drawings).
The internal circuit activates the motor to rotate in • The valve must be installed so that the plug
the proper direction. The gear train and drive seats against the flow, as indicated by the
screw move the valve stem to the position called arrows on the valve.
for by the input signal.
Actuator stem
Direct Acting (DA)
M
Retracted
M
Extended
Revers Acting (RA)
0 1 9 10 VDC
Signal Increase
“Signal Fail” safe position
A signal failure on proportional models will cause
the actuator to automatically move the stem to a
(via jumper) pre-selected position (completely
extended or completely retracted).
E 14
4 VA-7150
W iring instructions WARNING
• All wiring must be in accordance with local
regulations and national electrical codes and
Shock Hazard
should be carried out by authorised personnel
only. Disconnect the power supply before wiring
• Make sure that the line power supply is in connections are made to prevent personal injury.
accordance with the power supply specified on Equipment Damage Hazard
the device.
Make and check all wiring connections before
applying power to the system. Short circuited or
improperly connected wires may result in
permanent damage to the unit.
Wiring Diagrams:
Proportional model 24 VAC
Floating models 24 VAC
Electronic
PCB
1 2 3 4
VA-7152-xx01
VA-7150-xx01
Floating models 230VAC
VA-7150-xx03
E 14
VA-7150 5
A djustments for proportional models 4. Set the signal fail position jumper to select
default position of fully up or fully down. If the
Input Selection
signal is lost at the actuator (open connection),
Fail Position Jumper Long/Short the actuator will default to the pre- designated
Selection Jumper position of full up or full down.
1 2 3 4
Stroke 5. Apply voltage specified by application
DA
Potentiometer requirements to drive the actuator to the full
LED
RA up position using the following chart:
Direct/Reverse
Action Selection
Jumper
Application Values Calibration Values
Zero Adjust 0-10 1-9
0-5 1-4
5-10 6-9
VA-7152 Components
Note: Use of the calibration values in Figure 3
Factory calibration is set for direct acting 1 to 9 will ensure proper shutoff throughout the
VDC ± 0.5 VDC for use with 0 to 10 VDC controller life of the valve (accounts for seat wear).
and 19 mm stroke. Valve fail position jumper is
DA: full up (minimum voltage)
factory positioned for fully up.
RA: full up (maximum voltage)
VA-7152 Calibration Values
Down Up
S
0-10 V
Stroke L
0-5 V
5-10 V DA
RA
Jumpers
Calibration
1. Set the input selection jumpers to match the
desired operating range:
• Top Jumper = 0 to 10 V
• Center Jumper = 0 to 5 V
• Bottom Jumper = 5 to 10 V
2. Set the short/long travel selection jumper:
• Short for stroke lengths 13 mm or less
• Long for strokes over 13 mm
3. Set the direct/reverse action jumper so that the
valve stem travels in the desired direction (per
changes in control signal):
• Direct Action DA (Top jumper) = stroke
down on signal increase
• Reverse Action RA (Bottom jumper) =
stroke up on signal increase
E 14
6 VA-7150
12. Check for proper operation using the desired
Stroke minimum and maximum operating voltages.
Potentiometer Allow the actuator to operate through several
complete cycles.
LED Note: The LED will remain on for 3-10 minutes
after the actuator has completed operation
cycle.
Zero Adjust
13. Replace the cover and secure with the screw.
The unit is ready for operation.
VA-7152 Adjustments
6. To ensure that the valve stem is in the full up
position, turn the zero adjust knob completely
to the left, until the valve stem reaches the end
of stroke.
7. Slowly turn the zero adjust knob to the right,
and stop as soon as the LED flashes or goes
out.
Note: As the actuator is driving, the LED will be
on. The actuator circuit contains a time out
feature. If calibration takes longer than 3-
10 minutes, the LED will go out giving a
false satisfied condition.
If this occurs, turn off the power, wait
several seconds, turn the power on, and
then readjust the zeroing knob.
8. Apply the input voltage specified by application
requirements to drive the valve stem to the full
down position per calibration value (figure 3).
9. To ensure that the valve stem is in the full
down position, adjust the stroke potentiometer
fully clockwise until the valve stem reaches the
end of stroke.
10. Slowly turn stroke potentiometer
counterclockwise until LED goes off.
11. Adjust voltage to drive actuator to the full up
position. Verify zero adjustment.
E 14
VA-7150 7
D imensions (in mm)
97.5 97.5
80 80
153 153
VA-715x-100x VA-715x-820x
E 14
8 VA-7150
S pecifications
Models: Floating Proportional
Action / control: Optional 0…10 VDC feedback
Optional 2 k9 feedback 0…10 VDC
Optional 1 aux. switch
Type of motor: Synchronous / reversible
Supply voltage (50/60 Hz): 230 V ±15% 24 V ± 15% 24 V ± 15%
Motor ratings: 2.7 VA 2.7 VA 2.7 VA
Electronic positioner ratings: 2 VA
-
100 k9 input impedance
Actuator force: 500 N ± 20%
Stroke: 20 mm maximum
Nominal speed at 50 Hz (60 Hz): 10 (8,5) s/mm
Enclosure protection: IP 40 (IEC 60529)
Materials:
Enclosure: Self extinguishing VO-UL 94 ABS + PC
Yoke: Die cast aluminium
Ambient Operating condition: -5 to +55° C, non condensing
Ambient Storage condition: -20 to +65 °C, non condensing
2 2 2
Electrical connections: 2.5 mm 2.5 mm 1.5 mm
2 2
Optional PCBs: - 1.5 mm 1.5 mm
Net weight: 0.8 kg
Compliance: European Directives:
EMC (89 / 336 EEC) according to standard EN 50081-1 and EN 50082-1
LVD (73 / 23 / EEC) according to standard EN 60335
The performance specifications are nominal and conform to acceptable industrial standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Johnson Controls International, Inc.
Headquarters: Milwaukee, WI, USA
European Headquarters: Westendhof 8, 45143 Essen, Germany
European Factories: Lomagna (Italy), Leeuwarden (The Netherlands), Essen (Germany)
Branch Offices: principal European Cities
This document is subject to change without notice Printed in Europe
E 14
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.