VA-7700 Series Electric Valve Actuator

Вид документаТехнічний паспорт
ВиробникJCI
МоделіVA-7700-1001, VA-7700-1003, VA-7740-1001, VA-7740-1003, VA-7706-1001, VA-7746-1001, VA-7700-8201, VA-7700-8203
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.9 МБ

Про документ

A compact, non spring return, synchronous motor driven electric valve actuator for valves in heating, ventilation and air conditioning applications. Available for floating (3-point) control or proportional control with 0-10 V position feedback signal, with a stroke capability of 8 mm to a maximum 20 mm and 500 N nominal force. It can be combined with VG7000, VG9000 and VGS8… valves and ordered as a separate unit or factory-fitted valve/actuator combination.

Ключові дані

Nominal force500 N ± 20%
Stroke20-mm maximum
Control signal0...10 VDC or 0(4)...20 mA
Feedback signal0…10 VDC
Supply voltage230 V ± 15 % / 24 V ± 15% 50/60 Hz
Enclosure protectionIP54 (IEC 60529)
Ambient operating condition-5 to +55, °C, 10…90% RH non condensing
Net weight0.8 kg

Застосування

  • Floating (3-point) control with controllers with PAT (Positioning Adjusting Time) output, in parallel operation
  • Proportional control with controllers with 0…10 V output, in parallel or sequential operation (positioner with selectable starting point and span, direct and reverse action)
  • Combination with VG7000 Series threaded valves (DN 15...50), VG9000 Series flanged valves (DN 15...50), VGS8... Series male threaded valves (DN 15... 40)

Особливості

  • Self adjusting proportional actuators — easy, quick and precise commissioning/servicing
  • Column of 5 LEDs for visualisation of actuator stroke position and status
  • Optional models with mechanical manual override; manual contact micro switch on all models with manual override signals automatic/manual mode
  • IP54 protection class
  • Unique "C" shaped yoke design allowing lateral mounting, reducing vertical space over the valve
  • Positioner with selectable starting point and span, direct and reverse action modes — enables sequence control
  • Magnetic clutch provides constant output force for valve close-off and protects motor in stall conditions
  • "Control-signal failure" stem pre-set position (extended/retracted), selectable in-situ via DIP-switches (not with 0…20 mA control)
  • Auto-calibration procedure for standard and freely defined control signal ranges
  • Electrical manual override via calibration buttons (DIP switch 7)

Технічні дані

Parameter Value
Supply voltage (floating 230 V models) 230 V ± 15 %, 50/60 Hz
Supply voltage (floating 24 V models) 24 V ± 15%, 50/60 Hz
Supply voltage (proportional models) 24 V ± 15%, 50/60 Hz
Control signal Positioner Adjustment Time (PAT) / 0...10 VDC or 0(4)...20 mA
Feedback signal 0…10 VDC
Manual override (VA-770x) None (floating) / Electrical (proportional)
Manual override (VA-774x) Mechanical (floating) / Electrical + Mechanical (proportional)
Type of motor Synchronous / reversible
Max. power consumption, active 3.5 W (230 V) / 2.6 W (24 V floating) / 3.2 W (24 V proportional)
Max. power consumption, apparent 3.9 VA / 2.6 VA / 4.7 W
Input impedance (positioner) 100 kΩ min. (0…10 VDC) / 250 Ω (0(4)…20 mA)
Resolution 0.5 % (up to 200 steps on 20 mm stroke)
Feedback ratings max 2mA at 0..10 VDC, 5 kΩ
Manual contact micro-switch max. load 2A Resistive 1A Inductive, 24 VAC (24 V switch); 2A Resistive 1A Inductive, 230 VAC only for VA-7740-1003
Force 500 N ± 20%
Stroke 20-mm maximum
Nominal full stroke time 8 mm 84 s (50 Hz) / 70 s (60 Hz)
Nominal full stroke time 13 mm 137 s (50 Hz) / 114 s (60 Hz)
Nominal full stroke time 19 mm 200 s (50 Hz) / 167 s (60 Hz)
Enclosure protection IP54 (IEC 60529)
Cover material Self extinguishing ABS + polycarbonate PC
Wiring cover material Polycarbonate
Hand wheel material Polyamide PA66
Yoke material Die cast aluminium
Plates material Zinc plated steel
Gears material Acetylic resin
Ambient operating condition -5 to +55, °C, 10…90% RH non condensing
Ambient storage condition -20 to +65 °C, 10…90% RH non condensing
Wiring 2.5 mm² terminal block
Wiring entrance (2) M20x1.5 cable conduit adapters – for separated power/accessories wiring access (cables from Ø6-mm to Ø12-mm)
Net weight 0.8 kg
Life time Tested for 250,000 full cycles

Варіанти замовлення

For VG7000 and VG9000 Series Valves:

  • VA-7700-1001 — 24 VAC, no manual override (floating)
  • VA-7700-1003 — 230 VAC, no manual override (floating)
  • VA-7740-1001 — 24 VAC, mechanical manual override (floating)
  • VA-7740-1003 — 230 VAC, mechanical manual override (floating)
  • VA-7706-1001 — 24 VAC, electrical manual override (proportional)
  • VA-7746-1001 — 24 VAC, electrical and mechanical manual override (proportional)

For VGS8… Series Valves:

  • VA-7700-8201 — 24 VAC, no manual override (floating)
  • VA-7700-8203 — 230 VAC, no manual override (floating)
  • VA-7740-8201 — 24 VAC, mechanical manual override (floating)
  • VA-7740-8203 — 230 VAC, mechanical manual override (floating)
  • VA-7706-8201 — 24 VAC, electrical manual override (proportional)
  • VA-7746-8201 — 24 VAC, electrical and mechanical manual override (proportional)

Factory-fitted valve/actuator combination: add "+M" to the end of the actuator ordering code (e.g. VA-7746-1001+M).

Допуски та стандарти

  • IP54 (IEC 60529)
  • EMC Directive 2004/108/EC
  • Low Voltage Directive 2006/95/EC

Позиції каталогу з цим документом

Текст документа

                                                                      PB_VA-7700_Electricl Valve Actuators_02 2011


VA-7700 Series
Electric Valve Actuators

The VA-77xx Series synchronous motor driven actuator, for
valves in heating, ventilation and air conditioning applications,
is available for floating (3-point) control or proportional control
with 0-10 V position feedback signal.
It provides a stroke capability of 8 mm to a maximum 20 mm.
This compact, non spring return actuator has a 500 N nominal
force and responds to a variety of input signals.
The actuator can be combined with VG7000, VG9000
and VGS8… valves in accordance with the maximum
close-off pressure ratings specified (see pertinent valve
product bulletins).
They can be ordered as a separate unit or as a factory fitted
valve / actuator combination.




■■Self adjusting proportional actuators
  Easy, quick and precise commissioning servicing
■■Column of 5 Light Emitting Diodes
  Allows easy visualisation of actuator stroke position and of the actuator status
■■Optional models with mechanical manual override
  Allows manual positioning independent of the power supply
■■Manual contact micro switch on all models with manual override
  Signals actuator mode status (automatic or manual) to external supervisory system.
■■IP54 protection class
  Allows installation in a wide range of environments
■■Unique “C” shaped yoke design
  Allows lateral mounting of the actuator reducing the vertical space over the valve needed for
  installation.
■■Positioner with selectable starting point and span, direct and reverse action modes
  Enables sequence control
■■Magnetic clutch
  Provides constant output force for close-off of valves, and protects motor in stall conditions
■■“Control-Signal failure ” stem to pre-determined position
  Actuator pre-set position after a control signal failure (extended/retracted), is selectable in-situ
                                                                                PB_VA-7700_Electricl Valve Actuators_02 2011


Ordering Codes
 For VG7000 and VG9000 Series Valves:                                For VGS8… Series Valves:
 Device code        Power supply            Manual override          Device code      Power supply         Manual override
                    Floating models (3-point)                                         Floating models (3-point)
 VA-7700-1001       24 VAC                  None                     VA-7700-8201     24 VAC               None
 VA-7700-1003       230 VAC                 None                     VA-7700-8203     230 VAC              None
 VA-7740-1001       24 VAC                  Mechanical               VA-7740-8201     24 VAC               Mechanical
 VA-7740-1003       230 VAC                 Mechanical               VA-7740-8203     230 VAC              Mechanical
         Proportional models (0…10 VDC / 0 (4)…20mA)                       Proportional models (0…10 VDC / 0 (4)…20mA)
 VA-7706-1001       24 VAC                  Electrical               VA-7706-8201     24 VAC               Electrical
 VA-7746-1001       24 VAC                  Electrical and           VA-7746-8201     24 VAC               Electrical and
                                            Mechanical                                                     Mechanical

 These actuators can be combined with the following valve            These actuators can be combined with the following valve
 ranges:                                                             ranges:

 • VG7000 Series Threaded Valves                                     • VGS8... Series Male Threaded Valves
 Female and male threaded valves                                     Male threaded valves
 VG7  T                all body types DN 15...50                 VGS8  W1N              3-way DN 15... 40
                                                                                              2-Way DN 15... 50
                                                                     • VG9000 Series Flanged Valves
                                                                     Flanged valves
                                                                     VG9  S1                all body types DN 15...50


Ordering procedure
The actuator can be ordered as a separate unit or a factory fitted
valve-actuator combination. Should the latter be requested,
please just add “+M” to the end of the actuator ordering code.

For Example:
Item 1     VG7203NT            (valve body)
Item 2     VA-7746-1001        (actuator)
Alternatively, to order a factory fitted combination
Item 1     VG7203NT            (valve body)
Item 2     VA-7746-1001+M (actuator)




                                                                                                                                2
                                                                                 PB_VA-7700_Electricl Valve Actuators_02 2011


Operation
Floating models                                                     Control signal failure pre-set position■
                                                                    (not functional with 0…20 mA control selected)
 Connections       Actuator Stem
                                                                    A control-signal failure on proportional models will cause the
      1-2              Extends
                                                                    actuator to automatically move the stem to a (via DIP-switches)
      1-3              Retracts                                     pre-selected position (100% extended or 100% retracted).


Proportional models■                                                Auto Calibration procedure with standard
(0…10 VDC or 0(4)…20 mA)                                            input signal ranges.
The VA-77x6 provides a proportional stroke corresponding to the     The standard control signals are selected by setting DIP switches
control signal.                                                     3 and 4 switch (see paragraph "DIP switch settings").
                                                                    It is recommended to set the actuator to the desired control signal
Following control signals are defined as standard:
                                                                    and action before fitting to the valve (see paragraph "DIP switch
0…10 VDC                                                            settings").
0…5 VDC                                                             Power must be connected before the auto-calibration cycle can
                                                                    be started.
5…10 VDC
0…20 mA
                                                                    Procedure: Actuator is mounted on valve.
                                                                    • Verify that with the stem fully retracted, there is a minimum
4…20 mA                                                               distance of 1 mm between the top of the actuator stem nut and
                                                                      the stem guide bush in the actuator motor housing base plate.
                  Input                       Position at             If necessary correct the distance by adjusting the actuator /
 Action■          control         Actuator    control-signal          valve stem connection.
 (DIP switch set) signal          Stem        failure *
                                                                    • To start the auto calibration cycle, push both calibration buttons
 Direct (DA)        Increases     Extends     Selectable*             for at least 5 seconds. The actuator will make a full cycle to
                    Decreases     Retracts    Selectable*             detect the stem extended and retracted limits.
 Reverse (RA)       Increases     Retracts    Selectable*                                        Calibration buttons
                    Decreases     Extends     Selectable*


* "Signal failure" position pre-set does not operate when 0…20
mA control is selected.
The action mode, DA (direct acting) and RA (reverse acting)
                                                                                                            > 5 sec
is set through the DIP switches (see paragraph "DIP switch
settings").
The actuator control signal has a buffer zone, at each end of the
span, of 0.3 V or 0.3 mA.
This ensures definite valve close-off.
                                                                           During auto-calibration cycle all five
                                                                           status indication LED flash simultaneusly




                                                                    • When the auto calibration cycle is completed the LED
                                                                      stop flashing, the actuator stem moves to the position that
                                                                      corresponds to the control signal and the five LED indicate the
                                                                      stem position.
                                                                    • When the control signal changes the actuator stem moves to
                                                                      the new position this is indicated by one flashing LED. The LED
                                                                      stops flashing when the position corresponding to the control
                                                                      signal has been reached.
                                                                    Note: When ever the actuator is newly placed on a valve,
                                                                          auto-calibration must be carried out.




                                                                                                                                      3
                                                                                   PB_VA-7700_Electricl Valve Actuators_02 2011


Auto-calibration procedure for freely defined                         Position feedback
control signal ranges                                                 The position feedback signal is for monitoring the actuator stroke
Non standard control signals for example 2…8 VDC are applied          position. It feeds information internally to the positioner and a
by setting the DIP switches 3 and 4 (see paragraph "DIP switch        0-10 VDC signal can supply an external supervisory system.
settings").                                                           Electrical manual override
It is recommended to set the actuator to the desired control-signal   To select electrical manual override DIP switch 7 must be
type and action before fitting to valve (see paragraph "DIP switch    switched to “on” (right hand position; see paragraph "DIP
settings").                                                           switch settings"). The actuator stem can now be driven via the
Power must be connected before the auto-calibration cycle can         calibration buttons. The upper button retracts the stem and the
be started. It is recommended that the signal span is always          lower button extends the stem. The stem remains in the position
set superior or equal to 3V or 6 mA in order to keep acceptable       at which the button is released. Switch DIP switch 7 to “off” to
proportional characteristics.                                         return to automatic drive. The five LED indicate the stem position.

Procedure: (Actuator is mounted on valve)                             Mechanical manual override
• Verify that with the stem fully retracted, there is a minimum       To select manual override turn the override knob from “AUT” to
  distance of 1 mm between the top of the actuator stem nut and       “MAN”, the hand wheel is then engaged and power disconnected
  the stem guide bush in the actuator motor housing base plate.       internally. Turning the hand wheel clockwise extends the stem
  If necessary correct the distance by adjusting the actuator /       and anti-clockwise retracts the stem. Turning the override knob to
  valve stem connection.                                              AUT disengages the hand wheel and reconnects the power.
• The auto calibration cycle is started by pushing both calibration
  buttons, on the pcb, simultaneously for at least 5 seconds.                     WARNING: The auxiliary switches (terminals
  The actuator will then make a full cycle to detect the stem                     10, 11, and 12) can be used to indicate manual
  extended and retracted limits.                                                  override or automatic mode.


                            Calibration buttons




                                        > 5 sec




      During auto-calibration cycle all five
      status indication LED flash simultaneusly




• Apply one of the control signal values and confirm by
  pressing one of the two calibration buttons for 2 seconds
  (the 5 LED will illuminate for 5 sec to confirm the setting).
  Now apply the second control signal value and again confirm
  by pressing one of the two calibration buttons for 2
  seconds (the 5 LED will illuminate for 5 sec to confirm the
  setting).
• Both the minimum and the maximum control signal values are
  stored in the memory of the actuator.
• When the auto calibration cycle is completed the LED
  stop flashing, the actuator stem moves to the position that
  corresponds to the control signal and the five LED indicate the
  stem position.
• When the control signal changes the actuator stem moves to
  the new position this is indicated by one flashing LED. The LED
  stops flashing when the position corresponding to the control
  signal has been reached.




                                                                                                                                       4
                                                                          PB_VA-7700_Electricl Valve Actuators_02 2011


DIP switches settings (Proportional models only)
The DIP switches are accessed by removing the transparent cover.




                              1                   1
1, 2:                                                                  Default setting from factory:
                                      VDC                mA
Control signal Type                                                    All switches in left hand position
                              2                   2

                              3                                                   1.
                                      0...10
                                                                                       Voltage control
                                      VDC
                              4                                                   2.
                                                          ---
                              3                                                   3.
                                      0...5 VDC                                        0...10 VDC
                              4                                                   4.

3, 4, 5:                      3                                                   5. ---
Control signal Ranges                 5...10
                                      VDC
                              4                                                   6. Direct Acting mode
                                                          ---
                              3                                                   7. Electrical manual override "off"
                                      Free
                                      Range
                              4                                                   8. "Signal failure position" pre-set = "Up"

                                                  5      0...20 mA
                                      ---
                                                  5      4...20 mA

6: Action                     6       DA          6      RA

7: Electrical Manual Override 7       OFF         7      ON


8: Control signal failure
                              8             Up    8             Down
position preset*


* Does not operate with mA control.




                                                                                                                                5
                                                                                  PB_VA-7700_Electricl Valve Actuators_02 2011


Standard operating mode                                              Fault mode
The LED display indicates the actuator stem position.                If the actuator enters fault mode, the LED will flash as shown.
The LED stops flashing when the position corresponding to the        The indication is general and is displayed when:
control signal has been reached.
                                                                                 • Stem comes to unexpected stop; retry cycle fails
                                                                                   to clear problem

                                                                                 • Freely defined control-signal settings are
                                                                                   incomplete or not stored.

                                                                                 • Invalid E2PROM parameters




                                                                     Specific fault indication
                                                                     To indicate the specific fault press one of the calibration buttons
                                                                     for 2 seconds. A fault diagnosis is displayed:

     Actuator stem moving               Actuator stopped                         Specific alarm codes displayed by LED
  between 40 to 60% of stroke      between 40 to 60% of stroke              A                 B                C                D



Actuator status indication ■
(Proportional models only)
The actuator microprocessor carries out a failure diagnosis when
a failure has been detected.
The actuator status is indicated by the LED display.                                              Diagnosis
LED definition                                                        A   Calibration interrupted before completion or values missing
                                                                      B   Invalid E2PROM parameters
        LED permanently ON
                                                                      C   Actuator stalled due to valve blockage
                                                                      D   Default E2PROM parameters defective
        LED flashing
                                                                     When the problem has been solved, pressing one of the
                                                                     calibration buttons for at least 5 seconds will cause the actuator
        LED permanently OFF
                                                                     to leave the fault mode and the LED will show present actuator
                                                                     status. Standard operating mode.
When the micro processor detects that the stem has come to an
unexpected stop it initiates a retry cycle, this is repeated three
times and if unsuccessful the actuator status is switched to fault
mode and the LED indicate a general alarm code. If the problem
is cleared however, the actuator continues normal function.




                                                                                                                                           6
                                                                                                   PB_VA-7700_Electricl Valve Actuators_02 2011


Applications: Parallel and sequential operation
Actuators without built-in positioner for                                         Actuators with built-in positioner for
controllers with PAT (Positioning Adjusting                                       controllers with 0…10V output in parallel
Time) output in parallel operation                                                operation
Although synchronous motors have the same running speed                                                 24V
(rate of travel), deviation in travel between motors can                                     24VAC Com Com 0...10V

accumulate during starts and stops because of varying loads.                            0...10 V
                                                                                  0...10 V Com
This deviation depends on the number of on/off cycles.                            24 VAC Com
By periodical switching of the actuators to end of travel,                              24 VAC
actuators running in parallel can be reasonably synchronous.                                       1       2       3       4       1    2       3       4         1    2    3      4
                                                                                                       Actuator 1                      Actuator 2                     Actuator 3

           24Vac         24Vac          24Vac
           Com           Up             Down                                      The controller 0…10 V output can operate several actuators with
24Vac Down                                                                        built-in electronic positioner.
                                                                                  The number of actuators that can be linked to a single controller
24Vac Up
                                                                                  depends on the controller’s active power in relation to the
24Vac Com
                                                                                  actuators power consumption.
                                                                                  Each positioner has its own adjustment for starting point between
                   1        2       3           1    2       3   1     2      3
                                                                                  0…10 V.
                                                                                  Each actuator can have a different input (for instance 0…5 VDC /
                       Actuator 1               Actuator 2       Actuator 3
                                                                                  5...10 VDC).
                                                                                  Each positioner can be switched for direct or reverse action.
The number of actuators that can be linked to a single controller
depends on the controller’s active power in relation to the
actuators power consumption.




                                                                                           DIP switch setting


                                                                                         Starting        End Point ■
                                                                                          Point   (Starting Point + Span)                                       Positioner Action
                                                                                   Y1        0.3 V                             9.7 V                        DA        Factory Setting
                                                                                   Y2        5.3 V                             9.7 V                        RA
                                                                                   Y3        6.0 V                             8.0 V                        DA


                                                                                              M
                                                                                        0%
                                                                                                                       Y1                                       Y2

                                                                                      50%
                                                                                                                                                    Y3



                                                                                    100%
                                                                                              0        1       2       3       4   5        6       7       8     9    10

                                                                                                                   Control signal (VDC)




                                                                                                                                                                                       7
                                                                                  PB_VA-7700_Electricl Valve Actuators_02 2011


Mounting instructions                                                Wiring instructions
When mounting the actuator on a valve, please follow the             • All wiring must be in accordance with local regulations
instructions below:                                                    and national electrical codes and should be carried out by
                                                                       authorised personnel only.
• It is recommended that the valves be mounted upright or at
  angles not greater than 90° in an easily accessible location.      • Make sure that the line power supply is in accordance with the
                                                                       power supply specified on the device.
                                                                     • See also the instructions in paragraph “Application”.

                                                                                 WARNING: ■
                                                                                 Shock Hazard
                                                                                 • Disconnect the power supply before wiring
                                                                                   connections are made to prevent personal
                                                                                   injury.
                                                                                 Equipment Damage Hazard
                                                                                 • Make and check all wiring connections before
• The actuator must be protected against dripping water, which                     applying power to the system. Short circuited
  could enter the housing and damage the mechanism or motor.                       or improperly connected wires may result in
• Do not cover with insulating material.                                           permanent damage to the unit.
• Sufficient clearance must be allowed for actuator removal (refer
  to the dimension drawings).
• The valve must be installed so that the plug seats against the
  flow, as indicated by the arrows on the valve.

            WARNING: These actuators are intended to
            control equipment under normal operating
            conditions. Where failure or malfunction of the
            actuator could lead to an abnormal operating
            condition that could cause personal injury or
            damage to the equipment or other property,
            other devices (limit or safety controls) or
            systems (alarm or supervisory systems)
            intended to warn of or protect against failure
            or malfunction of the actuator must be
            incorporated into and maintained as part of the
            control system.




                                                                                                                                    8
                                                     PB_VA-7700_Electricl Valve Actuators_02 2011


Wiring Diagrams (Models with mechanical manual override)
                                                     WARNING: ■
                                                     Equipment Damage Hazard
                                                     • On 24 V models with manual override, it is not
                                                       permitted to connect voltages greater than ■
                                                       24 V to terminals 10, 11, and 12




   VA-7740-xx01 - Floating models, 24 VAC supply




  VA-7740-xx03 - Floating models, 230 VAC supply




                 Com   0...10VDC   Com
                       /0...20mA
                       0...10VDC




 VA-7746-xx01 - Proportional models, 24 VAC supply




                                                                                                        9
                                                     PB_VA-7700_Electricl Valve Actuators_02 2011


Wiring Diagrams (Models without mechanical manual override)




   VA-7700-xx01 - Floating models, 24 VAC supply




  VA-7700-xx03 -  Floating models, 230 VAC supply




                Com   0...10VDC   Com
                      /0...20mA
                      0...10VDC




 VA-7706-xx01 - Proportional models, 24 VAC supply




                                                                                              10
                                                           PB_VA-7700_Electricl Valve Actuators_02 2011


Dimensions (in mm)




             VA-77xx-10xx




                                  A   25 mm   VA-770x: actuators without manual override
                                  A   80 mm   VA-774x: actuators with manual override




    87




    90




                   VA-77xx-82xx



                                                                                                    11
                                                                                            PB_VA-7700_Electricl Valve Actuators_02 2011


Technical Specifications
Product                                                                                   VA-7700
Models                                                         Floating                                             Proportional
Supply voltage                                 230 V ± 15 %                24 V ± 15%                                 24 V ± 15%
                                                 50/60 Hz                   50/60 Hz                                   50/60 Hz
Control signal                                     Positioner Adjustment Time (PAT)                          0...10 VDC or 0(4)...20 mA
Feedback signal                                                                                                       0…10 VDC
Mechanical Manual override
                              - VA-770x                          None                                                  Electrical
                              - VA-774x                      Mechanical                                        Electrical + Mechanical
Type of motor                             Synchronous / reversible
Max. Power Consumption
                               - Active             3.5 W                      2.6 W                                     3.2 W
                          - Apparent                3.9 VA                    2.6 VA                                     4.7 W
Electronic positioner                                                                                        100 kΩ min. (0…10 VDC)
                                                                   ---
Input impedance                                                                                                250 Ω (0(4)…20 mA)
Resolution                                                                                                            0.5 %
                                                                                                        (up to 200 steps on 20 mm stroke)
Feedback ratings                                                                                            max 2mA at 0..10 VDC, 5 kΩ
Manual contact                            2A Resistive 1A Inductive, 24 VAC (24 V switch)
micro-switch max. load                    2A Resistive 1A Inductive, 230 VAC only for VA-7740-1003
Force                                     500 N ± 20%
Stroke                                    20-mm maximum
Nominal full stroke time                  mm 50 Hz            60 Hz
                                          8     84 s          70 s
                                          13    137 s         114 s
                                          19    200 s         167 s
Enclosure protection                      IP54 (IEC 60529)
Materials
                                - Cover Self extinguishing ABS + polycarbonate PC
                       - Wiring Cover Polycarbonate
                        - Hand wheel Polyamide PA66
                                 - Yoke Die cast aluminium
                               - Plates Zinc plated steel
                                - Gears Acetylic resin
Ambient Operating Condition               -5 to +55, °C, 10…90% RH non condensing
Ambient Storage Condition                 -20 to +65 °C, 10…90% RH non condensing
Wiring                                    2.5 mm2 terminal block
Wiring entrance                           (2) M20x1.5 cable conduit adapters – for separated power/accessories wiring access
                                          (cables from Ø6-mm to Ø12-mm)
Net weight                                0.8 kg
Life time                                 Tested for 250,000 full cycles
                                          Johnson Controls, Inc., declares that these products are in compliance with the essential
                 Compliance               requirements and other relevant provisions of the EMC Directive 2004/108/EC and
                                          Low Voltage Directive 2006/95/EC




                                                                                                                                 Building Efficiency
                                                                                                             Headquarters: Milwaukee, Wisconsin, USA
                                                                                                            Branch Officies: Principal Cities World-wide
                                                              Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                                                                        All other marks herein are the marks of their respective owners.
                                     © Copyright 2011 Johnson Controls, Inc. All rights reserved. Any unauthorized use or copying is strictly prohibited.
                                                                                                                          www.johnsoncontrols.com
