| Вид документа | Технічний паспорт |
|---|---|
| Виробник | JCI |
| Моделі | V5210ZC, V52x0BC, V52x0CC, V52x0DC, V52x0EC, V5210JC, V5210KC, V5210MC |
| Група обладнання | valves |
| Мова документа | англійська |
| Розмір файлу | 0.3 МБ |
Про документ
The V5000 Valve Series regulates the flow of water in response to the demand of a controller in zone and terminal unit applications. Valves are available as 2-way PDTC (Normally Open), 3-way mixing/diverting, and 3-way mixing/diverting with built-in bypass, with BSPP or compression fitting body connections. They combine with VA-7047/VA-7048 thermal ON/OFF actuators, VA-7067 thermal 0...10 VDC actuator and VA-747x electric actuators.
Ключові дані
| Body rating | PN16 Nominal, maximum rated pressure |
|---|---|
| Inherent flow characteristic | Equal percentage |
| Rangeability | 50:1 (control port) |
| Fluid temperature limits | 0...120 °C |
| Ambient temperature limits | 2...50 °C |
| Leakage | Max 0,01% of KVS, Class IV for ANSI FCI 70-2 and EN60534-4 modif. 1 |
| Connection to actuator | M30 x 1.5 |
| Service | Water, glycol solutions (max 50%) for HVAC applications |
Застосування
- Zone and terminal unit flow control in HVAC applications
- Hot or cold water and water glycol mixtures up to 50%
- Mixing and diverting service (3-way configurations)
Особливості
- 2-way PDTC (NO) and 3-way configurations — flexible applications
- 3-way with built-in bypass configuration reduces piping installation time and cost
- Forged brass body, stainless steel stem and spring — long life, compact
- Rubber compound plug for bubble-tight shut-off — maximises energy saving
- Actuator can be field installed after piping — simplifies installation in confined locations
- Commissioning cap — easy commissioning and manual operation without actuator
- Built-in return spring allows valve to return to normal position when actuator is not mounted or when VA-7047 is de-energised
- BSPP and compression fitting body connection
Технічні дані
| Parameter | Value |
|---|---|
| Models | V5210 / V5810 / V5510 |
| Body type | 2-way PDTC (NO); 3-way mixing/diverting; 3-way mixing/diverting with built-in bypass |
| Body rating | PN16 Nominal, maximum rated pressure |
| Inherent flow characteristic | Equal percentage |
| Rangeability | 50:1 (control port) |
| Service | Water, glycol solutions (max 50%) for HVAC applications; Fluid Group 1 according 67/548/EEC (proper water treatment recommended, refer to VDI 2035) |
| Body size (according ANSI B36.10) | DN10, DN15, DN20 |
| Max pressure drop p (2-way) | DN10: 380 kPa; DN15: 110 kPa; DN20: 110 kPa |
| Max pressure drop p (3-way) | DN10: 170 kPa; DN15: 140 kPa; DN20: 100 kPa |
| Kvs and max close-off pressure | See ordering codes table below |
| Body connection | BSP Parallel (ISO 228/1, BS 2779, DIN 259); Compression fitting (EN1254-2) |
| Nominal stroke | 2-way: 4 mm; 3-way: 3.7 mm |
| Connection to actuator | M30 x 1.5 |
| Valve body and seat materials | DN10: Cu Zn 40 Pb2 as per EN12164; Cu Zn 39 Pb 1 AI-C as per EN1982. DN15 and DN20: Cu Sn 3 Zn 8 Pb5-C as per EN1982 |
| Spindle | X10 Cr Ni18-8 / X8 Cr Ni S 18-9 as per EN188-1 |
| Plug and stuffing box | Cu Zn 40 Pb2 as per EN12164 |
| Leakage | Max 0,01% of KVS, Class IV for ANSI FCI 70-2 and EN60534-4 modif. 1 |
| Fluid temperature limits | 0...120 °C |
| Ambient temperature limits | 2...50 °C |
| Weight (packaging excluded), 2-way | DN10: 180 g; DN15: 280 g; DN20: 330 g |
| Weight (packaging excluded), 3-way mixing/diverting | DN10: 300 g; DN15: 330 g; DN20: 360 g |
| Weight (packaging excluded), 3-way + built-in bypass | DN10: 380 g; DN15: 420 g; DN20: 500 g |
Варіанти замовлення
Order code suffix x = 1: BSPP; x = 9: Compression Fitting.
| Code | Type | Size | Kvs control port | Kvs bypass port | Close-off pressure (kPa) | A (mm) | B (mm) | C (mm) | D (mm) |
|---|---|---|---|---|---|---|---|---|---|
| V5210ZC | 2 way | 10 | 0.16 | --- | --- | 60 | 27.5 | 15.5 | --- |
| V52x0BC | 2 way | 10 | 0.4 | --- | --- | 60 | 27.5 | 15.5 | --- |
| V52x0CC | 2 way | 10 | 0.63 | --- | 400 | 60 | 27.5 | 15.5 | --- |
| V52x0DC | 2 way | 10 | 1 | --- | --- | 60 | 27.5 | 15.5 | --- |
| V52x0EC | 2 way | 10 | 1.6 | --- | --- | 60 | 27.5 | 15.5 | --- |
| V5210JC | 2 way | 15 | 2.5 | --- | --- | 65 | 33.7 | --- | --- |
| V5210KC | 2 way | 15 | 3.5 | --- | 110 | 65 | 33.7 | --- | --- |
| V5210MC | 2 way | 20 | 4.5 | --- | --- | 65 | 33.7 | --- | --- |
| V5810BC | 3 way | 10 | 0.4 | 0.3 | --- | 120 | 60 | 27 | 15.2 |
| V5810CC | 3 way | 10 | 0.63 | 0.4 | --- | 120 | 60 | 27 | 15.2 |
| V5810DC | 3 way | 10 | 1 | 0.63 | --- | 120 | 60 | 27 | 15.2 |
| V5810EC | 3 way | 10 | 1.6 | 1 | --- | 120 | 60 | 27 | 15.2 |
| V5810JC | 3 way | 15 | 2.5 | 1.6 | --- | 150 | 60 | 27 | 15.2 |
| V5810KC | 3 way | 15 | 4 | 2.5 | --- | 150 | 60 | 27 | 15.2 |
| V5810MC | 3 way | 20 | 5 | 3.5 | 110 | 150 | 60 | 27 | 15.2 |
| V55x0BC | 3 way + BP | 10 | 0.4 | 0.3 | --- | 180 | 40 | 60 | 27 |
| V55x0CC | 3 way + BP | 10 | 0.63 | 0.4 | --- | 180 | 40 | 60 | 27 |
| V55x0DC | 3 way + BP | 10 | 1 | 0.63 | --- | 180 | 40 | 60 | 27 |
| V55x0EC | 3 way + BP | 10 | 1.6 | 1 | --- | 180 | 40 | 60 | 27 |
| V5510JC | 3 way + BP | 15 | 2.5 | 1.6 | --- | 150 | 40 | 60 | 27 |
| V5510KC | 3 way + BP | 15 | 4 | 2.5 | --- | 150 | 40 | 60 | 27 |
| V5510MC | 3 way + BP | 20 | 5 | 3.5 | 110 | 150 | 50 | 60 | 27 |
Compression Fitting Kit available for DN15 and DN20:
- DN15: 0378145015
- DN20: 0378145020
Valve–actuator combinations:
| Item code | Action | Supply voltage |
|---|---|---|
| VA-7047-21 | Direct Acting (stem extends when energized) | 24 VAC / VDC |
| VA-7048-21 | Reverse Acting (stem retracts when energized) | 24 VAC / VDC |
| VA-7047-23 | Direct Acting (stem extends when energized) | 230 VAC / VDC |
| VA-7048-23 | Reverse Acting (stem retracts when energized) | 230 VAC / VDC |
| VA-7067-21 | Stem extends with increasing input signal | 24 VAC |
| VA-7470-1001 | Stem extends with increasing input signal | 24 VAC |
| VA-7472-1001 | Stem extends with increasing input signal | 24 VAC |
| VA-7472-9001 | Stem extends with increasing input signal | 24 VAC |
Допуски та стандарти
- PED (Pressure Equipment Directive) 23/97/CE (Paragraph 3, comma 3); CE marking is not applicable
- ROHS
- Leakage class IV per ANSI FCI 70-2 and EN60534-4 modif. 1
Позиції каталогу з цим документом
Текст документа
V5000 Terminal Unit Valves Series
Product Bulletin
PB_V5000
Issue Date 10 2008
The V5000 Valve Series is primarily designed
to regulate the flow of water in response
to the demand of a controller in zone and terminal
unit applications and can be used in combination
with VA-7047 and VA-7048 Thermal ON/OFF
Actuators, VA-7067 Thermal 0...10 VDC Actuator
and VA-747x Electric Actuator Series.
The valves are available in 2-way PDTC
(Normally Open), 3-way mixing/diverting
and 3-way mixing/diverting with built-in bypass
with BSPP and compression fitting body connection.
V5000 Valves
Features and Benefits
Features Benefits
2-way PDTC (NO) and
Flexible applications
3-way configurations
3-way with built-in bypass configuration Reduces piping installation time and cost
3-way valves designed for mixing and diverting
Wide range of application
application
Forged brass body, stainless steel stem
Ensure long life and it is compact
and spring
Rubber compound plug for bubble-tight shut-off Maximises energy saving
Actuator can be field installed after piping Simplifies installation in confined location
Commissioning Cap Easy commissioning and manual operation without actuator
Allows the valve to return to normal position when actuator is not
Built-in return spring
mounted or when VA-7047 is de-energised
BSPP and Compression Fitting Body
Flexible applications
Connection
Dimensions
2-way valve
3-way valve
3-way bypass valve
Ordering Codes
Valve Body Kvs Kvs Close-Off Dimensions (mm)
Codes * Type Size Control Port Bypass Port Pressure (kPa) A B C D
V5210ZC 0.16
V52x0BC 0.4
V52x0CC 10 0.63 400 60 27.5
V52x0DC 1
2 way --- 15.5 ---
V52x0EC 1.6
V5210JC * 2.5
15
V5210KC 3.5 110 65 33.7
V5210MC
* 20 4.5
V5810BC
* 0.4 0.3
V5810CC 0.63 0.4
10 120
V5810DC 1 0.63
V5810EC 3 way 1.6 1 60 27 15.2 30
V5810JC 2.5 1.6
15 150
V5810KC 4 2.5
V5810MC 20 5 3.5 110
V55x0BC 0.4 0.3
V55x0CC 0.63 0.4
10 180
V55x0DC 1 0.63
3 way + 40
V55x0EC 1.6 1 60 27 15.2
BP
V5510JC 2.5 1.6 150
V5510KC
* 15
4 2.5
V5510MC
* 20 5 3.5 110 50
*
x = 1: BSPP
9: Compression Fitting
* = Compression Fitting Kit
available for DN15 and DN20
DN15: 0378145015
DN20: 0378145020
2 V5000 Terminal Unit Valves Series - Product Bulletin
Valve Selection
The valve size for water applications can be defined using the diagrams below.
Kvs selection diagram in SI units
V5000 Terminal Unit Valves Series - Product Bulletin 3
Valve - Actuators Combinations Operation
The V5000 series valves are designed to be used These valves are used for hot or cold water and for
with following actuators: water glycol mixtures up to 50%.
Supply Note: These valves are intended to control
Item code Action voltage equipment under normal operating conditions.
Direct Acting Where failure or malfunction of the valves could lead
VA-7047-21 (stem extends when to an abnormal operating condition that could cause
actuator is energized) personal injury or damage to the equipment or other
24 VAC / VDC
Reverse Acting property, other devices (limit or safety controls) or
VA-7048-21 (stem retracts when
actuator is energized) systems (alarm or supervisory systems) intended to
Direct Acting warn of or protect against failure or malfunction of
VA-7047-23 (stem extends when the valves must be incorporated into and maintained
actuator is energized) as part of the control system.
230 VAC / VDC
Reverse Acting
VA-7048-23 (stem retracts when
actuator is energized)
VA-7067-21
VA-7470-1001 Stem extends with
24 VAC
VA-7472-1001 increasing input signal
VA-7472-9001
See “VA-704x and VA-706x Thermal Valve
Actuators” and “VA-747x Electric Actuators”
Product Bulletins for more information.
Stem Movement / Flow
Valve Type Actuator Stem down Actuator Stem up
2-Way PDTC (NO)
A AB
3-Way MIXING
B
AB A
3-Way DIVERTING
B
RETURN
3-Way + bypass
SUPPLY
SUPPLY
3-Way + bypass
RETURN
4 V5000 Terminal Unit Valves Series - Product Bulletin
Mounting Instructions Commissioning
Prior to commissioning check information on
General Guidelines
material, pressure, temperature and flow direction in
In addition to general installation instructions, please conjunction with the installation piping system plan.
observe the following points: Impurities in the piping system and valves, such as
• Ensure that valve body and piping are free of dirt, welding beads etc. will cause the system to leak.
impurities. Prior to commissioning a new installation or
re-commissioning after repairs or service, ensure
• Pay attention to position of the valve relative to that:
the flow direction.
• Correct installation and assembly work has been
• Note arrows on valve body. completed.
• Ensure that threaded connections of valve and • Only qualified personnel carry out
piping are tighten. commissioning.
• Ensure installation without tension and torque. • Correct functional position of the valve is
• Do not use the valve as a step or fixation point. ascertained.
Only piping supports it. • Maintenance of existing protective facilities is
• Protect valve from dust or dirt on construction carried out.
sites. Valve Removal
• Provide strainer or filter upstream of valve. In addition to general guidelines the following points
should be observed:
• Use compensators to balance thermal
expansion of piping. • Pressure free piping system
• Ensure that stem thread and shaft are kept free • Cooled fluid
of paint.
• Drained piping system
Installation Site Information
• With corrosive or aggressive fluids, the piping
The valve installation site should be easily system should be vented.
accessible and provide sufficient room for service
and removal of actuators. Manual shut-off valves Work to be performed by qualified personnel only.
should be located up and downstream of the control
valve, to facilitate service and repairs without
drainage of the piping system. The control valve
should preferably be installed in vertical or horizontal
position.
Piping should be insulated to protect actuators
against high temperatures. Insulation should leave
sufficient room for service of stem packing.
To ensure trouble free function of the control valves
the pipe immediately upstream of the valve should
be straight far the length of at least. 2x DN and the
pipe immediately downstream straight far the length
at least 6x DN.
V5000 Terminal Unit Valves Series - Product Bulletin 5
Technical Specifications
Products V5000
Models V5210 V5810 V5510
2-way 3-way 3-way mixing diverting
Body Type PDTC (NO) mixing/diverting with built-in bypass
Body Rating PN16 Nominal, maximum rated pressure
Inherent Flow Characteristic Equal percentage
Rangeability 50:1 (control port)
Service Water, glycol solutions (max 50%) for HVAC applications.
Fluid Group 1 according 67/548/EEC.
(proper water treatment is recommended, refer to VDI 2035)
Body Size DN10
(according ANSI B36.10) DN15
DN20
Max Pressure drop p DN10: 380 kPa DN10: 170 kPa
DN15: 110 kPa DN15: 140 kPa
DN20: 110 kPa DN20: 100 kPa
Kvs and max. close-off See “Ordering Code and Dimensions” on page 2
pressure
Body Connecticus Gas BSP Parallel (ISO 228/1, BS 2779, DIN 259); Compression fitting (EN1254-2)
Nominal Stroke 4 mm 3.7 mm
Connection to Actuator M30 x 1.5
Materials
Valve body and seat: DN10:
Cu Zn 40 Pb2
as per EN12164
Cu Zn 39 Pb 1 AI-C as per EN1982
DN15 and DN20:
Cu Sn 3 Zn 8 Pb5-C
as per EN1982
Spindle: X10 Cr Ni18-8
X8 Cr Ni S 18-9 as per EN188-1
as per EN188-1
Plug and stuffing box: Cu Zn 40 Pb2
Cu Zn 40 Pb 2 as per EN12164
as per EN12164
Leakage Max 0,01% of KVS, Class IV for ANSI FCI 70-2 and EN60534-4 modif. 1
Fluid Temperature Limits 0...120 °C
Ambient Temperature Limits 2...50 °C
Max weight packaging 2-way 3-way
3 way
excluded mixing / diverting
NO mixing / diverting
+ built-in bypass
DN10 180 g 300 g 380 g
DN15 280 g 330 g 420 g
DN20 330 g 360 g 500 g
Compliance PED (Pressure Equipment Directive) 23/97/CE (Paragraph 3, comma 3)
CE marking is not applicable.
ROHS
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.
Johnson Controls International, Inc.
Headquarters: Milwaukee, Wisconsin, USA
Branch Offices: Principal Cities World-wide
6 V5000 Terminal Unit Valves Series - Product Bulletin www.johnsoncontrols.com
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.