SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Room Command Module, TM-1100 Series

Вид документаТехнічний паспорт
ВиробникJCI
МоделіTM-1140-0000, TM-1150-0000, TM-1160-0000, TM-1160-0005, TM-1160-0002, TM-1160-0007, TM-1170-0005, TM-1170-0007
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.3 МБ

Про документ

The TM-1100 series of Room Command Modules are designed for use with the TC-9102, TC-9109 and TCU series of DDC terminal unit controllers. The set point dial enables the room occupant to adjust the working set point within 12…28 °C or -3 K to +3 K depending on model; an occupancy button switches between COMFORT and STANDBY or requests temporary COMFORT during NIGHT operation, with a LED showing the current mode. Models with a 3-speed fan override are available for TC-9102/TCU fan coil applications, and models without a built-in temperature sensor suit installations where the sensor is mounted inside the fan coil unit.

Ключові дані

set point dial range12…28 °C or ± (range 3 K)
temperature sensorNTC Thermistor 2252 ohm at 25 °C
sensor accuracy+/-0.5 °C
ambient operating conditions0 to 50 °C, 10 to 90% RH non condensing
protection classIP30 (EN 60529)
max wiring distanceMax 50 m
dimensions80 mm x 80 mm x 32 mm / 35 mm

Застосування

  • Wall-mounted room control in public buildings and hotels
  • Fan coil unit control with TC-9102 and TCU controllers (3-speed fan override models)
  • Remote room temperature sensing where the sensor is mounted inside the Fan Coil Unit

Особливості

  • Modern and attractive cover which snaps onto a plug-in mounting base — blends in with room decor, easy installation
  • Terminals located on mounting base — easy wiring and commissioning
  • All models available with or without Occupancy override button
  • Set point dial marked 12…28 °C or ± (deviation to controller set point program)
  • LED mode indicator: steady on = COMFORT, flashing = STANDBY, off = NIGHT/OFF
  • 3-speed fan override adjuster: AUTO, OFF, I (low), II (medium), III (high); active only in COMFORT mode (high speed forced in Low Limit mode)
  • Temporary COMFORT (bypass) mode for one hour when pressed during NIGHT operation

Технічні дані

Parameter Value
Supply Voltage Power from TC-9102, TC-9109 or TCU Series Controller
Ambient Operating Conditions 0 to 50 °C, 10 to 90% RH non condensing
Ambient Storage Conditions -20 to 70 °C, 10 to 90% RH non condensing
Terminations Terminal block in base for 1 x 1.5 mm² (maximum) cable
Temperature Sensor NTC Thermistor 0 to 40°C, 2252 ohm at 25 °C
Accuracy +/-0.5 °C
Remote Set Point 10 kOhm potentiometer marked for 12 °C to 28 °C or ± (range ±3 K)
3-Speed Fan Override 10 kOhm potentiometer with mechanically guided positions for Auto, Off, I, II, III
Occupancy Button Momentary contact (switches 5V at 1 mA)
Mode Indicator Green LED (5V, 4 mA)
Mounting Direct surface mount, plastic base for surface mount with wiring conduits
Materials ABS+PC; self extinguishing HB UL 94
Colours RAL9016 (GE86280), RAL7047 (GE GY81118)
Protection Class Enclosure IP30 (EN 60529)
Dimensions (H x W x S) TM-1140-0000 80 mm x 80 mm x 32 mm
Dimensions (H x W x S) TM-1150/1160/1170/1190 80 mm x 80 mm x 35 mm
Shipping Weight 0.15 kg
Wiring distance Max 50 m (Min. 0.8 mm diameter wire)

Варіанти замовлення

Table 1: Room Command Module

Ordering Code Fan Speed Override Occupancy Button Setpoint Dial Scale Built-in Sensor
TM-1140-0000 - - - NTC K2
TM-1150-0000 - Yes - NTC K2
TM-1160-0000 - Yes 12...28 °C NTC K2
TM-1160-0005 - Yes ± NTC K2
TM-1160-0002 3-speed fan override Yes 12...28 °C NTC K2
TM-1160-0007 3-speed fan override Yes ± NTC K2
TM-1170-0005 - Yes ± -
TM-1170-0007 3-speed fan override Yes - -
TM-1190-0000 - - 12...28 °C NTC K2
TM-1190-0005 - - ± NTC K2

Accessories:

Ordering Code Description
TM-1100-8931 Plastic Surface Mounting Base - White
TE-9100-8501 Unit Mount NTC Temperature Sensor (1.5-m cable)
TM-9100-8900 Special tool for opening enclosure

Допуски та стандарти

  • EMC Directive 2004/108/EC (Johnson Controls declaration of compliance)
  • IP30 per EN 60529

Позиції каталогу з цим документом

Текст документа

                                                                                         Product Bulletin    TM-1100
                                                                                             Issue Date      02 2011


                    TM-1100 Series Room Command Module

The TM-1100 series of Room Command Modules are
designed for use with the TC-9102, TC-9109 and TCU
series of DDC terminal unit controllers. The set point
dial enables the room occupant to adjust the working
set point of the controller within the range of 12…28 °C
or -3 K to +3 K, according to the model number.
The occupancy button enables the occupant to switch
the mode of operation of the controller between
COMFORT and STANDBY or to request a temporary                        TM-1140-0000          TM-1150-0000
COMFORT mode during NIGHT operation.
A LED indicator shows the current operating mode.
For TC-9102 and TCU Fan Coil Unit controllers,
a Room Command Module with a 3-speed fan
override adjuster is available, and models without a
temperature sensor are provided for application where
the room temperature sensor is mounted inside the
Fan Coil Unit.                                                TM-1190-0005       TM-1160-0000       TM-1160-0007




                                           Features and Benefits
       Modern and attractive cover which snaps            Blends in with room decor.
          onto a plug-in mounting base                     Easy installation.

       Terminals located on mounting base.                Easy wiring and commissioning.

       All models available with or without               Covers a large number of applications in public
          Occupancy override button                        buildings and hotels




© 2011 Johnson Controls, Inc.                                                                                          1
  Code N. 24.140 E                                                                              www.johnsoncontrols.com
Application Overview
Set Point Dial                                                   Mode Indicator
The Room Command Module is available with a set                  The LED indicator directly next to the Occupancy
point dial marked 12…28 °C or ±. The module must                 Button shows the current operating mode of the
be connected to a TC-9102/9 TCU series controller                controller as follows:
with the corresponding remote set point range.                   Steady On         COMFORT Mode (occupied)
The 12…28 °C range module determines the set                     Flashing          STANDBY Mode
point of the controller while the ± range module
gives a deviation to the room temperature set point              Off               NIGHT (unoccupied) or OFF Mode
programmed into the controller.
                                                                 3-Speed Fan Override Adjuster
Refer to “Ordering Codes”.
                                                                 When connected to a TC-9102 Controller which has
Occupancy Button                                                 a 3-speed fan control auxiliary output, the 3-speed
                                                                 fan override adjuster allows manual control of the
When pressed for approximately one second,                       speed of the fan. The positions of the adjuster are
the occupancy button changes the mode of                         as follows:
operation of the controller to the “alternate” mode or
back to normal mode. When the controller is in                   AUTO Automatic fan speed is set by the TC-9102
COMFORT (occupied) mode the alternate mode is                              or TCU Controller.
STANDBY (and vice versa), and when in NIGHT                      OFF      Fan OFF
(unoccupied) mode the alternate mode is a
temporary COMFORT (bypass) mode for a period of                  I        Fan low speed
one hour.                                                        II       Fan medium speed
Full details of the alternate modes can be found in
the “TC-9102 Technical Bulletin” (Ordering Code                  III       Fan high speed
MN-9100-2117) of the System 91 Manual or “TCU                    The fan speed adjuster is only active when the
Technical Bulletin” (Ordering Code MN-LCC-01) in                 controller is in COMFORT mode. In Low Limit mode
LONWORKS® Compatible Controllers Manual.                         the fan always runs at high speed.


Ordering Codes
Table 1: Room Command Module
                                                    Occupancy          Temperature Setpoint
 Ordering Codes       Fan Speed Override                                                          Built-in Sensor
                                                      Button               Dial Scale
 TM-1140-0000                     -                         -                     -                   NTC K2
 TM-1150-0000                     -                        Yes                    -                   NTC K2
 TM-1160-0000                     -                        Yes                12...28 °C              NTC K2
 TM-1160-0005                     -                        Yes                    ±                   NTC K2
 TM-1160-0002           3-speed fan override               Yes                12...28 °C              NTC K2
 TM-1160-0007                                                                     ±
                        3-speed fan override               Yes                                        NTC K2
 TM-1170-0005                                                                     ±
                                  -                        Yes                                           -
 TM-1170-0007                                                                     ±
                        3-speed fan override               Yes                                           -
 TM-1190-0000                     -                         -                 12...28 °C              NTC K2
 TM-1190-0005                     -                         -                     ±                   NTC K2

Table 2: Accessories

Ordering Codes        Description

TM-1100-8931          Plastic Surface Mounting Base - White
TE-9100-8501          Unit Mount NTC Temperature Sensor (1.5-m cable)
TM-9100-8900          Special tool for opening enclosure




2 TM-1100 Series Room Command Module
Installation                                              Mounting
The TM-1100 Series Room Command Module is                 Remove the base of the module from the cover by
designed for wall mounting in the room to be              inserting the point of the special TM tool (Ordering
controlled. It should be located where the occupant       Code TM-9100-8900) into the small hole at the
can easily read and adjust the set point and fan          center top of the cover. While pressing down gently,
speed override. If the module has an NTC                  prise the base away from the cover. As the two parts
temperature sensor, it should be placed where the         separate, remove the tool and continue to pull the
temperature is representative of the general room         cover away from the base until the cover is free.
conditions. Cold or warm air draughts, radiant heat       To reassemble the room command module, place
and direct sunlight should be avoided.                    the cover over the lower edge of the base and push
                                                          the upper part of the cover until it “clicks” firmly in
The installation of electrical wiring must conform to
                                                          place.
local codes and should be carried out by authorized
personnel only. Users should ensure that all
Johnson Controls products are used safely and
without risk to health or property.




                             TM-9100-8900




                                      Figure 1: Removing Cover from Base




                                                               TM-1100 Series Room Command Module             3
Direct Surface Mounting                                  Surface Mounting with Mounting Kit
For direct surface mounting:                             (TM-1100-8931)

                                                                        U P       OB EN
                                                                                                                   A
                                                                                  B




                                                         1. Remove one of the notches (A) with a suitable
                                                            tool.
                                                         2. Mark the position of the holes (B) on the wall and
                                                            drill holes 5 mm in diameter. Insert plastic plugs
                                                            into holes.



                                                                                                          D
                                                                              C

    Figure 2: Module Base (Dimensions in mm)


1. Mount the module base on the wall to cover the
electrical outlet and secure with at least two screws.



                                                                                        Conduit


                                                         3. Position and fix the mounting base to the wall
                                                            using the two long screws (C) provided in the kit.
                                                         4. Fix the base of the TM-1100 to the mounting
                                                            base using the two short screws (D) provided in
                                                            the kit.

                                                                                      U P         OB EN



                                                                                       58

                                                                                                  5.0         78

                                                                                            3.5




                                                                   25                       78

                                                                                                  11
                                                                                                  17
                                                                                            13
                                                                                            20

                                                                  Figure 3: Surface Mounting Base
                                                                        (Dimensions in mm)



4 TM-1100 Series Room Command Module
Wiring
                                                                       wires. Follow the wiring diagrams shown in the
Before connecting or disconnecting any wires,
                                                                       figures below. All wiring to the module is at extra low
ensure that all power supplies have been switched
                                                                       (safe) voltage and must be separated from power
off and all wires are potential-free to prevent
                                                                       line voltage wiring. Do not run wiring close to
equipment damage and avoid electrical shock.
                                                                       transformers or high frequency generating
Terminations are made on the terminal blocks in the
                                                                       equipment. Complete and verify all wiring
base of the module, which accept up to 1.5 mm2
                                                                       connections before applying power to the controller
                                                                       to which the module is connected.



                                AD-TCU
                            TC-9102/9 Series                     TM-110 Series
                              Controllers                    Room Command Module




                                       20                         20              NTC Sensor


                                       21                         21              Common

                                               Max 50 m

                                       (Min. 0.8 mm diameter wire)




                                            Figure 4: TM-1140-0000 Wiring




                              AD-TCU
                          TC-9102/9 Series                    TM-110 Series
                             Controllers                  Room Command Module


                                  14                         14                Occupancy Button
                                  15                         15                Mode LED
                                  20                         20                NTC Sensor


                                  21                         21                Common
                                             Max 50 m

                                   (Min. 0.8 mm diameter wire)




                                            Figure 5: TM-1150-0000 Wiring




                                                                            TM-1100 Series Room Command Module             5
                         AD-TCU
                     TC-9102/9 Series                    TM-110 Series
                        Controllers                  Room Command Module


                           14                        14          Occupancy Button
                           15                        15          Mode LED
                           20                        20          NTC Sensor
                           23                        23          Remote Set Point
                           21                        21          Common
                           22                        22          +5V
                                   Max 50 m

                            (Min. 0.8 mm diameter wire)




                       Figure 6: TM-1160-0000 and TM-1160-0005 Wirings




                         AD-TCU
                     TC-9102/9 Series                    TM-110 Series
                        Controllers                  Room Command Module


                           51                        51
                                                                 Three-Speed Fan
                                                                 Override

                           14                        14          Occupancy Button
                           15                        15          Mode LED
                           20                        20          NTC Sensor
                           23                        23          Remote Set Point
                           21                        21          Common
                           22                        22          +5V
                                   Max 50 m

                            (Min. 0.8 mm diameter wire)




                       Figure 7: TM-1160-0002 and TM-1160-0007 Wirings




6 TM-1100 Series Room Command Module
    AD-TCU
TC-9102/9 Series                    TM-110 Series
   Controllers                  Room Command Module


      14                        14          Occupancy Button
      15                        15          Mode LED


      23                        23          Remote Set Point
      21                        21          Common
      22                        22          +5V
              Max 50 m

       (Min. 0.8 mm diameter wire)




             Figure 8: TM-1170-0005 Wiring




    AD-TCU
TC-9102/9 Series                    TM-110 Series
   Controllers                  Room Command Module


      51                        51
                                            Three-Speed Fan
                                            Override

      14                        14          Occupancy Button
      15                        15          Mode LED


      23                        23          Remote Set Point
      21                        21          Common
      22                        22          +5V
              Max 50 m

       (Min. 0.8 mm diameter wire)




             Figure 9: TM-1170-0007 Wiring




                                          TM-1100 Series Room Command Module   7
                         AD-TCU
                     TC-9102/9 Series                    TM-110 Series
                        Controllers                  Room Command Module




                             20                        20          NTC Sensor
                             23                        23          Remote Set Point
                             21                        21          Common
                             22                        22          +5V
                                     Max 50 m

                              (Min. 0.8 mm diameter wire)




                      Figure 10: TM-1190-0000 and TM-1190-0005 Wirings




8 TM-1100 Series Room Command Module
Dimensions




                           Figure 11: TM-1140-0000


                Mode
                LED




              Occupancy
              Button




                           Figure 12: TM-1150-0000




             Temperature
             Set Point
             Adjustment
             Dial




                           Figure 13: TM-1190-0005

                                             TM-1100 Series Room Command Module   9
              Three Fan
              Speed
              Override




                              Figure 14: TM-1160-0007 and TM-1170-0007




                                        Figure 15: TM-1160-0000




                                        Figure 16: TM-1190-0000

10 TM-1100 Series Room Command Module
Technical Specifications
 Supply Voltage                                   Power from TC-9102, TC-9109 or TCU Series Controller
 Ambient Operating                                0 to 50 °C
 Conditions                                       10 to 90% RH non condensing
 Ambient Storage Conditions                       -20 to 70 °C
                                                  10 to 90% RH non condensing
 Terminations                                     Terminal block in base for 1 x 1.5 mm² (maximum) cable.
 Temperature Sensor                               NTC Thermistor 0 to 40°C, 2252 ohm at 25 °C.
 Accuracy                                         +/-0.5 °C
 Remote Set Point                                 10 kOhm potentiometer marked for 12 °C to 28 °C or  (range 3 K )
 3-Speed Fan Override                             10 kOhm potentiometer with mechanically guided positions for
                                                  Auto, Off, I (low speed), II (medium speed) and III (high speed).
 Occupancy Button                                 Momentary contact (switches 5V at 1 mA).
 Mode Indicator                                   Green LED (5V, 4 mA)
 Mounting                                         Direct surface mount, plastic base for surface mount with wiring conduits
                                                  (See “Ordering Codes”)
 Materials                                        Enclosure
                                                  Base
                                                  Occupancy Override Button       ABS+PC; self extinguishing HB UL 94
                                                  Fan Speed Override Dial
                                                  Setpoint Dial
 Colours                                          Enclosure
                                                  Base
                                                                                  RAL9016 (GE86280 )
                                                  Occupancy Override Button
                                                  Fan Speed Override Dial
                                                  Setpoint Dial                   RAL7047 (GE GY81118)
 Protection Class                                 Enclosure                       IP30 (EN 60529)
 Dimensions (H x W xS)                            TM-1140-0000
                                                                                              80 mm x 80 mm x 32 mm
                                                  TM-1150-0000
                                                  TM-1160-000x
                                                  TM-1170-000x                                80 mm x 80 mm x 35 mm
                                                  TM-1190-000x
 Shipping Weight                                                                              0.15 kg
        Compliance                                Johnson Controls, Inc. declares that these products are in compliance
                                                  with the essential requirements and other relevant provisions of the EMC
                                                  Directive 2004/108/EC
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult
the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.




Building Efficency
Headquarters: Milwaukee, Wisconsin, USA
Brach Offices: Principal Cities World-Wide
        ®                        ®
Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc.
All marks herein are the marks of their respective owners.
© Copyright 2011 Johnson Controls, Inc.All right reserved. All rights reserved.
Any unauthorized use or copying is strictly prohibited.
www.johnsoncontrols.com
                                                                                         TM-1100 Series Room Command Module                            11


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.