SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fan coil controller units TC-8900 and remote setpoint module ES-8930

Вид документаКаталожна сторінка
ВиробникJCI
МоделіTC-8903-1131-WK, TC-8901-2131-WK, TC-8904-2131-WK, TC-8906-2131-WK, TC-8903-1132-WK, TC-8901-2132-WK, TC-8904-2132-WK, TC-8906-2132-WK
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.4 МБ

Про документ

The TC-8900 is a family of analogue controllers designed for the control of fan coils with 2 pipe, 2 pipe with change-over, 2 pipe with electrical coil, or 4 pipe configurations. The family includes All-in-one Controller Units (TC-8900), a Remote Setpoint Module (ES-8930) and Built-in Controller Units (TC-8930). It integrates sensor, direct/reverse input, window input, PI control, up to two valve outputs, mode (comfort/stand-by) push button and setpoint readjustment potentiometer in one package.

Ключові дані

Supply24VAC ±15%
Power consumption1.5 VA with no load
OutputTC-89x1: 0…10V 10mA max; TC-89x3/4/6: triac 0,5A max
Ambient operating temperature0…50°C
Storage temperature-20 +70°C
ProtectionIP30 (IEC529)
Dimensions (H x W x D)80 mm x 80 mm x 33 mm
Shipping Weight0.15 kg

Застосування

  • Control of fan coils with 2 pipe configuration
  • 2 pipe with change-over configuration
  • 2 pipe with electrical coil configuration
  • 4 pipe configuration
  • Wall mount or fan coil mount operation, optionally receiving the set point from the Remote Setpoint Module

Особливості

  • All-in-one condensed package: sensor, direct/reverse input, window input, PI control, up to two valve outputs, mode (comfort/stand-by) push button and setpoint readjustment potentiometer
  • Option to limit the setpoint adjustment range or to cancel the setpoint adjustment
  • Active or passive input flexibility: temperature, humidity, differential pressure etc.
  • Modern and discreet cover which snaps onto a plug-in mounting base
  • Electric terminals located on mounting base for easier wiring and commissioning
  • Standard range of mounting kits for mounting flexibility

Технічні дані

Parameter Value
Supply 24VAC ±15% (ES-8930 supplied by TC-8930)
Power consumption 1.5 VA with no load
Output TC-89x1: 0…10V 10mA max; TC-89x3/4/6: triac 0,5A max 24VAC
Sensor recalibration CW + 0.8 °C; CCW – 0.8 °C
Remote sensor NTC K10 10kΏ at 25°C (TE-9100-8502 or TS-9104 series); 0…10V (input impedance >50kΩ) (TS-9101, HT-9000, PS-910x PT-910x series)
Ambient operating temperature 0…50°C
Humidity range 0 to 95% not condensing
Storage temperature -20 +70°C
Mode indicator Red LED to indicate comfort (ON), standby (blinking), off (OFF), not available on TC-8930
Mounting Direct surface mount, plastic base for surface mount with wiring conduits, recessed wall box and panel mounting kits
Housing material ABS + polycarbonate, self-extinguishing VO UL94
Protection IP30 (IEC529)
Color RAL-9010 pure white
Dimensions (H x W x D) 80 mm x 80 mm x 33 mm
Shipping Weight 0.15 kg
Technical characteristics - models with NTC sensor input
Parameter TC-8901 series TC-8903 series TC-8904 series TC-8906 series
Dead Band 0 to 2 K - 0 to 2 K 0 to 2 K
Differential - - - 0.2 to 2 K
Proportional Band 1…4 K 2…8 K 1…4 K -
Time base - 120 seconds 5…15 minutes -
Integral Time - Off or 4 minutes - -
Standby Offset BSB 2K 2K 2K 2K
Window Offset BOF 5K 5K 5K 5K
Technical characteristics - models with 0…10V sensor input
Parameter TC-8901-2183-WK TC-8903-1183-WK
Dead Band 0 to 10% -
Proportional Band 5 to 20% 10 to 40%
Integral Time - Off or 4 minutes
Standby Offset BSB 10% 10%
Window Offset BOF 25% 25%

Варіанти замовлення

All-in-one Controller Units:

Order code Output Sensor input*
TC-8903-1131-WK 1xPAT Built-in NTC
TC-8901-2131-WK 2x0…10V Built-in NTC
TC-8904-2131-WK 2xDAT Built-in NTC
TC-8906-2131-WK 2xOn/Off Built-in NTC
TC-8903-1132-WK 1xPAT Remote NTC
TC-8901-2132-WK 2x0…10V Remote NTC
TC-8904-2132-WK 2xDAT Remote NTC
TC-8906-2132-WK 2xOn/Off Remote NTC
TC-8903-1151-WK 1xPAT Built-in NTC
TC-8903-1152-WK 1xPAT Remote NTC
TC-8903-1183-WK 1xPAT Remote 0…10V
TC-8901-2183-WK 2x0…10V Remote 0…10V

Built-in Controller Units:

Order code Output Sensor input*
TC-8933-1112-W 1xPAT From ES
TC-8931-2112-W 2x0…10V From ES
TC-8934-2112-W 2xDAT From ES
TC-8936-2112-W 2xOn/Off From ES

Remote Setpoint Module:

Order code Output Sensor input*
ES-8930-3031-WK - Built-in NTC

Setpoint ranges: built-in/remote NTC models 12…28°C; TC-8903-1151/1152-WK 0…40°; TC-8903-1183-WK and TC-8901-2183-WK 0…100%; remote setpoint see ES-8900.

Accessories (order separately):

Order code Description
TM-9100-8900 Opening tool for sensor case
TM-9100-8901 Dial stop screws kit (bag of 100 self tapping screws)
TM-9100-8931-W Plastic surface mounting kit
TM-9100-8941-W Wall box mounting kit
TM-9100-8951-W Panel mounting kit

Допуски та стандарти

  • EMC (89/336 EEC) according to EN 50081-1 and EN 50082-1

Позиції каталогу з цим документом

Текст документа

                                                            European Electronic Controls Catalogue
                                                                                 Catalogue Section    F
                                                                                   Product Bulletin   TC-8900
                                                                                         Issue date   06 2000

                   TC-8900 All-in-one Controller Units
                  and ES-8930 Remote Setpoint Module

 Introduction
 TC-8900 is a family of analogue controllers,
 designed for the control of fan coils with 2 pipe, 2
 pipe with change-over, 2 pipe with electrical coil, or
 4 pipe configurations.
 The family includes All-in-one Controller Units (TC-
 8900), a Remote Set point Module (ES-8930) and
 Built-in Controller Units (TC-8930).
 The TC-8900 has been designed to be easy to
 use, while integrating the most common room air
 conditioning control functions.                                  TC-8900 All-in-one Controller Unit




                                                           ES-8930 Remote Setpoint Module with TC-8930
                                                                     Built-in Controller Unit


                                      Features and Benefits
G All in one condensed package: sensor,            Provides better value for money in the smallest
   direct/reverse input, window input, PI          package
   control, up to two valve outputs, mode
   (comfort/stand-by) push button and
   setpoint readjustment potentiometer

G Option to limit the setpoint adjustment          Usability in critical environments where limited
   range or to cancel the setpoint                 adjustability is preferred
   adjustment

G Active or passive input                          Flexibility on the input: temperature, humidity,
                                                   differential pressure etc.

G Modern and discreet cover which snaps            Blends in with room décor. Easier installation
   onto a plug-in mounting base

G Electric terminals located on mounting           Easier wiring and commissioning
   base

G Standard range of mounting kits                  Mounting flexibility




 ©2000 Johnson Controls, Inc.                                                                            F30
 Order Nr.24.245E
2                                                                                                   TC-8900


O rdering data
   All-in-one            Output   Sensor input*              Built-in Controller      Output       Sensor input*
 Controller Units                                                   Units
TC-8903-1131-WK          1xPAT     Built-in NTC               TC-8933-1112-W          1xPAT          From ES
TC-8901-2131-WK      2x0…10V       Built-in NTC                  TC-8931-2112-W      2x0…10V         From ES
TC-8904-2131-WK          2xDAT     Built-in NTC                  TC-8934-2112-W       2xDAT          From ES
TC-8906-2131-WK       2xOn/Off     Built-in NTC                  TC-8936-2112-W      2xOn/Off      From ES
                                                             •     Setpoint range: remote, see ES-8900
TC-8903-1132-WK          1xPAT     Remote NTC
TC-8901-2132-WK      2x0…10V       Remote NTC
                                                             Remote Setpoint          Output       Sensor input*
TC-8904-2132-WK          2xDAT     Remote NTC                   Module
TC-8906-2132-WK 2xOn/Off           Remote NTC                ES-8930-3031-WK        -               Built-in NTC
• Setpoint range: 12…28°                                     • Setpoint range: 12…28°C

   All-in-one
 Controller Units
                         Output   Sensor input*
                                                             Accessories
                                                            Accessories (order separately)
TC-8903-1151-WK          1xPAT     Built-in NTC
TC-8903-1152-WK     1xPAT          Remote NTC               Order code             Description
• Setpoint range: 0…40°                                     TM-9100-8900           Opening tool for sensor case
                                                            TM-9100-8901           Dial stop screws kit (bag of
   All-in-one            Output   Sensor input*                                    100 self tapping screws)
 Controller Units                                           TM-9100-8931-W         Plastic surface mounting kit
TC-8903-1183-WK          1xPAT       Remote                 TM-9100-8941-W         Wall box mounting kit
                                     0…10V                  TM-9100-8951-W         Panel mounting kit
TC-8901-2183-WK      2x0…10V         Remote
                                     0…10V                   See “RS-9100 product bulletin” for details
                                                             on accessories.
• Setpoint range: 0…100%
*Remote sensor input: see “Specifications”
last page of this document

Technical characteristics - models with NTC sensor input
          Models             TC-8901 series       TC-8903 series         TC-8904 series          TC-8906 series
        Dead Band               0 to 2 K                  -                 0 to 2 K                0 to 2 K
        Differential                -                     -                     -                  0.2 to 2 K
     Proportional Band           1…4 K                 2…8 K                 1…4 K                      -
         Time base                  -              120 seconds           5…15 minutes                   -
       Integral Time                -             Off or 4 minutes              -                       -
    Standby Offset BSB             2K                    2K                    2K                      2K
    Window Offset BOF              5K                    5K                    5K                      5K

Technical characteristics - models with 0…10V sensor input
         Models              TC-8901-2183-WK           TC-8903-1183-WK
        Dead Band                0 to 10%                       -
     Proportional Band           5 to 20%                  10 to 40%
       Integral Time                  -                 Off or 4 minutes
    Standby Offset BSB              10%                       10%
    Window Offset BOF               25%                       25%




F30
TC-8900                                                                                                          3



Application
The TC-89x0 Controllers operate either wall mount or fan coil mount, optionally receiving the set point
from the Remote Setpoint Module.




       TC-8900                                                          ES-8930-3031-WK




                                                                                             TC-8930



            FAN COIL                                                 FAN COIL




“All-in-one Controller Unit”, wall mount                Unit mount “Built-in Controller Unit“,
                                                             with “Remote Setpoint Module”


Adjustment
Front description
•   TC-8900 and ES-8930 (sliding cover open)


                                                                                    Sensor recalibration


                                                                                   Dir/Rev switch
                                                                                   Factory set in
                                                                                   RA position


                                                                                              RA
                                                                                              DA
Set point adjustment                                                                Mode status LED


                                                                                     Stand-by/comfort
                                                                                     push button
              LED status                   Mode Status
                           on                comfort
                       blinking              stand-by
                           off             Window open


•   TC-8930
No front adjustment


                                                                                                           F30
4                                                                                                                             TC-8900



Back description
TC-8900 and TC-8930
PB:     Proportional band
DB:     Dead band
Tn:     Integral time for PAT
Time:   Time base for DAT
Diff:   Differential for on/off control




                                                                            RA                                DA
                          RA                    DA                          PB                                PB
                          PB                    PB                   2             3                    2            3
                 2                 3        2        3
                                                                     1      K          4                1      K         4
                 1        K        4        1   K    4                                 DB
                                                                                       1                    TIME
                                   DB                                                                        10
                                    1

                                                                                                                     I
                                                                            0          K        2       5 I              15
                                                                                                              Min.
                          0        K    2




                                                         TC-89X4 (DAT)
TC-89X1 (0…10 V)




                                                                      RA                                     DA
                                                                     DIFF                                   DIFF
                     PB                                        0.8           1.4                    0.8              1.4
                     I
                                                               0.2   K      2                       0.2       K      2

             2
             I            I    8
                     K
                                                                                            DB
                                                                                             1
                 Tn (TI)
                 5 Min.
                                                                                   0                2
                                                                                            K




TC-89X3 (PAT) (factory default – jumper closed            TC-89X6 (ON/OFF)
                         TI= 4 min)




Factory settings: All trimmers are set at middle value.


ES-8930
No back adjustment



F30
        TC-8900                                                                                                           5



        Operation
        SP:    Setpoint
        PB:    Proportional band
        DB:    Dead band
        BSB:   Standby offset
        BOF:   “Window open” offset


        2x0…10V Outputs (e.g. 4-pipe system)

                                       BOF                                                         BOF
         Output
                                              BSB    RA PB                         DA PB        BSB

           100 %




                                                                                                               Process
               0%
                                                                                                               Variable
                                         Off                   DB        DB                        Off
                                               Standby                                  Standby
                                                         Comfort              Comfort
                                                                    SP


        1x0…10V DA or RA Output (2-pipe system with change-over, use the “RA” output of the controller)


Output             BOF                                         Output                                          BOF

                          BSB   RA PB                                                           RA PB    BSB

100 %                                                          100 %




                                              DB                                        DB


 0%                                                 Process                                                          Process
                                                                    0%
                                                    Variable                                                         Variable

                    Off                        SP                                 SP                           Off
                          Standby                                                                   Standby
                                    Comfort                                                  Comfort


        RA (Reverse acting)                                                   DA (Direct acting)




                                                                                                                     F30
  6                                                                                                          TC-8900

  2XDAT Outputs (e.g. 4-pipe system)

Output                                                                                BOF
                              BOF


                             BSB            RA PB                      DA PB         BSB

      100 %




         0%                                                                                             Process

                                                                                                        Variable
                                                     DB        DB
                       Off                                                                  Off
                              Standby                                         Standby
                                                          SP
                                                Comfort             Comfort


  1XDAT DA or RA Output (2-pipe system with change-over, use the “RA” output of the controller)



 Output                 BOF
                                                           Output                                 BOF


                       BSB          RA PB                                          RA PB    BSB

   100 %                                                   100 %




                                               DB                             DB


                                                    Process                                                        Process
        0%                                                      0%

                                                    Variable                                                       Variable
                 Off                                                     SP                        Off
                       Standby                                                        Standby
                                               SP

                                     Comfort                              Comfort

  RA (Reverse acting)                                                DA (Direct acting)




  F30
TC-8900                                                                                                                      7

2xOn/Off Outputs (e.g. 4-pipe system)


Output                     BOF                                                              BOF
                                     BSB       RA DIF                 DA DIF          BSB

 100 %




                                                                                                                      Process
    0%
                                                         DB DB                                                        Variable

               Off                                                                                        Off

                          Standby                                                      Standby
                                           Comfort             SP            Comfort



1xOn/Off DA or RA Output (2-pipe system with change-over, use the “RA” output of the controller)


   Output                                                           Output

                        BOF                                                                             BOF
                                      RA DIF                                            RA DIF
                               BSB                                                                BSB

   100 %                                                             100 %




                                               DB                                 DB


                                                    Process                                                           Process
         0%                                                            0%
                                                    Variable                                                           Variable
                                Comfort        SP                                SP     Comfort
                     Standby                                                                       Standby
              Off                                                                                               Off



    RA (Reverse acting)                                                        DA (Direct acting)




                                                                                                                         F30
8                                                                                                                             TC-8900


Wiring Diagram
The following drawings indicate the connection diagrams of the different stand alone models and Remote
Setpoint Module.
The contacts have the following functions:
Window contact (      ):     Window closed = contact closed
Dir /Reverse contact (    ): Direct (summer) = contact closed
                             Reverse (winter) = contact open
A change-over thermostat can be connected to terminals 7 and 8. In that case the internal contact must
be fixed at winter (open).

Models                                Diagram n°                         Models                            Diagram n°
TC-8903-1131-WK                       1                                  TC-8903-1151-WK                   1
TC-8901-2131-WK                       2                                  TC-8903-1152-WK                   1
TC-8904-2131-WK                       1
TC-8906-2131-WK                       1                                  TC-8903-1183-WK                   3
                                                                         TC-8901-1283-WK                   4
TC-8903-1132-WK                       1
TC-8901-2132-WK                       2                                  TC-8933-1112-W                    5
TC-8904-2132-WK                       1                                  TC-8931-2112-W                    5
TC-8906-2132-WK                       1                                  TC-8934-2112-W                    5
                                                                         TC-8936-2112-W                    5
                                                                         ES-8930-3131-WK                   5



Diagram 1                                                                      Note:
                                                                               On TC-890X Window Jumper factory set.      8       9
                                                                               Remove when window input is used.
                                 2 x DAT (TC-8904-21xx-WK)
                               2 x ON/OFF (TC-8906-21xx-WK)



                                           Com



                                1 x PAT (TC-8903-11xx-WK)


                                            M          15 VDC
             24 VAC Com
                  24 VAC                                                                                     Remote Sensor
                                           Com                                                            (TC-8903/4/6-x1x2-WK)


                           1   2      3      4     5     6                7     8    9 10 11 12                   OR

                                                                                                            Built-in Sensor
                                                                                                        (TC-8903/4/6-x1x1-WK)




PAT models (TC-8903) : terminals 3 & 5 functions

        Jumper Action Position                                  Temperature (*)                         Terminal Energised
                                                                                                      3                    5
                                                                                                     ON                  OFF
                      RA                                           Set point                        OFF                    OFF
                                                                                                    OFF                    ON
                                                                                                    OFF                    ON
                      DA                                           Set point                        OFF                    OFF
                                                                                                    ON                     OFF
(*)   Temperature increase                             Temperature decrease




F30
TC-8900                                                                                                                            9

Diagram 2
                                            15 VDC
                        RA               DA
                      0...10 V       0...10 V
24 VAC Com
                              Com                                                            Remote Sensor
     24 VAC
                                                                                           (TC-8901-21x2-WK)


                                                                                                    OR
              1   2     3        4         5       6        7       8       9 10 11 12
                                                                                             Built-in sensor
                                                                                           (TC-8901-21x1-WK)




Diagram3


                                 1 x PAT
                                                                                     0...10 VDC
                                                                                        input
                                  M
                                                   15 VDC                            Com

                                     Com
24 VAC Com
     24 VAC




              1   2       3          4         5       6        7       8     9 10 11 12




Diagram4


                                                                                       0...10 VDC
                                                                                          input
                                                   15 VDC
                          RA                 DA
                        0...10 V         0...10 V                                      Com
24 VAC Com
     24 VAC
                                 Com



              1   2         3        4         5       6        7       8     9 10 11 12




                                                                                 Note:
                                                                                 On TC-890X Window Jumper factory set.   8   9
                                                                                 Remove when window input is used.



                                                                                                                                 F30
10                                                                                                                   TC-8900

Diagram 5

     ES-8930-3131-WK
                                                                                SetPoint




                                                                                                                     Com


     1     2      3 18 19 6                                 7           8                            9 10 11 12




                                                                                 Stand-by/Window Status
                                                                Signal common                                        Signal common   Temperature
                                     15 VDC           Dir/Rev                                             Setpoint



         See all in one models
          connection diagram




     1     2      3      4       5       6                  7           8                            9 10 11 12


     TC-8930




 Note:
 On ES-8930 Window Jumper factory set.
                                              18 19
 Remove when window input is used.




F30
          TC-8900                                                                                       11




          Dimensions (in mm)
                     80                               33


               20


     16                   24
                                    Set Point
                                    Dial

80                        28
     12

                °C

                                    Mode
                                    LED

                                    Occupancy
                                    Button
                                                           tmtbdim




          TC-8900 series stand alone and ES-8930
          TC-8930 series has the same external dimensions as TC-8900, without setpoint dial, push button,
          LED and sliding cover.




                                                                                                      F30
12                                                                                                                                   TC-8900




Specifications
                             Models                         TC-89x0                                          ES-8930
                             Supply                      24VAC ±15%                                  Supplied by TC-8930

          Power consumption                          1.5 VA with no load                                          ---

                             Output        TC-89x1: 0…10V 10mA max                      ---
                                           TC-89x3/4/6: triac 0,5A max
                                                        24VAC
          Sensor ricalibration             CW + 0.8 °C                                  ---
                                           CCW – 0.8 °C
                 Remote sensor             • NTC K10 10kΏ at 25°C (TE-9100-8502 or TS-9104 Sensor
                                                                       series)
                                           •   0…10V (input impedance >50kΩ) (TS-9101, HT-9000, PS-910x
                                                                               PT-910x Sensor series)

            Ambient operating                                                        0…50°C
                 temperature
                 Humidity range                                           0 to 95% not condensing

         Storage temperature                                                        -20 +70°C

                  Mode indicator           Red LED to indicate comfort (ON), standby (blinking), off (OFF), not
                                           available on TC-8930
                          Mounting         Direct surface mount, plastic base for surface mount with wiring
                                           conduits, and recessed wall box and panel mounting kits. (See
                                           Ordering Codes.)
                           Housing         Material: ABS + polycarbonate, self-extinguishing VO UL94.
                                           Protection: IP30 (IEC529)
                                           Color: RAL-9010 pure white
     Dimensions (H x W x D)                80 mm x 80 mm x 33 mm


               Shipping Weight             0.15 kg

                     Compliance:           EMC (89/336 EEC) according to the standard EN 50081-1
                                           and EN 50082-1

* Note: other technical characteristics can be found in page 2
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these
specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages resulting from
misapplication or misuse of its products.




Johnson Controls International, Inc.
Headquarters: Milwaukee, WI, USA
European Headquarters: Westendhof 8, 45143 Essen, Germany
European Factories: Lomagna (Italy), Leeuwarden (The Netherlands), Essen (Germany)
Branch Offices: principal European Cities
This document is subject to change without notice                                                                            Printed in Europe

F30


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.