SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Room Command Module RS-1100 Series

Вид документаТехнічний паспорт
ВиробникJCI
МоделіRS-1140-0000, RS-1150-0000, RS-1160-0000, RS-1160-0005, RS-1180-0000, RS-1180-0005, RS-1190-0000, RS-1190-0005
Група обладнанняautomation
Мова документаанглійська
Розмір файлу1.2 МБ

Про документ

The RS-1100 Series Room Command Modules are room units for use with Johnson Controls Facility Explorer Series or System 91 controllers. They provide a 0…10 V signal directly proportional to the sensed temperature and let the occupant view space temperature and adjust the setpoint via an LCD display and dial (on display models) or a simple dial/pushbutton (on non-display models). Models are available with or without LCD display, setpoint adjustment dial, temporary occupied override function, and fan speed selection.

Ключові дані

output signal0 to 10 VDC (linear in the range of 0 to 40 °C)
sensing elementPt1000 class A / class B, EN 60751
power requirement15 VDC ± 5% or 24 VDC ± 15% / 24 VAC ±15%, 50/60 Hz
ambient operating conditions0 to 50 °C, 10 to 90% RH non condensing (max. 30 °C dew point)
protection classIP30 (EN 60529)
accuracy (models with display)±0.5°C
setpoint adjustment range±3 °C or 12...28 °C
enclosure materialABS+PC; self extinguishing HB UL 94

Застосування

  • Space temperature sensing in rooms controlled by TC-9100 Series, SC-9100 Series, DC-9100 Series, DX-9100 Series, FX Series controllers (except FX05)
  • Public buildings and hotels
  • Occupant comfort control: setpoint adjustment, temporary occupancy override, fan speed selection

Особливості

  • Modern cover which snaps onto a plug-in mounting base; easy installation
  • Compact backlit display with time out, suitable for dimly lit conditions
  • Big temperature setpoint adjustment dial for easy operation
  • Integrated temporary override function on LCD display models; pushbutton on non-display models
  • Fan speed selection button on models with display (Auto-OFF-1-2-3)
  • Terminals located on mounting base for easy wiring and commissioning
  • Green LED indicates occupation mode status
  • Maintenance symbol shows temperature sensor failure

Технічні дані

Parameter Value
Power requirement 15 VDC ± 5% (models without display); 15 VDC ± 5% or 24 VDC ± 15%, 24 VAC ±15%, 50/60 Hz (models with display)
Power consumption 0.1 VA no load / 0.15 VA max load (without display); 1 VA no load / 1.5 VA max load (with display)
Ambient operating conditions 0 to 50 °C, 10 to 90% RH non condensing (and max. 30 °C dew point)
Ambient storage conditions -40 to 70 °C, 5 to 95% RH non condensing (and max. 30 °C dew point)
Sensing element Pt1000 class A, EN 60751 (output signals table); Pt1000 class B, EN 60751 (sensing element row)
Output signal, ambient temperature 0 to 10 VDC (linear in the range of 0 to 40 °C)
Output signal, temperature setpoint 0 to 10 VDC, linear in the range of 0 to 40 °C (actual range 3 to 7 V)
Output signal, temporary occupancy request Momentary contact switch (5 V at 1 mA) without display; Open Collector - 1 V @ 2 mA max. with display
Output signal, fan speed override --- (without display); 0...10 VDC (with display, Auto-OFF-1-2-3)
Output load min. 5 kΩ − max. 2 mA
Accuracy 3.5% from 0 to 10°C; 1.2% from 10 to 30°C; 3.5% from 30 to 40°C (without display); ±0.5°C (with display)
Operation status indication Green LED for occupation mode indication and symbol for sensor failure; 3-digit LCD display for temperature indication (resolution: 0.5 °C) and 6 symbols for Fan Speed (with display)
Terminations Terminal block with screw terminals in base for 1,5 mm² / 14 AWG (max.) wires
Mounting Direct surface mounting; plastic base for surface mount with wiring conduits available on request
Enclosure material ABS+PC; self extinguishing HB UL 94
Colours Enclosure - Base - Occupancy Override Button: RAL9016 (GE86280); Setpoint Dial: RAL7047 (GE GY81118); Backlight: White
Protection class Enclosure: IP30 (EN 60529)
Dimensions (H x W x D) RS-1140-0000 / RS-1150-0000: 80 mm x 80 mm x 32 mm; RS-1160-000x / RS-1190-000x: 80 mm x 80 mm x 35 mm; RS-1180-000x: 80 mm x 80 mm x 35 mm
Shipping weight 0,2 kg

Варіанти замовлення

Ordering code LCD Display Setpoint Adjustment Dial Range Temporary Occupancy Override Function Fan Speed Selection
RS-1140-0000 --- --- --- ---
RS-1150-0000 --- --- Pushbutton ---
RS-1160-0000 --- 12...28 °C Pushbutton ---
RS-1160-0005 --- -...+ Pushbutton ---
RS-1180-0000 Yes 12...28 °C Integrated ---
RS-1180-0005 Yes -...+ Integrated ---
RS-1190-0000 --- 12...28 °C --- ---
RS-1190-0005 --- -...+ --- ---
RS-1180-0002 Yes 12...28 °C Integrated Yes
RS-1180-0007 Yes -...+ Integrated Yes

Accessories (order separately):

  • TM-1100-8931 — Plastic Surface Mounting Kit
  • TM-9100-8900 — Pointed tool for enclosure opening

Допуски та стандарти

  • CE Directive: 2004/108/EC, EN 61000-6-3, EN 61000-6-2
  • Sensing element per EN 60751
  • Protection class per EN 60529

Позиції каталогу з цим документом

Текст документа

RS-1100 Series Room Command Module
Product Bulletin
                                                                                                     PB_RS-1100
                                                                                               Issue Date 09 2009




The RS-1100 Room Command Modules
are designed for use with Facility Explorer Series
or System 91 controllers from Johnson Controls
and provides a 0…10 V signal directly proportional
to the sensed temperature.
Models are available with and without LCD display,
room temperature setpoint adjustment dial,
temporary occupied override function, and fan speed
selection.
The LCD display and the dial on the front
of the module allow the room occupant to view the
space temperature and adjust the temperature
setpoint. Modules with LCD display will automatically
request the temporary occupied (bypass) mode
when the dial is moved during unoccupied or
standby periods.
On models without LCD display this function
is activated by means of the temporary occupied
button on the left side of the module.




Features and Benefits
 Features                                   Benefits
 Modern and attractive cover which snaps    Blends in with room decor. Easy installation.
 onto a plug-in mounting base
 Compact Display for temperature            Easy to read
 indication
 Display is back lighted with time out      Suitable for dimly lit conditions
 Big temperature setpoint adjustment dial   Easy operations for the user
 All models available with or without       Covers a large number of applications in public buildings and hotels
 occupancy override
 Integrated Temporary override function     Easy override without the need of an additional push button
 on LCD display models
 Terminals located on mounting base         Easy wiring and commissioning
 Models with display available with Fan     Covers a large number of applications
 Speed Button




                                            RS-1100 Series Room Command Module - Product Bulletin                  1
Environmental and Comfort Data                          Fan Speed Override
for the Occupant                                        The user can press the fan pushbutton to change
All RS-1100 Series Room Command Modules                 the fan speed. The actual fan status is shown by the
provides a 0...10 V signal directly proportional        speed bars and the AUTO symbol disappears to
to the sensed temperature.                              confirm a manual override condition. When the fan is
                                                        stopped in the manual mode, the OFF symbol
Models without LCD Display without                      appears.
Temperature Dial
                                                        Pressing the pushbutton until the AUTO symbol
These models are used for space temperature             appears cancels a manual override and restores
sensing only.                                           automatic fan speed control according to the room
Models without LCD Display                              temperature and setpoint.
with Temperature Dial                                   Fan Speed Override Display
The setpoint dial indicates the desired room
temperature setpoint.                                                               LCD Display
                                                         Fan Speed
When the controller is not in occupied mode,                                        Three speed
the green LED blinks slowly. Operating the
pushbutton will set the controller into temporary            Auto                      AUTO
occupied mode and the LED will go steady
indicating the comfort mode.
                                                              Off                       OFF
Models with LCD Display
The room command module displays the space
temperature. When the occupant is moving the dial         1st speed
the setpoint is displayed with a slow blink cycle.
The maintenance symbol of the display can show:           2nd speed
•   Temperature Sensor Failure
Controlling Comfort and the                               3rd speed
Environment
The RS-1100 room command modules with
Temperature Dial are configured to allow the
occupant to adjust or override operating parameters     Installation
of the connected controller.                            The room command module has a separable base
                                                        with wiring terminals. The base is installed first and
Set point adjust
                                                        the power and network wiring can be completed and
The set point of the controller can be adjusted for     checked before installing the electronic circuits that
a warmer or cooler temperature within the range         are located in the room module cover.
of ±3 °C or to a specific temperature within a range
of values such as 12 to 28 °C using the dial on the     This procedure provides the easiest and safest way
face of the module.                                     to install the control system and avoids accidental
                                                        damage to the electronic circuits when being
Temporary occupancy override                            mounted in the room on the construction site.
Outside of the normal occupancy periods, in the
evening or on the weekend for example, one touch        A surface mounting kit is available for the Room
on the dial (for models with LCD display) or            Command Module.
pushbutton (for models without display) will give the
occupant comfort conditions for a set period of time.
The green LED is configured to slowly blink when
the controller is not in occupied or temporary
occupied mode.




2     RS-1100 Series Room Command Module - Product Bulletin
Mounting                                                 Mounting Kit
Direct Wall Mounting                                     They may also be mounted by using the mounting kit
                                                         shown. The wiring must be entered from the back.
The RS-1100 room sensors are suitable for direct
wall mounting using two of the four screw holes
                                                                                   U P                OB EN
on the base.
•   Choose an appropriate place to achieve
                                                                                       58
    good control of the ambient temperature.
    The room temperature element only senses                                                          5.0           78
    the temperature at the place where it is
    mounted.                                                                                3.5

•   When mounting ensure that there is sufficient
    space for air circulation but do not mount
    the sensor near windows or doors so as to avoid
    draughts that will falsify measurements.                     25                         78

•   Put insulation material in the wiring conduit to                                                  11
    prevent introduction of air from outside the room.                                                17
                                                                                            13
The sensor should not be exposed to direct radiation                                        20
(lamps, radiators, etc.) or to the sun, as this would
lead to incorrect measurement.                               Figure 2: TM-1100-8931 Surface Mounting Kit

                                                         •    Remove one of the notches (A) with a suitable
                                                              tool.

                                                                        U P        OB EN
                                                                                                                A
                                                                                   B




                                                         •    Mark the position of the holes (B) on the wall and
                                                              drill holes 5 mm in diameter. Insert plastic plugs
                                                              into holes.


                                                                                                            D
                                                                               C


        Figure 1: RS-1100 Mounting Base




                                                                                       C o n d u it

                                                         •    Position and fix the mounting base to the wall
                                                              using the two long screws (C) provided in the kit.
                                                         •    Fix the base of the RS-1100 to the mounting
                                                              base using the two short screws (D) provided in
                                                              the kit.


                                            RS-1100 Series Room Command Module - Product Bulletin                        3
Wiring
•   All wiring must be in accordance with local
    regulations and national rules.
•   Do not attempt field repairs. If the transmitter is
    not operating properly, even though it is wired
    correctly, it should be replaced.

            WARNING
            When wiring or servicing make sure
            that:
            • The electric voltage to the sensor is       Figure 6: RS-1180-0000 and RS-1180-0005
              switched off to avoid possible
    !         damage to the equipment, personal
              injury or shock.
            • You do not touch or attempt to
              connect or disconnect wires when
              electric power is on.




                                                          Figure 7: RS-1180-0002 and RS-1180-0007




              Figure 3: RS-1140-0000




                                                          Figure 8: RS-1190-0000 and RS-1190-0005




              Figure 4: RS-1150 - 0000




    Figure 5: RS-1160-0000 and RS-1160-0005


4       RS-1100 Series Room Command Module - Product Bulletin
Dimensions in mm and Printings




                             Figure 9: RS-1140-0000




                             Figure 10: RS-1150-0000




                             Figure 11: RS-1160-0000




                                 RS-1100 Series Room Command Module - Product Bulletin   5
                                   Figure 12: RS-1160-0005




                                   Figure 13: RS-1190-0000




                                   Figure 14: RS-1190-0005




6   RS-1100 Series Room Command Module - Product Bulletin
Figure 15: RS-1180-0000 and RS-1180-0005




Figure 16: RS-1180-0002 and RS-1180-0007




         RS-1100 Series Room Command Module - Product Bulletin   7
Ordering Codes
Room Command Module
                              Interface to Occupant                                                    Suitable Controllers




                                                        Fan speed Selection
                                                                              TC-9100 Series   SC-9100 Series   DC-9100 Series   DX-9100 Series
                                                                                                                                                    FX Series

                LCD Display
 Ordering                      Setpoint    Temporary
 Codes                                     Occupancy
                              Adjustment
                                            Ovveride
                              Dial Range    Function                                                                                              (Except FX05)


 RS-1140-0000     ---             ---          ---          ---               Yes              Yes              Yes              Yes                 Yes
 RS-1150-0000     ---             ---      Pushbutton       ---               Yes              Yes              Yes              Yes                 Yes
 RS-1160-0000     ---         12...28 °C   Pushbutton       ---               Yes              Yes              Yes              Yes                 Yes
 RS-1160-0005     ---            -...+     Pushbutton       ---               Yes              Yes              Yes              Yes                 Yes
 RS-1180-0000   Yes           12...28 °C   Integrated       ---               Yes              Yes              Yes              Yes                 Yes
 RS-1180-0005   Yes              -...+     Integrated       ---               Yes              Yes              Yes              Yes                 Yes
 RS-1190-0000     ---         12...28 °C       ---          ---               Yes              Yes              Yes              Yes                 Yes
 RS-1190-0005     ---            -...+         ---          ---               Yes              Yes              Yes              Yes                 Yes
 RS-1180-0002   Yes           12...28 °C   Integrated   Yes                   Yes              Yes              Yes              Yes                 Yes
 RS-1180-0007   Yes              -...+     Integrated   Yes                   Yes              Yes              Yes              Yes                 Yes

Accessories (order separately)
 Ordering Codes                   Description
 TM-1100-8931                     Plastic Surface Mounting Kit
 TM-9100-8900                     Pointed tool for enclosure opening




8    RS-1100 Series Room Command Module - Product Bulletin
Technical Specifications
Products                                Models without Display                                 Models with Display
                                            RS-1140-0000
                                            RS-1150-0000
                                            RS-1160-000x                                           RS-1180-000x
                                            RS-1190-000x
Power Requirement                                                                                 15 VDC ± 5%
                                              15 VDC ± 5%                                        24 VDC ± 15%
                                                                                             24 VAC ±15%, 50/60 Hz
Power Consumption                            0.1 VA, no load                                       1 VA, no load
                                            0.15 VA, max load                                    1.5 VA, max load
Ambient Operating           0 to 50 °C
Conditions                  10 to 90% RH non condensing (and max. 30 °C dew point)
Ambient Storage             -40 to 70 °C
Conditions                  5 to 95% RH non condensing (and max. 30 °C dew point)
Sensing Element             Pt1000 class A, EN 60751
Output Signals              Ambient Temperature:                                 Ambient Temperature:
                            0 to 10 VDC (linear in the range of 0 to 40 °C)      0 to 10 VDC (linear in the range of 0 to 40 °C)
                            Temperature Setpoint:                                Temperature Setpoint:
                            0 to 10 VDC, linear in the range of 0 to 40 °C       0 to 10 VDC, linear in the range of 0 to 40 °C
                            (actual range 3 to 7 V)                              (actual range 3 to 7 V)
                            Temporary Occupancy Request:                         Temporary Occupancy Request:
                            Momentary contact switch (5 V at 1 mA)               Open Collector - 1 V @ 2 mA max.
                            Fan Speed Override:                                  Fan Speed Override (Auto-OFF-1-2-3):
                            ---                                                  0...10 VDC
Output load                 min. 5 kΩ − max. 2 mA
Sensing Element             Pt1000 class B, EN 60751
Accuracy                    3.5% from 0 to 10°C
                            1.2% from 10 to 30°C                                 ±0.5°C
                            3.5% from 30 to 40°C
Operation Status                                                                 3-digit LCD display for temperature indication
Indication                  Green LED for occupation mode indication             (resolution: 0.5 °C) and 6 symbols for Fan Speed
                                                                                 and symbol for sensor failure.
Terminations                Terminal block with screw terminals in base for 1,5 mm² / 14 AWG (max.) wires
Mounting                    Direct surface mounting.
                            Plastic base for surface mount with wiring conduits available on request
                            (see “Ordering Codes”)
Enclosure Material          ABS+PC; self estinguishing HB UL 94
Colours                     Enclosure - Base - Occupancy Override Button: RAL9016 (GE86280)
                            Setpoint Dial: RAL7047 (GE GY81118)
                                                                                 Backlight: White
Protection Class            Enclosure: IP30 (EN 60529)
Dimension                   RS-1140-0000 / RS-1150-0000
(H x W x D)                 80 mm x 80 mm x 32 mm                                RS-1180-000x
                            RS-1160-000x / RS-1190-000x                          80 mm x 80 mm x 35 mm
                            80 mm x 80 mm x 35 mm
Shipping Weight             0,2 kg
                            CE Directive:
        Compliance          2004 / 108 / EC         EN 61000-6-3, EN 61000-6-2
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.




Johnson Controls International, Inc.
Headquarters: Milwaukee, Wisconsin, USA
Branch Offices: Principal Cities World-wide

www.johnsoncontrols.com                            RS-1100 Series Room Command Module - Product Bulletin                              9


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.