| Вид документа | Інструкція |
|---|---|
| Виробник | JCI |
| Моделі | LN-VSTAT, LN-PSTAT, LIT-12011302, LN-VSTAT-1, LN-PSTAT-1 |
| Група обладнання | automation |
| Мова документа | англійська |
| Розмір файлу | 0.5 МБ |
Про документ
Installation instructions for the Johnson Controls LN Series LN-VSTAT-1 and LN-PSTAT-1 wall sensors, which connect to the SMRT ports of LN Series controllers. The SMRT ports supply power and serial communications to the sensor, which provides precision local temperature sensing, allows occupants to adjust the local setpoint, and displays occupancy status, local space temperature, and outside air temperature.
Ключові дані
| Ambient temperature range | 32º to 158ºF (Oº to 70ºC) |
|---|---|
| Relative humidity | 0% to 95%, non-condensing |
| Communication connection | SMRT+ / SMRT- serial inputs |
| LON cable type | Level IV 22 AWG (0.65 mm), unshielded |
| Stub length for bus topology | less than 3 meters |
Застосування
- The LN-VSTAT-1 works with the LN-VAVFLFS-1 and LN-VVTLFS-1 controllers.
- The LN-PSTAT-1 works with the LN-PFCU-1 and LN-PFCUA-1 controllers.
- Portable VAV balancing using the LN-VSTAT connected via an 1/8 in. audio plug to an LN-Sensor communication jack.
Особливості
- Connects to the SMRT ports of the LN Series controllers, which supply power and serial communications.
- Occupants can adjust the local setpoint and view occupancy status, local space temperature, and outside air temperature.
- Optional LON network connection at Terminals 3 and 4; access to the LON network with a laptop through a 1/8 in. communications jack on the LN-VSTAT.
- Can be used as a portable device for VAV balancing with an 1/8 in. mono or stereo audio cable.
- Not designed for outdoor use.
Технічні дані
| Parameter | Value |
|---|---|
| Compatible controllers (LN-VSTAT-1) | LN-VAVFLFS-1, LN-VVTLFS-1 |
| Compatible controllers (LN-PSTAT-1) | LN-PFCU-1, LN-PFCUA-1 |
| Ambient operating temperature | 32º to 158ºF (Oº to 70ºC) |
| Relative humidity | 0% to 95%, non-condensing |
| Controller connection terminals | SMRT+, SMRT- |
| Optional network terminals | LON (Terminals 3 and 4) |
| Communications jack | 1/8" jack |
| Approved LON communication cable | Level IV 22 AWG (0.65 mm), UNSHIELDED, one or two pair |
| Bus topology requirement | stub length less than 3 meters |
| Free topology requirement | stub length greater than 3 meters |
| Wire stripping length | 1/4 in. per wire |
| Conductor material | Copper conductors only |
Варіанти замовлення
- LN-VSTAT-1 — sensor for use with LN-VAVFLFS-1 and LN-VVTLFS-1 controllers.
- LN-PSTAT-1 — sensor for use with LN-PFCU-1 and LN-PFCUA-1 controllers.
- Document code No. LIT-12011302.
Допуски та стандарти
- United States: Compliance Statement (Part 15.19) — this device complies with Part 15 of the FCC Rules; operation is subject to two conditions (may not cause harmful interference; must accept interference received). Warning (Part 15.21): changes or modifications not expressly approved could void the user's authority to operate. To comply with FCC RF exposure requirements, the transmitter should only be used or installed where there is at least 20cm separation distance between the antenna and all persons.
- Canada: Industry Canada Statement — this Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
- Wiring must comply with the National Electrical Code and all local regulations.
Текст документа
LN Series LN-VSTAT and LN-PSTAT Sensors
Installation Instructions
Code No. LIT-12011302
LN-VSTAT-1, LN-PSTAT-1 Issued April 24, 2014
Supersedes November 9, 2007
Applications • Allow for proper clearance of device casing and
wiring terminals for easy access, hardware
The LN Series LN-VSTAT and LN-PSTAT sensors are
configuration, and maintenance.
specifically designed to connect to the SMRT ports of
the Johnson Controls’ LN Series controllers. The • The sensor is designed to operate under the
LN-VSTAT-1 works with the LN-VAVFLFS-1 and following conditions:
LN-VVTLFS-1 controllers. The LN PSTAT-1 works with
• Ambient temperature between 32º to 158ºF
the LN-PFCU-1 and LN-PFCUA-1 controllers. The
(Oº to 70ºC)
SMRT ports supply power and serial communications
to the LN-VSTAT and LN-PSTAT sensors. The device • Relative humidity from 0% to 95%,
provides precision local temperature sensing and it non-condensing
allows occupants to adjust the local setpoint and view
• Ensure proper ventilation of devices and avoid
the occupancy status, local space temperature, and
areas where corroding, deteriorating, or explosive
outside air temperature.
vapors, fumes, or gasses may be present.
North American Emissions Compliance IMPORTANT: Work in a static-free area. Discharge
United States static electricity by touching a known, securely
grounded object. Do not handle the controller without
Compliance Statement (Part 15.19) proper protection against static discharge. Use a wrist
This device complies with Part 15 of the FCC Rules. strap when handling the controller. Secure the wrist
Operation is subject to the following two conditions: strap clamp to earth ground.
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired
operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the
party responsible for compliance could void the user’s
authority to operate the equipment.
To comply with FCC RF exposure requirements for mobile
transmitting devices, this transmitter should only be used
or installed at locations where there is at least 20cm
separation distance between the antenna and all persons.
Canada
Industry Canada Statement
This Class (A) digital apparatus meets all the requirements
of the Canadian Interference-Causing Equipment
Regulations.
Le terme «IC» précédant le numéro de d'accréditation/
inscription signifie simplement que le produit est conforme
aux spécifications techniques d'Industry Canada.
Installation
For proper installation and subsequent operation of the
LN-VSTAT and LN-PSTAT sensors, follow these
recommendations:
LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions 1
Dimensions
Figure 1: LN-VAVLF, LN-VAVCF, and LN-VVTLF Controller Dimensions
Mounting • Install the sensor away from discharge air grills
Location Considerations • Install the sensor away from areas where it can be
The LN-VAV/VVT controllers are designed for easy affected by the sun
installation. However, certain conditions apply when • Install the sensor in an area that provides proper
choosing a location for the device: device ventilation. Ensure nothing restrains air
• The LN-VSTAT and LN-PSTAT sensors should not circulation to the sensor.
be installed on an outside wall Note: The LN-VSTAT and LN-PSTAT sensors are not
• Install the sensor away from any heat source designed for outdoor use.
2 LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
Installation 11. Flip the printed circuit board back into place.
1. Unscrew the security screw on the bottom of the 12. .Flip down the front cover verify it clips tightly into
casing (Figure 2). place.
13. Install the security screw (Figure 3).
FIG:mntng_bs
Figure 2: Mounting the LN-VSTAT and
LN-PSTAT sensors
2. Open the cover by pulling the bottom side of the
casing outwards. Flip printed circuit board to
access mounting hole.
3. Pull cables 6 in. out of the wall and insert them in
the central hole of the base.
4. Align the base and mark the location of the two
mounting holes on the wall. Ensure the correct side
of the base is facing upwards.
5. Remove the device and drill holes, if necessary.
6. Install anchors into the wall, if necessary.
7. Ensure the mounting surface is flat and clean.
8. Insert screws in mounting holes of the base. Do not
overtighten the screws.
Figure 3: LN-VSTAT and LN-PSTAT Sensors
9. Strip each wire 1/4 in.
Security Screw
10. Gently push excess wiring back into the wall.
LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions 3
Wiring The LN-VSTAT and LN-PSTAT sensors draw power
and communicate with the associated controller over
IMPORTANT: Make all wiring connections in
the SMRT wiring using a serial communication protocol.
accordance with the National Electrical Code and all
Figure 4 shows the terminal wiring details.)
local regulations. Use Copper conductors only. Do not
exceed the control’s electrical rating.
LON (Optional)
CAUTION: Risk of Electric Shock.
Disconnect power supply before making
! electrical connections to avoid shock.
MISE EN GARDE : Risque de décharge
électrique. SMRT+
LON (Optional)
Débrancher l'alimentation avant de
réaliser tout raccordement électrique afin
d'éviter tout risque de décharge SMRT-
électrique.
1/8" Com. 1 2 3 4
Jack
Figure 4: LN-VSTAT and LN-PSTAT Sensors
Terminal Wiring Details
Wiring the LN-VSTAT and LN-PSTAT Sensors
to a Controller
The LN-VSTAT and LN-PSTAT sensors use a serial
communication protocol and are designed to connect to
the serial inputs labelled SMRT+ and SMRT- on the
LN-VAVLF and LN-VVTLF controller.
Note: The LN-VAVCF controller does not support the
LN-VSTAT and LN-PSTAT sensors.
To wire a wall mounted LN-VAV/VVT controller:
1. Remove the faceplate.
2. Use a screwdriver to press down the tabs located
on the bottom of the sensor to remove the cover.
4 LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
3. Connect the SMRT+ and SMRT- output terminals To connect the LN-VSTAT sensors to an LN-Sensor
of the LN-VSTAT to the SMRT+ and SMRT- input using an 1/8 in. mono or stereo audio cable:
terminals on the LN-VAV/VVT controller (Figure 6).
1. Use the taps on the bottom of the sensor to remove
the sensor face plate.
2. Connect the SMRT+ and SMRT- output terminals
of the LN-VSTAT sensors to two wires that
terminate in the 1/8 in. audio plug (Figure 7).
LN-VAV LN-VSTAT
Figure 6: LN-VSTAT and LN-PSTAT Sensors -
Wired to Controller
Using the LN-VSTAT as a Portable Device
You can use the LN-VSTAT sensors as a portable
device to perform VAV balancing. If an LN-Sensor is
already connected to the VAV that you intend to
balance, directly connect the LN-VSTAT to the
communication jack within the LN Series Sensor. Figure 7: SMRT+ and SMRT- Output Terminals
with Audio Plug
Note: Terminals 1 and 2 of the right most terminal
block within the LN Sensor must be connected to the 3. Remove the LN Sensor faceplate and insert the 1/8
SMRT+ and SMRT- inputs of the VAV controller before in. audio plug into the communication jack. Ensure
you can use the communication jack. Typically, these the two output terminals on the right side of the
connections should have been made when the VAV LN-Sensor are wired to the SMRT+ and SMRT-
controller and LN Sensor were first installed. terminals of the LN-Sensor (Figure 8).
LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions 5
LN-VAV LN Sensor LN-VSTAT
Figure 9: LN-VSTAT and LN-PSTAT sensors Wired
to LN Sensor Using an Audio Plug
Connect 1/8 in. Audio Plug
from LN-VSTATSensor
Figure 8: LN Sensor Wiring
6 LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
INPUT+
OUTPUT+
TO SMRT+ TO SMRT-
(0-10 VDC or 24 VAC)
INPUT+ COM OUTPUT-
1 2 3 4 5 6 C o m 1. C o m.2 S M R T + S M R T-
+ - - + + -
L N-- S E N S O R L N- P S T A T
Figure 10: LN-Sensor to an LN-PSTAT Sensor Wiring Details
Communications Wiring Note: The LN-VSTAT and LN-PSTAT sensors do not
have an effect on the network topology for LON
You can optionally wire Terminals 3 and 4 of the
networks.
LN-VSTAT and LN-PSTAT sensors to the LON
terminals of the controller. Before you insert multiple Note: The Bus topology network configuration allow
wires into any of the terminals on the controller, ensure for easy network troubleshooting for LON
you properly twist the wires together. communication wiring.
You can access the LON network with a laptop by Topology Wiring Choices
plugging into the communications jack on the If the distance between the sensor and the controller
LN-VSTAT with a 1/8 in. audio plug. (stub length) is less than 3 meters a bus topology must
Approved cable types for LON communication is Level be used (Figure 11). If the stub length is greater than 3
IV 22 AWG (0.65 mm), UNSHIELDED. You can use meters, a free topology in a daisy-chain manner must
both one pair and two pair wires. The LON be used (Figure 12).
communication wire is not polarity sensitive and can be Note: In Figure 11 and Figure 12, the wire runs from
laid out in a bus, star, loop, or free topology network the two communication terminals of the LN-VSTAT and
configuration. For loop topology, polarity is important, LN-PSTAT sensors to the LON/NET terminals of a
take special care when connecting the LON network to controller. When you insert multiple wires into the
avoid a short circuit. terminals, ensure you properly twist the wires together
prior to inserting them into the terminal connectors.
7 LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
Figure 11 shows a bus topology (wired in a daisy chain)
with stub length of less than 3 meters.
Bus Bus
Topology Topology
Terminator Terminator
CONTROLLER CONTROLLER CONTROLLER
Stub Length
<3m
Figure 11: Bus Topology, Stub < 3m
Figure 12 shows free topology (with stub) wired in
daisy chain manner.
Free
Topology
Terminator
CONTROLLER CONTROLLER CONTROLLER
Stub Length
>3m
Figure 12: Free Topology, Stub > 3m
The wiring scheme in figure is almost identical to a bus requires a free topology terminator.
topology network, but since the stub length exceeds 3
meters, it becomes a free topology network which
8 LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
For additional information and detailed explanations on Note: Use proper network terminators depending on
network topology and wire length restrictions, refer to the type of network topology used. Failure to do so may
Echelon Corporation’s Junction Box and Wiring result in communication errors between controllers. Do
Guideline for Twisted Pair LONWORKS Networks not use multiple gauges of cable on the same
(Part # 005-0023-01). communication bus, as this may also result in
communication errors.
Troubleshooting
Table 1: Troubleshooting
Problem Possible Cause Solution
Temperature is not read Wrong connection Verify that every connection is properly wired.
properly
Wrong connection Verify that every connection is properly wired.
Temperature setpoint is not
read properly Software configuration Verify that the setpoint is configured correctly according to
the selected sensor model.
Controls Group Metasys® is a registered trademark of Johnson Controls, Inc.
507 E. Michigan Street All other marks herein are the marks of their respective owners.
Milwaukee, WI 53202 © 2014 Johnson Controls, Inc.
LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions 9
Published in U.S.A. www.johnsoncontrols.com