LN-VSTAT — LN-VSTAT and LN-PSTAT sensors installation instructions

Файл за старою адресою не зберігся. Нижче — документ виробника на те саме обладнання.

Вид документаІнструкція
ВиробникJCI
МоделіLN-VSTAT, LN-PSTAT, LIT-12011302, LN-VSTAT-1, LN-PSTAT-1
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.5 МБ

Про документ

Installation instructions for the Johnson Controls LN Series LN-VSTAT-1 and LN-PSTAT-1 wall sensors, which connect to the SMRT ports of LN Series controllers. The SMRT ports supply power and serial communications to the sensor, which provides precision local temperature sensing, allows occupants to adjust the local setpoint, and displays occupancy status, local space temperature, and outside air temperature.

Ключові дані

Ambient temperature range32º to 158ºF (Oº to 70ºC)
Relative humidity0% to 95%, non-condensing
Communication connectionSMRT+ / SMRT- serial inputs
LON cable typeLevel IV 22 AWG (0.65 mm), unshielded
Stub length for bus topologyless than 3 meters

Застосування

  • The LN-VSTAT-1 works with the LN-VAVFLFS-1 and LN-VVTLFS-1 controllers.
  • The LN-PSTAT-1 works with the LN-PFCU-1 and LN-PFCUA-1 controllers.
  • Portable VAV balancing using the LN-VSTAT connected via an 1/8 in. audio plug to an LN-Sensor communication jack.

Особливості

  • Connects to the SMRT ports of the LN Series controllers, which supply power and serial communications.
  • Occupants can adjust the local setpoint and view occupancy status, local space temperature, and outside air temperature.
  • Optional LON network connection at Terminals 3 and 4; access to the LON network with a laptop through a 1/8 in. communications jack on the LN-VSTAT.
  • Can be used as a portable device for VAV balancing with an 1/8 in. mono or stereo audio cable.
  • Not designed for outdoor use.

Технічні дані

Parameter Value
Compatible controllers (LN-VSTAT-1) LN-VAVFLFS-1, LN-VVTLFS-1
Compatible controllers (LN-PSTAT-1) LN-PFCU-1, LN-PFCUA-1
Ambient operating temperature 32º to 158ºF (Oº to 70ºC)
Relative humidity 0% to 95%, non-condensing
Controller connection terminals SMRT+, SMRT-
Optional network terminals LON (Terminals 3 and 4)
Communications jack 1/8" jack
Approved LON communication cable Level IV 22 AWG (0.65 mm), UNSHIELDED, one or two pair
Bus topology requirement stub length less than 3 meters
Free topology requirement stub length greater than 3 meters
Wire stripping length 1/4 in. per wire
Conductor material Copper conductors only

Варіанти замовлення

  • LN-VSTAT-1 — sensor for use with LN-VAVFLFS-1 and LN-VVTLFS-1 controllers.
  • LN-PSTAT-1 — sensor for use with LN-PFCU-1 and LN-PFCUA-1 controllers.
  • Document code No. LIT-12011302.

Допуски та стандарти

  • United States: Compliance Statement (Part 15.19) — this device complies with Part 15 of the FCC Rules; operation is subject to two conditions (may not cause harmful interference; must accept interference received). Warning (Part 15.21): changes or modifications not expressly approved could void the user's authority to operate. To comply with FCC RF exposure requirements, the transmitter should only be used or installed where there is at least 20cm separation distance between the antenna and all persons.
  • Canada: Industry Canada Statement — this Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
  • Wiring must comply with the National Electrical Code and all local regulations.

Текст документа

LN Series LN-VSTAT and LN-PSTAT Sensors
Installation Instructions
                                                                                           Code No. LIT-12011302
LN-VSTAT-1, LN-PSTAT-1                                                                       Issued April 24, 2014
                                                                                      Supersedes November 9, 2007



Applications                                                   •   Allow for proper clearance of device casing and
                                                                   wiring terminals for easy access, hardware
The LN Series LN-VSTAT and LN-PSTAT sensors are
                                                                   configuration, and maintenance.
specifically designed to connect to the SMRT ports of
the Johnson Controls’ LN Series controllers. The               •   The sensor is designed to operate under the
LN-VSTAT-1 works with the LN-VAVFLFS-1 and                         following conditions:
LN-VVTLFS-1 controllers. The LN PSTAT-1 works with
                                                                   •   Ambient temperature between 32º to 158ºF
the LN-PFCU-1 and LN-PFCUA-1 controllers. The
                                                                       (Oº to 70ºC)
SMRT ports supply power and serial communications
to the LN-VSTAT and LN-PSTAT sensors. The device                   •   Relative humidity from 0% to 95%,
provides precision local temperature sensing and it                    non-condensing
allows occupants to adjust the local setpoint and view
                                                               •   Ensure proper ventilation of devices and avoid
the occupancy status, local space temperature, and
                                                                   areas where corroding, deteriorating, or explosive
outside air temperature.
                                                                   vapors, fumes, or gasses may be present.
North American Emissions Compliance                            IMPORTANT: Work in a static-free area. Discharge
United States                                                  static electricity by touching a known, securely
                                                               grounded object. Do not handle the controller without
 Compliance Statement (Part 15.19)                             proper protection against static discharge. Use a wrist
 This device complies with Part 15 of the FCC Rules.           strap when handling the controller. Secure the wrist
 Operation is subject to the following two conditions:         strap clamp to earth ground.
 1. This device may not cause harmful interference, and
 2. This device must accept any interference received,
     including interference that may cause undesired
     operation.
 Warning (Part 15.21)
 Changes or modifications not expressly approved by the
 party responsible for compliance could void the user’s
 authority to operate the equipment.
 To comply with FCC RF exposure requirements for mobile
 transmitting devices, this transmitter should only be used
 or installed at locations where there is at least 20cm
 separation distance between the antenna and all persons.

Canada
 Industry Canada Statement
 This Class (A) digital apparatus meets all the requirements
 of the Canadian Interference-Causing Equipment
 Regulations.
 Le terme «IC» précédant le numéro de d'accréditation/
 inscription signifie simplement que le produit est conforme
 aux spécifications techniques d'Industry Canada.

Installation
For proper installation and subsequent operation of the
LN-VSTAT and LN-PSTAT sensors, follow these
recommendations:




                                          LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions              1
Dimensions




                 Figure 1: LN-VAVLF, LN-VAVCF, and LN-VVTLF Controller Dimensions


Mounting                                               •   Install the sensor away from discharge air grills
Location Considerations                                •   Install the sensor away from areas where it can be
The LN-VAV/VVT controllers are designed for easy           affected by the sun
installation. However, certain conditions apply when   •   Install the sensor in an area that provides proper
choosing a location for the device:                        device ventilation. Ensure nothing restrains air
•   The LN-VSTAT and LN-PSTAT sensors should not           circulation to the sensor.
    be installed on an outside wall                    Note: The LN-VSTAT and LN-PSTAT sensors are not
•   Install the sensor away from any heat source       designed for outdoor use.




2     LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
Installation                                                       11. Flip the printed circuit board back into place.
1. Unscrew the security screw on the bottom of the                 12. .Flip down the front cover verify it clips tightly into
   casing (Figure 2).                                                  place.
                                                                   13. Install the security screw (Figure 3).




                                                    FIG:mntng_bs




       Figure 2: Mounting the LN-VSTAT and
                 LN-PSTAT sensors

2. Open the cover by pulling the bottom side of the
   casing outwards. Flip printed circuit board to
   access mounting hole.
3. Pull cables 6 in. out of the wall and insert them in
   the central hole of the base.
4. Align the base and mark the location of the two
   mounting holes on the wall. Ensure the correct side
   of the base is facing upwards.
5. Remove the device and drill holes, if necessary.
6. Install anchors into the wall, if necessary.
7. Ensure the mounting surface is flat and clean.
8. Insert screws in mounting holes of the base. Do not
   overtighten the screws.
                                                                        Figure 3: LN-VSTAT and LN-PSTAT Sensors
9. Strip each wire 1/4 in.
                                                                                      Security Screw
10. Gently push excess wiring back into the wall.




LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions                                                                3
Wiring                                                   The LN-VSTAT and LN-PSTAT sensors draw power
                                                         and communicate with the associated controller over
IMPORTANT: Make all wiring connections in
                                                         the SMRT wiring using a serial communication protocol.
accordance with the National Electrical Code and all
                                                         Figure 4 shows the terminal wiring details.)
local regulations. Use Copper conductors only. Do not
exceed the control’s electrical rating.



                                                                                                 LON (Optional)
            CAUTION: Risk of Electric Shock.
            Disconnect power supply before making
    !       electrical connections to avoid shock.
            MISE EN GARDE : Risque de décharge
            électrique.                                                              SMRT+
                                                                                                 LON (Optional)
            Débrancher l'alimentation avant de
            réaliser tout raccordement électrique afin
            d'éviter tout risque de décharge                                         SMRT-
            électrique.




                                                           1/8" Com.                1 2          3 4
                                                              Jack
                                                             Figure 4: LN-VSTAT and LN-PSTAT Sensors
                                                                        Terminal Wiring Details

                                                         Wiring the LN-VSTAT and LN-PSTAT Sensors
                                                         to a Controller
                                                         The LN-VSTAT and LN-PSTAT sensors use a serial
                                                         communication protocol and are designed to connect to
                                                         the serial inputs labelled SMRT+ and SMRT- on the
                                                         LN-VAVLF and LN-VVTLF controller.
                                                         Note: The LN-VAVCF controller does not support the
                                                         LN-VSTAT and LN-PSTAT sensors.
                                                         To wire a wall mounted LN-VAV/VVT controller:
                                                         1. Remove the faceplate.
                                                         2. Use a screwdriver to press down the tabs located
                                                            on the bottom of the sensor to remove the cover.




4    LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
3. Connect the SMRT+ and SMRT- output terminals         To connect the LN-VSTAT sensors to an LN-Sensor
   of the LN-VSTAT to the SMRT+ and SMRT- input         using an 1/8 in. mono or stereo audio cable:
   terminals on the LN-VAV/VVT controller (Figure 6).
                                                        1. Use the taps on the bottom of the sensor to remove
                                                           the sensor face plate.
                                                        2. Connect the SMRT+ and SMRT- output terminals
                                                           of the LN-VSTAT sensors to two wires that
                                                           terminate in the 1/8 in. audio plug (Figure 7).




           LN-VAV               LN-VSTAT
   Figure 6: LN-VSTAT and LN-PSTAT Sensors -
                Wired to Controller

Using the LN-VSTAT as a Portable Device
You can use the LN-VSTAT sensors as a portable
device to perform VAV balancing. If an LN-Sensor is
already connected to the VAV that you intend to
balance, directly connect the LN-VSTAT to the
communication jack within the LN Series Sensor.           Figure 7: SMRT+ and SMRT- Output Terminals
                                                                        with Audio Plug
Note: Terminals 1 and 2 of the right most terminal
block within the LN Sensor must be connected to the     3. Remove the LN Sensor faceplate and insert the 1/8
SMRT+ and SMRT- inputs of the VAV controller before        in. audio plug into the communication jack. Ensure
you can use the communication jack. Typically, these       the two output terminals on the right side of the
connections should have been made when the VAV             LN-Sensor are wired to the SMRT+ and SMRT-
controller and LN Sensor were first installed.             terminals of the LN-Sensor (Figure 8).




LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions                                            5
                                                         LN-VAV         LN Sensor        LN-VSTAT
                                                      Figure 9: LN-VSTAT and LN-PSTAT sensors Wired
                                                              to LN Sensor Using an Audio Plug

                  Connect 1/8 in. Audio Plug
                    from LN-VSTATSensor




         Figure 8: LN Sensor Wiring




6   LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
                                            INPUT+

                                            OUTPUT+


                                                                      TO SMRT+   TO SMRT-
                                            (0-10 VDC or 24 VAC)

                        INPUT+   COM        OUTPUT-




                            1      2    3      4       5      6    C o m 1. C o m.2                                   S M R T + S M R T-
                            +      -    -      +       +      -




                                       L N-- S E N S O R                                                  L N- P S T A T
                                 Figure 10: LN-Sensor to an LN-PSTAT Sensor Wiring Details
Communications Wiring                                                                       Note: The LN-VSTAT and LN-PSTAT sensors do not
                                                                                            have an effect on the network topology for LON
You can optionally wire Terminals 3 and 4 of the
                                                                                            networks.
LN-VSTAT and LN-PSTAT sensors to the LON
terminals of the controller. Before you insert multiple                                     Note: The Bus topology network configuration allow
wires into any of the terminals on the controller, ensure                                   for easy network troubleshooting for LON
you properly twist the wires together.                                                      communication wiring.
You can access the LON network with a laptop by                                             Topology Wiring Choices
plugging into the communications jack on the                                                If the distance between the sensor and the controller
LN-VSTAT with a 1/8 in. audio plug.                                                         (stub length) is less than 3 meters a bus topology must
Approved cable types for LON communication is Level                                         be used (Figure 11). If the stub length is greater than 3
IV 22 AWG (0.65 mm), UNSHIELDED. You can use                                                meters, a free topology in a daisy-chain manner must
both one pair and two pair wires. The LON                                                   be used (Figure 12).
communication wire is not polarity sensitive and can be                                     Note: In Figure 11 and Figure 12, the wire runs from
laid out in a bus, star, loop, or free topology network                                     the two communication terminals of the LN-VSTAT and
configuration. For loop topology, polarity is important,                                    LN-PSTAT sensors to the LON/NET terminals of a
take special care when connecting the LON network to                                        controller. When you insert multiple wires into the
avoid a short circuit.                                                                      terminals, ensure you properly twist the wires together
                                                                                            prior to inserting them into the terminal connectors.




7     LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
Figure 11 shows a bus topology (wired in a daisy chain)
with stub length of less than 3 meters.

                             Bus                                                                    Bus
                           Topology                                                               Topology
                          Terminator                                                             Terminator




            CONTROLLER                         CONTROLLER                         CONTROLLER

                                                                  Stub Length
                                                                     <3m




                                       Figure 11: Bus Topology, Stub < 3m
Figure 12 shows free topology (with stub) wired in
daisy chain manner.

                                                                                                  Free
                                                                                                Topology
                                                                                               Terminator




             CONTROLLER                        CONTROLLER                       CONTROLLER

                                                                 Stub Length
                                                                    >3m




                                       Figure 12: Free Topology, Stub > 3m

The wiring scheme in figure is almost identical to a bus    requires a free topology terminator.
topology network, but since the stub length exceeds 3
meters, it becomes a free topology network which


8     LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions
For additional information and detailed explanations on    Note: Use proper network terminators depending on
network topology and wire length restrictions, refer to    the type of network topology used. Failure to do so may
Echelon Corporation’s Junction Box and Wiring              result in communication errors between controllers. Do
Guideline for Twisted Pair LONWORKS Networks               not use multiple gauges of cable on the same
(Part # 005-0023-01).                                      communication bus, as this may also result in
                                                           communication errors.
                                                           Troubleshooting
Table 1: Troubleshooting
 Problem                       Possible Cause              Solution
 Temperature is not read       Wrong connection            Verify that every connection is properly wired.
 properly
                               Wrong connection            Verify that every connection is properly wired.
 Temperature setpoint is not
 read properly                 Software configuration      Verify that the setpoint is configured correctly according to
                                                           the selected sensor model.




Controls Group                                              Metasys® is a registered trademark of Johnson Controls, Inc.
507 E. Michigan Street                                    All other marks herein are the marks of their respective owners.
Milwaukee, WI 53202                                                                        © 2014 Johnson Controls, Inc.

LN Series LN-VSTAT and LN-PSTAT Sensors Installation Instructions                                                          9

Published in U.S.A.                                                                        www.johnsoncontrols.com
