SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

HX-9100 Dew Sensor

Вид документаТехнічний паспорт
ВиробникJCI
МоделіHX-9100-8001, HX-9100-9001
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.2 МБ

Про документ

The HX-9100 Dew Sensor is used to prevent condensation on surfaces such as cold water pipes and windows. It senses the dew point precisely via a conductive polymer sensing element and signals condensation conditions to a controller. Two variants exist: an open collector ON/OFF output (-8001) for digital inputs, and an active 0…10 V output (-9001) for DDC controllers.

Ключові дані

thresholdTypically 90% rH
output0 - 10 Vdc (HX-9100-9001) / open collector (HX-9100-8001)
supply_voltage15VDC ±10%, nominal
hysteresisTypically 1%
ambient_operating_conditions0…50°C
protection_classIP44 (EN 60529)
electrical_connections1.5 m 3-wire cable with terminal sleeves

Застосування

  • Preventing condensation on cold water pipes and windows
  • Cool ceiling systems (chilled ceilings, with suitable delay function in the DDC controller)
  • Use with Johnson Controls System 91 controllers to provide override functions when condensation is forming
  • Usable with any DDC regulator managing digital signals; can be used in conjunction with TC-9100

Особливості

  • Determines precisely the dew point with electronic measurement — achieve optimal efficiency for cool ceiling systems
  • 0…10 V or open collector output — can be used with any DDC regulator managing digital signals
  • Small hysteresis of 1…2% RH avoids oscillations of the information
  • Requires a suitable delay time in the DDC controller (DX-9100, FX, etc.) for chilled ceiling applications

Технічні дані

Parameter Value
Product HX-9100
Models HX-9100-8001, HX-9100-9001
Action On/Off (HX-9100-8001); 0 - 10 Vdc (HX-9100-9001)
Supply voltage 15VDC ±10%, nominal
Threshold Typically 90% rH
Output at 90%…100% rH Open collector closed: 0.5Vdc max; ≤ +0.5 Vdc
Hysteresis Typically 1%
Max current consumption Approximately 7.0 mA
Open collector characteristics Max 15Vdc, 10 mA
Ambient operating conditions 0…50°C
Humidity operating limits No permanent moisture condensation; no change of characteristic after 1,000 hours under condensation
Protection class IP44 (EN 60529)
Storage conditions -20 to +80°C, non condensing
Electrical connections 1.5 m 3-wire cable with terminal sleeves

Варіанти замовлення

Order code: HX-9100-001 Options:

  • 8 — Open collector output (HX-9100-8001)
  • 9 — 0/10 VDC output (HX-9100-9001)

Допуски та стандарти

  • IP44 (EN 60529)
  • Compliance: 89/336 EEC directive: EN 61000-6-3 (EN 50081-1); EN 61000-6-1 (EN 50082-1)

Позиції каталогу з цим документом

Текст документа

                                                                                    European Electronics Catalogue
                                                                                    Catalogue Section A
                                                                                    Product Bulletin HX-9100
                                                                                    Issue Date 07 2003

                                                   HX-9100
                                                  Dew Sensor

The HX-9100 Dew Sensor is used to prevent
condensation on surfaces such as cold water pipes,
and windows.
The HX-9100 can be connected to Johnson Controls
System 91 controllers to provide override functions
when condensation is forming.




                                                                              HX-9100 Dew Sensor




                                                 Features and Benefits
                     Determines precisely the      Achieve optimal efficiency for cool ceiling systems.
                     dew point with electronic     Prevent condensation
                     measurement

                     0…10V                         Can be used with any DDC regulator managing
                     or open collector output      digital signals




© 2003 Johnson Controls, Inc.                                                                                         1
  Order Nr. DS 24.132E, Rev. A                                                                   www.johnsoncontrols.com
Operation
The principle of the sensor is based on the change in      HX-9100-8001
resistance of a conductive polymer in a thin film on a     The sensing element is combined with an open
small ceramic substrate. As the sensing polymer            collector output to produce an ON/OFF output used by
becomes wet (90…95% RH), its resistance will               a digital input of a controller. The output is switched
increase drastically because the polymer expands and       from open to close position when 90-95% RH is
therefore causes a larger distance between the             sensed.
conductive particles.
The HX Sensor is used to sense precisely the dew           HX-9100-9001
point and provide the information to the connected         The sensing element is combined with an electronic
controller. A small hysteresis of 1…2% RH is present       circuit to produce an active output to a DDC controller.
in order to avoid oscillations of the information but it   The output drops from 10 to 0 VDC when 90…95%
can't be used to determine, in a reliable way, when the    RH is sensed
humidity has significantly fallen below the dew point.
Therefore for applications such as chilled ceilings it
requires a specific function in the controller, i.e. a
suitable delay time has to be introduce in the DDC
controller (DX-9100, FX, etc) reading the dew point
information in order act in a proper way (lock the valve
to the off position for a suitable time).
It can be used in conjunction with the TC-9100 and, in
general, with other controllers not equipped with the
possibility to define a delay interlock time, only for
cold water pipe applications, where there is usually a
small condensation on the pipe and therefore the HX
output remains active for a suitable time (the time
necessary to the valve to close the flow of cold water
and recover from the high humidity situation).


Ordering Data

HX-9100-       001
                     Options
                     8    Open collector output
                     9    0/10 VDC output




2   HX-9100
Installation




                                         Figure 1: Suggested Mounting Positions

                                                                 mounted. Use only the special double-sided
                                                                 bonding tape which is packed with the sensor.
                                                                 Using standard bonding tape results in incorrect
                                                                 operation. Remove one side of the protective paper
                                                                 from the tape. Cable the paper to the metal plate
                                                                 and press it to allow a good and uniform contact.
                                                                 Bond strength can also be improved with firm
                                                                 application pressure and moderate heat, from 38°C
                                                                 (100°F) to 54°C (130°F), causing the adhesive to
                                                                 develop intimate contact with the bonding surface.
                                                                 Ideal tape application temperature range is 21°C to
                                                                 38°C (70°F to 100°F).
                                                             •   Fix HX-9100 Dew Point Sensor on surface using
                      Figure 2
                                                                 the double-sided bonding tape). Remove the
This Mounting Positions is not suggested for the pull            second side of the protective paper, put the
that the cable makes on the sensor that tents to                 HX-9100 on to the surface and press it for at least
weaken the adhesive grip. In case the position is                10 sec. To allow a good temperature transfer to the
necessary make sure to fix the cable as shown in the             sensing element. The retainer can be used when
figure.                                                          the sensor has to be clamped to metal pipes.
•   The HX-9100 Dew Point Sensor can be mounted to           •   The sensor wiring may be lengthened. Shielded
    plane glass or metal surfaces. For maximum bond              cable should be used if transient problems can
    strenght, the surface should be thoroughly cleaned           occur.
    and dried. Typical cleaning solvents are heptane or
    isopropyl alcohol. Clean and dry the surface on
    which HX-9100 Dew Point Sensor has to be

Wiring diagrams


                                                                                          RH
                                                                                                 E



                                                                                  White    Bue       Red

                     White   Bue   Red
                                                                                  0...10V        +15VDC
                   Ou tput    +15V DC                                             Output
                          Com                                                              Com

                    HX-9100-8001                                                  HX-9100-9001



                                                                                                           HX-9100 3
Technical Specifications
                Product                  HX-9100
                Models                                 HX-9100-8001                                         HX-9100-9001
                Action                                      On/Off                                            0 - 10 Vdc
           Supply voltage                                                       15VDC ±10%, nominal
              Threshold                                                            Typically 90% rH
     Output at 90%…100% rH               open collector closed: 0.5Vdc max                                    ≤ +0.5 Vdc
              Hysteresis                                                             Typically 1%
    Max Current Consumption                                                     Approximately 7.0 mA
           Open Collector                Max 15Vdc, 10 mA
           Characteristics
         Ambient Operating                                                              0…50°C
              Conditions
        Humidity Operating               No permanent moisture condensation; no change of characteristic after 1,000 hours
                 Limits                  under condensation
          Protection Class               IP44 (EN 60529)
        Storage Conditions               -20 to +80°C, non condensing
      Electrical Connections             1.5 m 3-wire cable with terminal sleeves
             Compliance                  89/336 EEC directive: EN 61000-6-3 (EN 50081-1); EN 61000-6-1 (EN 50082-1)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.




Johnson Controls International, Inc.
Headquarters:                      Milwaukee, Wisconsin, USA
European Customer Service Center: Westendhof 3, D-45143 Essen, Germany
European Factories:                Essen (Germany), Leeuwarden (The Netherlands) and Lomagna (Italy)
Branch Offices:                    Principal European Cities.


4   HX-9100
