| Вид документа | Технічний паспорт |
|---|---|
| Виробник | JCI |
| Моделі | HX-9100-8001, HX-9100-9001 |
| Група обладнання | automation |
| Мова документа | англійська |
| Розмір файлу | 0.2 МБ |
Про документ
The HX-9100 Dew Sensor is used to prevent condensation on surfaces such as cold water pipes and windows. It senses the dew point precisely via a conductive polymer sensing element and signals condensation conditions to a controller. Two variants exist: an open collector ON/OFF output (-8001) for digital inputs, and an active 0…10 V output (-9001) for DDC controllers.
Ключові дані
| threshold | Typically 90% rH |
|---|---|
| output | 0 - 10 Vdc (HX-9100-9001) / open collector (HX-9100-8001) |
| supply_voltage | 15VDC ±10%, nominal |
| hysteresis | Typically 1% |
| ambient_operating_conditions | 0…50°C |
| protection_class | IP44 (EN 60529) |
| electrical_connections | 1.5 m 3-wire cable with terminal sleeves |
Застосування
- Preventing condensation on cold water pipes and windows
- Cool ceiling systems (chilled ceilings, with suitable delay function in the DDC controller)
- Use with Johnson Controls System 91 controllers to provide override functions when condensation is forming
- Usable with any DDC regulator managing digital signals; can be used in conjunction with TC-9100
Особливості
- Determines precisely the dew point with electronic measurement — achieve optimal efficiency for cool ceiling systems
- 0…10 V or open collector output — can be used with any DDC regulator managing digital signals
- Small hysteresis of 1…2% RH avoids oscillations of the information
- Requires a suitable delay time in the DDC controller (DX-9100, FX, etc.) for chilled ceiling applications
Технічні дані
| Parameter | Value |
|---|---|
| Product | HX-9100 |
| Models | HX-9100-8001, HX-9100-9001 |
| Action | On/Off (HX-9100-8001); 0 - 10 Vdc (HX-9100-9001) |
| Supply voltage | 15VDC ±10%, nominal |
| Threshold | Typically 90% rH |
| Output at 90%…100% rH | Open collector closed: 0.5Vdc max; ≤ +0.5 Vdc |
| Hysteresis | Typically 1% |
| Max current consumption | Approximately 7.0 mA |
| Open collector characteristics | Max 15Vdc, 10 mA |
| Ambient operating conditions | 0…50°C |
| Humidity operating limits | No permanent moisture condensation; no change of characteristic after 1,000 hours under condensation |
| Protection class | IP44 (EN 60529) |
| Storage conditions | -20 to +80°C, non condensing |
| Electrical connections | 1.5 m 3-wire cable with terminal sleeves |
Варіанти замовлення
Order code: HX-9100-001 Options:
- 8 — Open collector output (HX-9100-8001)
- 9 — 0/10 VDC output (HX-9100-9001)
Допуски та стандарти
- IP44 (EN 60529)
- Compliance: 89/336 EEC directive: EN 61000-6-3 (EN 50081-1); EN 61000-6-1 (EN 50082-1)
Позиції каталогу з цим документом
Текст документа
European Electronics Catalogue
Catalogue Section A
Product Bulletin HX-9100
Issue Date 07 2003
HX-9100
Dew Sensor
The HX-9100 Dew Sensor is used to prevent
condensation on surfaces such as cold water pipes,
and windows.
The HX-9100 can be connected to Johnson Controls
System 91 controllers to provide override functions
when condensation is forming.
HX-9100 Dew Sensor
Features and Benefits
Determines precisely the Achieve optimal efficiency for cool ceiling systems.
dew point with electronic Prevent condensation
measurement
0…10V Can be used with any DDC regulator managing
or open collector output digital signals
© 2003 Johnson Controls, Inc. 1
Order Nr. DS 24.132E, Rev. A www.johnsoncontrols.com
Operation
The principle of the sensor is based on the change in HX-9100-8001
resistance of a conductive polymer in a thin film on a The sensing element is combined with an open
small ceramic substrate. As the sensing polymer collector output to produce an ON/OFF output used by
becomes wet (90…95% RH), its resistance will a digital input of a controller. The output is switched
increase drastically because the polymer expands and from open to close position when 90-95% RH is
therefore causes a larger distance between the sensed.
conductive particles.
The HX Sensor is used to sense precisely the dew HX-9100-9001
point and provide the information to the connected The sensing element is combined with an electronic
controller. A small hysteresis of 1…2% RH is present circuit to produce an active output to a DDC controller.
in order to avoid oscillations of the information but it The output drops from 10 to 0 VDC when 90…95%
can't be used to determine, in a reliable way, when the RH is sensed
humidity has significantly fallen below the dew point.
Therefore for applications such as chilled ceilings it
requires a specific function in the controller, i.e. a
suitable delay time has to be introduce in the DDC
controller (DX-9100, FX, etc) reading the dew point
information in order act in a proper way (lock the valve
to the off position for a suitable time).
It can be used in conjunction with the TC-9100 and, in
general, with other controllers not equipped with the
possibility to define a delay interlock time, only for
cold water pipe applications, where there is usually a
small condensation on the pipe and therefore the HX
output remains active for a suitable time (the time
necessary to the valve to close the flow of cold water
and recover from the high humidity situation).
Ordering Data
HX-9100- 001
Options
8 Open collector output
9 0/10 VDC output
2 HX-9100
Installation
Figure 1: Suggested Mounting Positions
mounted. Use only the special double-sided
bonding tape which is packed with the sensor.
Using standard bonding tape results in incorrect
operation. Remove one side of the protective paper
from the tape. Cable the paper to the metal plate
and press it to allow a good and uniform contact.
Bond strength can also be improved with firm
application pressure and moderate heat, from 38°C
(100°F) to 54°C (130°F), causing the adhesive to
develop intimate contact with the bonding surface.
Ideal tape application temperature range is 21°C to
38°C (70°F to 100°F).
• Fix HX-9100 Dew Point Sensor on surface using
Figure 2
the double-sided bonding tape). Remove the
This Mounting Positions is not suggested for the pull second side of the protective paper, put the
that the cable makes on the sensor that tents to HX-9100 on to the surface and press it for at least
weaken the adhesive grip. In case the position is 10 sec. To allow a good temperature transfer to the
necessary make sure to fix the cable as shown in the sensing element. The retainer can be used when
figure. the sensor has to be clamped to metal pipes.
• The HX-9100 Dew Point Sensor can be mounted to • The sensor wiring may be lengthened. Shielded
plane glass or metal surfaces. For maximum bond cable should be used if transient problems can
strenght, the surface should be thoroughly cleaned occur.
and dried. Typical cleaning solvents are heptane or
isopropyl alcohol. Clean and dry the surface on
which HX-9100 Dew Point Sensor has to be
Wiring diagrams
RH
E
White Bue Red
White Bue Red
0...10V +15VDC
Ou tput +15V DC Output
Com Com
HX-9100-8001 HX-9100-9001
HX-9100 3
Technical Specifications
Product HX-9100
Models HX-9100-8001 HX-9100-9001
Action On/Off 0 - 10 Vdc
Supply voltage 15VDC ±10%, nominal
Threshold Typically 90% rH
Output at 90%…100% rH open collector closed: 0.5Vdc max ≤ +0.5 Vdc
Hysteresis Typically 1%
Max Current Consumption Approximately 7.0 mA
Open Collector Max 15Vdc, 10 mA
Characteristics
Ambient Operating 0…50°C
Conditions
Humidity Operating No permanent moisture condensation; no change of characteristic after 1,000 hours
Limits under condensation
Protection Class IP44 (EN 60529)
Storage Conditions -20 to +80°C, non condensing
Electrical Connections 1.5 m 3-wire cable with terminal sleeves
Compliance 89/336 EEC directive: EN 61000-6-3 (EN 50081-1); EN 61000-6-1 (EN 50082-1)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Johnson Controls International, Inc.
Headquarters: Milwaukee, Wisconsin, USA
European Customer Service Center: Westendhof 3, D-45143 Essen, Germany
European Factories: Essen (Germany), Leeuwarden (The Netherlands) and Lomagna (Italy)
Branch Offices: Principal European Cities.
4 HX-9100