| Вид документа | Каталожна сторінка |
|---|
| Виробник | JCI |
|---|
| Моделі | HT-9000-UD1, HT-9001-UD1, HT-9003-UD1, HT-9005-UD1, HT-9006-UD1, HT-9009-UD1, HT-9000-UD2, HT-9001-UD2 |
|---|
| Група обладнання | automation |
|---|
| Мова документа | англійська |
|---|
| Розмір файлу | 0.3 МБ |
|---|
Про документ
A range of duct-mount and wall-mount humidity transmitters for HVAC and refrigeration installations, measuring relative humidity over the entire 0–100% RH range with optional integrated temperature sensing elements. The HT-9000 offers fast response and long-term reliability for refrigeration; the HT-1300 is a cost-effective high-accuracy duct sensor; the HT-1000 provides room sensing compatible with Johnson Controls System 91 and Facility Explorer controllers.
Ключові дані
| Humidity range | 0 to 100% RH (non condensing) |
|---|
| Humidity accuracy | 4% RH from 10 to 90% RH (HT-9000); 2,5% from 10 to 95% RH (HT-1300) |
|---|
| Supply voltage | 12...30 VDC / 24 VAC (HT-9000); 15...35 VDC / 24 VAC ±20% (HT-1300); 15 VAC / 24 VAC (HT-1000) |
|---|
| Output | 0...10 VDC |
|---|
| Duct probe length | 153 mm and 230 mm |
|---|
| Protection class | IP30 (HT-9000, HT-1000), IP65 (HT-1300) |
|---|
Застосування
- Refrigeration installations
- HVAC duct humidity measurement
- Room humidity monitoring in HVAC applications
- Compatible with Johnson Controls System 91 and Facility Explorer controllers or other systems having compatible input/output voltages
Особливості
- Wide operating temperature range
- Models with integrated temperature sensing elements
- Polymer capacitance humidity sensing element (HT-1000)
- ±2% or ±4% accuracy versions available (HT-1000)
- Inspection Certificate according EN 10204:2004 (HT-1300)
Технічні дані
HT-9000 series (Duct Mount)
| Parameter |
Value |
| Power supply |
12...30 VDC / 24 VAC |
| Humidity range |
0...100% (non condensing) |
| Humidity output |
0...10 VDC |
| Humidity accuracy |
4% RH from 10 to 90% RH |
| Temperature outputs |
0...10 VDC, NTC K2, Pt 100, Pt 1000, A99 |
| Temperature ranges |
0…40 °C (NTC K2 / 0…10 VDC models), 0…60 °C (Pt100 / Pt1000 / A99 models) |
| Duct probe lengths |
153 mm and 230 mm |
| Protection class |
IP30 |
HT-1300 series (Duct Mount)
| Parameter |
Value |
| Power supply |
15...35 VDC / 24 VAC ±20% |
| Humidity range |
0...100% |
| Humidity output |
0...10 VDC |
| Humidity accuracy |
2,5% from 10 to 95% RH |
| Temperature outputs |
0...10 VDC, Pt 1000 |
| Temperature range |
-15…60 °C |
| Duct probe length |
200 mm |
| Protection class |
IP65 |
| Inspection certificate |
according EN 10204:2004 |
HT-1000 series (Wall Mount)
| Parameter |
Value |
| Supply voltage |
15 VAC / 24 VAC; 12 to 30 VDC, 24 VAC ±15% per ordering table |
| Humidity range |
0…100% RH |
| Output RH% |
0...10 VDC |
| Humidity accuracy |
±2% or ±4% depending on model |
| Temperature ranges |
0...40°C (±2% models), 0...40°C / 0...60°C (±4% models) |
| Temperature output |
0…10 VDC, NTC K2, Pt1000 |
| Protection class |
IP30 |
Варіанти замовлення
HT-9000 series
| Ordering code |
Probe length (mm) |
Temperature output |
Notes |
| HT-9000-UD1 / HT-9000-UD2 |
153 / 230 |
--- |
Humidity only |
| HT-9001-UD1 / UD2 |
153 / 230 |
0…10 VDC |
Temp. range 0…40 °C |
| HT-9003-UD1 / UD2 |
153 / 230 |
NTC K2 |
Temp. range 0…40 °C |
| HT-9005-UD1 / UD2 |
153 / 230 |
Pt100 |
Temp. range 0…60 °C |
| HT-9006-UD1 / UD2 |
153 / 230 |
Pt1000 |
Temp. range 0…60 °C |
| HT-9009-UD1 / UD2 |
153 / 230 |
A99 |
Temp. range 0…60 °C |
All: 12 to 30 VDC / 24 VAC +15%, humidity range 0 to 100% RH, output 0 to 10 VDC.
HT-1300 series
| Ordering code |
Temperature output |
Supply |
| HT-1301-UD1 |
0…10 VDC |
15 to 35 VDC / 24 VAC ±20% |
| HT-1306-UD1 |
Pt1000 DIN A |
15 to 35 VDC / 24 VAC ±20% |
Both: humidity range 0 to 100% RH, humidity output 0 to 10 VDC.
HT-1000 series
| Ordering code |
Accuracy |
Temperature output |
Temp. range |
| HT-1201-UR |
±2% |
--- |
--- |
| HT-1300-UR |
±4% |
--- |
--- |
| HT-1301-UR |
±4% |
0…10 VDC |
0...40°C |
| HT-1303-UR |
±4% |
NTC K2 |
0...40°C |
| HT-1306-UR |
±4% |
Pt1000 |
0...60°C |
Supply: 12 to 30 VDC / 24 VAC ±15%; humidity range 0…100% RH, output 0…10 VDC. Note: HT-1300 is listed as available in Spring 2015.
Допуски та стандарти
- Inspection Certificate according EN 10204:2004 (HT-1300)
Позиції каталогу з цим документом
Текст документа
hvac control products
Sensors
Plant Humidity
HT-9000
Duct Mount
The HT-9000 series measures humidity over the entire range
of 0 to 100% RH (non condensing) and has a wide operating
temperature range. Its fast response, reliable long-term performance
makes this transmitter well suited for refrigeration and HVAC
installations.
This range also includes models with an integrated temperature
sensing elements.
Features
zz Power supply 12...30 VDC / 24 VAC
zz Humidity range 0...100% (non condensing)
zz Humidity output 0...10 VDC
zz Humidity accuracy 4% RH from 10 to 90% RH
zz Temperature outputs 0...10 VDC, NTC K2, Pt 100, Pt 1000, A99
zz Duct probes lengths 153 mm and 230 mm
zz Protection class: IP30
A
HT-90xx-UD1 153 mm
Dimensions in mm
HT-90xx-UD2 230 mm
Humidity Humidity Temperature Temperature Supply Probe Lenght
Ordering Codes Range Output Range Output Voltage (mm)
HT-9000-UD1 --- ---
HT-9001-UD1 0…40 °C 0…10 VDC
HT-9003-UD1 0…40 °C NTC K2
153
HT-9005-UD1 0…60 °C Pt100
HT-9006-UD1 0…60 °C Pt1000
HT-9009-UD1 0…60 °C A99 12 to 30 VDC
0 to 100% RH 0 to 10 VDC
HT-9000-UD2 --- --- 24 VAC +15%
HT-9001-UD2 0…40 °C 0…10 VDC
HT-9003-UD2 0…40 °C NTC K2
230
HT-9005-UD2 0…60 °C Pt100
HT-9006-UD2 0…60 °C Pt1000
HT-9009-UD2 0…60 °C A99
84
The European Products Catalogue 2015
Manufacturer reserves the right to change specifications without prior notice
hvac control products
Sensors
Plant Humidity NEW!
Available
HT-1300 in Spring 2015
Duct Mount
Specially designed for HVAC, the HT-1300 Duct Mount Humidity Sensor
is a cost effective, highly accurate and reliable solution for measuring
relative air humidity and temperature.
Features
zz Power supply 15...35 VDC / 24 VAC ±20%
zz Humidity range 0...100%
zz Humidity output 0...10 VDC
zz Humidity accuracy 2,5% from 10 to 95% RH
zz Temperature outputs 0...10 VDC, Pt 1000
zz Duct probes length 200 mm
zz Protection class: IP65 46
zz Inspection Certificate according EN 10204:2004
~205
Ø 12
101
80.6
Dimensions in mm
Humidity Humidity Temperature Temperature Supply
Ordering Codes Range Output Range Output Voltage
HT-1301-UD1 0…10 VDC 15 to 35 VDC
0 to 100% RH 0 to 10 VDC -15…60 °C
HT-1306-UD1 Pt1000 DIN A 24 VAC ±20%
85
The European Products Catalogue 2015
Manufacturer reserves the right to change specifications without prior notice
hvac control products
Sensors
Room Humidity
HT-1000
Wall Mount
The HT-1000 series room humidity sensors provide active sensing
of relative humidity and on specific models, also active/passive sensing
of temperature in HVAC applications.
It features a polymer capacitance humidity sensing element
and provides within either ±2% or ±4% accuracy a voltage output
signal proportional 0 to 100% relative humidity.
The HT-1000 series room humidity sensors are designed for use
with Johnson Controls System 91 and Facility Explorer controllers
or for other systems having compatible input and output voltages.
Features
zz Supply voltage: 15 VAC / 24 VAC
zz Output RH%: 0...10 VDC
zz Output Temperature: 0...10 VDC, NTC K2, Pt1000
zz Protection class: IP30
Dimensions in mm
Humidity Humidity Humidity Temperature Temperature Supply
Ordering Codes Range Output Accuracy Range Output Voltage
HT-1201-UR ±2% 0...40°C 0…10 VDC
HT-1300-UR --- ---
12 to 30 VDC
HT-1301-UR 0…100% RH 0…10 VDC 0…10 VDC
±4% 0...40°C 24 VAC ±15%
HT-1303-UR NTC K2
HT-1306-UR 0...60°C Pt1000
90
The European Products Catalogue 2015
Manufacturer reserves the right to change specifications without prior notice
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.