SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Duct Mount CO2 Transmitter, CD-Px0-00-0 Series

Вид документаТехнічний паспорт
ВиробникJCI
МоделіCD-P00-00-0, CD-PR0-00-0
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.1 МБ

Про документ

Compact duct-mounted CO2 transmitter for HVAC applications, measuring 0 to 2,000 ppm with a silicon-based CARBOCAP single-beam dual-wavelength sensor. Offers selectable 0–10 V or 0/4–20 mA output; the CD-PR0-00-0 variant adds a relay output module for fan control. Requires no recalibration over five years.

Ключові дані

Measuring range0 to 2,000 ppm CO2
Output signalJumper Selectable: 0 to 20 mA or 4 to 20 mA or 0 to 10 VDC (Default)
Accuracy at 77°F (25°C)< ±[30 ppm CO2 + 2.0% of reading]
Long-term stability< ±5.0% of Full Scale/5 Years
Operating temperature range23 to 113°F (-5 to 45°C)
Power supply range20 to 30 VAC (18 to 30 VDC), Class 2
Relay output (CD-PR0-00-0)30 V, 0.5 A, Class 2

Застосування

  • Demand Control Ventilation (DCV) strategies (potential 10 to 70% energy savings)
  • Fresh air and Indoor Air Quality (IAQ) systems
  • Rooftop air handling Economizer systems
  • Integrated Building Automation Systems (BAS), Metasys system or AD-DME series
  • Standalone mode operation

Особливості

  • CARBOCAP® single-beam, dual-wavelength design with tunable interference filter reference measurement
  • Silicon micro-machined construction; reliable in duct environments
  • 5 years of calibration reliability, no recalibration expenses
  • Adjustable duct probe depth
  • Optional relay output (CD-PR0-00-0) with configurable On/Off trip points (default On 1,000 ppm, Off 950 ppm)
  • UL Listed integrated package with strain relief/conduit adapter for standard 1/2 in. fittings; no separate hardware required
  • Not affected by dust, water vapor, most chemicals, or typical duct airflow rates
  • Altitude compensation possible above 1,969 ft (600 m) per installation instructions

Технічні дані

Parameter Value
Measuring Range 0 to 2,000 ppm CO2
Accuracy at 77°F (25°C) < ±[30 ppm CO2 + 2.0% of reading]
Non-Linearity < 0.5% of Full Scale
Temperature Dependence of Output < 0.56% of Full Scale/F° (<0.1% of Full Scale/C°)
Long-Term Stability < ±5.0% of Full Scale/5 Years
Response Time (0 to 63%) 1 Minute
Operating Temperature Range 23 to 113°F (-5 to 45°C)
Storage Temperature Range -4 to 158°F (-20 to 70°C)
Humidity Range 0 to 85% non-condensing
Transmitter Output Signal CO2 Jumper Selectable: 0 to 20 mA or 4 to 20 mA or 0 to 10 VDC (Default); Maximum Output Current: 25 mA; Maximum Output Voltage: 12.5 V
Recommended External Load Current Output: Maximum 500 ohms Load Resistance; Voltage Output: Minimum 1,000 ohms Load Resistance
Power Supply Range 20 to 30 VAC (18 to 30 VDC), Class 2
Power Consumption < 2.5 W Average, 4.1 VA
Relay Output Module (CD-PR0-00-0) Plugs into the PCB; offers a 30 V, 0.5 A Class 2 output with configurable on and off trip points
Maximum (relay) 30 V, 0.5 A, Class 2
Warm-Up Time < 5 minutes
Airflow Range 0 to 7,500 ft/Minute (0 to 2,286 m/Minute)
Duct Probe Material Duct Probe Meets Plenum Rating Requirements of UL 1995, Heating and Cooling Equipment
Housing Material ABS Plastic
Dimensions (H x W x D) 3-5/32 x 3-3/16 x 8 in. (80 x 81 x 204 mm)
Shipping Weight 0.3 lb (140 g)
Altitude (no compensation) 0 to 1,969 ft (0 to 600 m) above sea level

Варіанти замовлення

Product Code Number Description
CD-P00-00-0 Duct mount CO2 transmitter
CD-PR0-00-0 Duct mount CO2 transmitter with relay
ACC-CD-S Relay Setpoint Software Kit; includes software and interface cable to reset the On and Off relay setpoints for CD-PR0-00-0
Y6531-0 Multiple Primary Transformer, 40 VA, 12-/208/230V Primary 24V Class 2 Secondary with Screw Terminals, Foot Mounting or 4 x 4 in. (101.6 x 101.6 mm) Plate
ACC-CD-R Relay Output Module for use in CD-P00-00-0 or CD-PR0-00-0
ACC-CD-CFK1 Conduit Adaptor Kit

Допуски та стандарти

  • United States: UL Listed, CCN XAPX
  • Canada: UL Listed, XAPX7
  • Europe: CE Mark — compliant with essential requirements of the EMC Directive
  • FCC Part 15 Class A digital device (US emissions compliance)
  • Canadian Interference-Causing Equipment Regulations Class (A)
  • Duct probe meets plenum rating requirements of UL 1995

Позиції каталогу з цим документом

Текст документа

CD-Px0-00-0 Series Duct Mount CO2 Transmitters
Product Bulletin
                                                                                                      Code No. LIT-216525
CD-P00-00-0,
                                                                                                       Issued October 2016
CD-PR0-00-0


Johnson Controls offers a complete line of carbon
dioxide (CO2) transmitters for measuring and
transmitting CO2 levels, ranging from 0 to 2,000 parts
per million (ppm), within Heating, Ventilating, and Air
Conditioning (HVAC) applications. These compact,
duct mounted devices offer a choice of 0 to10 V or
0 to 20 mA output signals and feature an optional relay
output with or without a digital display.
Johnson Controls® CO2 transmitters are easy to install
and to operate.
The silicon-based CARBOCAP® sensor delivers high
accuracy and long-term measurement stability
(±100 ppm) over a five-year period without calibration.
The diffusion-aspirated, single-beam, dual-wavelength
                                                                       Figure 1: Duct Mount CO2 Transmitter with
sensor structure is remarkably simple. It consists of an
                                                                         Conduit Adaptor and Mounting Flange
infrared (IR) source, a sample cell, an IR detector, and
a tunable interference filter that enables measurements
at two wavelengths. Reference measurements made
using a tunable interference filter eliminate the typical
weakness of dual-beam sensors and permits shifting
the optical pass band electronically. This innovative
design provides precise reference readings that
eliminate the typically broad deviation expected from a
traditional CO2 sensor.
Table 1: Features and Benefits
 Features                                                   Benefits
 Energy Savings from DCV Strategies                         Offer potential for 10 to 70% energy savings.
 CARBOCAP® Single-Beam, Dual-Wavelength Design              Provides superior performance compared to other technologies.
 CARBOCAP Silicon, Micro-machined Construction              Provides reliable CO2 measurement in duct environments.
 Calibration Reliability                                    Offers 5 years of reliable calibration.
 Adjustable Duct Probe Depth                                Permits optimal placement of sensing tip in a duct.
 Extended (Optional) Features                               Offer relay output for fan control.




                                          CD-Px0-00-0 Series Duct Mount CO2 Transmitters Product Bulletin                   1
Product Overview                                             These compact, devices are designed to work:
This transmitter uses a completely new CO2 sensing           •   in standalone mode
technology. The silicon based CARBOCAP sensor
                                                             •   in support of Demand Control Ventilation (DCV)
provides stability and reliability.
                                                             •   with fresh air and Indoor Air Quality (IAQ) systems
The CARBOCAP sensor operates in accordance with
the single-beam, dual-wavelength method. This                •   as part of any integrated Building Automation
patented sensor has unique reference measurement                 System (BAS)
capabilities, offering excellent stability over both time
                                                             •   with rooftop air handling Economizer controls
and temperature. The monolithic Fabry-Perot
                                                                 systems
Interferometer (FPI) chip utilizes the optical,
mechanical, and electronic properties of silicon at the      •   connected to Metasys system or the AD-DME
same time.                                                       series
The transmitter is factory set to measure CO2 levels up      Calibration
to 2,000 (ppm). It requires a Class 2, 24 VDC/VAC            Johnson Controls CO2 transmitters are calibrated
power source and generates an output signal                  using certified gases for the following:
proportional to the CO2 level detected. The duct
mounted CO2 transmitter series offers:                       •   output signal (0 to 10 V) proportional to CO2
                                                                 concentration (0 to 2,000 ppm)
•     standard CO2 transmitter
                                                             •   altitude range of 0 to 1,969 ft (0 to 600m) above
•     transmitter with relay output                              sea level without compensation

    IMPORTANT: The CD-Px0-00-0 Series Duct Mount             •   relay output trigger point set for 1,000 ppm (in
    CO2 Transmitter is intended to provide an input to           models featuring the optional relay output)
    equipment under normal operating conditions.             CARBOCAP Technology
    Where failure or malfunction of the transmitter could
                                                             Johnson Controls is licensed to integrate the new,
    lead to personal injury or property damage to the
                                                             silicon based CARBOCAP CO2 sensor into HVAC or
    controlled equipment or other property, additional
    precautions must be designed into the control            Building Automation Systems. This sensor has several
    system. Incorporate and maintain other devices,          advantages: high accuracy, excellent stability,
    such as supervisory or alarm systems or safety or        negligible temperature dependence, and ease of
    limit controls, intended to warn of or protect against   installation.
    failure or malfunction of the transmitter.               The structure of the diffusion aspirated, single-beam
    IMPORTANT : Le CD-Px0-00-0 Series Duct Mount             dual-wavelength sensor is remarkably simple. It
    CO2 Transmitter est destiné à transmettre des            consists of an Infrared (IR) source, a sample cell, a
                                                             tunable interference filter, and an IR detector. The
    données entrantes à un équipement dans des
                                                             tunable interference filter enables measurements at
    conditions normales de fonctionnement. Lorsqu'une
                                                             two wavelengths. As a result, references are measured
    défaillance ou un dysfonctionnement du transmitter
                                                             accurately, without the typically broad tolerances
    risque de provoquer des blessures ou
                                                             inherent in dual-beam sensors.
    d'endommager l'équipement contrôlé ou un autre
    équipement, la conception du système de contrôle         Dust, water vapor, and most chemicals do not affect
    doit intégrer des dispositifs de protection              the measurement accuracy of the sensor. No special
    supplémentaires. Veiller dans ce cas à intégrer de       software compensation patches are required.
    façon permanente d'autres dispositifs, tels que des
    systèmes de supervision ou d'alarme, ou des
    dispositifs de sécurité ou de limitation, ayant une
    fonction d'avertissement ou de protection en cas de
    défaillance ou de dysfonctionnement du transmitter.




2        CD-Px0-00-0 Series Duct Mount CO2 Transmitters Product Bulletin
Packaging Innovation                                      Dimensions
Johnson Controls offers the industry's first duct mount   See Figure 2 and Figure 3 for CO2 transmitter and
package that is Underwriters Laboratories, Inc. (UL)      mounting flange dimensions.
Listed and requires no separate hardware. This                     2.52 (64.00)         3.14 to 5.51 (80.00 to 140.00)
product includes a strain relief/conduit adapter for
connecting to standard 1/2 in. fittings. The CARBOCAP
sensor is not affected by typical airflow rates
encountered in ducts or rooftop air handlers.                                                                                 0.59
                                                              3.13                                                           (15.00)
The compact design of the device requires only a small      (79.38)
hole in the ventilation duct, which eliminates the
problems associated with leaking gaskets. The
enclosure reduces material and labor costs by offering    1.50                                                                     FIG:trns_dim

an integrated product; no pressurized boxes, pitot        38.10)
pickups, or tubing and fittings are required.                 Figure 2: Transmitter Dimensions, in. (mm)
Energy Efficiency                                                                 1.65 (42)
Using the CO2 transmitter duct probe results in                                   0.87 (22)
considerable savings in installation, operation, and
maintenance costs with no recalibration expenses.
Johnson Controls CO2 transmitters, when used with
BAS/Economizer controllers (featuring DCV                                                          1.65 (42)
strategies), can generate energy savings ranging up to:
•   20 to 40% in office buildings
                                                                                                               FIG:mnt_dim
•   20 to 60% in restaurants/light retail facilities
•   10 to 70% in educational/business settings              Figure 3: Mounting Flange Dimensions, in. (mm)

                                                          Optional Feature
                                                          Relay Module
                                                          For applications where On/Off ventilation or fan control
                                                          is required to provide fresh air, order the CD-PR0-00-0
                                                          Transmitter. This model includes a relay output module
                                                          that plugs into the main Printed Circuit Board (PCB)
                                                          offering a 30V, 0.5A Class 2 output with configurable
                                                          On and Off trip points. Default On is 1,000 ppm, and
                                                          default Off is 950 ppm.
                                                          Note: To redefine the relay On and Off trip points to
                                                          suit the application, use the ACC-CD-S Relay Setpoint
                                                          Software.
                                                          Altitude Compensation
                                                          These devices are intended for an altitude range of 0 to
                                                          1,969 ft (0 to 600 m) without compensation. To
                                                          compensate for higher altitudes, refer to the installation
                                                          instructions for this device.




3     CD-Px0-00-0 Series Duct Mount CO2 Transmitters Product Bulletin
Ordering Information                                            Repair Information
Contact the nearest Johnson Controls representative to          If the CD-Px0-00-0 Series Duct Mount CO2 Transmitter
order a CO2 transmitter, and specify the desired                fails to operate within its specifications, replace the
product code number from Table 2. See Table 4 for               unit. For a replacement transmitter, contact the nearest
accessories and Table 3 for replacement parts                   Johnson Controls representative.
available for the duct mount CO2 transmitter.
Table 2: CO2 Transmitters
 Product Code Number                           Description
 CD-P00-00-0                                   Duct mount CO2 transmitter
 CD-PR0-00-0                                   Duct mount CO2 transmitter with relay

Table 3: Accessories for Duct Mount CO2 Transmitters
 Product Code Number                           Description
 ACC-CD-S                                      Relay Setpoint Software Kit; includes software and interface cable to reset
                                               the On and Off relay setpoints for CD-PR0-00-0
 Y6531-0                                       Multiple Primary Transformer, 40 VA, 12-/208/230V Primary 24V Class 2
                                               Secondary with Screw Terminals, Foot Mounting or 4 x 4 in.
                                               (101.6 x 101.6 mm) Plate

Table 4: Replacement Parts for Duct Mount CO2 Transmitters
 Product Code Number                           Description
 ACC-CD-R                                      Relay Output Module for use in CD-P00-00-0 or CD-PR0-00-0
 ACC-CD-CFK1                                   Conduit Adaptor Kit

Technical Specifications
CD-Px0-00-0 Series Duct Mount CO2 Transmitters (Part 1 of 2)
 Measuring Range                    0 to 2,000 ppm CO2
 Accuracy at 77°F (25°C)            < ±[30 ppm CO2 + 2.0% of reading] (includes manufacturing deviation and drift). All
                                    accuracy specifications reflect testing the transmitters using high-grade, certified
                                    gases. Transmitters are intended for an altitude range of 0 to 1,969 ft (0 to 600 m)
                                    above sea level without compensation
 Non-Linearity                      < 0.5% of Full Scale
 Temperature of Dependence of       < 0.56% of Full Scale/F° (<0.1% of Full Scale/C°)
 Output
 Long-Term Stability                < ±5.0% of Full Scale/5 Years
 Response Time (0 to 63%)           1 Minute
 Operating Temperature Range        23 to 113°F (-5 to 45°C)
 Storage Temperature Range          -4 to 158°F (-20 to 70°C)
 Humidity Range                     0 to 85% non-condensing
 Transmitter Output Signal CO2      Jumper Selectable: 0 to 20 mA or 4 to 20 mA or 0 to 10 VDC (Default)
                                    Maximum Output Current: 25 mA; Maximum Output Voltage: 12.5 V
                                    Maximum 30 V, 0.5 A, Class 2
 Recommended External Load          Current Output: Maximum 500 ohms Load Resistance
                                    Voltage Output: Minimum 1,000 ohms Load Resistance
 Power Supply Range                 20 to 30 VAC (18 to 30 VDC), Class 2
 Power Consumption                  < 2.5 W Average, 4.1 VA



4     CD-Px0-00-0 Series Duct Mount CO2 Transmitters Product Bulletin
CD-Px0-00-0 Series Duct Mount CO2 Transmitters (Part 2 of 2)
 Relay Output Module                           Plugs into the PCB; offers a 30 V, 0.5 A Class 2 output with
 (CD-PR0-00-0 Model)                           configurable on and off trip points
 Warm-Up Time                                  < 5 minutes
 Airflow Range                                 0 to 7,500 ft/Minute (0 to 2,286 m/Minute)
 Duct Probe Material                           Duct Probe Meets Plenum Rating Requirements of UL 1995, Heating and Cooling
                                               Equipment
 Housing Material                              ABS Plastic
 Dimensions (H x W x D)                        3-5/32 x 3-3/16 x 8 in. (80 x 81 x 204 mm)
 Shipping Weight                               0.3 lb (140 g)
 Compliance             United States          UL Listed, CCN XAPX
                        Canada                 UL Listed, XAPX7
                        Europe                 CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
                                               essential requirements and other relevant provisions of the EMC Directive.

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.


United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.


Canadian Emissions Compliance
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.


European Single Point of Contact:             NA/SA Single Point of Contact:               APAC Single Point of Contact:
JOHNSON CONTROLS                              JOHNSON CONTROLS                             JOHNSON CONTROLS
WESTENDHOF 3                                  507 E MICHIGAN ST                            C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN                                   MILWAUKEE WI 53202                           NO. 22 BLOCK D NEW DISTRICT
GERMANY                                       USA                                          WUXI JIANGSU PROVINCE 214142
                                                                                           CHINA




                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                    All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

5       CD-Px0-00-0 Series Duct Mount CO2 Transmitters Product Bulletin

Published in U.S.A.                                                                                                 www.johnsoncontrols.com


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.