| Вид документа | Каталожна сторінка |
|---|---|
| Виробник | JCI |
| Моделі | A19AAC, A19AAF, A19ABC, A19ACC, A19ADC, A19BAC, A19BBC, A19DAC |
| Група обладнання | temperature |
| Мова документа | англійська |
| Розмір файлу | 0.4 МБ |
Про документ
The Johnson Controls A19A/A19B/A19D series are liquid-filled capillary, space, immersion and strap-on thermostats for refrigeration, cooling, heating, ventilation and air-conditioning applications. Models are available with fixed or adjustable differential, remote or room sensing, and trip-free manual reset versions (A19ACC lock-out low, A19ADC lock-out high) for low/high limit functions.
Ключові дані
| Operating range | -35 to +290 °C |
|---|---|
| Electrical rating | ~15(8) A, 230 V |
| Ambient temp. limits | -35 to +55 °C |
| Protection class | IP30 |
| Contact type | SPDT (standard on all models) |
| Case material | 1.75 mm cold-rolled zinc plated steel |
| Cover material | 1.5 mm ABS plastic |
| Conduit opening | 22.3 mm diam. hole for PG-16 connector |
Застосування
- Refrigeration
- Cooling
- Heating
- Ventilation
- Air-conditioning
- Milk-cooler thermostat (type A19AAF with wholesaler code P)
Особливості
- Liquid filled sensing element — no cross ambient temperature problems; contact differential over the whole range
- Dust tight Penn switch — prevents pollution of contacts by electrostatic influences
- Trip free manual reset — override not possible in the control function
- Front adjustment — less mounting space required
- Built-in high or low limit stop possible on request, field-adjustable
- Universal adjustment: knob and sealing cap enclosed; screwdriver adjustment convertible to knob adjustment in the field
- Bulb clamp plus screw enclosed on all A19 style 1 wholesaler code models
Технічні дані
| Parameter | Value |
|---|---|
| Operating range | -35 to +290 °C (see type number selection table) |
| Differential | See type number selection table |
| Differential adjustment | Adjustment lever under cover (types A19ABC and A19BBC) |
| Sensor styles | Styles 1a, 1b, 2, 3, 4h, 20 |
| Electrical ratings | ~15(8) A, 230 V; except A19AAF and A19DAF: ~15(3) A 230 V; A19ABC-9036/9037: ~15(5) A 230 V |
| Contact function | SPDT standard on all models; types A19ACC/A19ADC have trip-free manual reset |
| Ambient temp. limits | -35 to +55 °C |
| Conduit opening | 22.3 mm diam. hole for PG-16 connector |
| Case material | 1.75 mm cold-rolled zinc plated steel |
| Cover material | 1.5 mm ABS plastic |
| Protection Class | IP30 |
| Shipping weight | Individual pack 0.4 kg; overpack 10 kg (24 pcs) |
| Capillary lengths | 2 m to 6.5 m depending on model |
| Max. bulb temp. | 60 °C to 290 °C depending on model |
Type A19AAC — capillary thermostat, fixed differential
| Range (°C) | Diff. (K) | Bulb style | Setting | Cap. length | Max. bulb temp. | Order number |
|---|---|---|---|---|---|---|
| -35 to +10 | 2.5 | 1b | set low | 2 m | 60 °C | A19AAC-9102 |
| -5 to +28 | 2 | 1b | set low | 2 m | 60 °C | A19AAC-9005 |
| -5 to +28 | 2 | 1b | set low | 5 m | 60 °C | A19AAC-9124 |
| 1 to 60 | 2 | 1b | set low | 3 m | 85 °C | A19AAC-9127 |
| 40 to 120 | 3.5 | 1b | set high | 2 m | 145 °C | A19AAC-9009 |
| 35 to 150 | 4 | 1a | set high | 2 m | 180 °C | A19AAC-9107 |
| 90 to 290 | 5.5 | 1a | set high | 2 m | 290 °C | A19AAC-9108 |
Type A19ABC — capillary or immersion thermostat, adjustable differential
| Range (°C) | Diff. (K) | Bulb style | Setting | Cap. length | Max. bulb temp. | Wholesaler code | Order number |
|---|---|---|---|---|---|---|---|
| -35 to +40 | 2.8 to 8 | 1b | set low | 3.5 m | 60 °C | A19-A4 | A19ABC-9037 |
| -35 to +40 | 2.8 to 8 | 1b | set low | 6.5 m | 60 °C | A19-A5 | A19ABC-9036 |
| -35 to +10 | 2.8 to 11 | 1b | set low | 2 m | 60 °C | A19-A1 | A19ABC-9103 |
| -5 to +28 | 2 to 8 | 1b | set low | 2 m | 60 °C | A19-A2 | A19ABC-9104 |
| 1 to 60 | 2 to 8 | 1b | set low | 5 m | 85 °C | – | A19ABC-9117 |
| 1 to 60 | 2 to 8 | 1b | set low | 3 m | 85 °C | A19-A3 | A19ABC-9116 |
| 10 to 95 | 3.5 to 13 | 1a | set high | 3.5 m | 115 °C | – | A19ABC-9106 |
| 40 to 120 | 3.5 to 13 | 2 | set high | – | 145 °C | – | A19ABC-9011 (bulb well incl.) |
| 40 to 120 | 3.5 to 13 | 4h | set high | 2 m | 145 °C | – | A19ABC-9012 (bulb well incl.) |
Type A19ACC — capillary thermostat, lock-out low with manual reset
| Range (°C) | Diff. (K) | Bulb style | Setting | Cap. length | Max. bulb temp. | Wholesaler code | Order number |
|---|---|---|---|---|---|---|---|
| -35 to +10 | 6 M | 1b | set low | 2 m | 60 °C | – | A19ACC-9100 |
| -35 to +10 N | 6 M | 1b | set low | 3.5 m | 60 °C | – | A19ACC-9105 |
| -35 to +10 N | 6 M | 1b | set low | 5 m | 60 °C | – | A19ACC-9111 |
| -35 to +10 N | 6 M | 1b | set low | 6.5 m | 60 °C | A19-F | A19ACC-9116 |
| -5 to +28 | 4 M | 1b | set low | 2 m | 60 °C | – | A19ACC-9101 |
| -5 to +28 | 4 M | 1b | set low | 5 m | 60 °C | – | A19ACC-9103 |
| -5 to +28 | 4 M | 1b | set low | 3 m | 60 °C | – | A19ACC-9107 |
Type A19ADC — immersion thermostat, lock-out high with manual reset
| Range (°C) | Diff. (K) | Bulb style | Setting | Max. bulb temp. | Order number |
|---|---|---|---|---|---|
| 40 to 120 | 7 O | 2 | set high | 145 °C | A19ADC-9200 (bulb well incl.) |
Type A19AAF — capillary thermostat, close, fixed differential
| Range (°C) | Diff. (K) | Bulb style | Setting | Cap. length | Max. bulb temp. | Wholesaler code | Order number |
|---|---|---|---|---|---|---|---|
| 0 to 10 | 1.5 | 1a | set low | 2 m | 80 °C | – | A19AAF-9101 |
| 0 to 10 | 1.5 | 1a | set low | 2 m | 80 °C | A19-M P | A19AAF-9102 |
| 5 to 32 | 0.75 | 1b | set high | 2 m | 60 °C | – | A19AAF-9103 |
Type A19BAC — space thermostat, fixed differential
| Range (°C) | Diff. (K) | Bulb style | Setting | Max. bulb temp. | Wholesaler code | Order number |
|---|---|---|---|---|---|---|
| -35 to +10 | 2.5 | 3 | set low | 60 °C | A19-B1 | A19BAC-9250 |
| -5 to +28 | 2 | 3 | set low | 60 °C | A19-B2 | A19BAC-9251 |
| 0 to 43 | 2 | 3 | set high | 60 °C | A19-B3 | A19BAC-9001 |
Type A19BBC — space thermostat, adjustable differential
| Range (°C) | Diff. (K) | Bulb style | Setting | Max. bulb temp. | Wholesaler code | Order number |
|---|---|---|---|---|---|---|
| -35 to +40 | 2.8/8 | 3 | set low | 60 °C | A19-B4 | A19BBC-9275 |
Type A19DAC / A19DAF — strap-on thermostat, fixed differential
| Range (°C) | Diff. (K) | Bulb style | Setting | Max. bulb temp. | Order number |
|---|---|---|---|---|---|
| 40 to 120 | 4.5 | 20 | set high | 145 °C | A19DAC-9001 |
| 92 to 116 | 2 | 20 | set high | 145 °C | A19DAF-9001 |
Notes: M = reset possible on temperature increase above cut-out point; O = reset possible on temperature decrease below cut-out point; N = low limit stop factory set +2.5 °C, may be removed in the field; P = milk-cooler thermostat.
Bulb size and finish, bulb wells| Range (°C) | Style | Bulb size (mm) | Finish | Bulb well (optional) |
|---|---|---|---|---|
| -35 to +10 | 1b | 9.5 x 110 | Tin-plated | WEL14A602R |
| -35 to +10 | 3 | – | Stainless Steel | – |
| -5 to +28 | 1b | 9.5 x 135 | Tin-plated | WEL14A603R |
| -5 to +28 | 3 | – | Stainless Steel | – |
| -35 to +40 | 1b | 9.5 x 110 | Tin-plated | WEL14A602R |
| -35 to +40 | 3 | – | Stainless Steel | – |
| 0 to 13 | 1a | 9.3 x 80 | – | WEL16A601R |
| 0 to 43 | 3 | – | Stainless Steel | – |
| 1 to 60 | 1b | 9.5 x 115 | – | WEL14A602R |
| 5 to 32 | 1b | 9.5 x 155 | Tin-plated | No bulb well available |
| 10 to 95 | 1a | 7.4 x 75 | – | WEL11A601R |
| 40 to 120 | 1b | 9.5 x 100 | – | WEL14A602R |
| 35 to 150 | 1a | 5 x 265 | – | No bulb well or closed tank connector possible |
| 90 to 290 | 1a | 5 x 155 | – | No bulb well or closed tank connector possible |
Варіанти замовлення
Type number matrix:
- A19AAC — capillary thermostat, fixed differential
- A19AAF — capillary thermostat, special close fixed differential
- A19ABC — capillary or immersion thermostat, adjustable differential
- A19ACC — capillary thermostat, lock-out low with manual reset
- A19ADC — immersion thermostat, lock-out high with manual reset
- A19BAC — space thermostat, fixed differential
- A19BBC — space thermostat, adjustable differential
- A19DAC — strap-on thermostat
- A19DAF — strap-on thermostat
Accessories (optional):
| Order no. | Dimension A | Dimension B | Dimension C (internal) |
|---|---|---|---|
| WEL11A601R | 60 mm | 118 mm | 7.3 mm |
| WEL14A602R | 125 mm | 171 mm | 9.8 mm |
| WEL14A603R | 147 mm | 193 mm | 9.8 mm |
| WEL16A601R | 71 mm | 117 mm | 9.5 mm |
- Bulb well (brass, copper pipe), with bushing, set screw, adapter 1/2"-14 NPT
- Duct flange for closed-tank connector FTG13A-600R — order number T-752-1001
- Closed-tank connector FTG13A-600R (for style 1b swaged bulb)
Допуски та стандарти
- All types have VDE and SEV approval
- CE conformity according to low voltage directive and EMC directive
- According to EN 60730: type 1 action, independently mounted control, suitable for surface mounting on a plane surface and use in normal pollution situation
Текст документа
PSC9705 European Refrigeration Controls Catalogue
Catalog Section 1
Product Bulletin A19A
Issue 03/03/2003
Series A19A/A19B/A19D
Thermostats for Refrigeration, Cooling, Heating, Ventilation
and Air-conditioning
Introduction
These thermostats are designed for
refrigeration, cooling, heating, ventilation and
air-conditioning applications. Standard models
are provided for remote sensing or room
sensing. Models with manual reset are
available for low or high limit functions.
Description
These thermostats are available with fixed or
adjustable differential. The various control
ranges cover a broad range of temperature
applications with a minimum number of models.
On request a built-in high or low limit stop is
possible and can be adjusted quickly and easily
in the field. All models have a universal way of
adjustment. For this purpose a knob and sealing
cap are enclosed.
All A19 style 1 wholesaler code models have a
bulb clamp plus screw also enclosed.
A19A capillary thermostat
A19B space thermostat
Feature and Benefits
Liquid filled sensing element No cross ambient temperature problems
Contact differential over the whole range
Dust tight Penn switch Prevents pollution of the contacts by
electrostatic influences.
Trip free manual reset Override is not possible in the control function
Front adjustment Less mounting space required.
© 2003 Johnson Controls Inc. Catalogue Section 1
Order No. PD-A19A-E
A19A
2 Issue 03/03/2003
Note Note
These controls are designed for use only The standard screwdriver adjustment can
as operating controls. Where an operating be converted easily in the field to knob
control failure would result in personal injury
or loss of property it is the responsibility of adjustment. Also concealing of adjustment
the installer to add devices or systems that and scale is possible after installation.
protect against, or warn of, control failure.
SPDT contacts are standard on all models.
Contact functions
Instruments have compact sizes. Types Types A19AAC, 3 2
A19ACC and A19ADC have a trip-free manual A19AAF, A19ABC,
reset . Reset button must be pressed and A19BAC, A19BBC,
released. Contact cannot be blocked in closed A19DAC
θ>
position. All types have VDE and SEV approval.
To facilitate ordering, wholesaler codes have 1
been added on some universal models.
All models are provided with a separate knob
and sealing cap.
Fig. 1
1-2 closes on temperature increase
Type number matrix Type A19ACC
A19AAC capillary thermostat, fixed differential. 2 3
A19AAF capillary thermostat, special close
fixed differential.
A19ABC capillary or immersion thermostat,
adjustable differential. θ<
A19ACC capillary thermostat, lock-out low
with manual reset.
A19ADC immersion thermostat, lock-out high 1
with manual reset.
A19BAC space thermostat, fixed differential.
A19BBC space thermostat, adjustable Fig. 2
differential. 1-2 opens on temperature decrease
A19DAC strap-on thermostat.
A19DAF strap-on thermostat Type A19ADC
2 3
Adjustment θ>
1. Models “set low” (refer to cover label)
The dial indicates the low switch point
(1 - 2 open, 1 - 3 closed). 1
The high switch point (1 - 2 closed,
1 - 3 open) is obtained by adding the
differential to the low switch point. Fig.3
2. Models “set high” (refer to cover label)
1-2 opens on temperature increase
The dial indicates the high switch point
(1 - 2 closed, 1 - 3 open). The low switch
point (1 - 2 open, 1 - 3 closed) is obtained by
deducting the differential from the high switch
point.
Repair and replacement
Exception: Type A19ADC, dial indicates high Repair is not possible. In case of an improperly
switch point ( 1 - 3 closed, 1 - 2 open). functioning control, please check with your
nearest supplier. When contacting the supplier
for a replacement you should state the
type/model number of the control. This number
can be found on the data plate or cover label.
Catalogue Section 1 © 2003 Johnson Controls Inc.
Order No. PD-A19A-E
A19A
Issue 03/03/2003 3
Sensor styles
½" x 14 NPT
58.3 60
Fig. 4 Fig. 7
Style 1a (drawn bulb) Style 2
Fig.5
Style 1b swaged bulb, can be used with
closed-tank connector FTG13A-600
Fig. 8
Style 20
½ " x 14 NPT
33.3 60
Fig. 6
Style 4h Fig. 9
Style 3 (coil)
Bulb size and finish, bulb wells
Range (°C) Style Bulb size Finish Bulb well (optional)
(mm)
-35 to +10 1b 9.5 x 110 Tin-plated WEL14A602R
-35 to +10 3 - Stainless Steel -
-5 to +28 1b 9.5 x 135 Tin-plated WEL14A603R
-5 to +28 3 - Stainless Steel -
-35 to +40 1b 9.5 x 110 Tin-plated WEL14A602R
-35 to +40 3 - Stainless Steel -
0 to 13 1a 9.3 x 80 - WEL16A601R
0 to 43 3 - Stainless Steel -
1 to 60 1b 9.5 x 115 - WEL14A602R
5 to 32 1b 9.5 x 155 Tin-plated No bulb well available
10 to 95 1a 7.4 x 75 - WEL11A601R
40 to 120 1b 9.5 x 100 - WEL14A602R
35 to 150 1a 5 x 265 - No bulb well or closed tank
connector possible
90 to 290 1a 5 x 155 - No bulb well or closed tank
connector possible
© 2003 Johnson Controls Inc. Catalogue Section 1
Order No. PD-A19A-E
A19A
4 Issue 03/03/2003
Type number selection table:
Range Diff. Bulb Setting Cap. Max. Wholesaler Order
( °C) (K) style (see page 2 length bulb code number
adjustment) temp.
Type A19AAC Capillary thermostat, fixed differential
-35 to +10 2.5 1b set low 2m 60 °C A19AAC-9102
-5 to +28 2 1b set low 2m 60 °C A19AAC-9005
-5 to +28 2 1b set low 5m 60 °C A19AAC-9124
1 to 60 2 1b set low 3m 85 °C A19AAC-9127
40 to 120 3.5 1b set high 2m 145 °C A19AAC-9009
35 to 150 4 1a set high 2m 180 °C A19AAC-9107
90 to 290 5.5 1a set high 2m 290 °C A19AAC-9108
Type A19ABC Capillary or immersion thermostat, adjustable differential
-35 to +40 2.8 to 8 1b set low 3.5 m 60 °C A19-A4 A19ABC-9037
-35 to +40 2.8 to 8 1b set low 6.5 m 60 °C A19-A5 A19ABC-9036
-35 to +10 2.8 to 11 1b set low 2m 60 °C A19-A1 A19ABC-9103
-5 to +28 2 to 8 1b set low 2m 60 °C A19-A2 A19ABC-9104
1 to 60 2 to 8 1b set low 5m 85 °C A19ABC-9117
1 to 60 2 to 8 1b set low 3m 85 °C A19-A3 A19ABC-9116
10 to 95 3.5 to 13 1a set high 3.5 m 115 °C A19ABC-9106
40 to 120 3.5 to 13 2 set high - 145 °C A19ABC-9011
bulb well incl.
40 to 120 3.5 to 13 4h set high 2m 145 °C A19ABC-9012
bulb well incl.
Type A19ACC Capillary thermostat, lock-out low with manual reset
-35 to +10 6 M 1b set low 2m 60 °C A19ACC-9100
-35 to +10 N 6 M 1b set low 3.5 m 60 °C A19ACC-9105
-35 to +10 N 6 M 1b set low 5m 60 °C A19ACC-9111
-35 to +10 N 6 M 1b set low 6.5 m 60 °C A19-F A19ACC-9116
-5 to +28 4 M 1b set low 2m 60 °C A19ACC-9101
-5 to +28 4 M 1b set low 5m 60 °C A19ACC-9103
-5 to +28 4 M 1b set low 3m 60 °C A19ACC-9107
Type A19ADC immersion thermostat, lock-out high with manual reset
40 to 120 7O 2 set high - 145 °C A19ADC-9200
bulb well incl.
Type A19AAF Capillary thermostat, close, fixed differential
0 to 10 1.5 1a set low 2m 80 °C A19AAF-9101
0 to 10 1.5 1a set low 2m 80 °C A19-M P A19AAF-9102
5 to 32 0.75 1b set high 2m 60 °C A19AAF-9103
M Indicates temperature increase above cut-out O Indicates temperature decrease below cut-
point to make reset possible. out point to make reset possible.
N Low limit stop factory set +2.5 °C may be P Milk-cooler thermostat.
removed in the field.
Catalogue Section 1 © 2003 Johnson Controls Inc.
Order No. PD-A19A-E
A19A
Issue 03/03/2003 5
Type number selection table:
Range Diff. Bulb Setting Cap. Max. Wholesaler Order
( °C) (K) style (see page 2 length bulb code number
adjustment) temp.
Type A19BAC Space thermostat, fixed differential
-35 to +10 2.5 3 set low - 60 °C A19-B1 A19BAC-9250
-5 to 2 3 set low - 60 °C A19-B2 A19BAC-9251
+28
0 to 43 2 3 set high - 60 °C A19-B3 A19BAC-9001
Type A19BBC Space thermostat, adjustable differential
-35 to +40 2.8/8 3 set low - 60 °C A19-B4 A19BBC-9275
Type A19DAC, Strap-on thermostat, fixed differential
40 to 120 4.5 20 set high - 145°C A19DAC-9001
92 to 116 2 20 set high - 145°C A19DAF-9001
Note: If what you need is not in the type number selection table, then please contact your
representative.
© 2003 Johnson Controls Inc. Catalogue Section 1
Order No. PD-A19A-E
A19A
6 Issue 9811
Accessories (optional)
1 2 3
C
A
B
Order no. Dimension A Dimension B Dimension C
Internal
WEL11A601R 60 mm 118 mm 7.3 mm
WEL14A602R 125 mm 171 mm 9.8 mm
WEL14A603R 147 mm 193 mm 9.8 mm
WEL16A601R 71 mm 117 mm 9.5 mm
1. Bushing
2. Set screw
3. Adapter, 1/2"-14 NPT
Fig. 10
Bulb well (brass, copper pipe)
76 11.5 1 2 3 4 3 5 6
63
27
1. Style 1b bulb support tube
2. Packing nut
1/2"-14 NPT 3. Washer
4. Packing
ø 5.5 (3x) 5. Adapter, 1/2"-14 NPT
6 . Bulb
Fig. 11 Fig. 12
Duct flange to be used with closed-tank Closed-tank connector
connector FTG13A-600R. Order number FTG13A-600R
Order number T-752-1001
Catalogue Section 1 © 2003 Johnson Controls Inc.
Order No. PD-A19A-E
A19A
Issue 03/03/2003 7
Dimensions (mm)
55
32 40 21.5
3.6 13
1 2
19
28
19
7
6
16
75
125
13
3 4 46.5
1 Reset lever
2 Knob packed separately with the control
3 22.3 mm dia. cable inlet hole for PG-16
4 Earth screw
Fig. 13
© 2003 Johnson Controls Inc. Catalogue Section 1
Order No. PD-A19A-E
A19A
8 Issue 9811
Specifications
CE Conformity According to low voltage directive and EMC directive
Operating range -35 to +290 °C. See type number selection table.
Differential See type number selection table.
Differential adjustments Controls with adjustable differential (types A19ABC and A19BBC) have
an adjustment lever under the cover.
Sensor styles Styles 1a, 1b, 2, 3, 4h, and 20 (see drawings page 3)
Electrical ratings ~15(8) A, 230 V; except A19AAF and A19DAF: ~15(3) A 230 V, and
A19ABC-9036/9037: ~15(5) A 230 V
Ambient temp. limits -35 to +55 °C
Conduit opening 22.3 mm diam. hole for PG-16 connector
Material Case 1.75 mm cold-rolled zinc plated steel
Cover 1.5 mm ABS plastic
Protection Class IP30
Shipping weight Individual pack 0.4 kg
Overpack 10 kg (24 pcs)
Dimensions (see dimension drawing)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond
these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages
resulting from misapplication or misuse of its products.
Johnson Controls International, Inc.
Headquarters: Milwaukee, WI, USA
European Headquarters: Westendhof 8, 45143 Essen, Germany
European Factories: Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany)
Branch Offices: Principal European Cities.
This docum ent is subject to change Printed in Europe
Catalogue Section 1 © 2003 Johnson Controls Inc.
Order No. PD-A19A-E
PSC9720 Adjustment Réglage Einstellung
SHT067N600(003) Instelling Ajuste Regolazione ENGLISH NEDERLANDS
Ajuste Justering Säätö
Justering Justering Pύθµιση
Seřízení ! READ THIS INSTRUCTION SHEET CAREFULLY BEFORE ! NEEM DEZE INSTRUCTIES GRONDIG DOOR ALVORENS U
INSTALLING, RETAIN IT SAFELY FOR FUTURE REFER- BEGINT MET HET INSTALLEREN EN BEWAAR ZE VOOR
Instruction sheet ENCE. TOEKOMSTIG GEBRUIK
1 Setpoint dial 1 Temperatuur instellingsschijf
A19 2
3
Knob for adjustment (separate packed)
Cap for concealed adjustment (separate packed)
2
3
Knop voor temperatuur afstelling (apart verpakt)
Kap voor afdekking van temperatuurinstelling (apart verpakt)
Specification Description Spezifikation 4 Differential lever (adjustable differential models only) 4 Differentie instellingshendel (alleen bij modellen met verstelbare
Specificatie Especificación Specifiche 5 Cover (not on models A19AGC, A19AGF and BGC models) differentie)
Especificação Specifikationer Erittely 5 Deksel (niet op A19AGC, A19AGF en A19BGC modellen)
Beskrivelse Spesifikasjoner Προδιαγραφέσ The A19 is a temperature control designed to sense temperatures.
Technická data De A19 is een thermostaat ontworpen voor het meten van temperatu-
According to EN 60730 it is a type 1 action, independently mounted ren
control, suitable for surface mounting on a plane surface and for use in
normal pollution situation. The A19AGC,A19AGF and A19BGC mod- Volgens EN 60730 is het een, type 1 aktie, onafhankelijk te monteren
els are incorporate controls. apparaat, geschikt voor montage op een plat oppervlak en geschikt
voor gebruik in een normaal vervuilde omgeving. De A19AGC,
These controls are designed for use only as operating controls. Where A19AGF en A19BGC modellen zijn in te bouwen apparaten.
an operating control failure would result in personal injury or loss of
property, it is the responsibility of the installer to add devices or systems Deze apparaten zijn alleen ontworpen voor gebruik als regelaar. Als
that protect against, or warn of, control failure. een foutieve werking van de regelaar persoonlijk letsel of schade kan
veroorzaken, moet de installateur beveiliging of alarm apparatuur
Installation aansluiten die aangeeft dat de regelaar niet funktioneert.
DO NOT TURN SEALED SCREWS
Montage
! Disconnect from power supply before the cover is removed. NIET DRAAIEN AAN AFGELAKTE SCHROEVEN
180° ! Schakel de voedingsspanning af voordat het deksel wordt verwij-
! For A19AGC, A19AGF and A19BGC Disconnect power supply
before adjusting the control. derd
1 2 Wiring ! Voor A19AGC,A19AGF en A19BGC : Sluit de voedingsspanning
All wiring should conform to local codes and must be carried out by af voordat de regelaar wordt afgesteld.
3 authorized personnel only. When using multi stranded wire apply a
Set Low
cable ferrule to the cable end. Bedrading
1 2 De installatie, de elektrische aansluiting en de instellingen dienen
3 Check out procedure overeen te stemmen met de plaatselijke voorschriften en mogen enkel
Before leaving the installation observe at least three complete operat- worden uitgevoerd door bevoegd personeel.
°C ing cycles to be sure that all components are functioning correctly. If not Indien een draad met flexibele kern wordt toegepast dient het uiteinde
SP
T min.: - 35 °C 1 3 contact your supplier. van de draden te worden voorzien van een ader eindhuls.
T max.: + 55 °C
3 2 5 1 4 Set High
2 Controleprocedure
Controleer, voordat u de installatie zelfstandig laat werken, gedurende
1 3 ten minste drie complete werkcycli of alle onderdelen correct werken.
Werkt de installatie niet correct, neem dan contact op met uw leveran-
2 cier.
SP °C
≥ 6k (-35 to +10°C)
≥ 4k ( -5 to +10°C)
1 2 FRANÇAIS ESPAÑOL
Mounting Montage Montage
Montage Montaje Montaggio 3
Montagem Montering Kiinnitys ACC ! LISEZ ATTENTIVEMENT CES INSTRUCTIONS AVANT DE ! LEA DETENIDAMENTE ESTA HOJA DE INSTRUCCIONES
Montering Montering Mοντάρισµα 2 COMMENCER L’INSTALLATION ET CONSERVEZ- LES ANTES DE REALIZAR LA INSTALACION Y GUARDELA
1 POUR VOUS Y REFERER ULTERIEUREMENT
Instalace PARA FUTURAS CONSULTAS
3
1. Cadran de consigne 1 Cuadrante para fijar el punto de control
°C
SP 2. Bouton de réglage (emballé séparément) 2 Botón de ajuste (embalado por separado)
55 ≥ 7k ( +40 to 120°C) 3. Bouchon pour réglage caché (emballé séparément)
4. Levier de différentiel (uniquement pour modèles avec différentiel
3 Casquillo para ajuste oculto (embalado por separado)
3 4 Palanca diferencial (sólo en modelos con diferencial ajustable)
1 réglable)
40 2 5. Couvercle (pas sur les modèles A19AGC, A19AGF ni BGC)
5 Cubierta (no en los modelos A19AGC, A19AGF y BGC)
ADC El A19 es un control de temperatura diseñado para detectar tempera-
Max. 2x Le modèle A19 est un régulateur de température destiné à détecter les
1 3 turas.
Ø 3.5 mm températures
2 Según EN 60730, es un, acción tipo 1 control montado independien-
°C D’après la norme EN 60730 c’est un régulateur indépendant, action temente adecuado para montaje en superficie en una superficie plana
SP type 1, conçu pour un montage sur surface plane et utilisé dans des y para uso en condiciones de contaminación normal.
3 2 environnements normalement pollués. Les modèles A19AGC, A19AGF Los modelos A19AGC, A19AGF y A19BGC son controles incorpora-
et A19BGC sont des commandes incorporées. dos
AAC, AAF, ABC
θ> AGF, BAC, BBC
1
Cet appareil est destiné à assurer des fonctions de régulation. Lorsque Estos controles están diseñados para ser utilizados solamente como
la panne ou le mauvais fonctionnement de ce dernier risque d'entraîner controles de funcionamiento. En los casos en que un fallo de control
des dommages matériels ou corporels, il est de la responsabilité de de funcionamiento pudiera producir daños personales o a propieda-
125 2 3 2 3 l'installateur de prévoir des organes de sécurité indépendants afin de des, es responsabilidad del instalador añadir los dispositivos o siste-
75 θ> θ<
ne pas utiliser le régulateur en équipement de sécurité. mas que protejan o adviertan de los fallos de control.
1 1 Installation Instalación
NE PAS TOURNER LES VIS SCELLEES NO GIRE LOS TORNILLOS SELLADOS.
ADC ACC
! Couper l’alimentation électrique avant d’enlever le couvercle. ! Desconectar la corriente antes de quitar la tapa.
! Pour A19AGC, A19AGF et A19BGC, coupez l’alimentation avant ! Para A19AGC, A19AGF y A19BGC, desconecte la fuente de
de régler les commandes. alimentación antes de ajustar el control.
Câblage Cableado
Tous les raccordements doivent être conformes aux normes en Todo el cableado debe cumplir las normativas locales y debe realizar-
vigueur et ne peuvent être réalisés que par du personnel autorisé. se solamente por el personal autorizado. Cuando se utiliza cable
En cas d’utilisation de câble souple multi-brins, utiliser un embout à flexible aplicar terminales en los extremos.
sertir.
Wiring Raccordement Verdrahtung
Bedrading Cableado Cablaggio Procédure de contrôle Procedimiento de comprobación
Cablagem Ledningar Jodotus Après avoir terminé l’installation, observez au moins trois cycles Antes de finalizar la instalación, observe por lo menos tres ciclos de
Elektrisk installation Kabling Kαλωδίωση complets de fonctionnement pour s’assurer que tous les composants operación completos para asegurarse que todos los componentes
Zapojení fonctionnent correctement. Si cela n’est pas le cas, contactez votre estén funcionando correctamente. Sino es así, póngase en contacto
fournisseur. con su proveedor.
DEUTSCH ITALIANO
! BITTE LESEN SIE DIESE ANWEISUNGEN VOR DER IN- ! GERE ATTENTAMENTE LE ISTRUZIONI PRIMA DELL’IN-
STALLATION SORGFÄLTIG DURCH UND BEWAHREN SIE STALLAZIONE E lSERVARE PER FUTURE CONSULTAZIO-
2 SIE ZUR WEITEREN VERWENDUNG AUF. NI
1 Sollwertskalenscheibe 1 Scala del valore di riferimento
2 Einstellknopf (separat verpackt) 2 Manopola di regolazione (fornita a parte)
3 Aufsatz für verdeckte Einstellung (separat verpackt) 3 Cappellotto per regolazione protetta (fornito a parte)
4 Differentialhebel (Nur einstellbare Differentialmodelle) 4 Leva differenziale (solo modelli a differenziale variabile)
rdfguhlj;ko
5 Deckel (Nicht bei Modellen A19AGC, A19AGF und A19BGC) 5 Coperchio (eccetto modelli A19AGC, A19AGF e BGC)
b n b n , m/,. m
fchfchhbkjlkjn
Der A19 ist ein Temperaturregler zum Fühlen von Temperaturen. Il dispositivo A19 è un regolatore della temperatura in grado di rilevare
3 le temperature.
Dieses ist entsprechend EN 60730 ein, Wirkungsweise Typ 1, Unab-
(3x) hängig montiertes Regel- und Steuergerät Geeignet als Aufbaugerät, Secondo le EN 60730 è un, azione tipo 1 Regolatore montato indipen-
1 z. B. für Wandmontage und für Anwendung in Umgebungsbedingun- dentemente, adatto per montaggio su una superficie piatta e per uso
M 4x6 gen mit üblicher Verunreinigung. Bei den Modellen A19AGC, A19AGF in situazioni di normale inquinamento. I modelli A19AGC, A19AGF e
und A19BGC handelt es sich um Einbauregler. A19BGC sono comandi incorporati.
2 Diese Regler sind ausschließlich zur Verwendung als Bedienungs- Questi dispositivi hanno esclusivamente la funzione di comandi. Se un
0.5 to 4 mm elemente vorgesehen. In Situationen, in denen das Versagen eines comando può provocare danni alle persone o alle cose, è responsabi-
Bedienungselements Personenschäden oder Sachverluste nach sich lità dell’installatore aggiungere gli opportuni dispositivi o sistemi di
(20-12 AWG) ziehen kann, ist der Installateur dafür verantwortlich, entsprechende protezione o di segnalazione dello stato di guasto del comando stesso.
Vorrichtungen oder Systeme einzubauen, die einem Regelversagen
entgegenwirken oder die als entsprechende Frühwarnsysteme die- Installazione
nen. NON SBLOCCARE LE VITI SIGILLATE
Montage ! Staccare l’alimentazione prima di togliere il coperchio.
PLOMBIERSCHRAUBEN NICHT ANZIEHEN!
! Per A19AGC, A19AGF e A19BGC: togliere tensione prima di
! Vor dem Entfernen des Deckels Spannung abschalten. regolare il comando.
! A19AGC, A19AGF und A19BGC: Von Stromversorgung trennen, Cablaggio
bevor der Regler eingestellt wird. Il cablaggio deve essere conforme alle normative locali ed essere
eseguito esclusivamente da personale autorizzato. Quando si usa un
Verdrahtung cavo con filo a trefoli occorre applicare un capocorda alla fine di ogni
Alle Verdrahtungen müssen den am Einsatzort geltenden Vorschriften filo.
Показано початок документа. Повний текст — у PDF за посиланням вище.
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.