| Вид документа | Каталожна сторінка |
|---|---|
| Виробник | JCI |
| Код документа | p66-series-electronic-fan-speed-control-catalog-page |
| Група обладнання | P66 Single‐Phase Fan Speed Control |
| Сторінок | 2 |
| Мова документа | англійська |
| Розмір файлу | 0.3 МБ |
Текст документа
Code No. LIT-1927210
Issued May 2018
P66 Series Electronic Fan Speed Controls Catalog Page
Description Features
The P66 Series Electronic Fan Speed • exclusive Johnson Controls/PENN®
Controls are refrigerant pressure actuated, pressure transducer — responds quickly to
electronic motor-speed controllers. The P66 condenser pressure changes and
controls are designed for use with condenser air delivery requirements
single-phase permanent split-capacitor • soft start capability — provides a smooth
motors that are approved by the motor fan startup, which reduces motor-starting
manufacturer for speed control applications. noise and abrupt changes in motor speed
The P66 controls provide condenser pressure • 208-240/277/480 VAC, 60 Hz motor control
control by directly sensing condenser — suitable for a wide range of condenser
refrigerant pressure and automatically fan motor applications
adjusting the condenser fan motor speed • one or two pressure transducers —
according to the sensed pressure. applicable to single- and multi-circuit P66 Dual Sensor Fan Speed Control
condensers. The dual-sensor P66 control
The P66 provides an alternative to fan cycling
models select the higher pressure input to
control in many small and medium size
control the fan speeds.
refrigeration and Heating, Ventilating, and Air
Conditioning (HVAC) applications. • two Effective Throttling Ranges (ETRs) —
provide either a 30 or 60 psi (207 or 414
kPa) ETR
• NEMA 1 or NEMA 3R (Rainproof)
enclosures — allows indoor and panel
mounting or outdoor mounting
• built-in voltage surge protection, Radio
Frequency Interference (RFI) suppression,
and ground terminal screw
Selection Charts
P66 Series Control Model Information1 Replacement Guide1
Product Code Operating Start Voltage Capillary Length Original Control Model Number Replacement P66 Product Code
Number Range (psig) (% of Supply (in.) Number
Voltage) P15AJ-39 P66AAB-4C
Single Input Sensor Mode P15AK-11 P66AAB-6C
P66AAB-1C 190-250 10 60 P15AK-12 P66ABB-21C
P66AAB-4C 135-165 10 60 P15AK-13 P66AAB-6C
P66AAB-6C 170-230 16 60 P15AK-14 P66AAB-1C
P66AAB-9C 170-230 40 60 P15DJ-5 P66AAB-6C
P66AAB-10C 190-250 16 120 P15JJ-2 (Liebert® models) P66AAB-1C
P66AAB-11C 140-200 16 60 P15JJ-2 (Non Liebert models) P66AAB-9C
P66AAB-13C 60-90 16 60 P15JJ-7 P66ABB-21C
P66AAB-14C 220-280 40 120 P15JJ-8 P66AAB-1C
P66AAB-15C 190-250 40 60 P65AAB-1 P66AAB-1C
P66AAB-19C 115-145 40 60 P65AAB-2 P66AAB-1C
P66AAB-25C 180-240 10 120 P65AAB-4 P66AAB-4C
P66AAB-26C 220-280 40 60 P65AAB-6 P66AAB-6C
P66AAB-34C 320-410 40 60 P65AAB-9 P66AAB-9C
P66AAD-1C* 160-220 25 60 P65AAB-10 P66AAB-10C
Dual Input Sensor Models P65BAB-1 P66BAB-1C
P66BAB-1C 190-250 10 60 P65BAB-2 P66BAB-1C
P66BAB-3C 170-230 16 60 P65BAB-5 P66BAB-5C
P66BAB-4C 190-250 16 120 P65AAB-2 P66AAB-1C
P66BAB-5C 190-250 40 60 P66AAB-18 P66AAB-25C
P66BAB-9C 320-410 40 60 P66AAB-21 P66ABB-21C
P66BAD-1C* 160-220 25 60 P66BAB-2 P66BAB-1C
NEMA 3R Models P66BAB-4 P66BAB-1C
P66ABB-21C 220-280 16 120 1. When two P15s are used in parallel with one motor, replace both P15s with
P66ABB-24C 190-250 16 60 one P66BAB. Select the P66BAB with an operating range similar to that of
P66ABB-27C 170-230 40 60 the P15s being replaced. When replacing a P15 or P65 with a P66, 24 VAC
must be provided. It is recommended that the P66 be used only with low heat
1. All models are rated for 208-240/277/480 volt; 60 Hz except those with rise ball bearing motors that are approved by the motor manufacturer for fan
Product Code Numbers followed by an asterisk, indicating 50 Hz Models. speed control operation. Start voltage for P15 models = 40%.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2018 Johnson Controls. www.penncontrols.com
1
P66 Series Electronic Fan Speed Controls Catalog Page (Continued)
Technical Specifications
P66 Series Electonic Fan Speed Control
Pressure Ratings: Low Pressure Models Control Range: 80 to 200 psig (552 to 1,379 kPa)
Effective Throttling Range: 30 psig (207 kPa)
Maximum Working Pressure: 200 psig (1,379 kPa)
Maximum Overpressure: 250 psig (1,724 kPa)
Pressure Ratings: Medium Pressure Models Control Range: 140 to 350 psig (965 to 2,413 kPa)
Effective Throttling Range: 60 psig (414 kPa)
Maximum Working Pressure: 350 psig (2,413 kPa)
Maximum Overpressure: 400 psig (2,758 kPa)
Pressure Rating: High Pressure Models Control Range: 300 to 500 psig (2,068 to 3,447 kPa)
Effective Throttling Range: 90 psig (621 kPa)
Maximum Working Pressure: 500 psig (3,447 kPa)
Maximum Overpressure: 610 psig (4,206 kPa)
Control Voltage 24 VAC, Class 2, 1 A
Line Voltage Range 208 to 480 VAC
Start Voltage 10% to 40% of line (OEM specified - model specific)
Electrical Ratings: 208 VAC Full Load Amperes: 8.0
Locked Rotor Amperes: 16.5
Ambient Temperature Maximum: 130°F/54°C
Electrical Ratings: 240 VAC Full Load Amperes: 8.0
Locked Rotor Amperes: 16.5
Ambient Temperature Maximum: 130°F/54°C
Electrical Ratings: 277 VAC Full Load Amperes: 6.9
Locked Rotor Amperes: 14.3
Ambient Temperature Maximum: 130°F/54°C
Electrical Ratings: 480 VAC Full Load Amperes: 4.0
Locked Rotor Amperes: 10.5
Ambient Temperature Maximum: 150°F/66°C
Ambient Temperature Minimum -40°F/-40°C (at all voltages)
Ambient Storage Temperature -40°F/-40°C to 185°F/85°C
Construction Control Case: Galvanized steel case and cover
Base and Sensors: Galvanized steel
Plastic Enclosure: UV stabilized polycarbonate with closed cell foam gasket (NEMA 3R models only)
Enclosure NEMA 1 or NEMA 3R (Rainproof)
Wiring Connections Low Voltage: 1/4 in. quick connects (NEMA 1); Two 6 in. 22 AWG Wire Leads (NEMA 3R)
Line Voltage: 10-32 Screw Terminals
Pressure Connections 60 in./1.5 m or 120 in./3.0 m copper capillary with 1/4 in./6 mm flare nut and Schrader® valve depressor
Mounting Vertical only; two holes for No. 10 screws at the top and bottom
Compliance UL Recognized (U.S.): File SA516, Guide SDFY2
UL Recognized (Canada): File SA516, Guide SDFY8
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. © 2018 Johnson Controls. www.penncontrols.com
2Позиції каталогу з цим документом