P266 Series Single-Phase Condenser Fan Speed Controls
Product Bulletin
P266xxA-xx                                                                                      Code No. LIT-12011534
                                                                                                          Issued May 2018

The P266 Series Single-Phase Condenser Fan Speed
Controls are cost-effective, weather-resistant, durable
motor speed controls. The P266 Series Controls are
designed for approved single-phase, Permanent
Split-Capacitor (PSC) motors commonly used in a wide
variety of refrigeration and air conditioning condenser
fan applications.
The P266 Series Controls are designed to replace the
Johnson Controls® P66 Series and P215 Series Fan
Speed Controls, providing additional features and
flexibility, greater energy efficiency, and longer motor
life in a compact, rugged, weather-resistant package.
P266 Series Controls are available for 208 through
575 VAC 50/60 Hz range applications. P266 Series
Controls have current ratings from 4 to 12 A,
depending on the voltage and model.
Some P266 Series Controls provide optional control of
up to three auxiliary (fixed-speed) fans or fan stages. In
addition, some models provide two additional
high-voltage triacs that allow you to split the source                  Figure 1: P266 Series Single-Phase
power to the main and auxiliary windings, and connect                      Condenser Fan Speed Control
a low-speed capacitor to increase efficiency at
low-speed operation.
Table 1: Features and Benefits
 Features                                          Benefits
 One or Two Durable, Accurate, Stainless Steel,    Resist damage from physical shock, vibration, pressure pulsation, and
 Remote-Mount Pressure Transducers                 extreme environmental conditions; eliminate capillary tube breaks and
                                                   greatly reduce refrigerant loss potential; provide 1% total error band; and
                                                   are applicable to single and multi-circuit condenser applications.
 Available in 208/240 VAC (8 or 12 A),             Provides efficient PSC motor speed control for a wide range of
 380/460 VAC (4 A), or 460/575 VAC (4 A)           condenser fan applications.
 Wide, Adjustable Pressure Throttling Range        Enables application flexibility and allows you to tune condenser
                                                   operation to specific pressure ranges and ambient environments.
 Optional Auxiliary Fan Control                    Provides control of up to three fixed-speed fans or fan stages in
                                                   conjunction with the speed controlled fan or fan stage.
 Optional Low-Speed Capacitor Mode                 Enables cooler, quieter, and more efficient fan motor operation at low
                                                   speeds.
 NEMA3R, (IP54) Enclosure with Integral Metal      Provides a rugged, weather-resistant fan control with good heat
 Heat-Sink and Stand-Off Mounting Feet             dissipation and a sturdy mounting base.

                        P266 Series Single-Phase Condenser Fan Speed Controls Product
                                                   Bulletin
                                                      1
Application                                                   P266 Series Single-Phase Fan Speed Control
                                                              applications include:
 IMPORTANT: Use this P266 Series Single-Phase
                                                              •   computer room air conditioning
 Condenser Fan Speed Control only as an operating
 control. Where failure or malfunction of the fan             •   commercial refrigeration
 speed control could lead to personal injury or
                                                              •   commercial air conditioning
 property damage to the controlled equipment or
 other property, additional precautions must be               P266 Series Control Operation
 designed into the control system. Incorporate and            The P266 Series Control regulates fan motor speed by
 maintain other devices, such as supervisory or               limiting the supply voltage to the motor based on the
 alarm systems or safety or limit controls, intended to       sensed condenser pressure. In a typical P266 Series
 warn of or protect against failure or malfunction of         Control application, as the condenser pressure rises,
 the fan speed control.                                       the P266 Series Control increases the supply voltage
                                                              to the fan motor, which increases fan speed and air
            CAUTION: Risk of Property Damage                  movement across the condenser coil. The increased
            Use only single-phase PSC motors
     !      approved by the manufacturer for speed
                                                              air movement removes condenser heat faster, which
                                                              maintains the condenser pressure within the defined
            control applications with the P266 Series         range.
            Control. Failure to use a single-phase
                                                              P266 Series Control Setup Values and Modes
            PSC motor may damage the motor and
            other property.                                   The P266 Series Control ships with up to ten factory
                                                              default setup values and modes. These settings can be
The P266 Series Single-Phase Condenser Fan Speed              adjusted in the field (if required) to meet your specific
Control, in conjunction with a P266 Series Electronic         condenser application requirements.
Pressure Transducer, is a pressure-actuated, digital
                                                              The adjustable settings of the P266 Series Control
electronic motor speed control designed for approved
                                                              include:
single-phase PSC motors used in a wide variety of
HVACR applications.                                           •   Start Voltage establishes the initial minimum
                                                                  voltage delivered by the P266 Series Control to the
The P266 Series Control regulates supply voltage to
                                                                  fan motor, to idle the fan motor at the minimum
the fan motor in response to the condenser refrigerant
                                                                  speed.
pressure, and maintains the appropriate fan speed
(air movement) through the condenser regardless of            •   Start Pressure establishes the pressure setpoint
the ambient temperature or air delivery variations.               (bar or psig) at which the P266 Series Control
                                                                  outputs the start voltage and runs the fan motor at
The P266 Series Control can be used to modulate
                                                                  minimum speed.
multiple identical motors in an application. Refer
to the P266 Series Single-Phase Condenser                     •   End Voltage establishes the voltage output that is
Fan Speed Controls Installation Instructions                      maintained by the P266 Series Control when the
(Part No. 24-7664-2705) for more details.                         sensed pressure is equal to or greater than the end
                                                                  pressure. The end voltage to the motor can be set
The P266 Series Control is housed in a NEMA 3R
                                                                  to either 95% or 97% of the total input voltage to
(IP54) rainproof enclosure for outside applications.
                                                                  the P266 Series Control.
The P266 Series Control is an energy efficient and
                                                              •   End Pressure establishes the pressure setpoint
effective alternative to on/off fan-cycling controls,
                                                                  (bar or psig) at which the P266 Series Control
multiple-speed motors, temperature fan speed
                                                                  outputs the end voltage and runs the fan motor at
controls, modulating air damper systems, condenser
                                                                  the maximum speed.
flood-back systems, and other condenser pressure
control methods.                                              Figure 2 illustrates the relationship between start
                                                              voltage, start pressure, end voltage, and end pressure.
                                                              Low Pressure Mode (LPM) determines whether the
                                                              fan motor is powered on (at the start voltage and
                                                              typically idling at minimum speed) or is off when the
                                                              condenser pressure is below the start pressure. See
                                                              Figure 2.

                   P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin

                                                          2
                                                                                                                                 Low-Speed Capacitor              Low-Speed Capacitor
                            End                                                                                        End            Enabled                          Disabled
                           Voltage                                                                                    Voltage
                            Mode                                            r
                                                                         oto

 Voltage to Motor                                                                               Voltage to Motor
                                       Low                          oM
                                     Pressure                    get                                                                                                   to
                                                                                                                                                                         r
                                      Mode             Vo
                                                         l   t a                                                                                                     Mo
                                                                                                                                 Changeover Voltage          to
                                        On                                                                               CV
                                                                                                                                                         age
                            Start                                                                                                                     l t
                                                                                                                                                    Vo
                           Voltage
                                                Low Pressure Mode
                                                Off                                                                    Start

      FIG:p266_Valu_Rels
                                                                                                                      Voltage     LPM On
                                                                                                                                                 LPM
                                 0          Start                                 End                                                            Off

                                                                                                   FIG:p266_CV_Rels
                                          Pressure                              Pressure
                                                                                                                             0              Start                                    End
                                                Pressure at Sensor
                                                                                                                                          Pressure                                 Pressure
                           Figure 2: Relationship between Some P266                                                                             Pressure at Sensor
                           Series Fan Speed Control Values and Modes                                                  Figure 3:         Low-Speed Capacitor Operation
Split Winding Mode enables the M2 Triac on the
P266 Series Control, which allows you to split the main                                        Auxiliary Fan Stage Mode allows you to set up the
windings of the motor from the auxiliary windings (and                                         P266 Series Control to cycle (on/off) up to three
the M1 Triac), and power the main windings with the                                            additional (fixed-speed) fan motors or fan stages in
M2 Triac. Split winding operation increases fan motor                                          conjunction with the variable speed fan controlled by
efficiency.                                                                                    the P266 Series Control. Three low-voltage circuits can
                                                                                               be wired to control the auxiliary fan motor/stage
Note: Split winding mode is available for only                                                 starters.
240 VAC single-phase PSC motors that have split
winding wire leads. Refer to the motor manufacturer’s                                          Figure 4 shows a P266 Series Control application with
installation instructions to determine if your fan motor                                       one auxiliary fan operating in conjunction with the
may be wired to enable the split winding mode.                                                 speed-controlled fan. When the condenser load
                                                                                               exceeds the output capacity of the speed-controlled
Copeland Digital Scroll™ Compressor Mode allows                                                fan, the P266 Series Control powers on the auxiliary
you to use the P266 Series Control on a system that                                            fan and shifts the speed-controlled (P266) fan to a new
uses a digital scroll compressor. Failure to enable the                                        start pressure.
digital scroll compressor mode when using a digital
scroll compressor may cause your condenser fan to                                                                                           Fan Throttling Range

                                                                                                                                                                                          Fig:AuxFanOvrlap
oscillate.                                                                                                                                              % Fan
                                                                                                        Total                                           Overlap
Low-Speed Capacitor Mode allows you (on some
                                                                                                                                                                         ut

                                                                                                Capacity
P266 Series models) to connect a low-speed capacitor                                                                                    P266 Fan                      utp Aux.Fan
                                                                                                                                                                   n O
to the M3 triac on the control and the auxiliary windings                                                                                Stage                   Fa          Plus
                                                                                                                                          Shift              266          P266 Fan
on the fan motor, and power the M3 triac, which                                                                                                             P
                                                                                                                                                                            Output
                                                                                                        1st
provides additional power to the motor at low speed. In                                                Stage
many fan motor speed applications, the addition of the                                                                                                  t

                                                                                                Output
                                                                                                                                                     tpu           Auxiliary
low-speed capacitor circuit can provide more efficient,                                                                                            Ou                Fan
                                                                                                                                               Fa
                                                                                                                                                 n            On
quiet and cooler motor operation at low speeds.                                                                                           66      Off               Output
                                                                                                                                        P2
Changeover Voltage determines the voltage at which                                                                       0     Start                                             End
the P266 Series control connects and disconnects                                                                             Pressure                                          Pressure
power to the M3 triac, low-speed capacitor, and                                                                                            Pressure at Sensor
auxiliary motor windings (Figure 3).
                                                                                                 Figure 4: Graph Showing a Speed-Controlled
                                                                                                (P266) Fan Operating with One Auxiliary (On/Off)
                                                                                                   Fan Stage over the Entire Pressure Range

                                            P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin

                                                                                           3
Auxiliary Fan Overlap determines the pressure range             Ordering Information
overlap (as a percentage of the total pressure range)
                                                                The four basic types of P266 Series Controls are based
between the fan stages set up on the P266 Series
                                                                on the supply voltage rating and whether the control
Control. The fan overlap value is equal for all auxiliary
                                                                has an onboard, low-voltage power supply transformer.
fan stages set up on the control.
                                                                P266A type controls are 208 to 240 VAC range controls
Increasing the auxiliary fan overlap value decreases
                                                                without onboard, low-voltage transformers.
the (on/off) cycling rate of the auxiliary fans, and
increases the pressure differential between auxiliary           P266B type controls are 460 to 575 VAC range controls
fan stages (which increases the pressure range of each          without onboard, low-voltage transformers.
auxiliary fan stage).
                                                                P266C type controls are 380 to 460 VAC controls
Test Voltage Mode                                               without onboard, low-voltage transformers.
Test voltage mode is a special setup, testing, and              P266E type controls are 208 to 240 VAC range controls
tuning feature that allows you to wire a P266 Series            with an onboard, low-voltage transformers.
Control and fan motor in the field, and test operate the
fan motor at different start voltage values without             Table 2 provides product code numbers, descriptions,
connecting a pressure transducer. You can also set up           and details for the currently available P266 Series
and test low-speed capacitor operation in the test              Single-Phase Condenser Fan Speed Control models.
voltage mode. When your fan motor is operating as               Table 3 provides product code numbers and
desired, you can save the test settings, connect the            descriptions for the currently available P266 Series
transducer, and operate your application at the saved           Electronic Pressure Transducers.
settings.
                                                                Repair Information
                                                                If a P266 Series Single-Phase Condenser Fan Speed
                                                                Control fails to operate within its specifications, replace
                                                                the unit. For a replacement P266 Series Control,
                                                                contact the nearest Johnson Controls representative.
Table 2: P266 Series Fan Speed Control Model and Kit Product Code Numbers, Descriptions, and Details
         (Part 1 of 3)
 Product Code       Description                       Transducer        Voltage      Maximum       High         Available
 Number                                               Model             (in VAC)     Output        VAC          Auxiliary
                                                      Included                       Amperes       Triacs       Fan
                                                      in Kit                                                    Control
                                                                                                                Circuits1
 P266AAA-100C2      P266 Fan Speed Control (Only)     N/A               208/240      8             3            0

 P266ABA-100C2      P266 Fan Speed Control (Only)     N/A               208/240      8             3            3

 P266ACA-100C2      P266 Fan Speed Control (Only)     N/A               208/240      8             1            0

 P266ADA-100C2      P266 Fan Speed Control (Only)     N/A               208/240      8             1            3

 P266BGA-100C2      P266 Fan Speed Control (Only)     N/A               460/575      4             2            0

 P266BHA-100C2      P266 Fan Speed Control (Only)     N/A               460/575      4             2            3

 P266BCA-100C2      P266 Fan Speed Control (Only)     N/A               460/575      4             1            0

 P266BDA-100C2      P266 Fan Speed Control (Only)     N/A               460/575      4             1            3

 P266CHA-100C2      P266 Fan Speed Control (Only)     N/A               380/460      4             2            3

 P266ABA-1K2        P266 Fan Speed Control with       P266SNR-1C        208/240      8             3            3
                    One P266 Pressure Transducer      0 to 35 bar
                    and One 2 m (6.6 ft) Cable        (0 to 508 psig)
 P266ABA-3K2        P266 Fan Speed Control with       P266SNR-2C        208/240      8             3            3
                    One P266 Pressure Transducer      0 to 52 bar
                    and One 2 m (6.6 ft) Cable        (0 to 754 psig)

                    P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin

                                                            4
Table 2: P266 Series Fan Speed Control Model and Kit Product Code Numbers, Descriptions, and Details
         (Part 2 of 3)
Product Code     Description                     Transducer        Voltage    Maximum   High     Available
Number                                           Model             (in VAC)   Output    VAC      Auxiliary
                                                 Included                     Amperes   Triacs   Fan
                                                 in Kit                                          Control
                                                                                                 Circuits1
P266ABA-2K2      P266 Fan Speed Control with     P266SNR-1C        208/240    8         3        3
                 Two P266 Pressure Transducers   0 to 35 bar
                 and Two 2 m (6.6 ft) Cables     (0 to 508 psig)
P266ABA-4K2      P266 Fan Speed Control with     P266SNR-2C        208/240    8         3        3
                 Two P266 Pressure Transducers   0 to 52 bar
                 and Two 2 m (6.6 ft) Cables     (0 to 754 psig)
P266BHA-1K2      P266 Fan Speed Control with     P266SNR-1C        460/575    4         2        3
                 One P266 Pressure Transducer    0 to 35 bar
                 and One 2 m (6.6 ft) Cable      (0 to 508 psig)
P266BHA-3K2      P266 Fan Speed Control with     P266SNR-2C        460/575    4         2        3
                 One P266 Pressure Transducer    0 to 52 bar
                 and One 2 m (6.6 ft) Cable      (0 to 754 psig)
P266BHA-2K2      P266 Fan Speed Control with     P266SNR-1C        460/575    4         2        3
                 Two P266 Pressure Transducers   0 to 35 bar
                 and Two                         (0 to 508 psig)
                 2 m (6.6 ft) Cables
P266BHA-4K2      P266 Fan Speed Control with     P266SNR-2C        460/575    4         2        3
                 Two P266 Pressure Transducers   0 to 52 bar
                 and Two                         (0 to 754 psig)
                 2 m (6.6 ft) Cables
P266EAA-1K2      P266 Fan Speed Control with     P266SNR-1C        208/240    8         3        0
                 Internal Transformer and        0 to 35 bar
                 One P266 Pressure Transducer    (0 to 508 psig)
                 and One 2 m (6.6 ft) Cable
P266EAA-3K2      P266 Fan Speed Control with     P266SNR-2C        208/240    8         3        0
                 Internal Transformer and        0 to 52 bar
                 One P266 Pressure Transducer    (0 to 754 psig)
                 and One 2 m (6.6 ft) Cable
P266EBA-1K2      P266 Fan Speed Control with     P266SNR-1C        208/240    8         3        3
                 Internal Transformer and        0 to 35 bar
                 One P266 Pressure Transducer    (0 to 508 psig)
                 and One 2 m (6.6 ft) Cable
P266EBA-3K2      P266 Fan Speed Control with     P266SNR-2C        208/240    8         3        3
                 Internal Transformer and        0 to 52 bar
                 One P266 Pressure Transducer    (0 to 754 psig)
                 and One 2 m (6.6 ft) Cable
P266ECA-1K2      P266 Fan Speed Control with     P266SNR-1C        208/240    8         1        0
                 Internal Transformer and        0 to 35 bar
                 One P266 Pressure Transducer    (0 to 508 psig)
                 and One 2 m (6.6 ft) Cable
P266ECA-3K       P266 Fan Speed Control with     P266SNR-2C        208/240    8         1        0
                 Internal Transformer and        0 to 52 bar
                 One P266 Pressure Transducer    (0 to 754 psig)
                 and One 2 m (6.6 ft) Cable

                P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin

                                                      5
Table 2: P266 Series Fan Speed Control Model and Kit Product Code Numbers, Descriptions, and Details
         (Part 3 of 3)
 Product Code         Description                          Transducer        Voltage      Maximum       High         Available
 Number                                                    Model             (in VAC)     Output        VAC          Auxiliary
                                                           Included                       Amperes       Triacs       Fan
                                                           in Kit                                                    Control
                                                                                                                     Circuits1
 P266EDA-1K2          P266 Fan Speed Control with          P266SNR-1C        208/240      8             1            3
                      Internal Transformer and             0 to 35 bar
                      One P266 Pressure Transducer         (0 to 508 psig)
                      and One 2 m (6.6 ft) Cable
 P266EDA-3K2          P266 Fan Speed Control with          P266SNR-2C        208/240      8             1            3
                      Internal Transformer and             0 to 52 bar
                      One P266 Pressure Transducer         (0 to 754 psig)
                      and One 2 m (6.6 ft) Cable
 P266EEA-1K2          P266 Fan Speed Control with          P266SNR-1C        208/240      12            1            0
                      Internal Transformer and             0 to 35 bar
                      One P266 Pressure Transducer         (0 to 508 psig)
                      and One 2 m (6.6 ft) Cable
 P266EEA-3K2          P266 Fan Speed Control with          P266SNR-2C        208/240      12            1            0
                      Internal Transformer and             0 to 52 bar
                      One P266 Pressure Transducer         (0 to 754 psig)
                      and One 2 m (6.6 ft) Cable
 P266EFA-1K2          P266 Fan Speed Control with          P266SNR-1C        208/240      12            1            3
                      Internal Transformer and             0 to 35 bar
                      One P266 Pressure Transducer         (0 to 508 psig)
                      and One 2 m (6.6 ft) Cable

1.   24 VAC Class 2 at 1/4 A.
2.   Factory default settings: Start voltage is set to 40% of the supply line voltage. End voltage is set to 95% of the supply line
     voltage. Start pressure is set to 44% of the total pressure range of the P266 Pressure Transducer. End pressure is set to 51%
     of the total pressure range of the P266 Pressure Transducer.

P266 Series Electronic Pressure Transducers                         Note: On P266 Series Control applications that use
P266 Series Controls are designed to reference either               two P266 Series Transducers, the P266 Series Control
one or two Johnson Controls P266 Series Electronic                  always references the transducer that is sensing the
Pressure Transducers to monitor condenser pressure.                 higher pressure.

P266 Series Transducers are specialized versions of                  IMPORTANT: When two P266 Series Transducers
the P499 Series Electronic Pressure Transducers,                     are connected to a P266 Series Control, the
designed for use with P266 Series Fan Speed Controls.                transducers must be the same model (product code
See Table 3 for the available P266 Series transducer                 number). Failure to connect the same P266 Series
models.                                                              Transducer models to the P266 Series Control can
                                                                     result in erratic control behavior.
Refer to the P499 Series Electronic Pressure
Transducers Product/Technical Bulletin (LIT-12011190)
for detailed information on installing P266 Series
Transducers.
Table 3: P266 Series SNR Electronic Pressure Transducers
 Product Code              Description
 Number
 P266SNR-1C                Electronic Pressure Transducer: 0 to 35 bar (0 to 508 psig) Total Range
                           with a 1/4 in. SAE Female Flare Connection and a 2 Meter (6.6 ft) Cable
 P266SNR-2C                Electronic Pressure Transducer: 0 to 52 bar (0 to 754 psig) Total Range
                           with a 1/4 in. SAE Female Flare Connection and a 2 Meter (6.6 ft) Cable

                      P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin

                                                                6
Technical Specifications
P266 Series Single-Phase Condenser Fan Speed Controls
 Input Supply Power                       208/240 VAC 50/60 Hz, 380/460 VAC 50/60 Hz, or 460/575 VAC 50/60 Hz, Depending
                                          on the Model (Refer to the Label inside the P266 Series Control Housing Cover for
                                          Rated Voltage Range and Model-Specific Wiring Diagram)
 Short Circuit Current Rating             Suitable for Use on a Circuit Capable of Delivering Not More Than 5,000 rms
                                          Symmetrical Amperes, 600 Volts Maximum When Protected by Class H Fuses
 Low-Voltage Power Supply                 P266A, P266B, and P266C Types: External 24 VAC Class 2, 20 VA Supply Transformer
                                          P266E Types: Low Voltage Power for P266 Series Control is Provided by an Onboard
                                          Transformer
                                          Note: When auxiliary fan starters are connected to P266E type controls, you must
                                          provide an external Safety Extra-Low Voltage (SELV) AC supply to power the fan
                                          starters.
 Ambient Operating Conditions             Temperature: -40 to 60C (-40 to 140F)
                                          Humidity: Up to 95% RH Non-condensing; Maximum Dew Point 29C (85F)
 Ambient Shipping and                     Temperature: -40 to 85C (-40 to 185F)
 Storage Conditions                       Humidity: Up to 95% RH Non-condensing; Maximum Dew Point 29C (85F)
 Low Voltage Connections                  1/4 in. Quick-Connect Terminals, 30 m (100 ft) Maximum Wiring Runs
 Input Transducer                         P266SNR-x Pressure Transducer: 5 VDC for 0.5 to 4.5 VDC Ratiometric Analog Signal
 Enclosure Type                           NEMA 3R, IP54
 Case Construction                        Aluminum Die Casting
 Cover Construction                       UV Stabilized Polycarbonate
 Dimensions (H x W x D)                   159 x 177 x 70 mm (6-1/4 x 7 x 2-3/4 in.)
 Weight                                   Heaviest Model Weight: 1.0 kg (2.2 lb)
                                          Approximate Shipping Weight: 1.2 kg (2.6 lb)
 Compliance                               North America: cULus, File E244421;
                                          FCC Compliant to CFR47, Part 15, Subpart B, Class A
                                          Industry Canada (IC) Compliant to Canadian ICES-003, Class A Limits
                                          Europe: CE Mark – Johnson Controls declares that this product is in compliance with
                                          the essential requirements and other relevant provisions of the EMC Directive 2004/108/
                                          EC and the Low Voltage Directive 2006/95/EC.
                                          Australia: C-Tick Compliant (N1813)
 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
 these specifications, contact Johnson Controls Refrigeration Application Engineering at 1-800-275-5676 or 1-414-524-5535.
 Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.

United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.

Canadian Emissions Compliance
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

                                                                                                                   www.penncontrols.com

                                             ® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
                                United States of America and/or other countries. All other trademarks used herein are the property
                                            of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved.

                        P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin

                                                                       7

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.