P266 Series Single-Phase Condenser Fan Speed Controls
Product Bulletin
P266xxA-xx Code No. LIT-12011534
Issued May 2018
The P266 Series Single-Phase Condenser Fan Speed
Controls are cost-effective, weather-resistant, durable
motor speed controls. The P266 Series Controls are
designed for approved single-phase, Permanent
Split-Capacitor (PSC) motors commonly used in a wide
variety of refrigeration and air conditioning condenser
fan applications.
The P266 Series Controls are designed to replace the
Johnson Controls® P66 Series and P215 Series Fan
Speed Controls, providing additional features and
flexibility, greater energy efficiency, and longer motor
life in a compact, rugged, weather-resistant package.
P266 Series Controls are available for 208 through
575 VAC 50/60 Hz range applications. P266 Series
Controls have current ratings from 4 to 12 A,
depending on the voltage and model.
Some P266 Series Controls provide optional control of
up to three auxiliary (fixed-speed) fans or fan stages. In
addition, some models provide two additional
high-voltage triacs that allow you to split the source Figure 1: P266 Series Single-Phase
power to the main and auxiliary windings, and connect Condenser Fan Speed Control
a low-speed capacitor to increase efficiency at
low-speed operation.
Table 1: Features and Benefits
Features Benefits
One or Two Durable, Accurate, Stainless Steel, Resist damage from physical shock, vibration, pressure pulsation, and
Remote-Mount Pressure Transducers extreme environmental conditions; eliminate capillary tube breaks and
greatly reduce refrigerant loss potential; provide 1% total error band; and
are applicable to single and multi-circuit condenser applications.
Available in 208/240 VAC (8 or 12 A), Provides efficient PSC motor speed control for a wide range of
380/460 VAC (4 A), or 460/575 VAC (4 A) condenser fan applications.
Wide, Adjustable Pressure Throttling Range Enables application flexibility and allows you to tune condenser
operation to specific pressure ranges and ambient environments.
Optional Auxiliary Fan Control Provides control of up to three fixed-speed fans or fan stages in
conjunction with the speed controlled fan or fan stage.
Optional Low-Speed Capacitor Mode Enables cooler, quieter, and more efficient fan motor operation at low
speeds.
NEMA3R, (IP54) Enclosure with Integral Metal Provides a rugged, weather-resistant fan control with good heat
Heat-Sink and Stand-Off Mounting Feet dissipation and a sturdy mounting base.
P266 Series Single-Phase Condenser Fan Speed Controls Product
Bulletin
1
Application P266 Series Single-Phase Fan Speed Control
applications include:
IMPORTANT: Use this P266 Series Single-Phase
• computer room air conditioning
Condenser Fan Speed Control only as an operating
control. Where failure or malfunction of the fan • commercial refrigeration
speed control could lead to personal injury or
• commercial air conditioning
property damage to the controlled equipment or
other property, additional precautions must be P266 Series Control Operation
designed into the control system. Incorporate and The P266 Series Control regulates fan motor speed by
maintain other devices, such as supervisory or limiting the supply voltage to the motor based on the
alarm systems or safety or limit controls, intended to sensed condenser pressure. In a typical P266 Series
warn of or protect against failure or malfunction of Control application, as the condenser pressure rises,
the fan speed control. the P266 Series Control increases the supply voltage
to the fan motor, which increases fan speed and air
CAUTION: Risk of Property Damage movement across the condenser coil. The increased
Use only single-phase PSC motors
! approved by the manufacturer for speed
air movement removes condenser heat faster, which
maintains the condenser pressure within the defined
control applications with the P266 Series range.
Control. Failure to use a single-phase
P266 Series Control Setup Values and Modes
PSC motor may damage the motor and
other property. The P266 Series Control ships with up to ten factory
default setup values and modes. These settings can be
The P266 Series Single-Phase Condenser Fan Speed adjusted in the field (if required) to meet your specific
Control, in conjunction with a P266 Series Electronic condenser application requirements.
Pressure Transducer, is a pressure-actuated, digital
The adjustable settings of the P266 Series Control
electronic motor speed control designed for approved
include:
single-phase PSC motors used in a wide variety of
HVACR applications. • Start Voltage establishes the initial minimum
voltage delivered by the P266 Series Control to the
The P266 Series Control regulates supply voltage to
fan motor, to idle the fan motor at the minimum
the fan motor in response to the condenser refrigerant
speed.
pressure, and maintains the appropriate fan speed
(air movement) through the condenser regardless of • Start Pressure establishes the pressure setpoint
the ambient temperature or air delivery variations. (bar or psig) at which the P266 Series Control
outputs the start voltage and runs the fan motor at
The P266 Series Control can be used to modulate
minimum speed.
multiple identical motors in an application. Refer
to the P266 Series Single-Phase Condenser • End Voltage establishes the voltage output that is
Fan Speed Controls Installation Instructions maintained by the P266 Series Control when the
(Part No. 24-7664-2705) for more details. sensed pressure is equal to or greater than the end
pressure. The end voltage to the motor can be set
The P266 Series Control is housed in a NEMA 3R
to either 95% or 97% of the total input voltage to
(IP54) rainproof enclosure for outside applications.
the P266 Series Control.
The P266 Series Control is an energy efficient and
• End Pressure establishes the pressure setpoint
effective alternative to on/off fan-cycling controls,
(bar or psig) at which the P266 Series Control
multiple-speed motors, temperature fan speed
outputs the end voltage and runs the fan motor at
controls, modulating air damper systems, condenser
the maximum speed.
flood-back systems, and other condenser pressure
control methods. Figure 2 illustrates the relationship between start
voltage, start pressure, end voltage, and end pressure.
Low Pressure Mode (LPM) determines whether the
fan motor is powered on (at the start voltage and
typically idling at minimum speed) or is off when the
condenser pressure is below the start pressure. See
Figure 2.
P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin
2
Low-Speed Capacitor Low-Speed Capacitor
End End Enabled Disabled
Voltage Voltage
Mode r
oto
Voltage to Motor Voltage to Motor
Low oM
Pressure get to
r
Mode Vo
l t a Mo
Changeover Voltage to
On CV
age
Start l t
Vo
Voltage
Low Pressure Mode
Off Start
FIG:p266_Valu_Rels
Voltage LPM On
LPM
0 Start End Off
FIG:p266_CV_Rels
Pressure Pressure
0 Start End
Pressure at Sensor
Pressure Pressure
Figure 2: Relationship between Some P266 Pressure at Sensor
Series Fan Speed Control Values and Modes Figure 3: Low-Speed Capacitor Operation
Split Winding Mode enables the M2 Triac on the
P266 Series Control, which allows you to split the main Auxiliary Fan Stage Mode allows you to set up the
windings of the motor from the auxiliary windings (and P266 Series Control to cycle (on/off) up to three
the M1 Triac), and power the main windings with the additional (fixed-speed) fan motors or fan stages in
M2 Triac. Split winding operation increases fan motor conjunction with the variable speed fan controlled by
efficiency. the P266 Series Control. Three low-voltage circuits can
be wired to control the auxiliary fan motor/stage
Note: Split winding mode is available for only starters.
240 VAC single-phase PSC motors that have split
winding wire leads. Refer to the motor manufacturer’s Figure 4 shows a P266 Series Control application with
installation instructions to determine if your fan motor one auxiliary fan operating in conjunction with the
may be wired to enable the split winding mode. speed-controlled fan. When the condenser load
exceeds the output capacity of the speed-controlled
Copeland Digital Scroll™ Compressor Mode allows fan, the P266 Series Control powers on the auxiliary
you to use the P266 Series Control on a system that fan and shifts the speed-controlled (P266) fan to a new
uses a digital scroll compressor. Failure to enable the start pressure.
digital scroll compressor mode when using a digital
scroll compressor may cause your condenser fan to Fan Throttling Range
Fig:AuxFanOvrlap
oscillate. % Fan
Total Overlap
Low-Speed Capacitor Mode allows you (on some
ut
Capacity
P266 Series models) to connect a low-speed capacitor P266 Fan utp Aux.Fan
n O
to the M3 triac on the control and the auxiliary windings Stage Fa Plus
Shift 266 P266 Fan
on the fan motor, and power the M3 triac, which P
Output
1st
provides additional power to the motor at low speed. In Stage
many fan motor speed applications, the addition of the t
Output
tpu Auxiliary
low-speed capacitor circuit can provide more efficient, Ou Fan
Fa
n On
quiet and cooler motor operation at low speeds. 66 Off Output
P2
Changeover Voltage determines the voltage at which 0 Start End
the P266 Series control connects and disconnects Pressure Pressure
power to the M3 triac, low-speed capacitor, and Pressure at Sensor
auxiliary motor windings (Figure 3).
Figure 4: Graph Showing a Speed-Controlled
(P266) Fan Operating with One Auxiliary (On/Off)
Fan Stage over the Entire Pressure Range
P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin
3
Auxiliary Fan Overlap determines the pressure range Ordering Information
overlap (as a percentage of the total pressure range)
The four basic types of P266 Series Controls are based
between the fan stages set up on the P266 Series
on the supply voltage rating and whether the control
Control. The fan overlap value is equal for all auxiliary
has an onboard, low-voltage power supply transformer.
fan stages set up on the control.
P266A type controls are 208 to 240 VAC range controls
Increasing the auxiliary fan overlap value decreases
without onboard, low-voltage transformers.
the (on/off) cycling rate of the auxiliary fans, and
increases the pressure differential between auxiliary P266B type controls are 460 to 575 VAC range controls
fan stages (which increases the pressure range of each without onboard, low-voltage transformers.
auxiliary fan stage).
P266C type controls are 380 to 460 VAC controls
Test Voltage Mode without onboard, low-voltage transformers.
Test voltage mode is a special setup, testing, and P266E type controls are 208 to 240 VAC range controls
tuning feature that allows you to wire a P266 Series with an onboard, low-voltage transformers.
Control and fan motor in the field, and test operate the
fan motor at different start voltage values without Table 2 provides product code numbers, descriptions,
connecting a pressure transducer. You can also set up and details for the currently available P266 Series
and test low-speed capacitor operation in the test Single-Phase Condenser Fan Speed Control models.
voltage mode. When your fan motor is operating as Table 3 provides product code numbers and
desired, you can save the test settings, connect the descriptions for the currently available P266 Series
transducer, and operate your application at the saved Electronic Pressure Transducers.
settings.
Repair Information
If a P266 Series Single-Phase Condenser Fan Speed
Control fails to operate within its specifications, replace
the unit. For a replacement P266 Series Control,
contact the nearest Johnson Controls representative.
Table 2: P266 Series Fan Speed Control Model and Kit Product Code Numbers, Descriptions, and Details
(Part 1 of 3)
Product Code Description Transducer Voltage Maximum High Available
Number Model (in VAC) Output VAC Auxiliary
Included Amperes Triacs Fan
in Kit Control
Circuits1
P266AAA-100C2 P266 Fan Speed Control (Only) N/A 208/240 8 3 0
P266ABA-100C2 P266 Fan Speed Control (Only) N/A 208/240 8 3 3
P266ACA-100C2 P266 Fan Speed Control (Only) N/A 208/240 8 1 0
P266ADA-100C2 P266 Fan Speed Control (Only) N/A 208/240 8 1 3
P266BGA-100C2 P266 Fan Speed Control (Only) N/A 460/575 4 2 0
P266BHA-100C2 P266 Fan Speed Control (Only) N/A 460/575 4 2 3
P266BCA-100C2 P266 Fan Speed Control (Only) N/A 460/575 4 1 0
P266BDA-100C2 P266 Fan Speed Control (Only) N/A 460/575 4 1 3
P266CHA-100C2 P266 Fan Speed Control (Only) N/A 380/460 4 2 3
P266ABA-1K2 P266 Fan Speed Control with P266SNR-1C 208/240 8 3 3
One P266 Pressure Transducer 0 to 35 bar
and One 2 m (6.6 ft) Cable (0 to 508 psig)
P266ABA-3K2 P266 Fan Speed Control with P266SNR-2C 208/240 8 3 3
One P266 Pressure Transducer 0 to 52 bar
and One 2 m (6.6 ft) Cable (0 to 754 psig)
P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin
4
Table 2: P266 Series Fan Speed Control Model and Kit Product Code Numbers, Descriptions, and Details
(Part 2 of 3)
Product Code Description Transducer Voltage Maximum High Available
Number Model (in VAC) Output VAC Auxiliary
Included Amperes Triacs Fan
in Kit Control
Circuits1
P266ABA-2K2 P266 Fan Speed Control with P266SNR-1C 208/240 8 3 3
Two P266 Pressure Transducers 0 to 35 bar
and Two 2 m (6.6 ft) Cables (0 to 508 psig)
P266ABA-4K2 P266 Fan Speed Control with P266SNR-2C 208/240 8 3 3
Two P266 Pressure Transducers 0 to 52 bar
and Two 2 m (6.6 ft) Cables (0 to 754 psig)
P266BHA-1K2 P266 Fan Speed Control with P266SNR-1C 460/575 4 2 3
One P266 Pressure Transducer 0 to 35 bar
and One 2 m (6.6 ft) Cable (0 to 508 psig)
P266BHA-3K2 P266 Fan Speed Control with P266SNR-2C 460/575 4 2 3
One P266 Pressure Transducer 0 to 52 bar
and One 2 m (6.6 ft) Cable (0 to 754 psig)
P266BHA-2K2 P266 Fan Speed Control with P266SNR-1C 460/575 4 2 3
Two P266 Pressure Transducers 0 to 35 bar
and Two (0 to 508 psig)
2 m (6.6 ft) Cables
P266BHA-4K2 P266 Fan Speed Control with P266SNR-2C 460/575 4 2 3
Two P266 Pressure Transducers 0 to 52 bar
and Two (0 to 754 psig)
2 m (6.6 ft) Cables
P266EAA-1K2 P266 Fan Speed Control with P266SNR-1C 208/240 8 3 0
Internal Transformer and 0 to 35 bar
One P266 Pressure Transducer (0 to 508 psig)
and One 2 m (6.6 ft) Cable
P266EAA-3K2 P266 Fan Speed Control with P266SNR-2C 208/240 8 3 0
Internal Transformer and 0 to 52 bar
One P266 Pressure Transducer (0 to 754 psig)
and One 2 m (6.6 ft) Cable
P266EBA-1K2 P266 Fan Speed Control with P266SNR-1C 208/240 8 3 3
Internal Transformer and 0 to 35 bar
One P266 Pressure Transducer (0 to 508 psig)
and One 2 m (6.6 ft) Cable
P266EBA-3K2 P266 Fan Speed Control with P266SNR-2C 208/240 8 3 3
Internal Transformer and 0 to 52 bar
One P266 Pressure Transducer (0 to 754 psig)
and One 2 m (6.6 ft) Cable
P266ECA-1K2 P266 Fan Speed Control with P266SNR-1C 208/240 8 1 0
Internal Transformer and 0 to 35 bar
One P266 Pressure Transducer (0 to 508 psig)
and One 2 m (6.6 ft) Cable
P266ECA-3K P266 Fan Speed Control with P266SNR-2C 208/240 8 1 0
Internal Transformer and 0 to 52 bar
One P266 Pressure Transducer (0 to 754 psig)
and One 2 m (6.6 ft) Cable
P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin
5
Table 2: P266 Series Fan Speed Control Model and Kit Product Code Numbers, Descriptions, and Details
(Part 3 of 3)
Product Code Description Transducer Voltage Maximum High Available
Number Model (in VAC) Output VAC Auxiliary
Included Amperes Triacs Fan
in Kit Control
Circuits1
P266EDA-1K2 P266 Fan Speed Control with P266SNR-1C 208/240 8 1 3
Internal Transformer and 0 to 35 bar
One P266 Pressure Transducer (0 to 508 psig)
and One 2 m (6.6 ft) Cable
P266EDA-3K2 P266 Fan Speed Control with P266SNR-2C 208/240 8 1 3
Internal Transformer and 0 to 52 bar
One P266 Pressure Transducer (0 to 754 psig)
and One 2 m (6.6 ft) Cable
P266EEA-1K2 P266 Fan Speed Control with P266SNR-1C 208/240 12 1 0
Internal Transformer and 0 to 35 bar
One P266 Pressure Transducer (0 to 508 psig)
and One 2 m (6.6 ft) Cable
P266EEA-3K2 P266 Fan Speed Control with P266SNR-2C 208/240 12 1 0
Internal Transformer and 0 to 52 bar
One P266 Pressure Transducer (0 to 754 psig)
and One 2 m (6.6 ft) Cable
P266EFA-1K2 P266 Fan Speed Control with P266SNR-1C 208/240 12 1 3
Internal Transformer and 0 to 35 bar
One P266 Pressure Transducer (0 to 508 psig)
and One 2 m (6.6 ft) Cable
1. 24 VAC Class 2 at 1/4 A.
2. Factory default settings: Start voltage is set to 40% of the supply line voltage. End voltage is set to 95% of the supply line
voltage. Start pressure is set to 44% of the total pressure range of the P266 Pressure Transducer. End pressure is set to 51%
of the total pressure range of the P266 Pressure Transducer.
P266 Series Electronic Pressure Transducers Note: On P266 Series Control applications that use
P266 Series Controls are designed to reference either two P266 Series Transducers, the P266 Series Control
one or two Johnson Controls P266 Series Electronic always references the transducer that is sensing the
Pressure Transducers to monitor condenser pressure. higher pressure.
P266 Series Transducers are specialized versions of IMPORTANT: When two P266 Series Transducers
the P499 Series Electronic Pressure Transducers, are connected to a P266 Series Control, the
designed for use with P266 Series Fan Speed Controls. transducers must be the same model (product code
See Table 3 for the available P266 Series transducer number). Failure to connect the same P266 Series
models. Transducer models to the P266 Series Control can
result in erratic control behavior.
Refer to the P499 Series Electronic Pressure
Transducers Product/Technical Bulletin (LIT-12011190)
for detailed information on installing P266 Series
Transducers.
Table 3: P266 Series SNR Electronic Pressure Transducers
Product Code Description
Number
P266SNR-1C Electronic Pressure Transducer: 0 to 35 bar (0 to 508 psig) Total Range
with a 1/4 in. SAE Female Flare Connection and a 2 Meter (6.6 ft) Cable
P266SNR-2C Electronic Pressure Transducer: 0 to 52 bar (0 to 754 psig) Total Range
with a 1/4 in. SAE Female Flare Connection and a 2 Meter (6.6 ft) Cable
P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin
6
Technical Specifications
P266 Series Single-Phase Condenser Fan Speed Controls
Input Supply Power 208/240 VAC 50/60 Hz, 380/460 VAC 50/60 Hz, or 460/575 VAC 50/60 Hz, Depending
on the Model (Refer to the Label inside the P266 Series Control Housing Cover for
Rated Voltage Range and Model-Specific Wiring Diagram)
Short Circuit Current Rating Suitable for Use on a Circuit Capable of Delivering Not More Than 5,000 rms
Symmetrical Amperes, 600 Volts Maximum When Protected by Class H Fuses
Low-Voltage Power Supply P266A, P266B, and P266C Types: External 24 VAC Class 2, 20 VA Supply Transformer
P266E Types: Low Voltage Power for P266 Series Control is Provided by an Onboard
Transformer
Note: When auxiliary fan starters are connected to P266E type controls, you must
provide an external Safety Extra-Low Voltage (SELV) AC supply to power the fan
starters.
Ambient Operating Conditions Temperature: -40 to 60C (-40 to 140F)
Humidity: Up to 95% RH Non-condensing; Maximum Dew Point 29C (85F)
Ambient Shipping and Temperature: -40 to 85C (-40 to 185F)
Storage Conditions Humidity: Up to 95% RH Non-condensing; Maximum Dew Point 29C (85F)
Low Voltage Connections 1/4 in. Quick-Connect Terminals, 30 m (100 ft) Maximum Wiring Runs
Input Transducer P266SNR-x Pressure Transducer: 5 VDC for 0.5 to 4.5 VDC Ratiometric Analog Signal
Enclosure Type NEMA 3R, IP54
Case Construction Aluminum Die Casting
Cover Construction UV Stabilized Polycarbonate
Dimensions (H x W x D) 159 x 177 x 70 mm (6-1/4 x 7 x 2-3/4 in.)
Weight Heaviest Model Weight: 1.0 kg (2.2 lb)
Approximate Shipping Weight: 1.2 kg (2.6 lb)
Compliance North America: cULus, File E244421;
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Industry Canada (IC) Compliant to Canadian ICES-003, Class A Limits
Europe: CE Mark – Johnson Controls declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC Directive 2004/108/
EC and the Low Voltage Directive 2006/95/EC.
Australia: C-Tick Compliant (N1813)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
these specifications, contact Johnson Controls Refrigeration Application Engineering at 1-800-275-5676 or 1-414-524-5535.
Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
www.penncontrols.com
® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
United States of America and/or other countries. All other trademarks used herein are the property
of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved.
P266 Series Single-Phase Condenser Fan Speed Controls Product Bulletin
7Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.