Metasys Network Technical Manual 636
Function Modules Section
Technical Bulletin
Issue Date 0793
Output Analog Electrical Function Module
Introduction Page 3
• Description 3
• Application 4
• Capabilities 4
• Theory of Operation 5
• Specifications 6
Installation Guidelines 7
• General Information 7
• Physical Installation 7
• Current Source (0 to 20 mA) 8
• Voltage Source (0 to 10 volts) 9
• Current Control (0 to 20 mA) 10
Commissioning Procedures 11
• Physical Verification 11
• Software Verification 11
Troubleshooting Procedures 13
• Troubleshooting Chart 13
• Ordering Information 15
© 1993 Johnson Controls, Inc. 1
Order No. 636-041
2 Function Modules—Output Analog Electrical Function Module
Introduction
Description The Output Analog Electrical (OAE) Function Module is an interface
between the DCM and field devices. It may be configured to source
analog output voltage (0-10 VDC), source analog output current
(0-20 mA), or modulate current (0-20 mA) for externally powered devices.
The OAE Function Module features:
• digital to analog converter for converting DCM digital input into
analog output
• Auto/Manual (A-M) switch to enable/disable DCM control
• manual set potentiometer for manual output control (CW increases
output)
• feedback indication of the Auto/Manual switch setting to the DCM
For isolated analog outputs, use the OAI Function Module.
The OAE Function Module plugs into any one of the bottom ten slots
associated with the DCM. Figure 1 shows typical function module
locations in the NCU. A five slot panel is pictured.
Output FMs
DCMs
oae101
O AE 101
M A
Figure 1: OAE Function Module Locations
Function Modules—Output Analog Electrical Function Module 3
Application The OAE Function Module is typically used to:
• provide a controlled output voltage for an M100G
• provide current control (0 to 20 mA) for use with an external
(4 to 30 V) current source
• control a variable speed motor controller
Capabilities Table 1: OAE Function Module Capabilities
Capability Description Purpose
Input from DCM DCM inputs a digital command. Allows DCM to provide automatic
control of outputs.
Auto/Manual Switch, and Switch selects one of: Allows for manual override of
Manual Adjustment - Auto—DCM control of DCM control for special
outputs situations.
- Manual—DCM control
Allows for local/manual control,
disabled and output is
even if the DCM is not present.
controlled by manual
adjustment.
Power on Reset At low power or after power up, Provides controlled restart.
output goes to zero (in Auto
mode).
Output to Field Module outputs a voltage or Provides proportional control
current signal proportional to signals for motor driven actuators
input signal. or variable speed motor
controllers.
4 Function Modules—Output Analog Electrical Function Module
Theory of
Operation Figure 2 is a functional diagram of the OAE Function Module.
OAE
Control Current
DCM S ig n a l
Auto Source,
Electronics C o n d itio n e r
Voltage
Manual
Source, Field
Manual or Device
A d ju s tm e n t Current
Control
oae 101
Figure 2: OAE Function Diagram
The process is:
• The DCM provides a digital control signal.
• The control electronics in the OAE latch the digital control signal,
then convert it to a proportional analog signal.
• Depending on how the OAE is wired, this analog signal is a current
source, voltage source, or will modulate externally sourced current.
• A manually controlled Auto/Manual switch can disable DCM control
of the OAE outputs. The status of this switch is reported back to the
DCM.
• With the Auto/Manual switch in the Manual position, the module
output is controlled by a manual adjustment on the OAE.
(CW increases output.)
The unit will operate in Manual mode without the DCM present. The
corresponding power supply must be present.
Function Modules—Output Analog Electrical Function Module 5
Specifications Table 2: OAE Function Module Specifications
Specifications For Configurations
Category Voltage Source Current Source Current Control
Product Code FM-OAE101
Number
Output Range 0 to 10 V 0 to 20 mA 0 to 20 mA
(25 mA maximum) (4 VDC to 30 VDC)
(External power supply)
Output Limits 40 mA (maximum) 910 ohm maximum
load, including line
resistance
Output Projection Fused at 500 mA with a non-field replaceable fuse
Input-Output Linear analog output proportional to digital input value
Characteristics
Input Range 0 to 1024, based on a 10 bit data value from the DCM
Response Time 1 sec. for a full range change
Resolution 0.1% of full range
Accuracy ±0.4% of full scale output at 70 ±2°F. (21 ± 1.1°C)
Thermal Effects Gain Drift: ± 0.0055% per °F (±0.01% per °C) of full scale deviation
Offset Drift: ± 0.0055% per °F (±0.01% per °C) of full scale deviation
Calibration The module is factory calibrated.
Default Condition Output = 0 VDC on loss Output = 0 mA on loss Output = 0 mA on loss
of input power of input power of input power
Source Power Power is from the PWR in the NCU/NEU. (External power)
Operating 32 to 122°F (0 to 50°C)
Environmental 10 to 90% noncondensing relative humidity
Requirements 86°F (30°C) maximum dew point
Storage/Shipping -40 to 158°F (-40 to 70°C)
Environmental 5 to 95% noncondensing relative humidity
Requirements 86°F (30°C) maximum dew point
Size 0.85 in. H x 3.06 in. W x 7.0 in. L
(2.2 cm H x 7.8 cm W x 17.8 cm L)
Weight 0.5 lb. (0.22 kg)
Agency Compliance FCC Part 15 Subpart J - Class A, UL 916, CSA C22.2 No. 205
Agency Listings UL Listed and CSA certified as part of Metasys®
6 Function Modules—Output Analog Electrical Function Module
Installation Guidelines
General When installing and connecting function modules:
Information • Follow NEC and local codes.
• Observe maximums as specified in the specification table and in these
installation guidelines.
Physical
Installation
Assumptions The following procedure for the physical installation of the OAE Function
Module assumes:
• NCU/NEU panel is installed.
• Connections to field devices are complete.
• You have engineering drawings defining details for the installation.
• You are familiar with Metasys Network terminology, and the location
and operation of power switches.
Procedure For each OAE Function Module in the network, perform the following
steps.
1. Set the Auto/Manual switch to Manual.
2. Adjust output to minimum.
3. Refer to Figures 3 to 5, and identify the proper panel and slot number
location for this module.
4. Open the latch.
5. Insert the module in the appropriate slot.
6. Close latch, locking function module in place.
Function Modules—Output Analog Electrical Function Module 7
Current Source Figure 3 diagrams the wiring for Current Source (0 to 20 mA) applications
(0 to 20 mA) using the OAE Function Module.
2 5 0 ft. m a x .
OAE TBF No. 18 AW G
tw is te d p a ir
+
1
Control Signal
DCM A u to _
Electronics Conditioner Field
Variable
M anual Device
Current
Manual Source
Optional*
Adjustment 2
C o n n e c tio n to D C M * Optional for OAE.
co m p le te d th r o u g h Shield may be required by the
in te rn a l co n n e cto r TBF in left bay TBF in right bay field device for noise immunity.
o n e n d o f fu n ctio n of NCU/NEU of NCU/NEU See individual manufacturer's
m o d u le . specification sheet.
3 3
2 2
6 6
5 5
1 1
4 4
Strip wire and insert in side face of TBF. Use
set screw in front face to secure.
oaewire
Figure 3: Wiring for Current Source Applications
8 Function Modules—Output Analog Electrical Function Module
Voltage Source Figure 4 diagrams the wiring for Voltage Source (0 to 10 volts)
(0 to 10 volts) applications using the OAE Function Module.
2 5 0 ft. m a x .
OAE TBF No. 18 AW G
tw is te d p a ir
+
4
Control Signal
DCM A u to _
Electronics Conditioner Field
Variable
M anual Device
Current
Manual Source
O p tion a l*
Adjustment 5
C o n n e c tio n to D C M * O p tio n a l fo r O A E .
co m p le te d th r o u g h S h ie ld m a y b e r e q u ire d b y th e
in te rn a l co n n e cto r T B F in le ft b a y T B F in rig h t b a y fie ld d e vic e fo r n o is e im m u n ity .
o n e n d o f fu n ctio n o f N C U /N E U o f N C U /N E U S e e in d iv id u a l m a n u fa ctu r e r 's
m o d u le . sp e cific a tio n s h e e t.
3 3
2 2
6 6
5 5
1 1
4 4
S trip w ire a n d inse rt in sid e fa ce o f T B F . U s e
se t scre w in fro nt fa c e to se cu re .
oaewire
Figure 4: Wiring for Voltage Source Applications
Function Modules—Output Analog Electrical Function Module 9
Current Control Figure 5 diagrams the wiring for Current Control (0 to 20 mA)
(0 to 20 mA) applications using the OAE Function Module.
2 5 0 ft. m a x .
OAE TBF No. 18 AW G
tw is te d p a ir
+
2 E x t e r n a lly
DCM
Control Signal
A u to _ Powered
Electronics Conditioner
F ie ld
M anual Current
D e v ic e
Source (4 to 3 0 V )
Manual
O p tion a l*
Adjustment 3
C o n n e c tio n to D C M * O p tio n a l fo r O A E .
co m p le te d th r o u g h S h ie ld m a y b e r e q u ire d b y th e
in te rn a l co n n e cto r T B F in le ft b a y T B F in rig h t b a y fie ld d e vic e fo r n o is e im m u n ity .
o n e n d o f fu n ctio n o f N C U /N E U o f N C U /N E U S e e in d iv id u a l m a n u fa ctu r e r 's
m o d u le . sp e cific a tio n s h e e t.
3 3
2 2
6 6
5 5
1 1
4 4
S trip w ire a n d inse rt in sid e fa ce o f T B F . U s e
se t scre w in fro nt fa c e to se cu re .
oaewire
Figure 5: Wiring for Current Control Applications
10 Function Modules—Output Analog Electrical Function Module
Commissioning Procedures
Physical
Verification
Assumptions The following procedure for the physical verification of the OAE Function
Module assumes:
• Physical installation at the NCU/NEU panel is complete.
• Power is available at the panel power supply, and at the field device.
Procedure For each OAE Function Module in the network, perform the following
steps.
1. Power up the appropriate DCM power supply.
2. Adjust the manual control on the function module and verify that the
intended device responds, and that the response is appropriate.
Software
Verification
Assumptions The following procedure for the software verification of the OAE Function
Module assumes:
• Physical installation at the NCU/NEU panel is complete, including
NCM, DCM, FM, etc.
• The operating software for the network has been downloaded to the
NCM controlling the panel.
• An Operator Workstation is available.
Procedure For each OAE Function Module in the network, perform the following
steps.
1. Select the System summary that includes this OAE object.
2. Set Auto/Manual switch on the OAE to Auto.
3. Use the software override command and verify that the object’s Value
attribute (as seen in the summary) matches the actual value for the
field device.
Function Modules—Output Analog Electrical Function Module 11
12 Function Modules—Output Analog Electrical Function Module
Troubleshooting Procedures
Troubleshooting Use the diagram in Figure 6 (next page) as a troubleshooting guide. It
Chart applies for failures between point objects and field devices connected
through an OAE Function Module.
Function Modules—Output Analog Electrical Function Module 13
Start
Is the
Summary
Yes
containing this object Exit
displaying correct
values?
No
Is
Point Fix definition.
No
object definition See Operator Workstation
OK? User's Manual.
Yes
Is DCM
error LED off and Troubleshoot DCM
No
is N2 polling and See DCM 101 Technical
responding? Bulletin .
Yes
Is
No
external power
required?
Yes
Is
No Repair if JCI is
external power
responsible
supply OK?
Yes
Replace FM.
See Ordering Informationg for
Using a No
ordering information. Refer
DVM, check FM
to Material Return and
output. Is it
OK? Allowance Program,
Procedure 3C2700 for
Yes information on returning
defective FMs.
Using a No Troubleshoot
DVM, check input to connections
field device. and wiring.
OK?
Yes
Repair or replace field
device if JCI is responsible. oaeflow
Figure 6: OAE Troubleshooting
14 Function Modules—Output Analog Electrical Function Module
Ordering Table 3: Code Number
Information Description Product Code Number
OAE Function Module FM-OAE101-0
Function Modules—Output Analog Electrical Function Module 15
Notes
Controls Group FAN 636
507 E. Michigan Street Metasys Network Technical Manual
P.O. Box 423 Revision Date 0793
Milwaukee, WI 53201 Printed in U.S.A.
16 Function Modules—Output Analog Electrical Function ModuleПозиції каталогу з цим документом