SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

YLCS-SA/HA/AA — Microprocessor Based Control System operation manual, YLCS-SA/HA/AA & YAES-SA/DSA

Вид документаІнструкція
ВиробникJCI
МоделіYLCS-SA/HA/AA, YAES-SA 2 System, YAES-SA 3 System, YAES-DSA 4 System
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.8 МБ

Про документ

Operation instruction for the YORK Microprocessor Based Control System (MBCS) fitted to a range of YORK screw liquid chillers. The system provides multi-circuit control to maintain chilled liquid temperature, with heatpump operation available on YLCS HA units. It covers panel hardware, keypad programming of setpoints and cutouts, safeties, controls, I.S.N network messages, technical data tables and optional accessories.

Ключові дані

RefrigerantR134a
Display40 character LCD (2 x 20), update ~2 s (system 3/4 ~10 s)
Software version YLCS-SA/HA/AAB.A05.01.01 and higher
Software version YAES-DSA 4 System mainB.A06.14.07 and higher
Motor current electronic overload trip<5% or >115% FLA; >105% FLA for 30 sec
Oil pressure cutout<2.5 BAR G differential for 90 sec
Anti-recycle timermin start-to-start 10 min, stop-to-start 5 min (2 min after power failure)
Manual doc no.035L02631-100 Rev. 3 (11/05) GB

Застосування

  • Multi-circuit chilled liquid temperature control on YORK screw liquid chillers (YLCS SA/AA, YAES SA/3/4-system air cooled units)
  • Heatpump operation maintaining hot liquid temperature on YLCS HA units
  • Glycol cooling applications with programmable leaving water cutout and heater mat
  • Integration with York I.S.N network (remote shutdown, demand limit, setpoint, lead system)
  • Customer EMS interfacing via 0-10 Vdc, 4-20 mA dc or discrete contact closure setpoint reset

Особливості

  • 40 character backlit display (2 lines of 20 characters) with intensified viewing in direct sunlight
  • Real Time Clock with 10-year lithium battery back-up retaining programmed values during power failure
  • Rate Control / Rate Sensitivity anticipation to limit pulldown demand and prevent overshoot
  • Lockout, manual reset (3 faults in 90 minutes) and automatic reset safety categories
  • Anticipation safeties (motor current unloading, discharge pressure unloading) avoid total loss of cooling
  • Discharge pressure step 1 skip routine above 15.5 BAR
  • Daily start/stop and holiday scheduling with manual override (30 min)
  • Remote printout of live data and last 3 safety shutdowns; optional local printer kit (362L11330-002 UK / -003 EUROPE)
  • Optional York EMS micro interface card converting customer signals into 1–21 second PWM reset up to 22 °C
  • Slave control panel on YAES 3 & 4 system units linked by RS485 communication

Технічні дані

Parameter Value
Refrigerant R134a
Display 40 character liquid crystal, 2 lines of 20 characters
Display update rate ~2 seconds (systems 1 & 2); ~10 seconds (systems 3 & 4)
Software YLCS-SA/HA/AA B.A05.01.01 and higher
Software YAES-SA 2 System B.A05.01.01 and higher
Software YAES-SA 3 System main/slave Main B.A06.12.01 / Slave B.A05.13.01 and higher
Software YAES-DSA 4 System main/slave Main B.A06.14.07 / Slave B.A05.15.07 and higher
Chilled liquid temp display limits min -20.6°C, max 61.0°C
Ambient temp display limits min -18.4°C, max 56.2°C
Leaving water temp sensor check range -20 to +60 °C
LWT setpoint range (water cooling) 3.5 to 21.1 °C
LWT setpoint range (glycol cooling) -12.2 to 21.1 °C
Leaving Water Temp Cutout (water) 2.2 °C fixed
Leaving Water Temp Cutout (glycol) -13.3 to 2.2 °C programmable
Suction Pressure Cutout range 0.28 to 2.5 BAR G
Ambient Temp Low Cutout factory -18 °C, range -18 °C to +10 °C
Ambient Temp High Cutout 46 °C standard
Discharge cutout YLCS (micro/mech) 18.0 BAR SA / 22.0 BAR AA-HA micro; mech 18.9 BAR SA / 24.8 BAR AA-HA (second 19.3 BAR SA)
Discharge cutout YAES (micro/mech) 20.8 BAR micro; mechanical standard 24.0 BAR, Dutch 24.0 / 25.0 BAR
Discharge Pressure Unload 16.5 BAR SA / 20.0 BAR AA-HA (YLCS); 19.8 BAR (YAES)
Motor Current Unload factory 101% FLA, range 85 % to 101 %
Electronic overload thresholds <5% or >115% FLA shutdown; >105% for 30 sec shutdown (EN 60947-4-1 class 10A)
Oil pressure cutout <2.5 BAR G differential for 90 sec
High oil temperature shutdown >100 °C (start inhibit), running >95 °C after 120 s
High discharge temperature shutdown >105 °C, restart below 80 °C
Motor protector module trip/reset trip 110 °C (4.5 kΩ), reset 75 °C (2.75 kΩ)
Rate Control Temp factory 5.0 °C, range 0.1 to 11.1 °C
Rate Sensitivity factory 2.0 °C/min, range 0.3 to 8.0 °C/min
Local Control Range (YAES 4) 0.6 °C – 4.4 °C
Fan Control Dsch Pressure Setpoint factory 10.0 BAR, range 5–14 BAR (programmable)
Fan On/Off Press Diff factory 3.5 BAR, range 2–10.4 BAR
Fan stage spacing (single speed) +1.38, +2.41, +3.1, +3.79 BAR per stage
Two-speed fan stage 4 (fast) ON DP > FPSP + 4.14 BAR
Anti-recycle timer min start-to-start 10 min; stop-to-start 5 min; resets to 2 min after power failure
Anti-coincidence timer minimum 1 minute between compressor starts
Load timer / Unload timer normal 150 s (100 s YAES 4); down to 25 s (17 s YAES 4) in rate-control range
Pumpdown suction falls to suction cutout or pumpdown time exceeds 10 s
Heatpump HLTSP range 30 to 65 °C, control range 0.5 to 5 °C
LLTH sensor valid range -12.7 °C to 68.4 °C
Voltage free contacts rating 125 VA (York contacts); customer inputs 30 Vdc, gold contacts recommended
Chilled liquid pump contact terminals 33 & 34
Run contact terminals 35 & 36
Alarm contacts Sys 1: 32/31 close, 32/30 open; Sys 2: 39/38 close, 39/37 open
Remote emergency stop device connected to terminals 3 and 4
Printer interface RS232, 1200 baud, 8 data bits, no parity; max cable 7.5 m
Battery back-up 10-year lithium RTC chip (U13); ~10 yr clock off, ~5 yr clock on
History buffers 3 safety shutdown buffers

Варіанти замовлення

  • Local printer kit: 362L11330-002 (UK), 362L11330-003 (EUROPE)
  • Printer paper spare roll: 025L01992-000; spare ink ribbon: 025L01993-000
  • Optional accessories: York EMS Micro Interface Card (J18), micro gateway, discrete contact closure, 0-10 Vdc EMS signal, 4-20 mA dc EMS signal

Допуски та стандарти

  • EN 418 (emergency stop reset requirements)
  • EN 60204-1 (emergency stop / supply disconnect marking; customer wiring recommendation)
  • EN 60947-4-1 class 10A time-delay overload relays (electronic motor current protection, incl. phase loss sensitivity)

Текст документа

MICRO BASED CONTROL SYSTEM
YLCS-SA/HA/AA
YAES-SA 2 System
YAES-SA 3 System
YAES-DSA 4 System

                        OPERATION INSTRUCTION




YLCS-SA/HA/AA:     R134a - Software Version B.A05.01.01 and higher version levels
YAES-SA 2 System: R134a - Software Version B.A05.01.01 and higher version levels
YAES-SA 3 System: R134a - Main Software Version B.A06.12.01 and higher version levels
                   R134a - Slave Software Version B.A05.13.01 and higher version levels
YAES-DSA 4 System: R134a - Main Software Version B.A06.14.07 and higher version levels
                   R134a - Slave Software Version B.A05.15.07 and higher version levels




                                                                           035L02631-100 Rev. 3


                                                                                   (11/05)   GB
This manual contains a description of the operation of the Microprocessor Control System for a
range of York Chillers.

All work must be carried out in accordance with this manual and the relevant Installation,
Commissioning, Operation and Maintenance Documents for the specific Chiller.

This manual is essential as it contains information on Safety issues that relate to the product.
                                                              035L02631-100 Rev. 3            i


                                      Table of Contents

1    LOGIC SECTION                             5   PROGRAM KEY

     1.1 Introduction                    1         5.1 General                                    13

     1.2 Microprocessor Board            1         5.2 Leaving Water Temperature Setpoint         13

     1.3 Power Supply Board              1         5.3 Local Control Range                        13

     1.4 Relay Output Board              1         5.4 Selected Refrigerant                       13

     1.5 Current Transformer (-TC)       2         5.5 Discharge Cutout                           14

     1.6 40 Character Display            2         5.6 Ambient Temp Low Cutout                    14

     1.7 Emergency Stop Device           2         5.7 Ambient Temp High Cutout                   14

     1.8 Unit 1/0 (Auto/Off) Switch      2         5.8 Discharge Pressure Unload                  14

     1.9 System Switches                 3         5.9 Rate Control Temp                          14

     1.10 Keypad                         3         5.10 Leaving Water Temp Cutout                 14

     1.11 Battery Back-up                3         5.11 Suction Pressure Cutout                   15

                                                   5.12 Rate Sensitivity                          15
2    DISPLAY KEYS
                                                   5.13 Fan Discharge Pressure                    16
     2.1 General                         5
                                                   5.14 Fan On/Off Fan Differential               16
     2.2 Chilled Liquid Temps            5
                                                   5.15 Fan Speed Control                         16
     2.3 Ambient Temp                    5
                                                   5.16 Number of Fans                            16
     2.4 System 1 Pressures              5
                                                   5.17 Motor Current / % FLA                     16
     2.5 System 2 Pressures              6
                                                   5.18 Leaving Water Temperature
     2.6 Compressor Temperatures         6              Target Percent                            16
     2.7 Motor Current                   6         5.19 Heater Mat On Glycol                      16
     2.8 Operating Hours                           5.20 Manual/Auto Restart                       16
         Start Counter                   6

     2.9 Options                         6     6   CLOCK KEYS

                                                   6.1 General                                    18
3    STATUS KEY
                                                   6.2 Programming The Day, Time, and the
     3.1 General                         8             Date Set Time                              18
     3.2 General Status Message          8         6.3 Programming the Daily Start/Stop and
                                                       Holiday Schedule                           19
     3.3 Fault Status Messages          10
                                                   6.4 Units With Two Speed Fans                  20
4    ENTRY KEYS
                                                   6.5 Manual Override                            20
     4.1 General                        12
                                               7   SETPOINT KEYS
     4.2 Numerical Keypad               12
                                                   7.1 Programming
     4.3 Enter Key                      12             Leaving Water Control                      21
     4.4 Cancel Key                     12         7.2 Programming Leaving Water Rate Control 22
     4.5 AM/PM Key                      12         7.3 Leaving Water Temperature Control          24
     4.6 Advance Day Key                12




(11/05)
       ii         035L02631-100 Rev. 3



8    SYSTEM SAFETIES                                     12   OPERATING SEQUENCE

     8.1 Lockout Safeties (Lockout on first trip)   25   13   I.S.N RELATED STATUS MESSAGES
     8.2 Manual Reset Safeties
                                                              13.1 I.S.N. Pages                           64
         (Locks out after 3 faults in 90 minutes)   27

     8.3 Automatic Reset Safeties                   30   14   HEATPUMP OPERATION ON
                                                              YLCS HA UNITS
     8.4    Anticipation Safety Controls            31

     8.5 Discharge Pressure Step 1 Skip Routine     32        14.1 Mode Selection.                        68

                                                              14.2 LIQUID TEMP/RANGE KEY                  68
9    CONTROLS
                                                              14.3 Leaving Liquid Temperature Control     68
     9.1 Condenser Fan Control                      33
                                                              14.4 Leaving Liquid Hot\Cold Differential
     9.2 Imperial Display                           37             Skip Step 1 Routine                    71


10   PRINT KEYS                                          15   TECHNICAL DATA

                                                              15.1 Pressure, Temperature and
     10.1 General                                   46             Motor Current Tables                   72
     10.2 Remote Printout                                     15.2 Fan Pressure Settings                  73
          Oper Data                                 46
                                                              15.3 Motor Current Program Values           74
     10.3 Remote Printout
          History                                   46        15.4 Loading Charts                         76

     10.4 Local Display Readout                               15.5 Digital Input/Output Software
          Oper Data                                 47             Cross Reference Tables                 77

     10.5 Local Display Readout                          16   OPTIONAL ACCESSORIES
          History                                   50
                                                              16.1 York EMS Micro Interface Card          82
     10.6 Memory Battery Back-up                    54
                                                              16.2 Discrete Contact Closure               83

                                                              16.3 0-10 Vdc Customer EMS Signal           84
11   SYSTEM COMPONENTS
                                                              16.4 4-20 mA dc Customer EMS Signal         84
     11.1 Control Panel                             57

     11.2 Remote Emergency Stop Device              57

     11.3 Voltage Free Contacts                     57

     11.4 Alarm Contacts                            57

     11.5 Chilled Liquid Pump Contact               57

     11.6 Run Contact                               57

     11.7 Customer Voltage Free Contacts            58

     11.8 Remote Start/Stop                         58

     11.9 Flow Switch                               58

     11.10 Remote Unloading                         58

     11.11 Remote Setpoint Reset                    59

     11.12 Fan Full Speed Inhibit                   60

     11.13 Local Printer Option                     60




                                                                                                          (11/05)
                                                                       035L02631-100 Rev. 3          1



1         LOGIC SECTION                                Keypad commands are acted upon by the
                                                       microprocessor to change setpoints, cutouts,
1.1       Introduction                                 scheduling, operating requirements, and to
                                                       provide displays.
The YORK Microprocessor Based Control System
(MBCS) is capable of multi-circuit control to          A +12 V REG supply voltage from the Power
maintain chilled liquid temperature. On YLCS HA        Supply Board is converted to +5 V REG by a
units heatpump operation is also possible to           voltage regulator located on the Microprocessor
maintain a hot liquid temperature, see section 14      Board. This voltage is used to operate integrated
for details.                                           circuitry on the board.

A 40 character display (2 lines of 20 characters)      Four system switches located on the
allows the operator to display system operating        Microprocessor Board activate or deactivate the
parameters as well as access programmed                individual systems (compressors). These switches
information already in memory. A keypad for            are also used to reset electrical lockout conditions.
programming and accessing setpoints, pressures,
temperatures, motor current, cutouts, daily            1.3   Power Supply Board
schedule, options, and fault information is
provided.                                              The on-board switching power supply (protected
                                                       by fuse –F5) converts 24 Vac from the logic
A unit 1/0 (Auto/Off) (lockable in the off position)   transformer to +12 V REG which is supplied to the
switch is available to activate or de-activate the     Microprocessor Board, Relay Board and
chiller system. Separate system (SYS) switches         40 Character Display to operate the integrated
for each refrigerant system are provided on the        circuitry.
Microprocessor Board.
                                                       A rectifier and filtering circuit for each motor current
Remote cycling, unloading and liquid temperature       transformer (CT) rectifies and filters these current
reset can be accomplished by voltage free              signals to a proportional dc voltage.
customer contacts.
                                                       This dc voltage representing motor current is then
Compressor         starting/stopping        and        passed to the Microprocessor Board as an
loading/unloading decisions are performed by the       analogue input for processing into digital values.
microprocessor to maintain leaving water
temperature. These decisions are a function of         1.4   Relay Output Board
temperature deviation from setpoint and rate of
change of temperature.                                 This board is fitted with relays to operate as
                                                       outputs. Output 1 to 24 are directly connected to
1.2       Microprocessor Board                         output drivers on the micro board. For these
                                                       outputs the board convert the 12 V dc signal from
The Microprocessor Board is the controller and         the micro board into a 220/230 V level used by the
decision maker in the control panel. System inputs     motor contactors, solenoid valves, etc. to control
from pressure transducers and temperature              system operation. The common side of all relays
sensors are connected directly to the                  are connected to 12 Vdc unregulated.
Microprocessor Board.
                                                       The open collector outputs of the Micro Board
The Microprocessor Board circuitry multiplexes         drivers energise the DC relays by pulling the other
these analogue inputs, digitises them, and             side of the relay coil to 0 Vdc. When not energised,
constantly scans them to keep a constant watch on      both sides of the relay coils will be at 12 Vdc
the chiller operating conditions. From this            potential. Outputs 25 to 32 are controlled by relay
information, the microprocessor then issues            drivers which in turn are controlled by a data latch.
commands to the Relay Output Board to control          The latch is connected to 3 address, one enable
contactors, solenoids, etc. for water temperature      and one data line from the micro board. The
control and to react to safety conditions.             common side of all relays are connected to 12 Vdc
                                                       unregulated.


(11/05)
      2        035L02631-100 Rev. 3



The open collector outputs of the relay board          1.7   Emergency Stop Device
drivers energise the DC relays by pulling the other
side of the relay coil to 0 Vdc. When not energised,   The EMEGENCY STOP DEVICE takes the form of
both sides of the relay coils will be at 12 Vdc.       a red/yellow switch. This switch performs two
                                                       functions. The first function of the switch is an
The relay board has customer terminals for the         EMERGENCY STOP DEVICE. In the 0 (OFF)
connection of the customer voltage free contacts.      position the EMERGENCY STOP DEVICE will
The output relay board also has a seperate             remove the 220/230V control supply and supply to
customer terminal block which is connected to          the electronics. All devices are de-energised
voltage free contacts on the output relays to          including compressor and on air cooled units fan
provide remote signalling.                             contactors. The loss of supply to the Power Board
                                                       results in the display going off.
1.5   Current Transformer (-TC)
                                                       To conform with the requirement of EN 418 and
A Current Transformer on the 3 q power wiring of       EN 60204-1 that re-setting the EMERGENCY
each motor sends ac signals proportional to motor      STOP DEVICE will not initiate a restart, MANUAL
current to the Power Supply Board which rectifies      RESTART should be programmed under the
and filters the signal to variable dc voltage          PROGRAM key. MANUAL RESTART requires a
(analogue). This analogue level is then fed to the     reset using the unit switch under the key pad. The
Microprocessor Board to allow it to monitor motor      second function of the switch is as a common
current.                                               control circuit disconnector. The switch can be
                                                       locked in the 0 (OFF) position using a padlock.
1.6   40 Character Display
                                                       YAES 3 & 4 system units Emergency Stop
The 40 Character Display (2 lines of 20 characters)    Device
is a liquid crystal display used for displaying
system parameters and operator messages. The           The main panel Emergency Stop Device is as
display has back lighting for night viewing as well    described above and only affects systems 1 and 2.
as a special feature which intensifies the display     The slave panel is fitted with its own Emergency
for viewing in direct sunlight.                        Stop Device and has the same features as the
                                                       main panel Emergency Stop Device but for system
YAES 3 & 4 System Units                                3/4 only.

On the YAES 3 & 4 system units a second panel a        1.8   Unit 1/0 (Auto/Off) Switch
Slave control panel is fitted. This panel contains
the power contactors for the compressor and fans       A unit 1/0 (Auto/Off) Switch is located control
for system 3/4. It also contains a slave micro board   section door. This switch allows the operator to
powered from its own power board and controls its      turn the entire chiller OFF if desired. The switch
own relay board. The slave micro board is              must be placed in the 1 (AUTO) position for the
responsible for the control and safety routines for    chiller to operate.
system 3/4 and receives data such as capacity
demand step and other operating instruction from       Whenever the switch is placed in the 0 (OFF)
the main panel micro board via a R485                  position, a STATUS display indicating the
communications link. The slave panel is not fitted     condition will be displayed. This message is shown
with a keypad or display the required data being       below.
transmitted to the main panel where this data is
available along with system 1 and 2 data on a                UNIT SWITCH IS IN
                                                             THE OFF POSITION
single key pad and display. Due to the
communication link data for system 3/4 is only
                                                       On YAES 3 & 4 system unit the unit switch is fitted
updated every 10 second instead of 2 seconds for
                                                       to the main panel only.
systems 1 and 2.




                                                                                                    (11/05)
                                                         035L02631-100 Rev. 3   3


1.9       System Switches

SYSTEM 1-4 SWITCHES are located on the
Microprocessor Board.These switches allow the
operator to selectively turn ON or OFF a given
system as desired.

The System Switch for a designated system must
be ON, switch to right for the system to operate.

Whenever a switch is placed in the OFF position, a
STATUS display indicating this is displayed. A
sample of this message is shown below.

          SYS # 1 SYS SWITCH OFF
          SYS # 2 SYS SWITCH OFF

            This message will not appear if
            Anti-recycle or Anti-coincident timers are
            in effect and are being displayed.


On YAES 3 system unit there are two system 3
system switches, SYS 3(S4) on the main micro
board and SYS 1 (S2) on the slave micro board.
Both these switches must be in the On position for
system 3 to be allowed to run. Either switch in the
Off position will shutdown system 3. In the same
way on YAES 4 system unit system 4 uses SYS
4(S5) on main micro board and SYS2 (S3) on the
slave micro board.

1.10 Keypad

The operator keypad allows complete control of
the system from a central location. The keypad
offers a multitude of commands available to
access displays, program setpoints, and initiate
system commands.

1.11 Battery Back-up

The Microprocessor Board contains a Real Time
Clock integrated circuit chip with an internal battery
back-up. The purpose of this battery back-up is to
assure any programmed values (setpoints, clock,
cutouts, etc.) are not lost during a power failure
regardless of the time involved in a power cut or
shutdown period.




(11/05)
        4     035L02631-100 Rev. 3




                   POWER BOARD


                                                                      OPTIONAL
                                                                   MICRO GATEWAY




                                                 RELAY BOARD


                                                                          OPTIONAL
 J 18                                                                     EMS CARD



                         EPROM
              S6
                          (U6)

                                     S1
RTC                                    1
(U13)

  S2
  to
  S5                                 RS485

                                           J19

                                     RS232


             MICROPROCESSOR BOARD




        Microprocessor Board                         On YAES 3 & 4 system units main micro
  J18     Clock On/Off                               board S4 is system 3 system switch. On
  J19     Set to RS485                               YAES 4 system units main micro board
  RTC     Real Time Clock /                          S5 is system 4 system switch. Slave
          Battery Backup IC                          micro board DIP switch S1 is not used, S2
                                                     is system 3 system switch, S3 is system 4
 EPROM Software IC
                                                     system switch and S5 and S6 are not
       (Label shows Version)
                                                     used. When fitted optional micro gateway
   S1  Dip Switch
                                                     or optional EMS card are only fitted to the
  S1-5 Display - SI or Imperial
                                                     main panel.
   S2  System 1 Switch
   S3  System 2 Switch
   S4  Not used
   S5  Not used
   S6  ISN Mode Selection Switch




                                                                                          (11/05)
                                                                       035L02631-100 Rev. 3          5


                                                        Each of the keys and an example of the typical
                                                        corresponding display messages is detailed
                                                        below.

                                                        2.2    Chilled Liquid Temps

                                                        Displays chiller leaving water temperature from the
                                                        cooler.

                                                               LWT = 8.2 DEG C


                                                        Or on YAES 4 system units

                                                               LWT1 = 8.2 DEG
                                                               LWT2 = 8.1 DEG C

2         DISPLAY KEYS                                  The minimum limit is -20.6°C
                                                        The maximum limit is 61.0°C
2.1       General
                                                        2.3    Ambient Temp
The DISPLAY keys allow the user to retrieve
system pressures, system motor currents, chilled        Displays the ambient temperature.
liquid temperature, ambient temperature,
compressor running times, number of compressor                 AMBIENT AIR
starts, and option information on the chiller                  = 14.2 DEG C
package. This data is useful for monitoring chiller
operation, diagnosing potential future problems,        The minimum limit on the display is -18.4°C.
troubleshooting, and commissioning the chiller.         The maximum limit on the display is 56.2°C.

Displayed data will be real-time data displayed on      2.4    System 1 Pressures
a 40 character display consisting of two lines of 20
characters. The display will update all information               On YAES 3/4 system units press the
at a rate of about 2 seconds. For YAES 3/4 system                 System 1 & 2 Pressures key a second
units due to the communication delay with the                     time to display System 2 pressures.
slave panel the display of system 3 information is
at a rate of about 10 seconds.
                                                        Displays oil pressure, suction pressure, and
W h e n a DI S P L A Y k e y i s p r e s s e d t h e    discharge pressure on System 1 when this key is
corresponding message will be displayed and will        pressed.
remain there until another key is pressed.
                                                               SYS # 1 OIL = 4.7 BARD
                                                               SP = 4.18 DP = 17.4 BARG
The display message may show characters
indicating “greater than”(>) or “less than” (<) as an   The minimum limits are:
out of range value. These characters indicate the
actual values are greater than or less than the limit         Oil Pressure: 0 BAR_D (Differential)
and thus out of range.                                        Suction Pressure: 0 Bar
                                                              Discharge Pressure: 0 BAR
For YAES 3 system units System 1 pressures
becomes System 1 & 2. System 2 pressures                The maximum limits are:
becomes System 3 and on YAES 4 system units
system 3 & 4.                                                 Oil Pressure: 27.5 – Suction Pressure BAR_D
                                                              (Differential)
                                                              Suction Pressure: 13.79 BAR
                                                              Discharge Pressure: 27.5 BAR


(11/05)
        6         035L02631-100 Rev. 3



2.5    System 2 Pressures                                                COMP1 = 105 A 53% FLA
                                                                         COMP2 = 120 A 64% FLA
            On YAES 3 system units this key is for
                                                                   The minimum limit is “0" amps 0% FLA.
            system 3 pressures. On YAES 4 system
                                                                   The maximum limit is dependant on unit size.
            units this key is for system 3 & 4
            pressures. On YAES 4 system units press
                                                                   On YAES 3 system units pressing the key a second
            the System 3 & 4 Pressures key a second
                                                                   time displays system 3 motor current data as well
            time to display System 4 pressures.
                                                                   as system 4 data on YAES 4 system units.
Displays oil pressure, suction pressure, and
                                                                   2.8   Operating Hours
discharge pressure on System 2 when this key is
                                                                         Start Counter
pressed.

       SYS # 2 OIL = 4.9 BARD                                      Displays accumulated running hours and starts on
       SP = 4.21 DP = 18.3 BARG                                    each compressor when this key is pressed.

The minimum limits are:                                            The hours counters for an individual system count
                                                                   to a total of 99,999 hours before rollover. A total of
      Oil Pressure: 0 BAR_D (Differential)                         99,999 starts can be logged on a system before the
      Suction Pressure: 0 Bar                                      counter will roll over.
      Discharge Pressure: 0 BAR
                                                                         HRS 1 = 462, 2 = 718
                                                                         STR 1 = 37, 2 = 48
The maximum limits are:
                                                                   The numbers “1” and “2” on the display message
      Oil Pressure: 27.5 – Suction Pressure BAR_D
                                                                   indicate compressor #1 and compressor #2.
      (Differential)
      Suction Pressure: 13.79 BAR
                                                                   These counters are “zeroed” at the factory or will
      Discharge Pressure: 27.5 BAR
                                                                   indicate only run time and number of starts logged
                                                                   during factory testing at the time of shipment.
2.6    Compressor Temperatures
                                                                   On YAES 3 system units pressing the key a second
D i s p l a y s c o mp r e s s o r o i l a n d d i s c h a r g e
                                                                   time displays system 3 operating hours and starts
temperature for system 1 when this key is pressed
                                                                   counter as well as the data for system 4 on YAES 4
and system 2 when this key is pressed a second
                                                                   system units.
time.

       SYS1 OIL = 34.7 DEG C                                       2.9   Options
       SYS1 DSCH = 37.8 DEG C
                                                                   The Options key provides a display of options
The minimum limit oil is -17.7°C discharge 29.6°C                  factory set based on customer order.
The maximum limit oil is 122.4°C discharge
144.4°C                                                            When the OPTIONS key is pressed, the following
                                                                   message will first be displayed for 3 seconds:
On YAES 3 system units pressing the key a third
time displays system 3 compressor temperatures.                          THE FOLLOWING
                                                                         ARE PROGRAMMED
On YAES 4 system units pressing the key a fouth
                                                                   Option Messages will then follow. Each will be
time displays system 4 compressor temperatures
                                                                   displayed for 3 seconds before the next display is
                                                                   automatically indexed. When all messages are
2.7    Motor Current
                                                                   displayed, the display message will automatically
                                                                   change to show a chiller “STATUS” message, just
Displays motor currents and %FLA when this key
                                                                   as if the STATUS key was pressed.
is pressed.
                                                                   Below is a list and explanation of the messages in
                                                                   the order they appear. For all messages, two

                                                                                                                   (11/05)
                                                                      035L02631-100 Rev. 3          7


possible variations may appear for each of the        May be displayed as an alternative to remote
messages depending on the customer order.             control mode. When connected to a York I.S.N
                                                      system the I.S.N is only allowed to remotely
MESSAGE 1                                             monitor the machine.

          GLYCOL                                      MESSAGE 4
          COOLING
                                                            DIP SW 4 SPARE
The chilled liquid temperature setpoint can be
programmed from -12.2 to 21.1°C and cutout set in
the range of -13.3°C to 2.2°C                         MESSAGE 5

OR                                                          IMPERIAL
                                                            UNITS
          WATER
          COOLING                                     Display messages will show units of measure in
                                                      Imperial units (°F and PSI).
The chilled liquid temperature setpoint can only be
programmed from 3.5 to 21.1°C and the cutout is       OR
set to 2.2°C
                                                            SI
                                                            UNITS
MESSAGE 2 (2 System Units Only)

          STANDARD UNITS                              Display messages will show units of measure in SI
                                                      units (°C and Bar).

This message STANDARD UNITS indicates that            MESSAGE 6
the unit is configured to cover YAES and YLCS
SA/AA units                                                 SEQUENCE COMMANDER
                                                            OPTION DISABLED
          YLCS HA UNITS
                                                      This message shows that switch 6 of S1 DIP switch
                                                      on the microprocessor board is set to open. With
This message indicates the unit is configured for     this selection the unit is set for single unit operation
YLCS HA units. See section 14.                        using its own controls.

OR                                                    OR

MESSAGE 2 (3 System Units Only)                             SEQUENCE COMMANDER
                                                            OPTION ENABLED
          DIP SW 2 SPARE
                                                      This message shows that switch 6 of S1 DIP switch
                                                      on the microprocessor board is set to closed. With
MESSAGE 3                                             this selection the unit will operate under multiple
                                                      unit control using York Sequence Commander
          REMOTE CONTROL                              concept.
          MODE
                                                      MESSAGE 7
Standard mode. When connected to a York I.S.N
system the I.S.N is allowed to take control of the          USE ALL COMPRESSOR
systems operation and remotely monitor the                  LOADING STEPS
machine.
                                                      MESSAGE 8
OR
                                                            REFRIGERANT TYPE
          LOCAL CONTROL                                     R134a
          MODE



(11/05)
       8        035L02631-100 Rev. 3



                                                                   has been tampered with and the unit will
                                                                   not run.

                                                                UNIT SWITCH IS IN
                                                                THE OFF POSITION

                                                          This message informs the operator that the unit 1/0
                                                          (AUTO/OFF) switch on the main control panel is in
                                                          the 0 (OFF) position which will not allow the chiller
                                                          to run.

                                                                POWER FAILURE
                                                                MANUAL RESET
3     STATUS KEY
                                                          Or on YAES 3/4 system units:
3.1   General
                                                                MASTER POWER FAILURE
                                                                MANUAL RESET
Pressing the STATUS key will enable the operator
to determine current chiller operating status as a        or
whole and as individual systems. The messages
displayed will include running status, cooling                  SLAVE POWER FAILURE
demand, fault status, external cycling device                   MANUAL RESET
status, and anti-recycle timer status. The display
will be a single message relating to the highest          These messages inform the operator that a supply
priority message as determined by the                     interruption or under voltage condition has
microprocessor. Status messages fall into the             occurred and that manual reset after power failure
categories of General and Fault Status with each of       has been programmed under the PROGRAM key.
the categories discussed below.                           A reset using the unit switch is then required.

On YAES 3 system units pressing the Status key a          On YAES 3 & 4 system units leave the unit switch in
second time displays system 3 Status messages             the Off position for at least 10 seconds to allow the
as well as system 4 on YAES 4 system units.               reset to be transmitted to the slave panel. Or
                                                          alternatively the Slave panel power failure can be
3.2   General Status Message                              reset by setting the main panel micro board system
                                                          switch 3 (SYS 3(S4)) and switch 4 (SYS 4(S5)) to
Each of the general status messages with a                Off, thus resetting the slave panel without
description of it’s meaning will follow. In the case of   interrupting systems 1 and 2's operation.
messages which apply to individual systems,
                                                                DAILY SCHEDULE
SYS 1 and SYS 2 messages will both be displayed                 SHUTDOWN
and may be different.
                                                          The DAILY SCHEDULE SHUTDOWN message
For YAES 3 system units and YAES 4 system units           indicates that the schedule programmed into the
where the status messages are the same as for             “CLOCK” “SET SCHEDULE/HOLIDAY” is
system 1 & 2, they will not be given, only the            keeping the chiller from running.
messages unique to system 3 or system 4 will be
included.                                                       SYS#1 NO RUN PERM
                                                                SYS#2 NO RUN PERM
      REPROGRAM TYPE OF
      REFRIGERANT TO RUN                                  No Run Permissive shows that a remote contact is
                                                          open either the flow switch terminals 10 & 13 or the
           This message should never appear, if it        remote Off/Auto contacts/terminals 11 & 14 No.
           does consult your local York office. This      1 system and No. 2 system terminals 12 & 15.
           message is a warning that the setting for
           the type of refrigerant used with the unit     On YAES 3 system units a flow switch with two
                                                          separate normally open contacts or two separate


                                                                                                         (11/05)
                                                                         035L02631-100 Rev. 3        9


flow switches are required, the second contact            units fitted with a starting bypass valve this valve
wired to terminals 10 & 13 in the slave panel. With       opens at the start of the start sequence and closes
this contact open or the remote Off/Auto contact          when the starter goes into delta .
terminals 11 & 14 No 3 system slave panel a
SYS#3 NO RUN PERM message will be given.                        SYS#1 COMP RUNNING
                                                                SYS#2 COMP RUNNING
On YAES 4 system units a second flow switches is
                                                          The COMP RUNNING message indicates that the
required. No Run Permissive messages shows
                                                          respective compressor is running due to demand.
that a remote contact is open either the slave flow
switch slave panel terminals 10 & 13 or the remote              SYS#1 PUMPING DOWN
Off/Auto contacts slave panel terminals 11 & 14                 SYS#2 PUMPING DOWN
No. 3 system and No. 4 system terminals 12 & 15.
                                                          This message shows that a system is pumping
          SYS#1 SYS SWITCH OFF                            down before stopping. When system shut down is
          SYS#2 SYS SWITCH OFF
                                                          initiated by fall in demand the liquid line solenoid
                                                          valve will close.
This message informs the operator that a system
switch on the micro board in the logic section is set
                                                          The system will continue to run and only shut down
to OFF.
                                                          when the suction pressure falls to below the
          SYS#1 OIL TEMP INHIB                            suction pressure cutout value programmed under
          SYS#2 OIL TEMP INHIB                            the PROGRAM key.

This message informs the operator that a minimum          A system does not pump down on a fault shutdown
safe oil temperature above ambient has not been           or if the unit switch is set to off. This message is
reached, prior to allowing the system to start.           overwritten by the SYS SWITCH OFF and DAILY
                                                          SCHEDULE SHUTDOWN messages.
As the crankcase heater boils off the refrigerant
from the oil, the oil heats up until the required oil /         SYS#1 AR TMR 240 S
                                                                SYS#2 AR TMR 120 S
ambient temperature differential is reached and
the system is available to start if required.
                                                          The anti-recycle timer message shows the amount
          SYS#1 OIL LEVEL INHIB                           of time left on the respective anti-recycle timer.
          SYS#2 OIL LEVEL INHIB                           This message is displayed when demand requires
                                                          the respective system to start but is being held off
This message informs the operator that the oil level      due to the timer.
in the compressor is below the minimum safe oil
level thus preventing the system from starting.                 SYS#1 AC TMR 13 S
                                                                SYS#2 AC TMR 13 S
          SYS#1 NO COOL LOAD
          SYS#2 NO COOL LOAD                              The anti-coincident timer is a software feature that
                                                          guards against 2 compressors starting
This message informs the operator that the chilled        simultaneously. This assures instantaneous
liquid temperature is below the point (determined         starting current does not become excessively high
by the setpoint and control range) that the               due to simultaneous starts.
microprocessor will bring on a system, or that the
microprocessor has not yet loaded far enough into         The microprocessor limits the time between
the loading sequence to be ready to bring on the          compressor starts to 1 minute regardless of
indicated system ON. The lag system will display          demand of the anti-recycle timer being timed out.
this message until the loading sequence is ready          The time shown on the anti-coincident timer is the
for the lag system to start.                              time left on the timer before the respective system
                                                          will start. Demand must be present for the
          SYS#1 START SEQUENCE                            message to be displayed and will only appear
          SYS#2 START SEQUENCE
                                                          when the anti-recycle timer has timed out.
The start sequence messages indicate that the
system is in the 12 second start sequence. On

(11/05)
      10       035L02631-100 Rev. 3



      SYS#1 CURR LIMITING                              A detailed explanation of the shutdown thresholds
      SYS#2 CURR LIMITING
                                                       and associated information related to each fault is
                                                       covered in the SYSTEM SAFETIES Section.
Current limiting takes effect when the current nears
the point at which the high current cutout will
                                                       Chiller shutdown faults will shut the entire chiller
shutdown the system down. When this message
                                                       down, while system shutdown faults will only shut
appears the current has exceeded the
                                                       down and lock out the affected system
programmed threshold and the micro is unloading
                                                       (compressor).
the affected system to prevent shutdown, until load
conditions moderate to allow reloading. This
                                                       CHILLER FAULTS
would typically occur on high pull down conditions.
(Refer to Data section).                                     CHILLER FAULT
                                                             LOW AMBIENT TEMP
      SYS#1 DSCH LIMITING
      SYS#2 DSCH LIMITING                                    CHILLER FAULT
                                                             LOW WATER TEMP
Discharge Pressure Limiting takes affect when
discharge pressure nears the point at which the              CHILLER FAULT
                                                             HIGH AMBIENT TEMP
high pressure cutout will shut the system down
causing total loss of cooling. When this message             POWER FAILURE
appears, discharge pressure has exceeded the                 MANUAL RESET
programmed threshold and the microprocessor is
unloading the affected system to prevent               Or on YAES 3/4 system units:
shutdown on a manual high pressure cutout, until
                                                             MASTER POWER FAILURE
load conditions moderate to allow reloading. Refer           MANUAL RESET
to Data Section.

      MANUAL
                                                       or
      OVERRIDE
                                                             SLAVE POWER FAILURE
                                                             MANUAL RESET
If the MANUAL OVERRIDE key is pressed, the
STATUS display will display the message shown                CHILLER FAULT
above. This will indicate that the Daily Schedule is         LWT SENSOR FAULT
being ignored and the chiller will start-up when
                                                             CHILLER FAULT
water temperature remote contacts, unit Auto/Off             VAC UNDER VOLTAGE
switch and SYSTEM switches permit.
                                                       For YAES 3/4 system units:
         This is a priority message and cannot be
         overridden by anti-recycle messages,                LOSS OF COMM LINK
         fault messages, etc. when in the STATUS             TO SLAVE PANEL
         Display mode. Therefore, do not expect to
                                                             SYS# 3/4 LOCKED OUT
         see any other STATUS messages when                  LOSS OF COMM LINK
         in the MANUAL OVERRIDE mode.
         MANUAL OVERRIDE is to only be used in         For YAES 4 system units:
         emergencies or for servicing.
                                                             CHILLER FAULT
3.3   Fault Status Messages                                  MWT SENS FAULT

                                                             MASTER PANEL FAULT
A number of possible fault messages may appear               LWT SENS FAULT
when the STATUS key is pressed. Whenever a
fault message appears, the safety thresholds on              SLAVE PANEL FAULT
the chiller have been exceeded and the entire                LWT SENS FAULT
chiller or a single system will be shut down and in
some cases locked out.



                                                                                                     (11/05)
                                    035L02631-100 Rev. 3   11


SYSTEM FAULTS

          SYS#1 HIGH DSCH


          SYS #2 HIGH DSCH


          SYS #1 LOW OIL PRESSURE


          SYS #2 LOW OIL PRESSURE


          SYS #1 LOW SUCTION


          SYS #2 LOW SUCTION


          SYS #1 CURRENT/MP/HPX


          SYS #2 CURRENT/MP/HPX


          SYS #1 PUMP DOWN FAIL


          SYS #2 PUMP DOWN FAIL


          SYS #1 HIGH OIL TEMP


          SYS #2 HIGH OIL TEMP


          SYS#1 OIL LEVEL FAIL


          SYS#2 OIL LEVEL FAIL


          SYS#1 DSCH TEMP FAIL


          SYS#2 DSCH TEMP FAIL




(11/05)
      12       035L02631-100 Rev. 3



                                                       The ENTER key is also used to scroll through
                                                       available data after any one of the following keys is
                                                       pressed:

                                                             PROGRAM
                                                             SET SCHEDULE/HOLIDAY
                                                             OPER DATA
                                                             HISTORY

                                                       4.4    Cancel Key

                                                       The CANCEL key allows the user to change errors
                                                       in the data being programmed into memory.

4     ENTRY KEYS                                       When the CANCEL key is pressed, any data which
                                                       has been keyed in, but not entered, will be erased.
                                                       The original values will re-appear on the display
4.1   General                                          and the cursor will return to the first character to be
                                                       programmed in the display message.
The ENTRY key allows the user to change
numerical values programmed in as chiller              4.5    AM/PM Key
setpoints, cutouts, clock, etc.
                                                       The AM/PM key allows the user to change AM/PM
4.2   Numerical Keypad                                 while programming the correct time in the SET
                                                       TIME display. The same key allows changing the
The NUMERICAL keypad provides all keys                 AM/PM schedule while programming daily chiller
needed to program numerical values as required.        start and stop times in the SET
                                                       SCHEDULE/HOLIDAY display.
The “ * ” Key is used to designate holidays when
programming special start and stop times for           4.6    Advance Day Key
designated holidays in the SET SCHEDULE
/HOLIDAY display.                                      The ADVANCE DAY key advances the day when
                                                       the SET TIME display is being programmed. The
The “ * ” Key is also used when programming            day is normally advanced to correspond to the
languages.                                             current day of the week. The day will advance a
                                                       day at a time, each time the key is pressed.
“The “+/-” key allows programming -°C setpoints
and cutouts in the SI display mode.

4.3   Enter Key

The ENTER key must be pressed after any change
is made to setpoints, cutouts or the system clock.
Pressing this key tells the microprocessor to
accept the new values into memory.

If this is not done, the new numbers entered will be
lost and the original values will be returned.




                                                                                                        (11/05)
                                                                       035L02631-100 Rev. 3       13


                                                                 These values must be checked and
                                                                 properly     programmed        wh e n
                                                                 commissioning the chiller. Failure to
                                                                 properly program these values may
                                                                 cause damage to the chiller or
                                                                 operation problems.

                                                        5.2   Leaving Water Temperature Setpoint

                                                        YAES 4 system units only

                                                              LEAVING WATER TEMP
                                                              SETPOINT = 4.5 DEG C

                                                        The LEAVING WATER TEMP SETPOINT is the
5         PROGRAM KEY                                   minimum leaving water temperature from each of
                                                        the two coolers. See section on PROGRAMMING
PROGRAMMING OR VIEWING SAFETIES                         LEAVING WATER CONTROL for further details.
LIMITS                                                  On chilled water applications, WATER COOLING
                                                        is displayed when OPTION key is pressed, the
5.1       General                                       setpoint is adjustable from 3.5 to 21.1°C. On glycol
                                                        applications, GLYCOL COOLING is displayed
Pushing the PROGRAM key allows the user to              when OPTION key is pressed, the setpoint is
program “selected” system operating limits. As          adjustable from -12.2°C to 21.1°C.
well as the programmable values there are a
number of operating limits to inspect. The display      5.3   Local Control Range
includes cutout points for safeties, and the reaction
time of the microprocessor to abrupt changes in         YAES 4 system units only
the chilled water temperatures.
                                                              LOCAL CONTROL RANGE
                                                              1 DEG C
After the PROGRAM key is pressed the
microprocessor will respond by displaying:
                                                        The LOCAL CONTROL RANGE applies to each of
          PRESS ENTER TO                                the two coolers. Within the lower section of this
          PROGRAM DATA                                  range no further loading of its associated systems
                                                        can occur at the dictates of the mixed leaving
Pressing the ENTER key will display the first           temperature. See section on PROGRAMMING
setting. The ENTER key must be used to advance          LEAVING WATER CONTROL for further details.
the display to the next setting. Settings may be        The LOCAL CONTROL RANGE can be set in the
reprogrammed using the 12 “ENTRY” keys. New             range of 0.6°C - 4.4°C.
values will be programmed into memory when the
ENTER key is pushed.                                    5.4   Selected Refrigerant (Factory Set)

If the operator attempts to enter an unacceptable             SELECTED REFRIGERANT
                                                              R407C OR R134A = 134
value, the microprocessor will respond with a
momentary message indicating the value selected
                                                        Display the type of refrigerant the unit is designed
has been ignored. This error message is shown:
                                                        to operate with.
          OUT OF RANGE
          TRY AGAIN!                                          DISPLAY LANGUAGE
                                                              ENGLISH
The programmable setting displays are shown and
                                                        The following display languages can be
described below along with the range of values
                                                        programmed: English, German, French, Italian, ,
which the microprocessor will accept for each
                                                        Spanish and Portuguese. Press “ * ” repeatedly
setting.


(11/05)
      14        035L02631-100 Rev. 3



until the desired language is displayed. Then press        Motor Current Unloading
the ENTER key to accept the new language.
                                                                 MOTOR CURRENT
                                                                 UNLOAD = 101% FLA
5.5   Discharge Cutout (Factory Set)

      DISCHARGE CUTOUT                                     The motor current unload point can be set in the
      = 20.80 BARG                                         range 85% to 101%. Set to 101% to keep the
                                                           system from faulting on high motor current due to
The DISCHARGE CUTOUT is a software cutout in               high loads or pull down conditions. By unloading
the microprocessor and is backed-up by a                   the compressor at high motor currents, the chiller is
mechanical high pressure cutout located in the             allowed to continue to run automatically at reduced
refrigerant circuit. See Data Section for settings.        capacity until load conditions moderate to allow
                                                           re-loading. Settings within the range 85% to 100%
5.6   Ambient Temp Low Cutout                              can be used to limit current demand on the building
                                                           by unloading the systems.
      AMBIENT TEMP LOW
      CUTOUT = -17.6 C
                                                           5.9   Rate Control Temp
The AMBIENT TEMP LOW CUTOUT can be set to                        RATE CONTROL TEMP
establish a chiller low ambient temperature cutout               = 5.0 C
point. If the ambient falls below this point the chiller
will shut down. Restart can occur, if demand               The RATE CONTROL TEMP establishes a
allows, when temperature rises above the cutout.           temperature range over which the microprocessor
                                                           may override normal system loading timers and
For normal ambient applications, the cutout is set         react to actual rate of change of leaving water
at –18.0°C.                                                temperature. This temperature range starts at the
                                                           top of the control range with its band width being
5.7   Ambient Temp High Cutout                             pro

Показано початок документа. Повний текст — у PDF за посиланням вище.

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.