SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

YLAA0189SE-YLAA0485SE — Air & water cooled liquid chillers, Tempo & Zafiro (YLAA/YLAE/YCWL/YCRL) — operating instruction

Вид документаІнструкція
ВиробникJCI
МоделіYLAA0189SE-YLAA0485SE, YLAA0195HE-YLAA0515HE, YLAE0195SE-YLAE0490SE, YLAE0195HE-YLAE0510HE, YLAE0195LT-YLAE0490LT, YCWL0240SE-YCWL0395SE, YCWL0200HE-YCWL0610HE, YCRL0200HE-YCRL0610HE
Група обладнанняother
Мова документаанглійська
Розмір файлу1.2 МБ

Про документ

Operating instruction for YORK Tempo & Zafiro air-cooled (YLAA, YLAE) and water-cooled (YCWL/YCRL) liquid chillers using R410A, controlled by a microprocessor-based system with IPUII controller (software C.MMC.16.03 and higher). SE = standard efficiency, HE = high efficiency, LT = low temperature. The manual covers control panel operation, capacity control, setpoints, options, BAS/EMS reset signals, ISN/BACnet/Modbus communications, and the optional heatpump mode.

Ключові дані

RefrigerantR410A
SoftwareC.MMC.16.03 and higher
Chilled liquid SETPOINT (water)4.4°C to 21.1°C (default 6.7°C)
Chilled liquid SETPOINT (glycol)-7.2°C to 21.1°C (default 6.7°C)
Chilled liquid SETPOINT (low temp glycol)-13.3°C to 21.1°C (default 6.7°C)
Leaving liquid RANGE+/-0.8°C to +/-1.4°C (default +/-1.1°C)
Discharge pressure cutout range22.4 barg to 39.6 barg
Suction pressure cutout (water)5.52 barg to 8.27 barg
Anti-recycle timer240 s to 600 s

Застосування

  • Independent operation or integration via ISN (YorkTalk), BACnet or Modbus building management systems
  • Chilled liquid temperature maintenance for water or glycol circuits (low temperature glycol down to -13°C setpoint)
  • Optional heatpump mode (YCWL) for heating duty with hot leaving liquid control

Особливості

  • Dual refrigerant circuit (system 1/system 2) control with automatic or manual lead/lag rotation
  • Daily/holiday scheduling with internal real-time clock (battery-backed RTC)
  • Remote start/stop, load limiting (stage 1/stage 2), and chilled liquid temperature reset via voltage-free contacts
  • EMS-PWM remote setpoint reset by timed contact closure
  • Analog temperature reset inputs: 0-10 Vdc, 2-10 Vdc, 0-20 mA, 4-20 mA
  • Anti-recycle and anti-coincidence timers; pumpdown on shutdown; crankcase heaters
  • Condenser fan staging controlled from discharge pressure; two-speed fan option with star/delta dwell timing; fan full speed inhibit
  • Low ambient kit with variable-speed fan and evaporator solenoid valve
  • Optional Hydro Kit with single or dual (duty/standby) pumps
  • Optional soft start on last compressor of each system
  • Fault history buffers (last 6 safety shutdowns), optional serial printer (RS-232)
  • Display in SI or Imperial units, multiple display languages

Технічні дані

Parameter Value
Refrigerant R410A
Control software version C.MMC.16.03 and higher
Keypad/display Touch keypad + 40-character LCD (2 lines x 20 chars), lighted background
Leaving Liquid 'SETPOINT', Water Cooling 4.4°C to 21.1°C (default 6.7°C)
Leaving Liquid 'SETPOINT', Glycol Cooling -7.2°C to 21.1°C (default 6.7°C)
Leaving Liquid 'SETPOINT', Low Temp Glycol -13.3°C to 21.1°C (default 6.7°C)
Leaving Liquid 'RANGE' 0.8°C to 1.4°C (default 1.1°C)
Max EMS-PWM Remote Temperature Reset 1.0°C to 22.0°C (default 11.0°C)
Discharge Pressure Cutout 22.4 barg – 39.6 barg (default 38.6 barg; factory YLAA/YLAE 33.8 barg, YCWL 38.0 barg)
Suction Pressure Cutout, Water Cooling 5.52 barg – 8.27 barg (default 6.00 barg; factory YLAE 5.52 barg, YCWL 5.59 barg)
Suction Pressure Cutout, Glycol Cooling 2.90 barg – 8.27 barg (default 6.00 barg)
Low Ambient Temperature Cut-out -17.8°C to 15.6°C (default -3.9°C)
Leaving Chilled Liquid Temperature Cut-out Water 3.0°C fixed; Glycol -13.1°C to 3.0°C; LT Glycol -18.3°C to 3.0°C
Anti-Recycle Timer 240 s – 600 s (default/factory 600 s); stop-to-start fixed at 90 s (120 s on power-up)
Fan Control On-Pressure (YLAA/YLAE) 20.0 barg – 33.4 barg (default 23.0 barg)
Fan Differential Off-Pressure (YLAA/YLAE) 3.7 barg – 11.0 barg (default 5.5 barg)
Rate Sensitivity 1.0°C/min – 8.0°C/min (default 1.7°C/min)
Rate Control Temperature 1.0°C – 11.0°C (default 6.1°C)
Mechanical HP switch trip, YLAA 38.7 barg
Mechanical HP switch trip, YLAE first switch 38.7 barg; second (models 0255SE/0265HE+) 40.3 barg
Mechanical HP switch trip, YCWL/YCRL first 34.7 barg; second 36.3 barg
Compressor overload protection EN60947-4-1 tripping category class 10 A
Motor protector (-FMP) trip resistance 4.5 kW ± 20% trip, reset < 2.75 kW; 30 ± 5 min module reset delay
Voltage-free contact rating (run status/alarm) 125 VA (external circuit up to 254 Vac or 28 Vdc)
Remote start/stop terminals 13 & 14 (-ARB board, YLAA/YLAE) / 13 & 51 (-XTBC1, YCWL/YCRL)
Flow switch requirement rated 30 Vdc, 1–3 mA, gold contacts recommended
Analog input types (remote temp reset) 0–10 Vdc, 2–10 Vdc, 0–20 mA, 4–20 mA (jumper selectable 20 mA or 10 Vdc)
I/O board supply +12 Vdc relay coils; unregulated +30 Vdc digital inputs; +5 V sensors
Printer port RS-232 (TB3), baud rate 1200, parity none, 8 data bits
BACnet/Modbus ports Port P1 (RS485 TB1), Port P2 (RS485 TB2, HW select bit set to RS-485); baud rates 1200–76800; MAC address 0–127
Heating setpoint (YCWL heatpump) 30°C – 52°C
Heating RANGE (YCWL heatpump) 0.5°C – 5°C
Soft starter ramp time acceleration to full speed within 0.8 s
Variable speed fan pressure band (low ambient) maintains discharge pressure between 18 and 22.5 barg

Варіанти замовлення

  • Efficiency variants: SE — Standard Efficiency, HE — High Efficiency, LT — Low Temperature
  • Options referenced: Hydro Kit (single or dual pump), soft start, low ambient kit, printer kit YORK part numbers 362L11330-002 (UK) / 362L11330-003 (EUROPE), spare paper roll 025L01992-000, spare ink ribbon 025L01993-000
  • Control board terminal designations printed: AMB-XTB7-8/-9/-10, AMB-XTB10-8/-9/-10, AMB-XTB8-5/-8 (fan output relays)

Допуски та стандарти

  • EN60947-4-1 (compressor overload tripping category class 10 A)

Текст документа

Библиотека СОК 




                     YLAA0189SE-YLAA0485SE YLAA0195HE-YLAA0515HE
          YLAE0195SE-YLAE0490SE YLAE0195HE-YLAA0510HE YLAE0195LT-YLAE0490LT
             YCWL0240SE - YCWL0395SE YCWL/YCRL0200HE - YCWL/YCRL0610HE
          OPERATING INSTRUCTION            Revision 1      Form 201.26.OI1(11/09)

                                                           (035-21976-110)



                     AIR & WATER COOLED LIQUID CHILLERS
                    MICRO BASED CONTROL SYSTEM WITH IPUII

                   SOFTWARE VERSION C.MMC.16.03 AND HIGHER
                   SE - STANDARD EFFICIENCY, HE - HIGH EFFICIENCY
                               LT - LOW TEMPERATURE



                   Tempo & Zafiro




                                                                    R410A
                                                                                                  Form 201.26.OI1(11/09)



                                             TABLE OF CONTENTS

1   GENERAL                                                  6    ENTRY KEYS
    1.1 Control Panel                                  1.1        6.1 UP ARROW and DOWN ARROW Keys                 1.26
    1.1.1    AMB (IPU II and I/O Boards)               1.1        6.2 ENTER/ADV Key                                1.26
    1.1.2    Internal Clock & Memory Backup Battery 1.1
                                                             7    SETPOINTS KEYS
    1.1.3    Keypad and Display                        1.2
    1.1.4    Unit (Chiller) ON/OFF Switch              1.2        7.1 Cooling Setpoints                            1.26
    1.1.5    Customer Controls                         1.2        7.2 SCHEDULE/ADVANCE DAY Key                     1.27
    1.1.6    Remote Start/Stop                         1.2        7.3 PROGRAM Key                                  1.28
    1.1.7    Flow Switch                               1.2        7.4 Setpoint and Cut-out Settings                1.30
    1.1.8    EMS PWM Remote Setpoint Reset             1.2
    1.1.9    Load Limiting                             1.4
                                                             8    UNIT KEYS
    1.1.10   Fan Full Speed Inhibit (110 V circuit)               8.1 OPTIONS Key                                  1.31
             YLAE Units with Dual Speed Fans only      1.4
                                                                  8.2 CLOCK Key                                    1.33
    1.1.11   Fan Full Speed Inhibit (30VDC Circuit)
             YLAA Units with Dual Speed Fans only      1.4   9    OPTIONAL SOFT START
    1.1.12   Chilled Liquid Pump Control               1.4
                                                                  9.1 Diagnostics                                  1.34
    1.1.13   Alarms                                    1.4
    1.1.14   System Run Status                         1.4   10   INPUTS / OUTPUTS

2   Operation                                                     10.1 Digital Inputs                              1.35
                                                                  10.2 Analogue Inputs                             1.35
    2.1 Capacity Control                               1.5
                                                                  10.3 Digital Outputs                             1.36
    2.2 Anti-Recycle Timer                             1.7
                                                                  10.4 Analogue Output                             1.36
    2.3 Anti-Coincidence Timer                         1.7
    2.4 Compressor Crankcase Heater                    1.7   11   OPTIONAL PRINTER INSTALLATION
    2.5 Pumpdown (YLLSV) Control                       1.7        11.1 Installation Limitations                    1.37
    2.6 Evaporator Solenoid Valve (YESV) Control . 1.7            11.2 Parts                                       1.37
    2.6.1    YLAA Low Ambient Unit                     1.7        11.3 Assembly and Wiring                         1.37
    2.7 Lead/Lag Control                               1.8        11.4 Using Other Printers                        1.37
    2.8 Condenser Coil Fan Control                     1.8        11.5 Warranty                                    1.37
    2.8.1    Single speed fans                        1.11        11.6 Obtaining a Printout                        1.37
    2.8.2    YLAA and YLAE 2 Speed Fan Option         1.12
    2.8.3    Fan Star/Delta Dwell Time                1.13   12   BAS/EMS TEMPERATURE RESET USING A
                                                                  VOLTAGE OR CURRENT SIGNAL
3   Control Panel Keys
                                                                  12.1 0-10 Vdc Remote Signal                      1.38
4   Status Key                                                    12.2 2-10 Vdc Remote Signal                      1.38
    4.1 General Status Messages                       1.15        12.3 0-20 mA Remote Signal                       1.38
    4.2 Fault Status Messages                         1.17        12.4 4-20 mA Remote Signal                       1.38
                                                                  12.5 EMS-PWM Remote Temperature Reset            1.39
5   Display/Print Keys
                                                             13   ISN CONTROL
    5.1 OPER DATA Key                                 1.19
                                                                  (York Talk -AMB Terminal Block TB1)
    5.2 PRINT Key                                     1.22
                                                                  13.1 Received Data (Control Data)                1.39
    5.3 History Key                                   1.24
                                                                  13.2 Transmitted Data                            1.40
    5.3.1    Clearing History Buffers                 1.24
    5.3.2    History Messages                         1.24
    5.3.3    Software Version                         1.25




                                                                                                                     I-i
Form 201.26.OI1(11/09)



14     BACnet and Modbus
       (-AMB Board Terminal Block TB1)
       14.1 BACnet and Modbus Data Communication 1.41

15     HEATPUMP OPTION
       15.1 Heatpump Mode Selection                 1.45
       15.2 OPER DATA Key                           1.45
       15.3 SETPOINTS Key                           1.45
       15.4 Leaving Liquid Temperature Control      1.45
       15.5 BAS/EMS Temperature Reset - Voltage /
            Current Signal                          1.46
       15.5.1   0-10 Vdc Remote Signal              1.46
       15.5.2   2-10 Vdc Remote Signal              1.46
       15.5.3   0-20 mA Remote Signal               1.46
       15.5.4   4-20 mA Remote Signal               1.47
       15.6 EMS-PWM Remote Temperature Reset        1.47




I-ii
                                                                                            Form 201.26.OI1(11/09)




1       GENERAL                                              From this information, the IPU II then issues commands
                                                             to the I/O board relay outputs to control contactors,
The units are designed to work independently, or in          solenoids, etc. for Leaving Liquid Temperature Control
conjunction with other equipment via ISN, Bacnet or          and to react to safety conditions. The I/O board converts
Modbus building management systems or other                  logic signals to operate relay outputs to 115 VAC levels
automated control systems. When operating, the unit          used by motor contactors, solenoid valves, etc. to
controls monitor the chilled liquid system temperatures      control system operation. The low voltage side of all
at the unit and take the appropriate action to maintain      relay coils on the I/O board are powered by +12V.
the temperatures within desired limits. This action will
involve running one or more compressors to match the         Keypad commands are actuated upon by the
cooling effect of the refrigerating systems to the heat      microprocessor to change setpoints, cutouts,
load on the liquid system. The heat removed from the         scheduling, operating requirements, and to provide
chilled liquid is then rejected to the air or water cooled   displays. The keypad and display are connected to the
condenser.                                                   I/O board.

1.1     Control Panel                                        The on-board power supply converts 24 Vac from T1
                                                             (120/24 VAC transformer), to +12 Vdc, +5 Vdc and +3.3
A microprocessor based control system is fitted to the       Vdc using switching and linear voltage regulators
units. It is capable of dual refrigerant system (circuit)    located on the I/O and IPU II boards. These voltages are
control to maintain chilled liquid temperature within        used to operate integrated circuitry on the board. The
programmed limits, as well as sequencing, system             power supply for the 40 Character Display and unit
safeties, displaying status, and daily schedules.            sensors (transducers and temperature sensors) is also
                                                             derived from the +5 V. supply. The 24 Vac is also
Remote cycling, demand limiting and chilled liquid           rectified, but not regulated, to provide unregulated +30
temperature reset can be accomplished by field               Vdc to supply all of the digital inputs.
supplied contacts.
                                                             The IPU II board contains one green 'Power' LED to
Compressor starting/stopping and loading/unloading           indicate that the board is powered up and one red
decisions are performed by the microprocessor to             'Status' LED (flashing) to indicate that the processor is
maintain leaving liquid temperature. These decisions         operating.
are a function of temperature deviation from
‘SETPOINT’.                                                  The I/O board contains one green 'Power' LED to
                                                             indicate that the board is powered up and one red
A master (UNIT) ON/OFF switch is provided on the             'Status' LED (flashing) to indicate that the processor is
chiller control panel to activate or deactivate the          operating. The I/O board also contains two sets of
complete chiller.                                            Receiver/Transmit LED’s, one for each available serial
                                                             communication port. The receive LED’s are green, and
On YLAA and YLAE units with the optional Hydro kit the       the Transmit LED’s are red.
control of the single or duty/standby pumps are integral
to the control system.                                       A jumper on the I/O board selects 20 mA or 10 Vdc as
                                                             the input type on the remote temperature reset analog
1.1.1    AMB (IPU II and I/O Boards)                         input.

The IPU and I/O boards are assembled to function as a        1.1.2   Internal Clock & Memory Backup Battery
single microprocessor controller. The IPU II board
contains a 'Coldfire' microprocessor and is the controller   The AMB board contains a real time clock (RTC)
and decision maker in the control panel. The I/O board       integrated circuit chip with an internal battery backup.
handles all of the unit I/O (Inputs and Outputs). System     The battery backup assures that any programmed
inputs from pressure transducers and temperature             values (setpoints, clock, cut-outs, etc.) are not lost
sensors are connected to the I/O board.                      during a power failure or shutdown period regardless of
                                                             the time involved.
The I/O board contains a processor capable of reading
the inputs and controlling the outputs. It communicates
through the transition header with the IPU II
microprocessor. The I/O board circuitry multiplexes the
analog inputs, digitizes them, and constantly scans
them to keep watch on the unit operating conditions.
The input values are transmitted serially to the IPU II
microprocessor board.



                                                                                                                 1-1
Form 201.26.OI1(11/09)



1.1.3   Keypad and Display                                    SYSTEM INPUTS

User interface is via a touch keypad and a liquid crystal               Wiring from remote voltage free contacts
display allowing access to operating and programmed                     should be run in screened cable earthed at the
data. Information can be displayed in S.I. (Metric) or                  panel end only. If an inductive device (relay,
Imperial units. The 40 character liquid crystal display (2              contactor) is supplying these contacts, the coil
lines of 20 characters) is used for displaying system                   of the device must be suppressed with a
parameters and operator messages. The display has a                     standard RC suppresser across the inductive
lighted background for night viewing as well as a special               coil.
feature which intensifies the display for viewing in direct
sunlight.                                                     1.1.6   Remote Start/Stop

1.1.4   Unit (Chiller) ON/OFF Switch                          Remote start/stop can be accomplished using a time
                                                              clock, manual contact or other voltage free contact
The unit ON/OFF switch is located just below the              connected to terminals 13 and 14 (-ARB circuit board on
keypad. This switch allows the operator to turn the entire    YLAA and YLAE units) or 13 and 51 (-XTBC1 on
chiller OFF, if desired. The switch must be placed in the     YCWL/YCRL units). The contact must be closed to
ON position for the chiller to operate. Any time the switch   allow the chiller to run. Any time the contact opens for
is in the OFF position, a STATUS message will be              more than 3 seconds, the chiller will shutdown and the
displayed.                                                    'REMOTE STOP NO RUN PERM' message will be
                                                              displayed.
1.1.5   Customer Controls
                                                              1.1.7   Flow Switch (YCWL/YCRL and YLAA / YLAE
The microprocessor based control system can accept                    units without the hydro kit option)
remote signals to start and stop the chiller, to adjust the
leaving liquid temperature setpoint and to load limit the     The customer must install and wire a field mounted flow
unit. To reduce unit noise on YLAA and YLAE units with        switch. The flow switch should be rated for 30 Vdc 1 to 3
the 2 speed fan option, a customer voltage free contact       ma, gold contacts recommended, connected to
can be connected to inhibit fan full speed .These             terminals 13 and 18 (-ARB circuit board on YLAA and
functions can easily be controlled by connecting user         YLAE units) and 13 and 14 (-XTBC1 on YCWL/YCRL
supplied voltage free contacts to the customer terminals      units) to provide adequate protection against loss of
in the electronics section of the control panel.              liquid flow.

In addition, run status and alarm contacts are provided                 The flow switch should never be by-passed.
to remotely signal system status and faults.                            This will cause damage to the chiller and
                                                                        invalidate the warranty.



                                                              The optional Hydro Kit is fitted with a flow switch.

                                                              1.1.8   EMS PWM Remote Setpoint Reset
                                                                      (Activated on request)

                                                              The leaving liquid temperature setpoint programmed
                                                              into the microprocessor can be remotely adjusted to a
                                                              higher value using repeated timed closure of voltage
                                                              free contacts 13 and 20 (-ARB circuit board on YLAA
                                                              and YLAE units) and 13 and 20 (-XTBC1 on
                                                              YCWL/YCRL units). The duration of the contact closure
                                                              will decide the amount of adjustment.

                                                              For noise immunity, the microprocessor will ignore
                                                              closures of less than 1 second.




1-2
                                                                                                                                                                                                                                                                                                                                                                                           Form 201.26.OI1(11/09)



  -XTBC2         -F1
                                         -XTBC1                                                                                                                                         -ARB                                                                                                                                                                                               -ARB


                                          A- A+                                25 26 29 30 23 24 27 28 31 32                                                                                                                                                                                                                                                               14 16 13 18 13 13 21 20 13


      LK


                                                                                                                                                                                                                                                                                                                                                                                                                                                                                         SCREEN




                                                                                                          CHILLER RUN STATUS SYSTEM 1                                                                                LIQUID PUMP START CONTACTS                                 CHILLER RUN STATUS SYSTEM 2
                                                                                                                                                                SYSTEM 1 ALARM STATUS                                                                                                                                                 SYSTEM 2 ALARM STATUS
     L     5                            ANALOGUE
                                       TEMPERATURE                                                                                                                                                                                                                                                                                                                                FSI
                                       RESET SIGNAL                                                                                                                                                                                                                                                                                                                                                                   RU                                  PWM

                                                                                                                                                                                                                                                                                                                                                                                   FAN
                                                                                                                                                                                                                                                                                                                                                                    RP


                                                                                                                                                                                                                                                                                                                                                                                                                                                         2nd STAGE LOAD LIMIT



                                                                                                                                                                                                                                                                                                                                                                                                                      1st STAGE LOAD LIMIT
                                                                                                                                                                                                                                                                                                                                                                                 SPEED
                                                                                                                                                                                                                                                                                                                                                                                 INHIBIT

                                                                                                                                                                                                                                                                                                                                                                      REMOTE


                                                                                                                                                                                                                                                                                                                                                                   START/STOP
                                                                                                                                                                                                                                                                                                                                                                                                                                                                or PWM INPUT
                                                                                                                                                                                                                                                                                                                                                                                FLOW
                                                                                                                                                                                                                                                                                                                                                                                SWITCH
REMOTE EMERGENCY
   STOP DEVICE




                                                      YLAA Customer Controls

               -F4     -F1             -XTBC1                                                                                           -ARB                                                                                                                                                                                                                                            -ARB


                                        A- A+          33 34 25 26 29 30 23 24 27 28 31 32                                                                                                                                                                                                                                                                            14 16 13 18 13 13 21 20 13



                                                                                                                                                                                                                                                                                                                                                                                                                                                                                SCREEN
                                 LK



                                                                                                                                                                                                                                                                                                                                                                           FLOW




                                                                            CHILLER RUN STATUS SYSTEM 1                                                                                 LIQUID PUMP START CONTACTS                                CHILLER RUN STATUS SYSTEM 2
                                                                                                                                        SYSTEM 1 ALARM STATUS                                                                                                                                                 SYSTEM 2 ALARM STATUS
                                                        FAN SPEED INHIBIT
                                       ANALOGUE                                                                                                                                                                                                                                                                                                                            SWITCH
                             3    4   TEMPERATURE
                                      RESET SIGNAL                                                                                                                                                                                                                                                                                                                                             RU                                             PWM




                                                                                                                                                                                                                                                                                                                                                                                                                                             2nd STAGE LOAD LIMIT



                                                                                                                                                                                                                                                                                                                                                                                               1st STAGE LOAD LIMIT
                                                                                                                                                                                                                                                                                                                                                              RP



                                                                                                                                                                                                                                                                                                                                                                 REMOTE


                                                                                                                                                                                                                                                                                                                                                              START/STOP
                                                                                                                                                                                                                                                                                                                                                                                                                                                    or PWM INPUT
         REMOTE EMERGENCY
            STOP DEVICE




                                                      YLAE Customer Controls




                                                                                                                                                                                                                                                                                                                                                                                                                                                                                            1-3
Form 201.26.OI1(11/09)



1.1.9   Load Limiting                                        VOLTAGE FREE CONTACTS

Load Limiting prevents the unit from loading beyond a        A 28 Vdc or up to 254 Vac external circuit (supplied by
desired value. 4 compressor units can be load limited to     others) may be connected to these contacts. The
50% of the compressors by allowing only 1 compressor         contacts are rated at 125 VA.
per system to run. 5 compressor units can be load
limited to 40% or 80% of the compressors. The 80%                      If any inductive load device (relay or
would allows a up 2 compressors per system to run and                  contactor) is connected to these contacts, the
the 40% limit would allow up to 1 compressor per system                device must be suppressed at the load with a
to run. 6 compressor units can be load limited to 33% or               RC suppressor across the inductive coil.
66% of the compressors. The 66% limit would allow up                   Failure to install suppressors will result in
to 2 compressors per system to run, and the 33% limit                  nuisance faults and possible damage to the
would allow up to 1 compressor per system to run. No                   unit.
other values of limiting are available.
                                                             1.1.12 Chilled Liquid Pump Control
The unit can be load limited through remote                         (YCWL/YCRL and YLAA / YLAE units without
communication via an ISN, Bacnet or Modbus, or                      the hydro kit option)
through closing contacts connected to the Load Limit
terminals 13 and 21 and PWM inputs terminals 13-20.          Terminals 23 and 24 (-ARB circuit board on YLAA and
(-ARB circuit board on YLAA and YLAE units, -XTBC1           YLAE units) and 23 and 24 (-XTBC1 on YCWL/YCRL
on YCWL/YCRL units). Stage 1 of load limiting involves       units) close to start the liquid pump. After the "30 second
closing the Load Limit input. Stage 2 of load limiting       stop to start timer" has timed out, this contact is closed if
involves closing both the Load Limit and PWM inputs.         there is a 'Leaving Liquid Temperature Cutout', any of
The first stage of limiting is either 50% of unit on 4       the compressors are running, or, the daily schedule is
compressor units, 80% on 5 compressor units or 66.3%         not calling for a shutdown with the unit switch 'ON' and
on 6 compressor units. The second stage of limiting is       the remote stop/start input closed, terminals 13 and 14
only available on 5 and 6 compressor units,40% of unit       (-ARB circuit board on YLAA and YLAE units) and 13
on 5 compressor units or 33% on 6 compressor units.          and 51 (-XTBC1 on YCWL/YCRL units).
Remote unload when using remote contacts is available
when either REMOTE or LOCAL is selected for LOCAL /                    The contact must be used to ensure that the
REMOTE MODE under the OPTION key.                                      pump is running in the event of a 'Leaving
                                                                       Liquid Temperature Cutout'.
Simultaneous operation of Load Limiting and
EMS-PWM Temperature Reset is not possible.
However Load Limiting when using remote unload
contacts can be implemented if the analog temperature        The pump contact will not close to run the pump if the
reset is used.                                               unit has been powered up for less than 30 seconds, or if
                                                             the pump has run in the last 30 seconds, to prevent
1.1.10 Fan Full Speed Inhibit (110 V circuit)                pump motor overheating.
       YLAE Units with Dual Speed Fans only
                                                             1.1.13 Alarms
To reduce unit noise the fans can be limited to run at a
maximum step of all fans in star (reduced speed) i.e. fan    Contacts are provided on -ARB circuit board on YLAA
full speed is inhibited. Connect a customer voltage free     and YLAE units and -XTBC2 on YCWL/YCRL units,
contact to terminals 33 & 34 (-ARB circuit board).           which can be used to remotely signal alarms. The
                                                             contacts are normally open (N.O.) and will close when
The contact must be rated for 110 Vac, connecting            control power is applied to the panel, if no fault
wiring does not need to be run in screened cable. When       conditions are present. When a fault occurs which locks
the contact is closed fan full speed inhibit is in effect.   out a system or the unit power is lost, the contacts open.
                                                             To obtain a system alarm signal, connect the alarm
1.1.11 Fan Full Speed Inhibit (30VDC Circuit)                circuit to terminals 29 and 30 for No. 1 system and
       YLAA Units with Dual Speed Fans only                  terminals 31 and 32 for No. 2 system.

To reduce unit noise the fans can be limited to run at a     1.1.14 System Run Status
maximum step of all fans in star (reduced speed) i.e. fan
full speed is inhibited. Connect a customer voltage free     System run status is indicated by closure of contacts on
contact to terminals 13 & 16 (-ARB circuit board). When      -ARB circuit board on YLAA and YLAE units and
the contact is closed fan full speed inhibit is in effect.   -XTBC2 on YCWL/YCRL units, terminals 25 and 26 for
                                                             system 1 and terminals 27 and 28 for system 2.




1-4
                                                                                                                                                                                     Form 201.26.OI1(11/09)




2     Operation                                               As the load decreases below the 'SETPOINT', the
                                                              compressors will be shut down in sequence. This will
The operating sequence described below relates to             occur at intervals of either 30, 15 or 10 seconds based
operation on a cooling demand start after power has           on the liquid temperature as compared to 'SETPOINT',
been applied, such as start-up commissioning.                 and control mode.

When power is applied to the unit a 2 minute timer will       When the last compressor in each system is to be
start. This timer also prevents instantaneous starting        cycled off, the system will initiate a pump-down. On a
after a power failure if the option POWER FAILURE             non-safety, non-unit switch shutdown, the YLLSV will be
RESTART is set to AUTOMATIC under the OPTION                  turned off, and the last compressor will be allowed to run
key.                                                          until the suction pressure falls below the suction
                                                              pressure cut-out or for 180 seconds, which ever comes
If the option POWER FAILURE RESTART is set to                 first.
MANUAL under the OPTION key the unit switch must be
set to OFF then back to ON to reset the unit lockout          2.1         Capacity Control
condition UNIT FAULT: 115VAC UNDER VOLTAGE.
                                                              The control system will evaluate the need for cooling by
For a unit to run, the unit switch and the software system    comparing the actual leaving chilled liquid temperature
switches under the option key must be set to on, any          to the desired 'SETPOINT', and regulate the leaving
remote cycling contacts must be closed, the 'Daily            chilled liquid temperature to meet that desired
Schedule' must be scheduling the unit on, and a               'SETPOINT'.
temperature demand must be present. The status
message will read 'FLOW SWITCH OPEN' for 30                   The leaving chilled liquid 'SETPOINT' is the
seconds after which a contact closes to start the             temperature the unit will control to within +/- the
evaporator pump. On the closing of the flow switch the        'RANGE'. The Setpoint High Limit is the 'SETPOINT'
remaining time on the 120 second anti-recycle timers          plus the 'RANGE'. The Setpoint Low Limit is the
will be displayed.                                            'SETPOINT' minus the 'RANGE'.

At the end of the 2 minute timer, the microprocessor will     The 'RANGE' setting takes into account the number of
check for cooling demand. If all conditions allow for a       compressors on the unit and the temperature difference
start, the first compressor on the lead system will start     between leaving (LCHLT) and return (RCHLT) chilled
and the liquid line solenoid will open. Coincident with the   liquid at full load (refer to Section 7.1 for details).
start, the anti-coincident timer will be set and begin
                                                                                                                                                                             Low Limit            SETPOINT       High Limit
counting downward from '60' seconds to '0' seconds.
                                                                                                                                                                                            RANGE             RANGE



                                                                                10 s unloading                  10 s unloading           15 s unloading            30 s unloading
If the unit is programmed for 'Automatic Lead/Lag

                                                                                                                                                                                                                              60 s loading
Control', the system with the shortest average run-time
                                                                                                                                                                                            (no compressor staging)
of the compressors will be assigned as the 'lead'
system. A new lead/lag assignment is made whenever
                                                               Leaving Liquid


                                                                                                 LLTC + 0.6°C
all systems shut down.                                                                                                           5.8°C                     6.4°C                    6.7°C             7.8°C           8.9°C
                                                               Temp. Cut-out                                                                              Leaving Chilled Liquid Temperature
After 1 minute of compressor run time, the next
                                                               (LLTC)
compressor in sequence will start when a system has to
load. Additional compressors will be started at 60
second intervals as needed to satisfy temperature load.       Each system has its own anti-recycle timers. The
                                                              anti-recycle time under the PROGRAM key can be
If demand requires, the lag system will come on with the      programmed between 240 and 600 seconds and sets
same timing sequences as the lead system. However             the minimum start-to-start time of the lead compressor
the lead system must be running for a minimum of 5            in a system. Due to lead lag rotation in a system,
minutes before the lag system will be allowed to run.         consecutive lead compressor starts are not with the
                                                              same compressor. A second non-programmable
                                                              anti-recycle timer, stop to start is fixed at 90 seconds,
                                                              starts to countdown when the lead compressor in a
                                                              systems cycles off.




                                                                                                                                                                                                                         1-5
Form 201.26.OI1(11/09)



The lag compressors in a system, are not controlled by       If both systems are available to load the system with the
the anti-recycle timer. They have no start to start timer    lowest number of compressors running will load. If both
other than the effect of system lead/lag rotation and the    systems have the same number of compressors
load/unload timers. For a given compressor this gives a      running the lead system will load.
minimum start to start time of 140 seconds on systems
with 2 compressors or 210 seconds on systems with 3          On units without soft start the strategy for compressor
compressors. Their minimum stop to start time for a          loading within a system is to maximize individual
given compressor is 60 seconds, the 60 second load           compressor run time and ensure that the same
timer.                                                       compressor does not start twice in a row. This is
                                                             achieved by rotating the lead/lag sequence of the
When the leaving chilled liquid temperature is above the     compressors in a system when a compressor other than
Setpoint High Limit, the lead compressor on the lead         the lag most compressor in that system stops. In
system will be energised along with the liquid line          achieving this objective no attempt will be made to
solenoid.                                                    equalize each compressors individual total run hours
                                                             within a system.
After 60 seconds of run-time if the leaving chilled liquid
temperature is still above the Setpoint High Limit and the   On units with soft start the compressor in each system
leaving chilled liquid temperature is not falling faster     with soft start is always the last to start. Compressors
than the programmed RATE SENSITIVITY within the              are always started in the same order, No1 compressor
programmed RATE CONTROL TEMPERATURE                          first.
R A N G E o r a b o v e th e R A T E C O N T R O L
TEMPERATURE RANGE at 1.7°C per minute, the next              If the chilled liquid temperature falls below the Setpoint
compressor in sequence will be energised.                    High Limit but is greater than the Setpoint Low Limit,
                                                             loading and unloading do not occur. This area of control
Additional loading stages are energised at a rate of one     is called the 'CONTROL RANGE'.
every 60 seconds if the chilled liquid temperature
remains above the Setpoint High Limit and the same           If the chilled liquid temperature drops to less than
criteria on leaving chilled liquid temperature rate of       0.28°C below the Setpoint Low Limit, unloading occurs
change as above are met.                                     at a rate of 30 seconds. If the chilled liquid temperature
                                                             falls to a value greater than 0.28°C below the Setpoint
The strategy for loading/unloading is design to meet the     Low Limit but not greater than 0.83°C below the Setpoint
following criteria:                                          Low Limit, unloading occurs at a rate of 15 seconds. If
                                                             the chilled liquid temperature falls to a value greater
1. Minimise system starting and stopping;                    than 0.83°C below the Setpoint Low Limit, unloading
                                                             occurs at a rate of 10 seconds. If the leaving chilled
2. The lag system is not available to start until the lead   liquid temperature falls to 0.6 °C above the leaving liquid
   system cannot load further and has been running for       temperature cutout, unloading occurs at a rate of 10
   5 minutes;                                                seconds.

3. When both systems are running, balance loading /          If more than one compressor is running in a system then
   unloading between them.                                   on unloading the compressor to be stopped is not the
                                                             same compressor stopped during the last unload
With both systems running the next system to load is         sequence. This is achieved by rotating the lead lag
determined by the following rules;                           sequence of the compressors in a system when a
                                                             compressor in that system stops.
1. The system must not be fully loaded or pumping
   down;                                                     The leaving chilled liquid 'SETPOINT' is programmable
                                                             from 4.4°C to 21.1°C in the chilled liquid water mode and
2. Remote load limit, suction limiting or discharge          from -7°C to 21.1°C in chilled liquid glycol mode. In both
   limiting must not be in effect on the system.             modes, the 'RANGE' can be from +/-0.8°C to 1.4°C. A
                                                             low temperature glycol unit is available which will go
                                                             down to -13°C.




1-6
                                                                                                                       Form 201.26.OI1(11/09)



To ensure that the Setpoint Low Limit cannot be                                         2.3     Anti-Coincidence Timer
inadvertently set to low when setting the Setpoint and
Control Range in the water cooling mode the software                                    The anti-coincidence timer prevents both systems from
makes the following adjustments. If as a result of                                      starting simultaneously. This assures that the inrush
Setpoint and Control Range setting the Setpoint Low                                     current is kept to a minimum. A 60 second time delay will
Limit would be below 4.4°C the software will set the                                    always separate motor starts. This timer is not
Setpoint Low Limit to 4.4°C and raise the Setpoint High                                 programmable.
Limit by the difference to maintain the same Control
Range.                                                                                  2.4     Compressor Crankcase Heater

To ensure reliable operation of the unit the software will                              Each compressor is fitted with a crankcase heater (not
modify the operation of the 'Leaving Chilled Liquid                                     controlled by the micro processor) which is ON when the
Control' as follows:                                                                    compressor is OFF.

1. If the run time of the lead system is less than 5                                    2.5     Pumpdown (YLLSV) Control
   minutes the Setpoint High Limit is increased up to a
   maximum of 10°C by the 'Setpoint Adjust Value'                                       Each system has a pumpdown feature at shut-off. On a
   shown in the following graph. Any adjustment value                                   non-safety, non-unit switch shutdown, all compressors
   in excess of the value taking the Setpoint High Limit                                but one in the system will be shut off. The liquid line
   to 10°C is taken from the Setpoint Low Limit. When                                   solenoid (YLLSV) will also be turned off. The final
   the run time exceeds 5 minutes the 'Setpoint Adjust                                  compressor will be allowed to run until the suction
   Value' returns to zero. This will occur whilst the unit                              pressure falls below the cut-out or for 180 seconds,
   is running. Pressing the 'COOLING SETPOINTS'                                         which ever comes first. Systems can be manually
   key four times will display the lead system's last run                               pumped down, using the system switches under the
   time and the 'Setpoint Adjust Value'.                                                'OPTIONS' key.

2. If the run time of the lead system is less than 5                                    2.6     Evaporator Solenoid Valve (YESV) Control
   minutes on 3 successive occasions, the anti-recycle                                          YLAA Units only. System 1 on models 220HE,
   timer will be doubled, with a maximum allowable                                              240SE & 260HE, System 2 on models
   anti-recycle value of 10 minutes.                                                            240SE,260HE, 285 & 300HE.




Setpoint Adjust Value (°C)
                             3.0                                                        The valve is always closed when the system is not
                             2.5                                                        running. The valve is open by timer KT for the first 300
                                                                                        seconds of system operation. This prevents low suction
                             2.0
                                                                                        pressure problems on system start. On low ambient
                             1.5                                                        units a solenoid valve is fitted on each system, but the
                                                                                        timer KT is only fitted and operated as described on the
                             1.0
                                                                                        models and systems above. On low ambient units this
                             0.5                                                        solenoid valve opens when the system is running
                             0.0
                                                                                        provided the ambient temperature is below 4.4°C. The
                                   0       1          2          3          4       5   valve will close when the ambient temperature rises
                                           Last run time of lead system (minutes)       above 7.2°C provided KT is not fitted and acting to open
                                                                                        the valve.
2.2                                Anti-Recycle Timer
                                                                                        2.6.1    YLAA Low Ambient Unit
Each system has its own anti-recycle timers. The
anti-recycle time under the PROGRAM key can be                                          Low Ambient Kit
programmed between 240 - 600 seconds and sets the
minimum start-to-start time of the lead compressor in a                                 Each system on all low ambient units is fitted with an
system. A second non-programmable anti-recycle                                          Evaporator Solenoid Valve (YESV) which operates as
timer, stop to start is fixed at 90 seconds, starts to                                  describe above. On systems with less than 4 fans a fan
countdown when the lead compressor in a systems                                         speed controller is fitted to fan No1. Fan contactor KF1
cycles off. On power up only this timer is set to 120                                   is wired to energize when the system starts and the
seconds not 90 seconds.                                                                 speed of the fan is controlled according to discharge
                                                                                        pressure. The remaining fans are controlled as normal.
The lag compressor(s) in a system, are not controlled by                                A heater is also fitted to the power element on the TXV
the anti-recycle timer                                                                  as part of the low ambient kit. The heater is on when the
                                                                                        ambient temperature is below 4.4°C. The heater is off
                                                                                        when the ambient rise to above 7.2°C



                                                                                                                                            1-7
Form 201.26.OI1(11/09)



2.7   Lead/Lag Control                                               YLAA MODEL               SYSTEM 1       SYSTEM 2
                                                               0180SE to 320SE                    2              2
The chiller may be set up for AUTO or MANUAL                   0195HE to 0260HE
lead/lag. This is accomplished by programming the              0360SE, 0400SE                     3              2
option under the 'OPTIONS' key.                                0300HE
                                                               0390HE                             4              2
When AUTO lead/lag is used, the microprocessor
attempts to balance run time between the systems. A            0435SE, 0485SE                     3              3
                                                               0350HE
number of conditions can occur which will prevent this
from happening. Factors determining lead/lag selection         0440HE                             4              3
and the resulting lead/lag determination are:                  0455HE, 0515HE                     4              4
                                                                     YLAE MODEL               SYSTEM 1       SYSTEM 2
The microprocessor automatically defaults the lead to
                                                              0190SE to 330SE                     2              2
system 1 and the lag to system 2 if both systems are          0195HE to 0265HE
ready to start (Anti-recycle Timers timed out) and the
                                                              0315HE                              3              2
systems have equal run time.
                                                              0375SE to 0490SE                    3              3
                                                              0355HE to 0405HE
If both systems are waiting to start (Anti-recycle timers
                                                              0465HE to 0510HE                    4              4
have not timed out), the microprocessor will assign the
lead to the system with the shortest anti-recycle time to
provide cooling quickly.                                     Low Ambient Units

If the lead system is locked out, faulted and waiting to     On systems with 2 or 3 fans, fan number 1 is replaced by
restart the lag system is swapped to the lead.               a variable speed fan. On system 2 of YLAA180SE,
                                                             195HE and 210SE the two small fans are replace by one
MANUAL lead/Lag selection will be automatically              variable speed fan. The fan is not controlled by the
overridden by the microprocessor to allow the lag            discharge pressure stages but is energized directly from
system to automatically become the lead anytime the          the fan fuses when the unit power is turned on. The fan
selected lead system shuts down due to, lead system          motor has a integral invertor which controls fan speed to
faults.                                                      maintain a pressure between 18 and 22.5 barg. Below
                                                             18 barg the fan should be off, above 22.5 barg the fan
Automatic switch over in MANUAL mode is provided to          should be at full speed, with a linier response between
try to maintain chilled liquid temperature as close to       these two pressures. A separate 4-20ma pressure
‘SETPOINT’ as possible.                                      transducer (-BFDP) is wired via a relay (-KF1) to the fan.
                          

Показано початок документа. Повний текст — у PDF за посиланням вище.

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.