| Вид документа | Інструкція з монтажу |
|---|---|
| Виробник | JCI |
| Код документа | nu-ncm300-1-to-nu-ncm350-1-upgrade-kit-installation-guide |
| Група обладнання | Network Control Module |
| Сторінок | 2 |
| Мова документа | англійська |
| Розмір файлу | 0.1 МБ |
Текст документа
Installation Sheet
Issue Date 0600
NU-NCM300-1 to NU-NCM350-1 Upgrade Kit
Notes: Models NU-NCM300-0 and NU-NCM311-0 cannot be upgraded
in the field. To upgrade these units or units with earlier revision
levels than those listed below, contact the Repair Center. European
branches contact the Essen, Germany facility.
To complete the NU-NCM 300-1 to NU-NCM350-1 field upgrade,
the NCM must have one of the following, or later, revision levels:
Table 1: NCM Code Numbers and Revision Levels
NCM Code Number Revision Level
NU-NCM300-1 or NU-NCM300-2 Revision B or later
NU-NCM300-701 or NU-NCM300-702 Revision B or later
This procedure also applies to the upgrade of an NU-NCM311-1 (or later
revision) to an NU-NCM361-1. See the Network Control Module
300 Series Technical Bulletin (LIT-6360251) for more details.
! CAUTION: Equipment damage hazard. Do not touch the edge
of the NU-ROM150-1 connectors (contact fingers).
Touching the invisible coating along the edge of the
NU-ROM150-1 can destroy it. See Figure 1.
R3
R2 C1 R5 R9
R8 C1
R1 R4 R7
R6
A B
Invisible coating is along this edge.
Figure 1: NU-ROM150-1
Upgrade Kit The NU-NCM300 to NU-NCM350 upgrade kit includes the following:
Includes • ROM150 Flash Single Inline Memory Module (SIMM)
• installation instructions
• new NCM350 label
© 2000 Johnson Controls, Inc. 1
Part No. 24-8617-4, Rev. B www.johnsoncontrols.com
Installation Perform the following steps to upgrade the NCM300 to an NCM350
(see Figure 2 for locations of components):
1. Turn off power to the NCM300.
2. Disconnect the battery pack.
3. Remove the ISA Slot/Comm Port cover and the cardboard insulator.
1234 5678 IN
O RE
1 2 3 4 5 6 7 8 7 8 UT AD
LO
CO E ND
ON NF O
IG F
.
L IN
E - O RY
PO BEF N TERYM EM
W a b BAT
TIO TD I NG
D-
RA
ER NNE LL
M
EN SCO STA
TT DI IN
-A PLEASEO RE
F ER
2N 2 N
-
+
Apply Label a
NEXT SE
RVICE DATE:
BA
T TER
Y
IS
A
S
LO
TS
b
DI
T RE
G PO
N ECBEFOIN
W
RU
IC ES
ON ERRV PP
SC WSE LY
PO
I
l
II
CO
M
M
- PO
R
TS
III
ISA Slot/Comm ER
A NG ININ
E
OL
SI
V
T
DE
NCM
D L
IV AGE
Port Cover
Figure 2: NU-NCM300
4. Observe placement of the ROM101 in the NCM and note the two tabs
on either side of the SIMM connector. Remove the ROM101 from the
NCM300 and discard it.
5. Insert the ROM150 into the NCM300, and make sure the tabs on both
sides of the ROM150 memory module socket snap into the holes of
the ROM150 (see A and B in Figure 1). When the ROM150 is in
place, it should be vertical, not angled.
! CAUTION: Equipment damage hazard. A ROM101 or
ROM150 must be installed before powerup of an
NCM. If either is not installed on powerup, the
DRAM and NOVRAM on the NCM may become
corrupt. If the NOVRAM is corrupt, the NCM must
be replaced!
6. Reinstall the cardboard insulator and the ISA Slot/Comm Port cover.
7. Apply the new NCM350 label over the old label.
8. Restore power to the NCM.
9. Download the NCM.
10. Reconnect the battery pack.
Controls Group
507 E. Michigan Street
P.O. Box 423 www.johnsoncontrols.com
Milwaukee, WI 53201 Printed in U.S.A.