NS Series Network Discharge Air Sensors
Installation Instructions
NS-DTN7043-0, NS-DTN7043-2,                                                        Part No. 24-10336-0, Rev. H
NS-DTN7083-0, NS-DTN7083-2                                                                  Issued February 2016

Applications
The NS Series Network Discharge Air Sensors are
                                                              IMPORTANT: The NS Series Network Discharge
electronic duct sensors designed to function directly
                                                              Air Sensors are intended to provide an input to
with Johnson Controls® digital controllers in HVAC
                                                              equipment under normal operating conditions.
systems. Models in this series monitor the duct
                                                              Where failure or malfunction of the discharge air
temperature, typically at the discharge of the Variable
                                                              sensors could lead to personal injury or property
Air Volume (VAV) box, and transmit this data to the
                                                              damage to the controlled equipment or other
controller Sensor Actuator (SA) Bus using the
                                                              property, additional precautions must be designed
305 cm (10 ft) wiring lead included with the unit. The
                                                              into the control system. Incorporate and maintain
305 cm (10 ft) wiring lead consists of four
                                                              other devices, such as supervisory or alarm systems
0.6 mm (22 AWG) diameter color-coded wires encased
                                                              or safety or limit controls, intended to warn of or
in a plenum-rated jacket. Each of the wires is stripped
                                                              protect against failure or malfunction of the
and tinned for easy connection to the SA Bus screw
                                                              discharge air sensors.
terminal block.
                                                              IMPORTANT : Le NS Series Network Discharge Air
The NS Series Network Discharge Air Sensors are
                                                              Sensors est destiné à transmettre des données
available with either a 102 or 203 mm (4 or 8 in.)
                                                              entrantes à un équipement dans des conditions
temperature probe. All models include DIP switches for
                                                              normales de fonctionnement. Lorsqu'une défaillance
applications requiring multiple discharge air sensors,
                                                              ou un dysfonctionnement du discharge air sensors
each with a unique DIP switch address.
                                                              risque de provoquer des blessures ou
                                                              d'endommager l'équipement contrôlé ou un autre
                                                              équipement, la conception du système de contrôle
                                                              doit intégrer des dispositifs de protection
                                                              supplémentaires. Veiller dans ce cas à intégrer de
                                                              façon permanente d'autres dispositifs, tels que des
                                                              systèmes de supervision ou d'alarme, ou des
                                                              dispositifs de sécurité ou de limitation, ayant une
                                                              fonction d'avertissement ou de protection en cas de
                                                              défaillance ou de dysfonctionnement du discharge
                                                              air sensors.

                        NS Series Network Discharge Air Sensors Installation Instructions

                                                          1
North American Emissions Compliance                             Wiring
United States                                                   If the NS Series Network Discharge Air Sensor is used
                                                                in an application requiring multiple discharge air
    This equipment has been tested and found to                 sensors, each with a unique DIP switch address, set
    comply with the limits for a Class A digital device         the DIP switches before wiring the unit. Otherwise,
    pursuant to Part 15 of the FCC Rules. These limits          proceed directly to Step 5.
    are designed to provide reasonable protection
                                                                1. Loosen (but do not remove) the two cover-holding
    against harmful interference when this equipment is
                                                                   screws using a 6 mm (1/4 in.) blade screwdriver or
    operated in a commercial environment. This
                                                                   a 6 mm (1/4 in.) nut driver.
    equipment generates, uses, and can radiate radio
    frequency energy and, if not installed and used in          2. Remove the cover from the discharge air sensor.
    accordance with the instruction manual, may cause           3. See Figure 1 and set the DIP switch block on the
    harmful interference to radio communications.                  discharge air sensor circuit board to the desired
    Operation of this equipment in a residential area is           DIP switch address.
    likely to cause harmful interference, in which case
    the user will be required to correct the interference       Note: Table 1 lists the available DIP switch addresses
    at his/her own expense.                                     and the DIP switch settings required to obtain them.

                                                                                                         On
Canada                                                                                                (Closed)

    This Class (A) digital apparatus meets all the

                                                                                                                  FIG:dp_swtch_blck
    requirements of the Canadian Interference-Causing
    Equipment Regulations.                                                                               Off
                                                                              4      2       1         (Open)
    Cet appareil numérique de la Classe (A) respecte
    toutes les exigences du Règlement sur le matériel                  Figure 1: Setting the DIP Switch Block
    brouilleur du Canada.
                                                                Table 1: Setting the DIP Switch Address
Mounting
                                                                 Available               DIP Switch Settings
The following ambient operating conditions apply:                DIP Switch    Switch 4          Switch 2        Switch 1
•     Temperature: -10 to 60°C (14 to 140°F)                     Addresses
                                                                 204           Off (Open)        Off (Open)      Off (Open)
•     Humidity: 10 to 90% Relative Humidity (RH),
      noncondensing; 29°C (85°F) maximum dew point               205           Off (Open)        Off (Open)      On (Closed)
                                                                 206           Off (Open)        On (Closed)     Off (Open)
Note: The discharge air sensor is shock and vibration
resistant; however, be careful not to drop the unit or           207           Off (Open)        On (Closed)     On (Closed)
mount it where it could be exposed to excessive                  208           On (Closed)       Off (Open)      Off (Open)
vibration.                                                       209           On (Closed)       Off (Open)      On (Closed)
To mount the discharge air sensor:                               210           On (Closed        On (Closed)     Off (Open)
1. Drill a 10 mm (3/8 in.) diameter hole in the duct at          211           On (Closed)       On (Closed)     On (Closed)
   the desired mounting location.
                                                                4. Reinstall the cover on the discharge air sensor and
2. Insert the temperature probe into the drilled hole.
                                                                   tighten the two cover-holding screws to secure it in
3. Secure the discharge air sensor to the duct using               place.
   two No. 6 self-drilling sheet metal screws included
                                                                5. Wire the discharge air sensor to the SA Bus screw
   with the unit.
                                                                   terminal block as illustrated in Figure 2.

                           NS Series Network Discharge Air Sensors Installation Instructions

                                                            2
Note: For more details on wiring the MS/TP
Communications Bus, refer to the MS/TP
Communications Bus Technical Bulletin
(LIT-12011034) or the FX-PC Series Controllers
MS/TP Communications Bus Technical Bulletin
(LIT-12011670).

                                                                                                             FIG:scrw_trmnl_blck
Risk of Electric Shock.
Disconnect the power supply before making electrical
connections to avoid electric shock.

                                                                      Figure 2: Wiring to the SA Bus
                                                                          Screw Terminal Block
Risque de décharge électrique.
                                                           6. Use the Metasys® Controller Configuration
Débrancher l'alimentation avant de réaliser tout
                                                              Tool (MS-CCT) or Facility Explorer Programmable
raccordement électrique afin d'éviter tout risque de
                                                              Controller Tool (FX-PCT) Software to commission
décharge électrique.
                                                              the discharge sensor. Refer to the Controller Tool
                                                              Help (LIT-12011147) for more details.
 IMPORTANT: Failure to adhere to these wiring              Repair Information
 details causes the discharge air sensor to function
                                                           If the NS Series Network Discharge Air Sensor fails to
 incorrectly.
                                                           operate within its specifications, replace the unit. For a
                                                           replacement discharge air sensor, contact the nearest
                                                           Johnson Controls representative.

                        NS Series Network Discharge Air Sensors Installation Instructions

                                                       3
Technical Specifications
NS Series Network Discharge Air Sensors
 Supply Voltage                            9.8 to 16.5 VDC; 15 VDC nominal
 Current Consumption                       12 mA maximum (non-transmitting) per discharge air sensor;
                                           60 mA maximum total current consumption per SA Bus
 Terminations                              Four color-coded wiring leads, stripped and tinned;
                                           Factory-installed at the discharge air sensor screw terminal block
 Sensor Addressing                         DIP switch set (204 to 211); factory set at 204
 Wire Size                                 1.0 to 0.6 mm (18 to 22 AWG) diameter);
                                           0.6 mm (22 AWG) diameter recommended; 305 cm (10 ft) wiring lead included with the
                                           unit
 Communication Rate                        Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
 Temperature Measurement                   -10°C/14°F to 60°C/140°F
 Range
 Temperature Sensor Type                   Local 1k Ohm platinum resistance temperature detector (RTD); Class A per IEC 60751
 Temperature         NS Series             ±0.6C°/±1.0F°
 Accuracy            Discharge Air
                     Sensor
                     Temperature           0.2C° at 21°C (0.35F° at 70°F)
                     Element Only
 Ambient             Operating             -10 to 60°C (14 to 140°F); 10 to 90% RH, noncondensing; 29°C (85°F) maximum dew
 Conditions                                point
                     Storage               -40 to 70°C (-40 to 158°F); 5 to 95% RH, noncondensing
 Compliance          BACnet®               BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
                     International
                     United States         UL Listed, File E107041, CCN PAZX,
                                           Under UL 916, Energy Management Equipment
                                           FCC Compliant to CFR 47, Part 15, Subpart B, Class A
                     Canada                UL Listed, File E107041, CCN PAZX7,
                                           Under CAN/CSA C22.2 No. 205, Signal Equipment
                                           Industry Canada, ICES-003
                     Europe                CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the
                                           essential requirements and other relevant provisions of the EMC Directive.
                     Australia and         RCM Mark, Australia/NZ Emissions Compliant
                     New Zealand
 Dimensions          Sensor                76 x 76 x 51 mm (3 x 3 x 2 in.)
                     Enclosure
                     (Height x
                     Width x Depth)
                     Temperature           NS-DTN7043-x: 102 mm (4 in.) long
                     Probe
                                           NS-DTN7083-x: 203 mm (8 in.) long
 Shipping            NS-DTN7043-x          1.15 lb (0.52 kg)
 Weight
                     NS-DTN7083-x          1.17 lb (0.53 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or
misuse of its products.

                              NS Series Network Discharge Air Sensors Installation Instructions

                                                                        4
European Single Point of Contact:     NA/SA Single Point of Contact:            APAC Single Point of Contact:
JOHNSON CONTROLS                      JOHNSON CONTROLS                          JOHNSON CONTROLS
WESTENDHOF 3                          507 E MICHIGAN ST                         C/O CONTROLS PRODUCT
45143 ESSEN                           MILWAUKEE WI 53202                        MANAGEMENT
GERMANY                               USA                                       NO. 22 BLOCK D NEW DISTRICT
                                                                                WUXI JIANGSU PROVINCE 214142
                                                                                CHINA

                                                                                                     Building Efficiency
                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                     Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                            All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

                        NS Series Network Discharge Air Sensors Installation Instructions

Published in U.S.A.                                       5                                     www.johnsoncontrols.com