24- 10424- 6, Rev . E

NS Series CO2 Network Sensors
Installation Instructions
                                                                                     Part No. 24-10424-6, Rev. E
NS-BCN7004-0, NS-BCN7004-2                                                                        Issued March 2016

Applications
The NS Series CO2 Network Sensors are electronic              IMPORTANT: The NS Series CO2 Network
zone sensors designed to function directly with               Sensors are intended to provide an input to
Johnson Controls® BACnet® MS/TP digital controllers           equipment under normal operating conditions.
in Heating, Ventilating, and Air Conditioning (HVAC)          Where failure or malfunction of the network sensor
systems.                                                      could lead to personal injury or property damage to
                                                              the controlled equipment or other property,
These sensors monitor room carbon dioxide (CO2).              additional precautions must be designed into the
This data is transmitted to a field controller on the         control system. Incorporate and maintain other
Sensor Actuator (SA) Bus.                                     devices, such as supervisory or alarm systems or
                                                              safety or limit controls, intended to warn of or protect
Applications include Demand Control Ventilation
                                                              against failure or malfunction of the network sensor.
(DCV) with fresh air and Indoor Air Quality (IAQ), as
part of a system to meet ANSI/ASHRAE Standard                 IMPORTANT : Le NS Series CO2 Network Sensors
62.1-2010 Ventilation for Acceptable Indoor Air               est destiné à transmettre des données entrantes à
Quality. For DCV applications, fresh air is brought into      un équipement dans des conditions normales de
a zone                                                        fonctionnement. Lorsqu'une défaillance ou un
based on the concentration levels of CO2.                     dysfonctionnement du network sensor risque de
                                                              provoquer des blessures ou d'endommager
The NS Series CO2 Network Sensors include
                                                              l'équipement contrôlé ou un autre équipement, la
DIP switches to set a unique address in averaging
                                                              conception du système de contrôle doit intégrer des
applications. The wires connecting the network sensor
                                                              dispositifs de protection supplémentaires. Veiller
to the controller can be terminated using either a            dans ce cas à intégrer de façon permanente
modular jack or screw terminal block, offering wiring         d'autres dispositifs, tels que des systèmes de
flexibility.                                                  supervision ou d'alarme, ou des dispositifs de
The NS Series CO2 Network Sensors include an                  sécurité ou de limitation, ayant une fonction
SA Bus access port for connecting accessories to              d'avertissement ou de protection en cas de
access the SA Bus. This feature allows a technician to        défaillance ou de dysfonctionnement du network
commission or service the controller via the network          sensor.
sensor.

                                                     NS Series CO2 Network Sensors Installation Instructions             1
North American Emissions Compliance                         Note: The network sensor is shock and vibration
                                                            resistant; however, be careful not to drop the unit or
United States                                               mount it where it could be exposed to excessive
                                                            vibration.
    This equipment has been tested and found to
    comply with the limits for a Class A digital device     The following ambient operating conditions apply:
    pursuant to Part 15 of the FCC Rules. These limits
                                                            •      Temperature: 32 to 104°F (0 to 40°C)
    are designed to provide reasonable protection
    against harmful interference when this equipment is     •      Humidity: 10 to 90% Relative Humidity (RH),
    operated in a commercial environment. This                     noncondensing; 85°F (29°C) maximum dew point
    equipment generates, uses, and can radiate radio
                                                            To mount the network sensor to a wallbox:
    frequency energy and, if not installed and used in
    accordance with the instruction manual, may cause       1. Use a 1/16 in. (1.5 mm) Allen wrench or
    harmful interference to radio communications.              Johnson Controls T-4000-119 Allen-Head
    Operation of this equipment in a residential area          Adjustment Tool to loosen the security screw on
    may cause harmful interference, in which case the          the top of the unit.
    users will be required to correct the interference at
                                                            2. Insert a coin into the slot next to the security screw
    their own expense.
                                                               location, pressing the tab that keeps the unit
Canada                                                         closed. Then carefully pry the top edge of the
                                                               sensor assembly away from its mounting base and
    This Class (A) digital apparatus meets all the             remove.
    requirements of the Canadian Interference-Causing
    Equipment Regulations.                                      IMPORTANT: Do not insert tools into the housing.
                                                                Be careful not to damage any components when
    Cet appareil numérique de la Classe (A) respecte            pushing on the tab.
    toutes les exigences du Règlement sur le matériel
    brouilleur du Canada.                                       IMPORTANT: Do not remove the Printed Circuit
                                                                Board (PCB). Removing the PCB voids the product
Installation                                                    warranty.
Special Tools Needed
                                                            Pull out approximately 6 in. (152 mm) of cable from the
A 1/16 in. (1.5 mm) Allen wrench or a Johnson Controls
                                                            wallbox, and insert the cable through the hole in the
T-4000-119 Allen-Head Adjustment Tool is required
                                                            mounting base.
during installation.
                                                            3. Align the mounting base on the wallbox.
Mounting
                                                            Note: Confirm that the mounting base is positioned
Note: The NS Series CO2 Network Sensors are                 with the proper edge up. The mounting base is
intended to be mounted on a vertically roughed-in           positioned properly when the security screw is located
wallbox only; do not attempt to mount the network           on the top edge of the base.
sensor on a horizontally roughed-in wallbox.
                                                            4. Secure the mounting base to the wallbox using the
Location Considerations                                        appropriate mounting hardware (field furnished).
Locate the network sensor:
                                                            5. Wire the network sensor as follows:
•     on a partitioning wall, approximately 5 ft (1.5 m)           SA Bus Wiring: For the modular jack, simply snap
      above the floor in a location of average                     the wiring plug into the jack. See Figure 1 for
      temperature                                                  modular jack pin number assignments. A modular
•     away from direct sunlight, radiant heat, outside             jack requires a straight-through, one-to-one
      walls, outside doors, air discharge grills, or               connection (not a crossover). For the screw
      stairwells; and from behind doors                            terminal block, wire the unit as illustrated in
                                                                   Figure 2.
•     away from steam or water pipes, warm air stacks,
      unconditioned areas (not heated or cooled), or        Note: Connect to the SA Bus using either the screw
      sources of electrical interference                    terminal block or the modular jack. Do not use both.

2        NS Series CO2 Network Sensors Installation Instructions
    24-Volt Supply Wiring: Connect the
    24 VAC/VDC, Class 2 power supply required by
    the NS Series CO2 Network Sensors to the HOT
    and COM screw terminal block, whether using the
    screw terminal block or modular jack for the                                                   Main
    SA Bus connection.                                                                            Network
                                                                                                   Port
 IMPORTANT: Do not connect the 24 power
                                                                                         Pin Number Assignment for
 common to the SA Bus common. The SA Bus                                                   Straight-Through Cable
 common is an isolated signal common.
                                                                                                                                           FIG:mdlr_jck
                                                                                            6 5 4 3 2 1

For more details on wiring and distance guidelines
for the MS/TP Communications Bus, refer to the                                               Printed Circuit Board
MS/TP Communications Bus Technical Bulletin
(LIT-12011034).
                                                                                            r)                - +
                                                                                                            SA SA
                                                                        C om
                                                                             m           nso
            CAUTION: Risk of Electric Shock.                                  o
                                                                      SA S n (N        Se
                                                                                   k
            Disconnect the power supply before                                   or
                                                                        Bu A P etw
     !      making electrical connections to avoid
                                                                       w
                                                                        er
                                                                          s
                                                                             et
                                                                                w
                                                                                o
                                                                            C we ork
                                                                           (N
                                                                             om r
                                                                                m (To ens
                                                                                  on ol
                                                                                          S
                                                                                    (T Ac r)
                                                                                              o
            electric shock.
                                                                     Po               oo ce
                                                                                        l A ss
            MISE EN GARDE : Risque de décharge                  SA
                                                                Bu
                                                                                           cc )
                                                                                             es
                                                                  s                            s)
            électrique.                                       SA
            Débrancher l'alimentation avant de
            réaliser tout raccordement électrique afin      Figure 1: Modular Jack Pin Number Assignments
            d'éviter tout risque de décharge
            électrique.

 IMPORTANT: Failure to adhere to these wiring
 details causes the network sensor to function
 incorrectly. You will not be able to connect to the
 system using the wireless commissioning converter
 or the handheld Variable Air Volume (VAV) balancing
 tool, and you will not be able to expand the system
 with future offerings.

6. Align the tabs on the bottom edge of the mounting

                                                                                                                     FIG:scrw_trmnl_blck
   base with the slots on the bottom edge of the
   network sensor assembly, and rotate the assembly
   onto its mounting base.
Note: For the screw terminal block, be certain that the
terminal block pins align with the holes in the terminal
                                                              Figure 2: Wiring to the Screw Terminal Block
block.
7. Use a 1/16 in. (1.5 mm) Allen wrench or                 8. Use the Metasys® Controller Configuration
   Johnson Controls T-4000-119 Allen-Head                     Tool (CCT) or Facility Explorer Programmable
   Adjustment Tool to tighten the security screw and          Controller Tool (FX-PCT) software to commission
   fasten the network sensor assembly to the                  the network sensor. Refer to the Controller Tool
   mounting base.                                             Help (LIT-12011147) for more details.
Note: Do not overtighten the security screw; doing so
may damage the unit.

NS Series CO2 Network Sensors Installation Instructions                                                                                                   3
Setup and Adjustments                                                 As of Release 5.3, the NS Series CO2 Network
                                                                      Sensors (Zone Quality [ZN-Q] Analog Input [AI]) in the
Network Sensor Addressing
                                                                      CCT and FX-PCT software automatically change the
Table 1 lists the available DIP switch addresses and                  hPa value entered from Table 2 into the correct Offset
the DIP switch settings required to obtain them.                      value. The Offset value for the SA Bus device is
                                                                      labeled ppm; however, it is the proper field to enter the
                                         On
                                      (Closed)                        hPa value found in Table 2. Refer to the Controller Tool
                                                                      Help (LIT-12011147) for more details.
                                                                      Note: Enter the pressure value only in units of hPa.
                                                  FIG:dp_swtch_blck
                                         Off                          The sensor reads the value entered as hectopascals.
               4      2      1         (Open)                         The CO2 Present Value may require several minutes to
                                                                      settle after changing the Offset value.
       Figure 3: Setting the DIP Switch Block
                                                                      Table 2 lists local altitude values.
Table 1: Setting the DIP Switch Address                               Table 2: CO2 Altitude Compensation
 Available                DIP Switch Settings                            Altitude Above Sea             Absolute Pressure
 DIP Switch    Switch 4          Switch 2        Switch 1                       Level
 Addresses
                                                                          Feet          Meters          in. Hg        hPa
 212           Off (Open)        Off (Open)      Off (Open)
                                                                           -656           -200           30.6        1,038
 213           Off (Open)        Off (Open)      On (Closed)
                                                                            0               0            29.9        1,013
 214           Off (Open)        On (Closed)     Off (Open)
                                                                           656            200            29.2         989
 215           Off (Open)        On (Closed)     On (Closed)
                                                                          1,312           400            28.5         966
 216           On (Closed)       Off (Open)      Off (Open)
                                                                          1,969           600            27.9         943
 217           On (Closed)       Off (Open)      On (Closed)
                                                                          2,625           800            27.2         921
 218           On (Closed        On (Closed)     Off (Open)
                                                                          3,281          1,000           26.5         899
 219           On (Closed)       On (Closed)     On (Closed)
                                                                          3,937          1,200           25.9         877

CO2 Altitude Compensation                                                 4,593          1,400           25.3         856
                                                                          5,249          1,600           24.7         835
The Johnson Controls NS Series CO2 Network
Sensors ship from the factory calibrated for an altitude                  5,906          1,800           24.1         815
range of 0 to 2,000 ft (0 to 600 m) without                               6,562          2,000           23.5         795
compensation.                                                             7,218          2,200           22.9         775
For altitudes above 2,000 ft (600 m) where optimum                        7,874          2,400           22.3         756
accuracy of the CO2 concentration measurement is                          8,530          2,600           21.8         738
essential, modify the Offset property of the NS Series                    9,186          2,800           21.2         719
CO2 Network Sensors (Zone Quality [ZN-Q] Analog
                                                                          9,843          3,000           20.7         701
Input [AI]). The Offset represents the local atmospheric
pressure in hectopascals (hPa). Set the Offset to the
known local pressure or use the local altitude value                  Reset
listed in Table 2. The factory default value is 978 hPa.              If the NS Series CO2 Network Sensors need a reset,
                                                                      cycle the 24-volt power supply. The 15-volt SA Bus
                                                                      power does not require cycling.
                                                                      Repair Information
                                                                      If the NS Series CO2 Network Sensor fails to operate
                                                                      within its specifications, replace the unit. For a
                                                                      replacement network sensor, contact the nearest
                                                                      Johnson Controls representative.

4      NS Series CO2 Network Sensors Installation Instructions
Technical Specifications
NS Series CO2 Network Sensors (Part 1 of 2)
 Supply Voltage    Non-isolated: 20 to 30 VAC (18 to 30 VDC), Class 2 or Safety Extra-Low Voltage (SELV)
                   Isolated: 9.8 to 16.5 VDC; 15 VDC Nominal (From SA Bus)
 Current           Non-isolated: 22 mA Average at 24 VAC; 28 mA Average at 24 VDC
 Consumption
                   Isolated: 5 mA Maximum, Non-transmitting (From SA Bus)
 Power             Non-isolated: Less Than 0.7 W Average
 Consumption
 Terminations      Non-isolated Supply: Screw Terminal Block
                   SA Bus: Modular Jack or Screw Terminal Block
 Sensor            DIP Switch Set from 212 to 219; Factory Set at 212
 Addressing
 Wire Size         Modular Jack: 24 or 26 AWG (0.5 or 0.4 mm Diameter); Three Twisted Pair (Six Conductors)
                   Screw Terminal Block: 18 to 22 AWG (1.0 to 0.6 mm Diameter); 22 AWG (0.6 mm Diameter)
                   Recommended
 Communication     Auto-Detect: 9.6k, 19.2k, 38.4k, or 76.8k bps
 Rate
 CO2               0 to 2,000 ppm
 Measurement
 Range
 CO2 Sensing       Plus or Minus the Sum of 40 ppm and 2.0% of the CO2 Reading at 77°F (25°C) and 978 hPa or an
 Accuracy          Altitude of 1,000 ft/300 m
                   Note: All accuracy specifications reflect the testing of the device using high-grade certified gases. This
                   device is intended for an altitude range of 0 ft/0 m to 2,000 ft/600 m above sea level without
                   compensation.
                   Temperature Dependence of Output: -0.35% of the CO2 Reading per 1.8F°/1C° Typical
                   Pressure Dependence of Output: +0.15% of the CO2 Reading per 1 hPa Typical
 CO2 Sensing       1 ppm
 Resolution
 CO2 Sensing       1 Minute (0 to 90%)
 Response Time
 CO2 Sensing       Less Than 1 Minute; Less Than 10 Minutes for Full Accuracy
 Warm-Up Time
 CO2 Sensing       Less Than ±100 ppm Over 5 Years
 Long-Term
 Stability
 Mounting          Surface-Mounted or Vertical Wallbox-Mounted: 120 x 80 mm
 Ambient           Operating: 32 to 104°F (0 to 40°C); 10 to 90% RH, Noncondensing; 85°F (29°C) Maximum Dew Point;
 Conditions        700 to 1,200 hPa
                   Storage: -40 to 158°F (-40 to 70°C); 5 to 95% RH, Noncondensing

NS Series CO2 Network Sensors Installation Instructions                                                                         5
NS Series CO2 Network Sensors (Part 2 of 2)
 Compliance              BACnet International:
                         BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)
                         United States:
                         UL Listed, File E107041, CCN PAZX, Under UL 916, Energy Management Equipment;
                         FCC Compliant to CFR 47, Part 15, Subpart B, Class A
                         Canada:
                         UL Listed, File E107041, CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal Equipment;
                         Industry Canada, ICES-003
                         Europe:
                         CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential
                         requirements and other relevant provisions of the EMC Directive.
                         Australia and New Zealand:
                         RCM Mark, Australia/NZ Emissions Compliant
 Shipping Weight         0.35 lb (0.16 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or
misuse of its products.

European Single Point of Contact:               NA/SA Single Point of Contact:                   APAC Single Point of Contact:
JOHNSON CONTROLS                                JOHNSON CONTROLS                                 JOHNSON CONTROLS
WESTENDHOF 3                                    507 E MICHIGAN ST                                C/O CONTROLS PRODUCT
45143 ESSEN                                     MILWAUKEE WI 53202                               MANAGEMENT
GERMANY                                         USA                                              NO. 22 BLOCK D NEW DISTRICT
                                                                                                 WUXI JIANGSU PROVINCE 214142
                                                                                                 CHINA

                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                    All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.