NCM45x0-2 Network Control Module Product Bulletin
MS-NCM4510-2, MS-NCM4520-2 Code No. LIT-12011173
Software Release 6.0
Issued January 30, 2013
Supersedes October 4, 2010
The NCM45x0-2 Series Network Control Module is a fully The NCM45x0-2 uses the same hardware design as the
user-programmable supervisory controller. It is NAE45 Series controllers and can be optionally upgraded
responsible for monitoring and controlling networks of to an NAE45 as part of a migration strategy to the
field-level building automation devices and HVAC Metasys system extended architecture.
equipment. See Figure 1.
Figure 1: NCM45x0-2
The NCM45x0-2 is functionally similar to the NCM350/361
controllers. The primary differences between these
controllers are the support for one N2 trunk and two
Network Control Module (NCM) types: General with
Network Terminal (NT) and General with Operator
Terminal (OT). The NCM45x0-2 is available with the N2
Bus or LON Trunk interface.
The NCM45x0-2 communicates with all other Metasys®
Network Control Units (NCUs) over the N1 Network.
Systems with Person-Machine Interface (PMI) Software
Release 12.04 and the M-Series Workstation Software
products at Release 5.4 support the NCM45x0-2.
Table 1: Features and Benefits
Features Benefits
Compatibility with All Existing Controllers on Installs on the same N1 Ethernet Network as the legacy NCM products and
the Network can communicate with NCM100s and NCM200s when the NCM45x0-2 is
installed on the Ethernet side of the network.
NCM350/361 Controllers Replacement Provides for a manageable replacement strategy for older NCM350/361 models.
Current Level of Software and Tool Support Is compatible with PMI Software Release 12.04 and M-Series Workstation
Software at Release 5.4 and existing Metasys software tools.
Supervision of Field Controller Networks Supports connectivity to open network standards for complete flexibility in the
selection of field devices. Supported protocols include Metasys N2 Bus and
LONWORKS® network.
Field-Upgradable to an NAE45 Provides an easy migration path to the Metasys system extended architecture.
NCM45x0-2 Network Control Module Product Bulletin 1
Figure 2: Metasys Network with Multiple Network Automation Engines (NAEs)
Distributed Network of Communicate with N2 Bus or LON
Controllers Network Devices
The NCM is a stand-alone controller that connects directly We offer two models of the NCM45x0-2 that support
to an IP Ethernet network running at 10 or 100 Mbps. communication with N2 Bus devices or LON Network
The NCM communicates with other NCMs, NCUs, and devices.
operator devices over this network and through the
Metasys Ethernet Router to the Attached Resource The N2 Bus is the Johnson Controls® field
Computer Network (ARCNET®) Local Area Network communications trunk that links Application Specific
(LAN), if present. Controllers (ASCs) to a supervisory controller. ASCs
include the DX-9100, Air Handling Unit (AHU), Unitary
The NCM45x0-2 can share its information with the other (UNT) Controller, VAV controllers, and VAV Modular
NCMs and NCUs on the network. Unlike other systems, Assembly (VMA) devices. The NCM can coordinate the
this sharing is unlimited and allows the NCM access to activities of all these devices.
any information available to any other NCM. This
capability makes practical the ability to totally integrate The NCM can also supervise LONWORKS devices. The
every facet of a building’s operation on a single network. NCM supports LONWORKS devices if the network interface
follows current LONMARK® guidelines, preferably with the
The NCM can also serve as the network operator LONMARK certification, and uses the Free Topology
interface. The NCM organizes information for operator Transceiver FTT10.
reports and responds to operator’s commands and
program changes. Since each NCM has total access to The LONWORKS network interface in the NCM supports all
all NCM data on the N1 LAN, operator access through current LONMARK certified devices, including devices from
one NCM is the same as access to all NCMs. Johnson Controls, such as the LN Series Controllers and
the LONWORKS enabled programmable Flexible System
Controller (FSC).
NCM45x0-2 Network Control Module Product Bulletin 2
Figure 3: Support for Multiple User Devices
NCM Fits the Needs of Any Size
Facility
The NCM45x0-2 is a high-performance supervisory
controller that can handle a wide array of control duties.
In small facility applications, an NCM serves as the
primary supervisor for field controllers. Using a
combination of resident applications and custom
user-written programs, the NCM operates equipment at
peak efficiency while maintaining optimum occupant
comfort. The NCM communicates to the building manager
through local override controls, an easy to use NT, and
local or remote graphic Operator Workstations (OWSs)
and printers.
Medium and large facilities use several NCMs, each of
them controlling a portion of the facility, yet sharing
information and data as necessary. In each system, the Software Features
NCM coordinates a local network of ASCs as they perform The NCM provides many software features that
HVAC, fire, and access control functions. In this coordinate system-wide efficiency, keeping you informed
application, the NCM provides alarm monitoring and and in control while ensuring occupant safety and comfort.
integrated control functions for the stand-alone controllers. The application programs, user databases, and point
histories are stored in the NCM and backed up by a
Carrying out even one of these many functions would be
long-lasting, rechargeable battery.
a major accomplishment for many controllers, but the
Metasys NCM handles them all with ease. Scheduling
Scheduling provides a long-term, system-wide means for
Simple Versatile System Access issuing commands to objects (for example, on/off or
The building operator has access to the entire Metasys setpoint adjustment). Establish control on a time-of-day,
network through a family of operator interface devices day-of-week, or calendar basis. Virtually any number of
attached to the NCM. Two standard RS-232-C ports are commands may be scheduled per object.
available for use by a wide variety of operator devices.
These devices include the OWS, OT, NT, and Printer. Totalization
An OWS can connect locally or remotely via a modem to Capabilities of the NCM include Runtime Totalization,
one of the RS-232-C ports, enabling access to the entire which keeps track of total operation hours for fans,
network. Other choices include the OT (local or remote) pumps, and other equipment monitored or controlled with
and NT (local only). Each of these user devices can be a binary object. Analog Totalization and Pulse Totalization
used for object monitoring, overrides, setpoint monitor the consumption of chilled water, steam, gas,
adjustments, schedule changes, and parameter electricity, or other variables measured by either analog
modifications. Also, a local or remote printer can connect or pulse input sensors. Event Totalization counts how
to the RS-232-C port for recording important events in many times something has occurred, such as a
the system. compressor cycling on and off.
Demand Limiting
Demand Limiting monitors your building’s electrical
meters and predicts the electrical demand. Should the
prediction exceed a target value, the feature temporarily
turns off non-essential equipment. The Load Rolling
feature cycles equipment on and off to reduce electrical
power consumption.
NCM45x0-2 Network Control Module Product Bulletin 3
• LEDs to indicate power, communications, and fault,
Control Processes to allow easy servicing
User-written control processes allow programming of • plug-in screw terminals for 24 VAC power, N2 Bus or
additional application features into the NCM. With the LON network connections
powerful Graphic Programming Language (GPL), even
a non-programmer can write specialized programs for • standard 9-pin sub-D connectors for RS-232-C serial
optimal start time control, night setback, outside air ports
economizer programs, chiller plant optimization, and • RJ-45 connector for Ethernet connection
more. Enter these energy-saving programs from an OWS,
then load them into the NCM over the N1 LAN or through Easy Migration to the New
the direct RS-232-C connection. Architecture
Password Protection We designed the NCM45x0-2 with your future in mind.
The NCM provides password protection by assigning an Whenever you are ready, you can field-upgrade the
eight-character password ID to each operator. The ID is NCM45x0-2 into an NAE45, the supervisory controller
programmed to indicate which level of command authority that is part of the Metasys system extended architecture.
is granted, and to which groups of objects the operator After a simple flash download, you are on your way to
has access. discovering the exciting Web browser interface that our
new architecture provides. (For details on the NAE45,
Trending refer to the Network Automation Engine Product Bulletin
Trending monitors changes in an object’s value over time [LIT-1201160]).
as a means to collect data when the system is operating
properly, and to help diagnose problems in your facility. Conclusion
The NCM45x0-2 provides for the needs of any facility,
Hardware Features large or small. The entire Metasys family of products
The NCM45x0-2 provides the following features for the affirms the Johnson Controls position as a leader in the
building controls market: building automation industry and as an innovator of
solutions for the complete management of buildings.
• nonvolatile solid-state Flash memory to store all
programs and data Ordering Information
• battery backup to save data from Dynamic Random Contact the nearest Johnson Controls representative to
Access Memory (DRAM) into Flash memory when order an NCM45x0-2. Specify the desired product code
primary power to the NCM is interrupted from Table 2.
• real-time clock with battery backup
Table 2: NCM45x0-2 Ordering Information
Product Code Number
1 Description
MS-NCM45x0-2 (Base features of each Requires a 24 VAC power supply. Each model includes two RS-232-C serial ports,
NCM45x0) one Universal Serial Bus (USB) serial port (unused), one Ethernet port, and an
MS-BAT1020-0 Data Protection Battery.
MS-NCM4510-2 Supports one N2 trunk (RS-485 port). Up to 100 devices (60 to 200 TC-9100s or
up to 63 VMAs) are supported on the N2 trunk with the use of a repeater.
MS-NCM4520-2 Includes a LONWORKS port and supports one LONWORKS trunk. Up to 127 devices
are supported on the LONWORKS port.
1 All models are also available in a Buy American version (add a G after the code number). For repair parts, replace the -2 suffix
with -702.
Table 3: NCM45x0-2 Accessories Ordering Information
Product Code Number Description
MS-BAT1020-0 Replacement data protection battery: Rechargeable NiMH 3.6 VDC, 500 mAh
battery with a typical life of 5 to 7 years at 21°C (70°F) (Higher operating
temperatures reduce battery life.)
AS-XFR050-0 Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure
NCM45x0-2 Network Control Module Product Bulletin 4
Table 3: NCM45x0-2 Accessories Ordering Information
Product Code Number Description
MS-NC45NTK-0 NCM4500 NT Cable Kit (North American version)
MS-NC45NTE-0 NCM4500 NT Cable Kit (International version)
Technical Specifications
Table 4: NCM45x0-2 Model
Power Requirement Dedicated nominal 24 VAC, Class 2 power supply (North America), Safety Extra-Low
Voltage (SELV) power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC
maximum)
Power Consumption 25 VA maximum
Ambient Operating Temperature 0 to 50°C (32 to 122°F)
Ambient Operating Conditions 10 to 90% RH, 30°C (86°F) maximum dew point
Ambient Storage Temperature -40 to 70°C (-40 to 158°F)
Ambient Storage Conditions 5 to 95% RH, 30°C (86°F) maximum dew point
Data Protection Battery Supports data protection on power failure. Rechargeable NiMH battery: 3.6 VDC 500
mAh, with a typical life of 5 to 7 years at 21°C (70°F); Product Code Number:
MS-BAT1020-0
Processor 192 MHz Renesas® SH4 7760 RISC 32-bit processor
Memory 128 MB Flash nonvolatile memory 128 MB Synchronous Dynamic Random Access
Memory (SDRAM)
Note: Even though the unit has 128 MB of memory, it is sized to emulate the capacity
of an NCM300 Series controller with 10 MB of memory.
Operating System Microsoft® Windows® CE embedded Release 5.0
Metasys Features One N2 or LON Trunk, Dial-up access, local printer, JC-BASIC, Demand Limiting Load
Rolling (DLLR), Trend, Totalization, Scheduling, Point History, Report Router and Alarm
Management, Duty Standby (both models must be NCM45x0-2s), N1 on Ethernet,
Pass-through download and upload of ASCs, DX-9100s, and VMA-1400s, Battery backup
of data
Network Communication Module General with NT, General with OT
(NCM) Types
Network and Serial Interfaces One Ethernet port; 10/100 Mbps; 8-pin RJ-45 connector
One optically isolated RS-485 port; 9600 bps; pluggable and keyed 4-position terminal
block (Field Controller (FC) Bus terminal, used for N2 Bus, is available on NCM4510-2
model only)
One LONWORKS port; FTT10 78 Kbps; pluggable, keyed 3-position terminal block (LONWORKS
port available on NCM4520-2 model only)
Two RS-232-C serial ports with standard 9-pin sub-D connectors that support standard
baud rates
One USB serial port with standard USB connector (not used)
Dimensions (Height x Width x 131 x 270 x 62 mm (5.2 x 10.6 x 2.5 in.)
Depth)
Minimum space for mounting: 210 x 350 x 110 mm (8.3 x 13.8 x 4.3 in.)
Housing Plastic housing material: ABS + polycarbonate, Protection: IP20 (IEC60529)
Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail (DIN rail
mount recommended)
NCM45x0-2 Network Control Module Product Bulletin 5
Table 4: NCM45x0-2 Model
Shipping Weight 1.2 kg (2.7 lb)
Agency Listings United States
• UL Listed (PAZX), UL 916
• Federal Communications Commission (FCC) compliant, CFR47, Part 15, Class B
Canada
• UL Listed (PAZX7), CAN/CSA C22.2 No. 205
• Industry Canada: ICES-003
European Union
• CE Mark – Johnson Controls declares that the NCM45 Controllers are in compliance
with the essential requirements and other relevant provisions of the EMC Directive
2004/108/EC.
Australia/New Zealand
• C-Tick Mark based on EMC Directive, 89/336/EEC
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Canadian Emissions Compliance
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur du
Canada.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2013 Johnson Controls, Inc.
Published in U.S.A. www.johnsoncontrols.com
NCM45x0-2 Network Control Module Product Bulletin 6Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.