NxE85 Commissioning Guide
MS-NIE85SW-0, MS-NAE85SW-0                                                                                           Code No. LIT-12011044
                                                                                                                        Software Release 9.0
                                                                                                                         Issued August 2017

Document Introduction.............................................................................................................2
Summary of Changes................................................................................................................2
NxE85 Network Engines............................................................................................................2
   Differences between NxE85 and NAE55/NIE55 Models...................................................................3
   Guidelines for Commissioning an NxE85 ........................................................................................4
Detailed Procedures..................................................................................................................5
   Commissioning Requirements..........................................................................................................5
   Commissioning the NxE85 ................................................................................................................5
   Changing the NxE85 Name and the Computer Name......................................................................6
   Changing the NxE85 Name and the Computer Name - Overview........................................................6
   Preparing the Computer........................................................................................................................6
   Creating a New Archive........................................................................................................................7
   Downloading the NxE85.......................................................................................................................8
   Testing the NxE85.................................................................................................................................8
   Configuring the NxE85 in the Site Management Portal UI..............................................................9
   Licensing the NxE85 ........................................................................................................................10
Related Documentation...........................................................................................................11
NxE85 Technical Specifications.............................................................................................12

                     NxE85 Commissioning Guide                                                                                                      1
Document Introduction
This document describes how to commission a Network Integration Engine 85 (NxE85) Series for operation on a
Metasys® Building Automation System (BAS) network.
This document does not describe how to mount, wire, or power on an NxE85. Also, this document does not describe
how to build or download an archive database for a Metasys system site or how to configure an NxE85 to monitor
and control a specific BAS network or network devices.
This document supplements the NAE Commissioning Guide (LIT-1201519). Refer to that document for background,
related concepts, and general information regarding connecting to and commissioning a Network Automation Engine
(NAE) or a Network Integration Engine (NIE) on a Metasys site.

Summary of Changes
The following information is new or revised:
•   Updated NxE85 Technical Specifications.
•   Replaced Ready Access Portal with Metasys UI in Figure 1.

NxE85 Network Engines
The NxE85 models are designed to provide supervisory-level control of Metasys networks that include a large number
of BACnet® IP devices or N1 devices.
The NIE85 migrates large N1 networks into a Metasys network (Figure 1).
The NAE85 integrates large BACnet IP systems into a Metasys network (Figure 2).
Like the NAE55/NIE55, the NxE85 models provide the following:
•   monitoring and control of the BAS
•   a web-based user interface using HTTPS
•   web services for access to data and services in the NAE85 or NIE85
•   standard protocol clients:
    - Simple Network Management Protocol (SNMP) for network device management
    - Simple Network Time Protocol (SNTP) for time and date synchronization
    - Dynamic Host Configuration Protocol (DHCP) for dynamic IP address assignment (NAE85 only)
    - Simple Mail Transfer Protocol (SMTP) for sending email notification of alarms and events
•   routing of event and alarm notification to an Application and Data Server (ADS), Extended Application and Data
    Server (ADX), or Open Data Server (ODS). (ADS-Lite does not support the NxE85.)
•   the capability to send event and alarm notifications to pager and email destinations directly
•   data collection, trend sampling, and audit trail logging
The NxE85 supports only one language at a time. A Metasys system site must have the same language for every
NxE85 on the site.
See Differences between NxE85 and NAE55/NIE55 Models for information on how NxE85 models differ from NAE55
and NIE55 models.

NxE85 Commissioning Guide                                                                                       2
                            Figure 1: Metasys Network with an NIE85 N1 Migration

                     Figure 2: Metasys Network with an NAE85 BACnet IP Integration

Differences between NxE85 and NAE55/NIE55 Models
The NxE85 models have most of the same functions and capabilities as the NAE55/NIE55 models, except that an
NxE85 :
•   does not support N2 protocol
•   does not support LONWORKS® network protocol
•   does not support dial-out to an ADS/ADX or ODS

NxE85 Commissioning Guide                                                                                3
•   does not support modem communication (except for sending pager alarm and event notifications through the
    pager Destination Delivery Agent [DDA]
•   does not support the Reset Device command in the Site Management Portal (SMP) UI
•   does not have NAE LED status indicators
•   cannot be upgraded using the NAE/NIE Update Tool
•   is limited to 10 simultaneous users when configured as a Site Director
•   has no internal uninterruptible power supply (UPS) for orderly shutdown in the event of a sudden loss of power
•   supports up to eight integrations (for example, four Modbus TCP and four KNX TCP)
•   supports up to 10,000 objects
•   provides for a 15,000 object upgrade to support up to 25,000 objects total

Guidelines for Commissioning an NxE85
Follow these guidelines when connecting to and commissioning an NxE85:
•   When you configure the NxE85, browse to the SMP UI from a computer that is not running a server-class operating
    system (OS). See the Configuring the NxE85 in the Site Management Portal UI section for details.
•   Connect the NxE85 to a reliable UPS to avoid data loss in the event of a power outage. We recommend APC®
    Smart-UPS™ SC450 (APC Part No. SC450RM1U).
•   Do not install any software applications on the NxE85 other than the applications specifically recommended by
    Johnson Controls.
•   Keep the computer operating system up to date by applying Microsoft® Windows® security updates to the NxE85.
•   Designate one ADS/ADX as a Site Director if an NxE85 resides on a Metasys site with one or more ADS/ADXs.
    If an NxE85 is applied to a site without an ADS/ADX, the NxE85 can be the Site Director for up to four other
    network engines (NCE25, NAE35, NAE45 [excluding NAE45-Lite], NAE55, NIE55, NAE85, or NIE85).
•   Set the time, date, and time zone settings for network engines in the SMP UI. Refer to the Appendix: Time Zone,
    Date, and Time Management in the NAE Commissioning Guide (LIT-1201519) for detailed procedures on
    setting time and date on an NxE.
•   If you need to reset the NxE85, simply restart the Windows operating system. The NxE85 does not support the
    Reset Device command from the SMP UI.
•   When you commission an NxE85 on a network that supports DHCP and DNS, we recommend you configure
    DHCP to assign the same IP address to the NxE85 when the IP address lease expires and after the NxE85
    device resets. If a different IP address is issued to the NxE85, the address binding to the NxE85 from other
    devices breaks.
•   The NxE85 does not use DHCP or automatic private IP addressing (APIPA) for N1 networks. Disable DHCP on
    the Network tab in the NIE85 SMP UI.
•   The NIE85 supports communication with N1 devices on one User Datagram Protocol (UDP) port.
•   Back up the NxE85 data regularly by uploading the archive database to the SCT. Frequent backups preserve
    the NxE85 data and enhance the recovery procedure in the event of a system failure.
•   Be sure to follow the power conservation options on the NxE85 computer that have been intentionally disabled.
    These settings are:
    - Under Power Schemes, the hard disk is set never to turn off and the computer is set never to enter Standby
        mode.
    - Under Hibernation, the computer is set never to enter Hibernation mode.
    - Under the Power Management tab of the network card’s properties, the option Allow the computer to turn
        off this device to save power is disabled so that the NxE85 computer's network card never turns off.

NxE85 Commissioning Guide                                                                                        4
Detailed Procedures
Commissioning Requirements
To commission an NxE85, you need the following:
•   a server computer installed with the Metasys NxE85 software and connected to the building network
•   a computer monitor, USB keyboard, and mouse (these do not have to be dedicated to the NxE85)
•   an Ethernet patch cable
•   the network values for setting up the NxE85 on the customer network
We strongly recommend using a UPS, such as the APC Smart-UPS SC450, APC Part No. SC450RM1U.

Commissioning the NxE85
1. Set up the NxE85 computer and the recommended UPS (if you have not already done so). Refer to the UPS
   manufacturer’s installation documentation.
2. Connect a monitor, keyboard, and mouse to the NxE85 (if you have not already done so).
3. Connect the NxE85 to the BAS network with an Ethernet patch cable.

    Important: Before powering on the NxE85 for the first time, you must connect the NxE85 to an active network
               on Ethernet Port 1. Failure to follow this sequence prevents the NxE85 object from appearing in
               the SMP UI navigation panel.
   Note: We support the use of only one Ethernet port; any additional Ethernet ports should have been disabled
           before the NxE85 was installed. Refer to the NxE85 Installation and Upgrade Instructions (LIT-12011530).
4. Power on the NxE85 computer.
5. Update the antivirus software and the virus definition files according to the antivirus software manufacturer’s
   instructions, and then restart the computer.
   Note: Updating the antivirus software and virus definition files requires Internet access. Some network applications
          require a proxy server or special permissions to access the Internet. Contact the network administrator
          for proxy server address, port number, or any required permissions to access the Internet.
6. Update the Windows OS. To update Windows, go to Control Panel > System and Security > Windows Update.)
   Follow the instructions at the Windows Update website and then restart the computer.
    Notes:
        •    Updating the Windows OS requires an Internet connection. Some network applications require a proxy
             server or special permissions to access the Internet. Contact the network administrator for proxy server
             address, port number, or any required permissions to access the Internet.
        •    Update the Windows OS by downloading and installing all of the critical and security patches (only) for
             the OS. Do not install any service pack updates for the OS unless the service pack update is approved
             by Johnson Controls.
7. Use the ChangeModel utility to change the NIE85 to an NAE85 if necessary. Refer to the ToggleTunnel and
   ChangeModel Technical Bulletin (LIT-12011531) for information and procedures on changing NxE85 models.
8. If you need to change the NxE85 computer name, see Changing the NxE85 Name and the Computer Name.
    If you do not need to change the NxE85 computer name, the NxE85 is now commissioned and can be configured
    in the NxE85 SMP UI. See Configuring the NxE85 in the Site Management Portal UI.

NxE85 Commissioning Guide                                                                                            5
Changing the NxE85 Name and the Computer Name
Follow the steps in this section to change the name of an NxE85. The NxE85 name and the computer name must
match (including the domain name, if used) for proper functionality. You need to change the NxE85 name and
computer name only on network applications that specify naming conventions for computers on the network.
Notes:
     •   When you follow these procedures for an NxE85 defined as the Site Director, all references used in user
         views, graphics, and control systems break. To update the user views after changing the name of the Site
         Director, open each user view in Edit mode in the SCT and save it. The Site Director portion of the reference
         updates to match the new Site Director name.
     •   If you are implementing certificate management on an existing NxE85 engine, keep in mind that adding a
         trusted certificate may require you to add a domain name to the original host name of a server and engine.
         This action requires you to rename all data in the Metasys historical databases. This renaming operation
         requires intensive database operations that significantly prolong a system upgrade. Therefore, be sure to
         allocate extra time if you are renaming historical data as part of an upgrade to the new Metasys release.
         (For details about renaming, refer to Metasys® Database Manager Help (LIT-12011202).

Changing the NxE85 Name and the Computer Name - Overview
This section is an overview of the steps to change the NxE85 name and computer name. Follow all the steps in this
document in the correct order to ensure success.
To change the NxE85 name and the computer name:
1. Prepare the computer. See Preparing the Computer.
2. Create a new archive. See Creating a New Archive.
3. Download the NxE85. See Downloading the NxE85.
4. Test the NxE85. See Testing the NxE85.

Preparing the Computer
1.   Verify that the time zone, date, and time setting are correct in the SMP UI.
     Note: Time Zone, Date, and Time must be set in the SMP UI. Do not use the Windows OS time dialog box to
            set time zone, date, or time on the NxE85.
2.   Write down the name you want for the NxE85. Note the case of the name. The NxE85 name must:
     • begin with a letter
     • contain a maximum of 15 characters
     • contain only letters A to Z, numbers 0 to 9, and hyphens
3.   In Control Panel, select System and Security > System.
4.   Click Change Settings. The System Properties dialog box appears.
5.   Select the Computer Name tab.
6.   Write down the original computer name as it appears in the Full computer name field. Note the case of the
     name and also include the domain name, if present. See Figure 3.

NxE85 Commissioning Guide                                                                                           6
                                          Figure 3: System Properties Dialog Box

7.   Click OK to close the System Properties dialog box.
8.   Log in to the NxE85 computer to verify that the NxE85 is running.
     Note: Ignore the label for the NxE85 that appears in the Navigation Tree.
9.   Exit the NxE85.
10. Go to Creating a New Archive.

Creating a New Archive
1.   Log in to the SCT.
2.   Select Item > New Archive.
3.   In the New Archive Wizard window, click Create.
4.   When prompted to create a new site, click Yes.
5.   Follow the wizard instructions to create a new site. In the Configure step, verify the Time Zone attribute exactly
     matches the time zone for the computer that you verified in Step 1 of Preparing the Computer. If the time zone
     does not match that of the computer, select the correct time zone.
     Note: The order of the time zones in the Metasys software does not match the order in which they are presented
             in the Windows operating system.
6.   Finish the rest of the steps in the wizard.
7.   When the Create Device? window appears, select Supervisory Device from the drop-down selection box.
     Click OK.
8.   Follow the wizard instructions to create a new NxE85 device. On the Identifier screen, enter the name of the
     original computer name from Step 2 of Preparing the Computer, making sure you use the same capitalization
     and include the domain name, if present. Finish the rest of the steps in the wizard.
    When you are finished creating the new device, in the navigation tree, the name of the server should match the
    original computer name.
9. On the Tools menu, select Manage Archive.
10. On the Action screen, select Update From Device as the type.
11. Click Next and follow the wizard instructions.
12. On the Site Login screen, click Test Login. Finish the steps to start the upload process.
     Note: If the upload is not successful, restart the computer and go to Step 1 in this section.

NxE85 Commissioning Guide                                                                                            7
13. When upload Completion Status reads OK, right-click the server in the navigation tree and select Rename. The
    Rename window appears.
14. In the New Name field, enter the desired NxE85 name from Step 2 of Preparing the Computer (including the
    domain name if used).
15. Click OK.
16. Exit the SCT. Do not download or make other name changes in the SCT.
17. Go to Downloading the NxE85.

Downloading the NxE85
1.   Log in to the SCT.
2.   Select the Metasys server in the navigation tree.
3.   On the Tools menu, click Manage Archive.
4.   On the Action screen, select Download to Device as the type.
5.   Click Next and follow the wizard instructions.
6.   On the Site Login screen, click Test Login. Continue to follow the wizard instructions.
7.   On the Device Change screen (Figure 4), select the Use this option to rename a device via download check
     box and enter the original computer name from Step 6 in Preparing the Computer. The computer name is
     case-sensitive.
                                       Figure 4: Device Change Screen in the SCT

8. Click Next.
9. Click Finish in the Summary screen to begin the device download.
10. When download Completion Status reads OK, exit the SCT. The rename is complete.
11. Go to Testing the NxE85.

Testing the NxE85
1.   Log in to the NxE85.
2.   On the View menu, select Extended Labels.
3.   Double-click the server in the navigation tree.
4.   On the Focus tab, click Edit.
5.   In the Name attribute, enter the desired NxE85 name. Note the case of the name.
6.   Click Save.
7.   Right-click the navigation tree tab, and select Refresh.
8.   Exit the NxE85.

NxE85 Commissioning Guide                                                                                      8
     The NxE85 name and computer name change is complete. Go to Configuring the NxE85 in the Site Management
     Portal UI to finish configuring the NxE85.

Configuring the NxE85 in the Site Management Portal UI
You can configure the NxE85 by connecting a computer with the Windows® Internet Explorer® web browser or the
Apple® Safari® web browser to the network and browsing to the NxE85 SMP UI. You use the Launcher application
to reach the login screen for the SMP UI. You must install the Launcher if it is not already installed on your computer.
Refer to the Launcher Installation Instructions (LIT-12011783).
The Launcher is a software application installed on each client computer that lets you access any Metasys server
or supervisory engine on the building network, regardless of its software version. Its purpose is to remove the
dependency on the public Java® Runtime Environment (JRE) for the SMP UI at Release 6.0 or later by placing a
private edition of the JRE on the client computer. For details, refer to the Launcher Installation Instructions
(LIT-12011783).
Refer to the NAE Commissioning Guide (LIT-1201519) for detailed procedures on connecting to the NxE85 in
different network scenarios.
To configure the NxE85 in the SMP UI, follow these steps:
1.   Enter your user name and password in the login window of the NxE85 SMP UI.
     Notes:
          •  All NxE85s install with the same initial login user name and password. The initial login user name is
             MetasysSysAgent and is not case sensitive. For the MetasysSysAgent default password, contact your
             local Johnson Controls® representative.
         • For added security, the user name is obscured as you type it.
2.   Click Login.
     Note: When you log in for the first time, you must change the account password immediately.
3.   Click OK when the Password has expired message appears. The Change Password dialog box appears.

      The following password rules are enforced for English (en_US) users only. The password rules are as follows:
      •   The password must include a minimum of 8 characters and a maximum of 50 characters.
      •   The password cannot include spaces or include a word or phrase that is in the Blocked Words list.
      •   The password and the username cannot share the same three consecutive characters.
      •   The password must meet the four following conditions:
          - Include at least one number (0–9)
          - Include at least one special character (-, ., @, #, !, ?, $, %)
             Note: Only the special characters listed above can be used; all other special characters are invalid.
          - Include at least one uppercase character
          - Include at least one lowercase character
4.   Type the old password, and then type your new password twice. Make sure to follow the password rules when
     you create your new password.
5.   Click OK. The message Successfully changed the password appears.
6.   Click OK. The Terms and Conditions window appears.
7.   Click Accept to accept the terms and conditions. The SMP UI opens (Figure 5).

NxE85 Commissioning Guide                                                                                             9
                                               Figure 5: NxE85 in the SMP UI

     Note: The user name in the upper right corner of the SMP UI is partially obscured for added security (Figure
             5).
8.   Double-click the NxE85 in the navigation tree. Check for and establish the required Computer Name (host name)
     value on the Network tab. Establish other required network values on the Network tab. Set the DHCP value to
     False if DHCP is not required on the network. Refer to the Establishing the NAE Network Parameters section
     of the NAE Commissioning Guide (LIT-1201519) for detailed procedures.
9.   Establish the time zone, date, and time settings in the NxE85 NIE89 SMP UI. Refer to Appendix: Time Zone,
     Date, and Time Management in the NAE Commissioning Guide (LIT-1201519) for detailed procedures on setting
     time and date on an NxE85
     Note: Time Zone, Date, and Time must be set in the SMP UI. Do not use the Windows OS time dialog box to
           set the time zone, date, or time on the NxE85.
10. Establish the Site Director and Object Name for the NxE85 on the Focus tab. Refer to the Establishing Basic
    NAE Parameters in the Focus Screen section of the NAE Commissioning Guide (LIT-1201519) for detailed
    procedures.
     The NxE85 is now configured for the network and ready for Auto-Discovery (of BAS devices) and site configuration
     using the SCT.

Licensing the NxE85
The NxE85 requires an active, valid license. A license becomes active when you enter your Site Key in the License
Activator application and click Activate. A license is valid if the software is running within the maximum object count
for which it is licensed. The following licensing scenarios affect software operation:
•    During NxE85 startup, the Metasys system checks for an active license. If an active license is not found, the
     NxE85 Metasys software, including Ethernet and trunk communications to the Metasys system, automatically

NxE85 Commissioning Guide                                                                                           10
    shuts down. The NxE85 Metasys software does not permit you to log in, and a message appears that indicates
    the product is not licensed.
•   During operation, the Metasys system periodically checks the product license. If the license has been deactivated
    or if the license becomes invalid because the object count limit has been exceeded, the NxE85 software continues
    to run, but displays a warning message every 10 minutes to indicate that the product license is inactive or invalid.
For additional licensing information, refer to the NxE85 Installation and Upgrade Instructions (LIT-12011530) and
the Software License Activator Technical Bulletin (LIT-1201654).

Related Documentation
Table 1: NxE85 Related Documentation
For Information On                                               See Document
Installing or Upgrading the NxE85 Software, Licensing            NxE85 Installation and Upgrade Instructions (LIT-12011530)
NxE85 Software
Commissioning the NIE89 for the Modbus Protocol                  NIEx9 Commissioning for Modbus Vendor Integration Application
                                                                 Note (LIT-12011928)
Commissioning the NIE89 for the M-Bus Protocol                   NIEx9 Commissioning for M-Bus Vendor Integration Application
                                                                 Note (LIT-12011927)
Commissioning the NIE89 for the KNX Protocol                     NIEx9 Commissioning for KNX Vendor Integration Application
                                                                 Note (LIT-12011926)
Changing an NIE85 to an NAE85                                    ToggleTunnel and ChangeModel Technical Bulletin
                                                                 (LIT-12011531)
Connecting, Accessing the SMP UI, Commissioning,            NAE Commissioning Guide (LIT-1201519)
Troubleshooting, and Enabling a Serial Printer on a Network
Automation Engine
Setting up Secure Communication with Trusted Certificates Metasys® SCT Help (LIT-12011964)1

Installing the Launcher Application                              Launcher Installation Instructions (LIT-12011783)
Creating, Editing, and Loading Archive Databases with the Metasys® SCT Help (LIT-12011964)1
System Configuration Tool (SCT)
Daily Operation of the Metasys System Network, Navigating Metasys® SMP Help (LIT-1201793)1
the SMP UI, Monitoring and Controlling BAS Networks, and
Connecting to Cloud-Based Applications
Integrating BACnet IP Devices into the Metasys System            BACnet System Integration with NAE Technical Bulletin
Network                                                          (LIT-1201531)
Migrating N1 Networks to the Metasys System Network              N1 Migration with the NIE Technical Bulletin (LIT-1201535)
General Network and Information Technology Definitions Network and IT Guidance Technical Bulletin (LIT-12011279)
and Concepts
Security Issues, Including Adding Users and Roles to the Security Administrator System Technical Bulletin (LIT-1201528)
System, and Configuring Standard and Basic Access Modes

1   This LIT number represents a print-friendly version of the Help.

NxE85 Commissioning Guide                                                                                                     11
NxE85 Technical Specifications
Table 2: NAE85 Software System Recommendations for Installation/Upgrade
Recommended              Intel® Xeon® E5506, 2.13 GHz, 4 MB Cache
Computer Platform
                         2 x 160 GB 7.2K , 8.9 cm (3.5 in.) Cabled
                         3 Gbps, RAID 1 configuration with add-in SAS6/iR (SATA/SAS Controller)
Recommended              2 GB RAM minimum
Memory
Hard Disk                160 GB minimum
Supported Operating Windows® Server® 2016 (64-bit)
Systems and Software
                     Windows® Server® 2012 R2 with Update 1 (64-bit)
                         Windows® Server® 2012 (64-bit)
                         Note:    The NAE85 software requires two Windows components: Microsoft .NET Framework Version
                                  3.5 SP1 and Microsoft .NET Framework Version 4.6.1.
Supported Operating      Windows® 10 Pro and Enterprise Editions with Anniversary Update (version 1607) (64-bit)
Systems for Metasys
                         Windows® 8.1 Pro and Enterprise Editions with Update 1 (64-bit)
Client Computers
                         Windows® 7 Professional, Enterprise, and Ultimate Editions with SP1 (64-bit)
                         Windows® 7 Professional, Enterprise, and Ultimate Editions with SP1 (32-bit)
                         Apple® macOS® 10.12 Sierra
                         Apple® OS X® 10.11 El Capitan
                         Notes:
                             •    Apple® operating systems are supported for Metasys client computers only.
                             •    In Apple® OS X®, you cannot view Graphics+ graphics in the Site Management Portal UI.
Internal Optical Drive   DVD ROM, SATA
Recommended              Symantec Endpoint Protection version 12
Antivirus Software
Supported Web            Windows® Internet Explorer® 11.0.9600.18449 Update version 11.0.35 or later
Browser Software for
                         Note:    In Internet Explorer 11, select the Use Microsoft compatibility lists option, found under Tools
Metasys Client
                                  > Compatibility View Settings, to ensure that websites appear and function correctly.
Computers
                         Google® Chrome™ version 54 or later
                         Apple® Safari® 10 or later
                         (Other browsers, such as Mozilla® Firefox®, may also be used but are not fully supported.)
                         Note:    You use the web browser to download the Launcher application. After you install the Launcher
                                  application, you use the Launcher, not the web browser, to log in to Metasys Site Management
                                  Portal (SMP) UI.
Supported Virtual        Microsoft Hyper-V™, VMware®
Environments
Network                  Network Interface: 1 Gbps Ethernet network interface card connects at 10 Mbps, 100 Mbps, or 1 Gbps
Communication            (100 Mbps or better recommended)
Recommended Data         UPS for NxE85 model: APC Smart-UPS SC 450VA, 280 W, 120 VAC input/output, National Electrical
Protection               Manufacturers' Association (NEMA) 5-15R output connections, OEM Part No. SC450RM1U

NxE85 Commissioning Guide                                                                                                      12
Table 3: NxE85 Software System Recommendations for Installation/Upgrade
Product Code Number            MS-NXE85SW-0 Network Integration Engine Software for 10,000 objects (new projects
                               only software)

Recommended Computer           Intel Xeon E5506, 2.13 GHz, 4 MB Cache
Platform
                               2 x 160 GB 7.2K SATA, 8.9 cm (3.5 in.) Cabled
                               3 Gbps, RAID 1 configuration with add-in SAS6/iR (SATA/SAS Controller)
Recommended Memory             8 GB RAM minimum
Hard Disk                      160 GB minimum
Supported 64-bit Operating     •   Windows® Server® 2016 (64-bit)
Systems and Software           •   Windows® Server® 2012 R2 with Update 1 (64-bit)
                               •   Windows® Server® 2012 (64-bit)
                               Note:   Microsoft .NET Framework 3.5 Service Pack (SP) 1 and Microsoft .NET Framework
                                       4.6.1 are required for any of the operating systems.
Supported Operating Systems    Windows® 10 Pro and Enterprise Editions with Anniversary Update (version 1607) (64-bit)
for Metasys Client Computers
                               Windows® 8.1 Pro and Enterprise Editions with Update 1 (64-bit)
                               Windows® 7 Professional, Enterprise, and Ultimate Editions with SP1 (64-bit)
                               Windows® 7 Professional, Enterprise, and Ultimate Editions with SP1 (32-bit)
                               Apple® macOS® 10.12 Sierra
                               Apple® OS X® 10.11 El Capitan
                               Apple OS X 10.10 Yosemite
                               Note:   Apple operating systems are supported for Metasys client computers only. Also, in
                                       Apple OS X, you cannot view Graphics+ graphics in the Site Management Portal
                                       UI.
Internal Optical Drive         DVD ROM, SATA
Supported Web Browser          Windows® Internet Explorer® 11.0.9600.18449 Update version 11.0.35 or later
Software for Metasys Site
                               Note:   In Internet Explorer 11, select the Use Microsoft compatibility lists option, found
Management Portal Client
                                       under Tools > Compatibility View Settings, to ensure that websites appear and
Computers
                                       function correctly.
                               Google® Chrome™ version 54 or later
                               Apple® Safari® 10 or later
                               Other browsers, such as Mozilla® Firefox®, may also be used but are not fully supported.
Supported Virtual Environments Microsoft Hyper-V™, VMWare®
Network Communication          Selectable Network Interface (if computer has multiple network cards, during NxE85
                               installation, select the network card that was configured for Metasys system use before
                               installation)
                               Ethernet network interface card 10/100/1000 Mbps (100 Mbps or better recommended)
Recommended Data Protection Uninterruptible power supply (UPS)
                               Smart-UPS SC 450VA, 280 W, 120 VAC input/output, NEMA 5-15R output connections,
                               OEM Part No. SC450RM1U

                                                                                           Building Technologies & Solutions
                                                                                   507 E. Michigan Street, Milwaukee, WI 53202
                                                Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
                                         All other marks herein are the marks of their respective owners.© 2017 Johnson Controls

Published in U.S.A.                                                                                   www.johnsoncontrols.com
NxE85 Commissioning Guide                                                                                                    13