N2 Field Equipment Controllers and Related Products
Product Bulletin
Code No. LIT-12011808
Software Release 6.0
Issued April 2, 2013
Supersedes January 30, 2013
Our wide variety of network sensor models provides
Overview options for measuring and displaying zone temperature,
The Metasys® System N2 Field Equipment Controller occupancy detection, duct temperature, zone humidity,
family comprises a group of versatile controllers and carbon dioxide (CO2) level, setpoint adjustments, and
accessories designed to monitor and operate a wide
discharge air temperatures. The VMA1832 controller's
variety of commercial HVAC equipment and can be
embedded capabilities, in addition to its modular
networked together using the N2 Open Communications
accessories, make it well-suited as a replacement for
protocol. This family of controllers includes the VMA1832
legacy VMA14xx Series Controllers.
controller, which can be integrated to any supervisory
controller capable of managing N2 Open networks and Figure 1: VMA1832 Controller
devices, such as the Network Communication Module
(NCM) and Network Automation Engine (NAE).
The VMA1832 controller features an advanced design
that provides optimum performance and easy access to
power, network, and field terminations. These controllers
come with 32-bit microprocessors that meet and exceed
ever demanding industry standards.
Note: A software download that allows VMA1832
controllers to communicate as
BACnet® Multidrop Serial Bus/Token Passing
(MS/TP) devices will be available at a future date.
This functionality provides a differentiated and
cost-effective platform upgrade path for existing
customers who are looking for a gradual upgrade
strategy and should be considered during
installation of the controller.
Features and Benefits
Features Benefits
N2 Open Communications Protocol Can be integrated into existing N2 networks, which extends the life of the existing
Metasys system installations.
Standard Software Platform Uses a common software design to support use of a single tool for control
applications, commissioning, and troubleshooting to minimize technical training.
Auto Tuned Control Loops Reduce commissioning time, eliminate change-of-season re-commissioning,
and reduce wear and tear on mechanical devices.
Universal Inputs and Binary and Allow multiple signal options to provide input/output flexibility.
Configurable Outputs
Optional Local Controller Display/Keypad Allows convenient monitoring and adjusting capabilities at the local device.
(DIS1710)
N2 Field Equipment Controllers and Related Products Product Bulletin 1
Integration to the Metasys The Simulation mode allows you to review, run, or
simulate the application logic as if you were
System Supervisory Devices commissioning a live system. You can make adjustments
The VMA1832 controllers are designed to integrate into to setpoints, inputs, or sensors during a simulation
the Metasys system by connecting and communicating session to validate the logic before or after assigning the
directly to the NAE and NCM. With this integration, the configuration to a specific controller.
building operator can view the N2 Field Equipment
Controllers directly from the Metasys system user The Commissioning mode manages the downloading
interface. In addition, the operator can view controller of files to the controllers through the Wireless
information locally with the local display. Commissioning Converter (MS-BTCVT) between your
laptop and the controllers.
N2 Protocol Compatible After downloading the controllers, you can use the CCT
The Metasys system field controllers communicate with Commissioning mode to validate the sensor and control
the supervisor using the N2 Open Communications point interfaces and adjust key setpoints and setup
protocol. They communicate with Netsensors on the SA parameters (Figure 3).
Bus using the BACnet MS/TP protocol.
Figure 3: CCT User Interface
Controller Configuration Tool
The Controller Configuration Tool (CCT) is used to
configure, simulate, and commission the VMA1832
controllers on an N2/FC bus.
The Configuration mode allows you to select a number
of mechanical and control logic options through System
Selection Trees for typical air handling, terminal unit, VAV
box, and central plant mechanical systems (Figure 2).
When required, you can customize the standard logic
provided by the system selection process to meet your
specialized control logic requirements. Configuration
mode also allows you to customize certain display options
available to controllers that use a local controller display.
Figure 2: Mechanical Selection in CCT
For VAV applications, CCT features an optional box flow
test to automatically exercise the VAV box to ensure
correct mechanical installation and proper configuration
of the key flow setup parameters. Additionally, the
Metasys system provides multiple configurations of room
network sensors and a handheld VAV balancing tool that
can be used to perform VAV balancing tasks.
In addition, the Commissioning wizard has a Balancer
tab for VAV applications to easily auto calibrate VAV
boxes and set flow constants in one location.
A Commissioning mode only version of the CCT software
is available to the Johnson Controls® branch offices for
jobs or individuals having only commissioning tasks (for
example, balancing contractors). The Configuration and
Simulation modes are disabled in the CCT
Commissioning software.
N2 Field Equipment Controllers and Related Products Product Bulletin 2
The Handheld VAV Balancing Tool is lightweight and
Sensor Options portable. It can plug into any model of network sensor to
The NS Series Network Zone Sensors can be adapted access the VAV controller.
to function directly with Metasys system VMA1832
controllers. Several models of network zone sensors Figure 5: Handheld VAV Balancing Tool
monitor room temperature. Options are available to also
monitor zone humidity, carbon dioxide (CO2), local
temperature setpoint adjustments, occupancy, and other
variables. This data is transmitted to a field controller on
the SA Bus.
The VMA1832 controller is able to reuse existing TE-6xxx
Series Sensors from existing VMA14xx installations using
an adapter included with the VMA1832 controller.
TMZ-1600 applications require use of a new sensor when
installing a VMA1832. The VMA1832 controller can be
used with a WRZ Series Wireless Sensor and a
WRZ-7860 Series One-to-One Receiver. The VMA1832
can also reuse existing TE-700 Series Sensors from
existing VMA14xx installations. The VMA1832 also
supports the TE-730 Series Sensor.
Figure 4: NS Series Network Zone Sensors Applications
The VMA1832 controllers can be configured for both
single-duct and dual-duct VAV box applications. The
VMA1832 controllers require an additional damper
actuator and Differential Pressure Transducer (DPT)
sensor for dual-duct or supply/exhaust applications.
Note: Connecting an Input/Output Module (IOM) to the
VMA1832 via the SA Bus connection is not
supported.
Hardware
The VMA1832 controllers are enclosed in a plastic
housing with an attached metal shield. The controller,
transducer, and actuator are all integrated into a single
enclosure.
The VMA1832 controllers’ housing may eliminate the
need for a separate enclosure for the VMA. Check code
requirements for appropriate applications.
Handheld VAV Balancing Tool The N2/FC Bus has removable screw terminals and the
The VAV Balancing Tool allows you to easily adjust and SA Bus has spade terminals. Input/Output (I/O)
set the required parameters for VAV applications that connections to the VMA1832 are easy-to-use spade lugs.
reside on the Metasys system VMA1832 controllers. Screw terminal I/O connectors are available as optional
accessories.
The VAV balancing parameters appear on the tool’s LCD.
A dial and two buttons let you navigate through intuitive The differential pressure sensor in the VMA1832
menus to balance the VAV box. The menus are controllers provides consistent flow readings with minimal
customized to the type of application residing in the drift and requires minimal auto-zero calibration. There
controller. The balancing operation features an adjustable are no filters to change, which helps to ensure very close
time-out parameter that returns the tool and controller to tolerance to published accuracy.
normal operation if you leave the controller in balancing LEDs, visible through the housing, indicate the status of
mode. power to the controller, communications status, and a
number of diagnostic indicators.
N2 Field Equipment Controllers and Related Products Product Bulletin 3
The housing dimensions of the VMA1832 controllers
Installation (165 x 125 x 73 mm [6.5 x 4.92 x 2.9 in.]) meet industry
Field mounting the VMA1832 controller is straightforward. mounting requirements and make the controllers easy to
The VMA1832 controllers require minimal wiring and are handle.
mounted to the terminal box using a single sheet metal
screw and a single set screw to lock the actuator to the You can make the controller address unique for each
damper shaft. The set screw has a self-locking cup point VMA using the DIP switches that are accessible through
end to resist loosening due to vibration. the VMA controller housing.
The actuator coupling is serrated, providing additional The AC power input is isolated from the DC inputs and
damper shaft grip and minimizing shaft slippage during outputs by an internal transformer. This arrangement
operation. The coupling accommodates shafts from eliminates polarity issues, ground loops, and the need
10 mm (3/8 in.) square and up to 13 mm (1/2 in.) diameter for a separate isolation transformer. Power, N2
round. A gear release lever allows easy resetting of the communications, and binary outputs are all separately
damper to full open or full close. isolated.
Models and Capabilities
Table 2 lists the point type counts for the VMA1832
controllers.
Selection Charts
Table 1: VMA1832 Features and Point Type Counts per Model
Point Types Signals Accepted VMA1832
Modular Jack 8-pin SA bus supports analog
non-communicating sensor.
Universal Input (UI) Analog Input, Voltage Mode, 0–10 VDC 3
Analog Input, Resistive Mode, 0–2k ohm,
RTD (1k NI [Johnson Controls], 1k PT,
A998 SI), NTC (10k Type L, 2.252k
Type 2)
Binary Input, Dry Contact Maintained
Mode
Binary Output (BO) 24 VAC Triac 3
Configurable Output (CO) Analog Output, Voltage Mode, 0–10 VDC 2
Binary Output Mode, 24 VAC Triac
Integrated Actuator Internal 1
Integrated Flow Sensor Internal 1
Zone Sensor Input On SA Bus
1 Up to 4 NS Series Network Zone sensors
Up to 9 WRZ sensors when using the
ZFR1811 wireless router configuration and
up to 5 WRZ sensors when using the
one-to-one WRZ-78xx wireless
configuration.
1 A total of 10 SA bus addresses maximum can be used in a single VMA controller.
Table 2: Ordering Information
Product Code Number Description
MS-VMA1832-0 Replacement Integrated VAV Controller/Actuator/Pressure Sensor, N2/FC Bus, and SA Bus
(32-bit Processor)
N2 Field Equipment Controllers and Related Products Product Bulletin 4
Ordering Information Repair Information
Contact your Johnson Controls representative to order If the Metasys system field equipment controllers, network
Metasys field controllers and related products. See Table sensors, or any related product fails to operate within its
2 and Table 3 for product code numbers and product specifications, replace the unit. For a replacement device,
descriptions. contact the nearest Johnson Controls representative.
Accessories (Order Separately)
Table 3: VMA1832 Controller Accessories (Order Separately)
Product Code Number Description
Y64T15-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 92 VA, Foot Mount, 30 in.
Primary Leads and 30 in. Secondary Leads, Class 2
Y65A13-0 Transformer, 120 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AS), 8 in.
Primary Leads and 30 in. Secondary Leads, Class 2
Y65T42-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Hub Mount (Y65SP+),
8 in. Primary Leads and Secondary Screw Terminals, Class 2
Y65T31-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount (Y65AR+),
8 in. Primary Leads and Secondary Screw Terminals, Class 2
AS-CBLVMA-1 Cable Adapter, 8-pin Female Socket to 6-Pin Male Jack (Bulk Pack of 10)
AP-TBK4FC-0 Replacement MS/TP FC Bus Terminal, 4-Position Connector, Blue, Bulk Pack (10 pack)
AP-TBK1002-0 Removable 2-Position Screw Terminal Kit (100 Pieces)
AP-TBK1003-0 Removable 3-Position Screw Terminal Kit (100 Pieces)
AS-CBLVMA-2 Cable Adapter, 8-pin Female Socket to 8-pin Male Jack with 6-Pin Female Socket for Wireless
Commissioning Converter (Bulk Pack of 10)
MS-BTCVT-1 Wireless Commissioning Converter with Bluetooth® Technology
MS-DIS1710-0 Local Controller Display/Keypad
NS-WALLPLATE-0 Network Sensor Wall Plate (80 mm by 80 mm [3.15 in. by 3.15 in.] square), used with an
80 mm by 80 mm (3.15 in. by 3.15 in.) network sensor and must be mounted to a 0.6 m by
1.2 m (2 ft by 4 ft) wall box
TL-BRTRP-0 Portable BACnet IP to MS/TP Router
NS Series Network Sensors Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specific sensor
model descriptions.
Technical Specifications
Table 4: VMA1832 Controllers
Product Code Numbers MS-VMA1832-0: Cooling with Reheat and Fan Control
Supply Voltage 24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, Power Supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
Power Consumption 10 VA typical, 14 VA maximum
Note: The VA ratings do not include any power supplied to the peripheral devices
connected to Binary Outputs (BOs) or Configurable Outputs (COs), which can
consume up to 12 VA for each BO or CO for a possible total consumption of an
additional 60 VA (maximum).
Ambient Conditions Operating: 0 to 50°C (32 to 122°F)
Storage: -40 to 70°C (-40 to 158°F)
Terminations Inputs/Outputs, SA bus, and Supply Power: 6.3 mm (1/4 in.) Spade Lugs
N2/FC Bus Pluggable Screw Terminal Block
TSTAT Modular Port: RJ-45 8-Pin Modular Jack
N2 Field Equipment Controllers and Related Products Product Bulletin 5
Table 4: VMA1832 Controllers
Controller Addressing DIP switch set
N2 Open Protocol: Valid field controller device addresses 1–253
BACnet MS/TP: Valid field controller device addresses 4–127
(Device addresses 0–3 and 128–255 are reserved and not valid field controller addresses.)
Communications Bus N2 Open Protocol:
N2/FC Bus: 1.5 mm (18 AWG) standard 3-wire, twisted, shielded cable recommended
between the supervisory controller and field controllers
BACnet MS/TP Protocol:
SA Bus: 0.6 mm (22 AWG) stranded, 4-wire (2-twisted pairs) shielded cable recommended
from the VMA controller for network sensors and other sensor/actuator devices; includes
1
a terminal to source 15 VDC supply power from VMA to SA Bus devices
Input and Output Capabilities 3 - Universal Inputs: Defined as 0–10 VDC, 4–20 mA, 0–600k ohm, or Binary Dry Contact
3 - Binary Outputs: Defined as 24 VAC Triac (internal power source)
2 - Configurable Outputs: Defined as 0–10 VDC or 24 VAC Triac BO
Analog Input/Analog Output Analog Input:15-bit resolution on UIs
Accuracy
Analog Output: 0–10 VDC ± 200 mV
Differential Pressure Sensor Range: -1.5 inches to 1.5 inches H20
Performance Characteristics:
Total Error Band: ±1.3% Full Span Maximum
Accuracy: ±0.25% Full Scale Best Fit
Actuator Rating 4 N·m (35 lb·in) minimum shaft length = 44 mm (1-3/4 in.)
Mounting Mounts to damper shaft using single set screw and to duct with single mounting screw
Dimensions 165 x 125 x 73 mm (6.5 x 4.92 x 2.9 in.)
(Height x Width x Depth) Center of Output Hub to Center of Captive Spacer: 135 mm (5-5/16 in.)
Weight 0.65 kg (1.45 lb)
Compliance United States:
UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment; Suitable
for use in other environmental air space (plenums) in accordance with Section 300.22(C)
of the National Electric Code.
FCC Compliant to CFR47, Part 15, Subpart B, Class A.
Canada:
UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment;
Industry Canada Compliant, ICES-003
Europe:
CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Australia and New Zealand:
C-Tick Mark, Australia/NZ Emissions Compliant.
1 For more information, refer to the N2 Communications Bus Technical Bulletin (LIT-636018).
N2 Field Equipment Controllers and Related Products Product Bulletin 6
North American Emissions Compliance VMA1832 Series Controllers
United States Emissions Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area may cause harmful
interference, in which case the users will be required to correct the interference at their own expense.
Canadian Emissions Compliance
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du
Canada.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2013 Johnson Controls, Inc.
Published in U.S.A. www.johnsoncontrols.com
N2 Field Equipment Controllers and Related Products Product Bulletin 7Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.