FANs 125, 121
                                                                                       Temperature Controls Section          A
                                                                                                Installation Bulletin
                                                                                                          Issue Date         1199

                                              INSTALLATION BULLETIN

            MS2 Two Stage Electronic Temperature Control

                                                               W iring
 IMPORTANT:            All MS2 controls are designed for           !
                       use only as operating controls.                  WARNING: Risk of Electrical Shock.
                       Where an operating control                                Disconnect power supply before
                       failure would result in personal                          making electrical connections to
                       injury or loss of property, it is the                     avoid possible electrical shock or
                       responsibility of the installer to                        equipment damage.
                       add devices (safety, limit
                       controls) or systems (alarm,
                       supervisory systems) that protect       Follow these wiring guidelines:
                       against, or warn of, control
                       failure.                                   All wiring must conform to the National Electric
                                                                   Code and local regulations.
                                                                  Make all wiring connections using adequate gauge
Refer to the MS Series Multi-Stage Electronic                      copper conductors only. Connectors are rated for
Temperature Controls Product Bulletin, LIT-125198, for             14-22 AWG wiring.
necessary information on operation and performance                        Refer to Rating Table for more information.
specifications for this product.                                       Internal to Control
                                                                                                        Terminal Not Used

                                                                         C1         C2           V1 V2 D SC
M    ounting
                                                                                                         Binary
                                                                        Stage      Stage 
The MS2 control is not position-sensitive but should be                                            Power Input    Process
mounted for convenient wiring and adjustment.                                                      Supply         Sensor
                                                                                               Binary and Sensor Common
To mount the DIN Rail Mount version, install the DIN
rail where appropriate. Snap the control onto the rail in                Figure 1: MS2 Panel Mount Wiring
position.
To mount the Panel Mount version, ensure that there is                 Sensor Common Binary
                                                                                     Input
sufficient space behind the panel. At least                            Process                      Binary        Stage 
2-3/4 inches (70 mm) are needed. Make a cutout                         Sensor                       Common
1-3/16 by 2-13/16 inches (29 by 71 mm). Remove                                  S1 SC D CD                        C2 
retaining clip from control. Insert the control into the
hole. Install retaining clip and adjust for tightness.                                             Internal to Control
                                                                           V1 V2          C1   
                                                                                                   Terminal Not Used
                                                                            Power     Stage 
                                                                            Supply
                                                                               Refer to Rating Table for more information.

                                                                        Figure 2: MS2 DIN Rail Mount Wiring

© 1999 Johnson Controls, Inc.                                                                                                       1
  Part No. 24-7664-1725, Rev. A                                                                           www.johnsoncontrols.com
  Code No. LIT-125209
                                                           S etting Up the Stage Control
Use this table, with function So, to compensate for long   To lock/unlock the unit for programming
sensor wire.                                                                 Press the Enter, Up, and Down buttons
                                                                             simultaneously and hold until “- - -” is displayed.
Table 1: Sensor Wire Size and Length                                         Hold for about 10 seconds until the current
                                                                             temperature is displayed. This toggles the
 18 AWG        20 AWG        22 AWG           Offset                         keypad between locked and unlocked.
 300-599 ft    190-374 ft    120 -239 ft      1F°
 91-183 m      58-114 m      36-73 m          1C°          To run the self test procedure
 600-899 ft    375-564 ft    240-349 ft       2F°           IMPORTANT: Disconnect loads before beginning self-test
 183-274 m     114-172 m     73-107 m         2C°                      procedure. Cycle power to resume normal
 900+ ft       565+ ft       350+ ft          3F°                      operation.
 274+ m        172+ m        107+ m           3C°
                                                                             Press the Up and Down buttons in sequence,
                                                                             and hold for 5 seconds.
Table 2: Rating Table
 Rating Category               120     240          24
                                                           To select the mode of operation
                               VAC     VAC          VDC
                                                                             1. Press and hold the Enter and Down buttons
 Horsepower                    1/4     1/2          -                           simultaneously for approximately 7 seconds.
 Full Load Amperes             5.8     4.9          -
 Locked Rotor Amperes          34.8    29.4         -                        2. Press the Up or Down button until the desired
 Inductive (non-motor)         8       8            8                           setting is shown.
 Amperes                                                                         2d = Direct (cool)
 Pilot Duty VA                 275     450          -                            2r = Reverse (heat)
Relay outputs must not exceed 20 amperes total                                   2b = Deadband
                                                                                 2i = Independent Setpoint
connected load. Power supply is 24 VAC.
                                                                             3. Press the Enter button to save the new mode

F CC Compliance                                                                 of operation.

This equipment has been tested and found to comply         To change the setpoint (modes b, d, and r only)
with the limits for a Class A digital device pursuant to                     1. Hold the Enter button down for 3 seconds.
Part 15 of the FCC Rules. These limits are designed to                          The display will change to show the setpoint.
provide reasonable protection against harmful                                2. Press the Up or Down button until you reach
interference when the equipment is operated in a                                the new setpoint.
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if                         3. Press the Enter button to save the new
not installed and used in accordance with the                                   setpoint.
instruction manual, may cause harmful interference to      Note: If you do not press the Enter button after selecting the new
radio communications. Operation of this equipment in             setpoint, it is not saved. The control reverts to old setpoint.
a residential area is likely to cause harmful
                                                           To program other settings (modes b, d, r only) or to
interference, in which case the user will be required to
                                                           program setpoints and settings (mode i only)
correct the interference at his/her own expense.
                                                                             1. Hold the Enter button down for about
                                                                                10 seconds. The display will change to HY.
C anadian DOC Compliance                                                        (The display shows S1 if in Mode i.)
                                                                             2. Press the Up or Down button until the desired
This digital apparatus does not exceed the Class A                              setting is shown.
limits for radio noise emissions from digital apparatus
set out in the Radio Interference Regulations of the                         3. Press the Enter button. The setting’s current
                                                                                value is displayed.
Canadian Department of Communications.
                                                                             4. Press the Up or Down button until the desired
D isplay                                                                        value is shown.

Press Up and Down buttons to scroll through process                         5. Press the Enter button to save the new value.
temperature and binary input status (On or OF). After                           After 10 seconds of inactivity, the display will
15 seconds of inactivity, the display shows the process                         return to its normal function.
temperature.                                               Note: If you do not press the Enter button after selecting the new

2   A—MS2 Two Stage Electronic Temperature Control Installation Bulletin
value, it is not saved. The control reverts to the old value.

                                          A—MS2 Two Stage Electronic Temperature Control Installation Bulletin   3
Table 3: Functions and Settings
Mode                              2d = Direct 2r = Reverse 2b = Deadband 2i = Independent Setpoint                    d
Setting                           Description                                                 Setting Range           Default

SI    Setpoint                    Modes d, r, b: relay cut-off point                          -40 to 99°F             —
                                  Mode i:        heating independent setpoint                 (-40 to 70°C)
HI    Differential (Hysteresis)   Temperature difference relative to setpoint or offset at    1 to 9F° (1 to 9C°)     5
                                  which the load is switched On or Off
S2 Setpoint 2 (Offset)            Modes d, r:     difference between setpoint and Stage 2     d, r: 1 to 40F°         5
                                  Mode b:         deadband (centered on setpoint)                   (1 to 40C°)
                                  Mode I:         cooling independent setpoint                b: 2 to 40F°
                                                                                                    (2 to 40C°)
                                                                                              I:    LL to HL
H2 Differential (Hysteresis) 2 See Differential (hysteresis)                                  1 to 9F° (1 to 9C°)     5
LL Low Setpoint Stop              Lower limit of end-user setpoint adjustment                 -40F° (-40C°) to HL     32
HL High Setpoint Stop             Upper limit of end-user setpoint adjustment                 LL to 99°F (70°C)       90
Cc Anti-short Cycle Timer,        Time delay between equipment On cycles for cooling          0 to 9 minutes          2
   Cool                           stages
CH Anti-short Cycle Timer,        Time delay between equipment On cycles for heating          0 to 9 minutes          0
   Heat                           stages
rt    Soft Start                  Rate at which process temperature approaches setpoint       0 to 99                 10
                                                                                              minutes/degrees
AH High Temperature Alarm         High temperature alarm setpoint relative to main setpoint   0 to 50F° (0 to 50C°)   15
                                                                                              above setpoint
AL Low Temperature Alarm          Low temperature alarm setpoint relative to main setpoint    -50 to 0F° (-50 to 0C°) -15
                                                                                              below setpoint
Ad Alarm Differential             Temperature difference relative to high and low alarms at   1 to 9F° (1 to 9C°)     5
                                  which alarm output is switched Off
At Alarm Time Delay               Delay between alarm detection and activation                0 to 99 minutes         15
So Sensor Offset                  Compensates for long sensor leads or sensor location        -20 to +20F°            0
                                                                                              (-20 to +20C°)
Un Units Used                     Temperature units used                                      0 = °C   1 = °F         1
PU Display Refresh Rate           Time delay between display refreshes                        1 to 99 seconds         1
IF    Binary Input Function       Configuration for normally closed binary input              0 = No binary input     0
                                                                                              1 = Shutoff/alarm
                                                                                                  signaling
                                                                                              2 = Setback
                                                                                              3 = Remote shutoff
Sb Setback                        Value of setpoint shift when binary input is open and IF=2 0 to 20F° (0 to 20C°)    10
Id    Binary Input Time Delay     Time between binary input detection and enabling of IF      0 to 99 minutes         0
iS    Interstage Time Delay       Minimum amount of time between two successive stages        3 to 90 seconds         3

R epair and Replacement
Field repair must not be made. In case of defective or           When requesting a replacement, reference the model
improperly functioning control, contact your nearest             number found on the data plate of the control.
authorized Johnson Controls/PENN distributor.

4    A—MS2 Two Stage Electronic Temperature Control Installation Bulletin
         F ault/Alarm Codes
         Table 4: Status Codes (steady on display)
           Status Code                                   Indicates
           On                                            Binary Input is closed.
           OF                                            Binary Input is open.

         Table 5: Fault/Alarm Codes
          Error Code (Flashing on Display)                                          System Status

          EE Program failure; control must be replaced.                             Alarm message displays, other outputs off.
          FI    Indicates an open or shorted temperature sensor.                    Alarm message displays. Correct problem and cycle
                                                                                    power to reset.
          AI    Binary input (IF) Option 1 selected and binary input open           Control output is switched off; alarm message displays.
                for longer than time delay (id).                                    Correct condition to reset.
          DF Binary input (IF) Option 3 is selected and binary input open.          Control output is switched off. Close binary input to reset.
          HI    Temperature has reached or exceeded (setpoint + AH).                Alarm message displays. Correct condition to reset.

          LO Temperature has reached or fallen below (setpoint - AL).               Alarm message displays. Correct condition to reset.

         O rdering Information
         Table 6: Specifications
           Power Requirements               3.7 VA @ 24 VAC, 50/60 Hz, Class 2 (20-30 VAC)

           Ambient Conditions               Operating:     +14 to +140°F (-10 to +60°C); 0 to 95% RH (non-condensing)
                                            Storage:       -22 to +176°F (-30 to +80°C); 0 to 95% RH (non-condensing)
           Accuracy                         +1.8 F° (+1C°)

           Agency Listings                  UL Recognized: File E194024, CCN XAPX2
                                            Canadian UL Recognized: File E194024, CCN XAPX8
                                            FCC Compliant per Class A Digital Device, Part 15
                                            Canadian DOC Compliant per Class A, Radio Interference Regulations

         Table 7: Ordering Information
           Item Code                        Description
           MS2DR24T-11C                     MS2 DIN Rail Mount Control; A99BB-200C sensor included
           MS2PM24T-11C                     MS2 Panel Mount Control; A99BB-200C sensor included
           A99BB-200C                       A99B Temperature Sensor; Cable length 6-1/2 ft (2 m)

         The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
         specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be
         liable for damages resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                             Printed in U.S.A
Milwaukee, WI 53201                                                                                              www.johnsoncontrols.com

                                                         A—MS2 Two Stage Electronic Temperature Control Installation Bulletin                         5