FANs 125, 121
                                                                                          Pressure Controls Section          P
                                                                                                Installation Bulletin
                                                                                                          Issue Date         1199

                                              INSTALLATION BULLETIN

                           MS2 Two Stage Electronic Control

                                                               W iring
 IMPORTANT:            All MS2 controls are designed for           !
                       use only as operating controls.                 WARNING: Risk of Electrical Shock.
                       Where an operating control                               Disconnect power supply before
                       failure would result in personal                         making electrical connections to
                       injury or loss of property, it is the                    avoid possible electrical shock or
                       responsibility of the installer to                       equipment damage.
                       add devices (safety, limit
                       controls) or systems (alarm,
                       supervisory systems) that protect       Follow these wiring guidelines:
                       against, or warn of, control               All wiring must conform to the National Electric
                       failure.                                    Code and local regulations.
                                                                  Make all wiring connections using adequate gauge
                                                                   copper conductors only. Connectors are rated for
Refer to the MS Series Multi-Stage Electronic Controls             14-22 AWG wiring.
Product Bulletin, LIT-125502, for necessary
                                                                        Refer to Rating Table for more information.
information on operation and performance
specifications for this product.                                                                Internal to Control

                                                                        C1         C2        V1 V2 D SC             VO
M    ounting                                                                                                             +
                                                                       Stage      Stage      Power
The MS2 control is not position-sensitive but should be                                        Supply
mounted for convenient wiring and adjustment.                                 Terminal                    Binary /
                                                                                                                   Sensor
                                                                              Not Used   Binary Input      Sensor
To mount the DIN Rail Mount version, install the DIN                                                      Common
rail where appropriate. Snap the control onto the rail in
position.                                                               Figure 1: MS2 Panel Mount Wiring
To mount the Panel Mount version, ensure that there                                                       Binary
is sufficient space behind the panel. At least                          Sensor    Sensor Common          Common
2-3/4 inches (70 mm) are needed. Make a cutout                                           Binary Input
                                                                                                               Stage 
1-3/16 by 2-13/16 inches (29 by 71 mm). Remove
retaining clip from control. Insert the control into the                  +
hole. Install retaining clip and adjust for tightness.                    VO S1 SC         D   CD              C2    
                                                                                                        Internal
                                                                                                        to Control
                                                                           V1 V2          C1   
                                                                                                               Terminal
                                                                                                               Not Used
                                                                        Power Supply      Stage 
                                                                       Refer to Rating Table for more information.

                                                                       Figure 2: MS2 DIN Rail Mount Wiring

© 1999 Johnson Controls, Inc.                                                                                                       1
  Part No. 24-7664-1814, Rev. A                                                                           www.johnsoncontrols.com
  Code No. LIT-125504
                                                           process temperature.

Table 1: Wiring
    MS Series          P99-1V            HE-6300 or
    Terminal          Wire Color          HE-6310
                                          Terminal
    VO                  Brown (+)              PWR
    SC               Green (common)            COM
    S1                White (signal)           OUT

Table 2: Rating Table
 Rating Category               120      240       24
                               VAC      VAC      VDC
 Horsepower                     1/4      1/2         -
 Full Load Amperes              5.8      4.9         -
 Locked Rotor Amperes          34.8     29.4         -
 Inductive (non-motor)          8        8           8
 Amperes
 Pilot Duty VA                  275     450          -

Power supply is 24 VAC.
Terminal VO output is 12-17 VDC.

F CC Compliance
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when the equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in
a residential area is likely to cause harmful
interference, in which case the user will be required to
correct the interference at his/her own expense.

C anadian DOC Compliance
This digital apparatus does not exceed the Class A
limits for radio noise emissions from digital apparatus
set out in the Radio Interference Regulations of the
Canadian Department of Communications.

D isplay
Press Up and Down buttons to scroll
through process temperature and binary
input status (On or OF). After 15 seconds
of inactivity, the display shows the
2    P—MS2 Two Stage Electronic Control Installation Bulletin
                                                                                          1. Hold the Enter button down for 3 seconds.
S etting Up the Stage Control                                                                The display will change to show the setpoint.

                                                                                          2. Press the Up or Down button until you reach
                                                                                             the new setpoint.
To lock/unlock the unit for programming
                Press the Enter, Up, and Down buttons                                     3. Press the Enter button to save the new
                simultaneously and hold until “- - -” is displayed.                          setpoint.
                Hold for about 10 seconds until the current
                condition value is displayed. This toggles the          Note: If you do not press the Enter button after selecting the new
                keypad between locked and unlocked.                           setpoint, it is not saved. The control reverts to old setpoint.

To run the self test procedure                                          To program other settings (modes b, d, r only) or to
                                                                        program setpoints and settings (mode i only)
 IMPORTANT: Disconnect loads before beginning self-test
                                                                                          1. Hold the Enter button down for about
            procedure. Cycle power to resume normal
                                                                                             10 seconds. The display will change to HY.
            operation.
                                                                                             (The display shows S1 if in Mode i.)
                Press the Up and Down buttons in sequence,                                2. Press the Up or Down button until the desired
                and hold for 5 seconds.                                                      setting is shown.

                                                                                          3. Press the Enter button. The setting’s current
                                                                                             value is displayed.
To select the mode of operation
                1. Press and hold the Enter and Down buttons                              4. Press the Up or Down button until the desired
                   simultaneously for approximately 7 seconds.                               value is shown.

                2. Press the Up or Down button until the desired                           5. Press the Enter button to save the new
                   setting is shown.                                                           value. After 10 seconds of inactivity, the
                                                                                               display will return to its normal function.
                   2d =Direct
                   2r = Reverse                                         Note: If you do not press the Enter button after selecting the new
                   2b = Deadband                                              value, it is not saved. The control reverts to the old value.
                   2i = Independent Setpoint
                3. Press the Enter button to save the new mode
                   of operation.

To change the setpoint (modes b, d, and r only)

                                                                 P—MS2 Two Stage Electronic Control Installation Bulletin                   3
Table 3: Functions and Settings
Mode                            2d = Direct    2r = Reverse          2b = Deadband       2 = Independent Setpoint      d
Setting                         Description                                                   Setting Range            Default

SI    Setpoint                  Modes d, r, b: relay cut-off point                            0 to 99                  —
                                Mode I:        primary setpoint
HY Differential (Hysteresis)    Difference relative to setpoint or offset at which the        1 to 9                   5
                                load is switched On or Off
S2 Setpoint 2 (Offset)          Modes d, r: difference between setpoint and Stage 2           d, r: 1 to 40            5
                                Mode b:     deadband (centered on setpoint)                   b: 2 to 40
                                Mode I:     secondary setpoint                                I: LL to HL
H2 Differential (Hysteresis) 2 See Differential (Hysteresis).                                 1 to 9                   0
LL Low Setpoint Stop            Lower limit of end-user setpoint adjustment                   0 to HL                  99
HL High Setpoint Stop           Upper limit of end-user setpoint adjustment                   LL to 99                 90
Cc Anti-short Cycle Timer,      Time delay between equipment On cycles for direct             0 to 9 minutes           2
   Direct                       stages
CH Anti-short Cycle Timer,      Time delay between equipment On cycles for reverse            0 to 9 minutes           0
   Reverse                      stages
rt    Soft Start                Rate at which condition approaches setpoint                   0 to 99 minutes/         10
                                                                                              (1% or 1 psi)
AH High Condition Alarm         High condition alarm On, value relative to setpoint           0 to 50 above setpoint   15
AL Low Condition Alarm          Low condition alarm On, value relative to setpoint            -50 to 0 below setpoint -15
Ad Alarm Differential           Condition difference relative to high and low alarms at       1 to 9                   5
                                which alarm output is switched Off
At Alarm Time Delay             Delay between alarm detection and activation                  0 to 99 minutes          15
So Sensor offset                Compensates for long sensor leads or sensor location          -20 to +20               0
Lr    Low range Analog Input    Adjusted condition value when sensor input is 0.0 VDC         -40 to Hr                0
Hr High range Analog Input      Adjusted condition value when sensor input is 10.0 VDC        Lr to 99                 99
PU Display Refresh Rate         Time delay between display refreshes                          1 to 99 seconds          1
IF    Binary Input Function     Configuration for normally closed binary input                0 = No binary input      0
                                                                                              1 = Shutoff/alarm
                                                                                                  signaling
                                                                                              2 = Setback
                                                                                              3 = Remote shutoff
Sb Setback                      Value of setpoint shift when binary input is open and         0 to 20                  10
                                IF=2
Id    Binary Input Time Delay   Time between binary input detection and enabling of IF        0 to 99 minutes          0
iS    Interstage Time Delay     Minimum amount of time between two successive                 3 to 99 seconds          3
                                stages

R epair and Replacement
Field repair must not be made. In case of defective or          When requesting a replacement, refer to the model
improperly functioning control, contact your nearest            number found on the data plate of the control.
authorized Johnson Controls/PENN distributor.

4    P—MS2 Two Stage Electronic Control Installation Bulletin
         F ault/Alarm and Status Codes
         Table 4: Status Codes (steady on display)
           Status Code                       Indicates

           On                                Binary Input is closed
           OF                                Binary Input is open.

         Table 5: Fault/Alarm and Status Codes
          Error Code (Flashing on Display)                                     System Status

          EE Program failure; control must be replaced.                        Alarm message displays, other outputs off.
          FI    Indicates an open or shorted sensor.                           Alarm message displays. Correct problem and cycle power to
                                                                               reset.
          AI    Binary input (IF) Option 1 selected and binary input           Control output is switched off; alarm message displays.
                open for longer than time delay (id).                          Correct condition to reset. Restarts without using soft start.
          DF Binary input (IF) Option 3 is selected and binary input           Control output is switched off. Close binary input to reset.
             open.                                                             Restarts using soft start.
          HI    Condition has reached or exceeded (setpoint + AH).             Alarm message displays. Correct condition to reset.

          LO Condition has reached or fallen below (setpoint - AL).            Alarm message displays. Correct condition to reset.

         O rdering Information
         Table 6: Specifications
           Power Requirements               3.7 VA @ 24 VAC, 50/60 Hz, Class 2 (20-30 VAC)

           Ambient Conditions               Operating:     +14 to +140oF (-10 to +60oC); 0 to 95% RH (non-condensing)
                                            Storage:       -22 to +176oF (-30 to +80oC); 0 to 95% RH (non-condensing)
           Agency Listings                  UL Recognized: File E194024, CCN XAPX2
                                            Canadian UL Recognized: File E194024, CCN XAPX8
                                            FCC Compliant per Class A Digital Device, Part 15
                                            Canadian DOC Compliant per Class A, Radio Interference Regulations

         Table 7: Ordering Information
           Item Code                        Description
           MS2DR24V-11C                     MS2 DIN Rail Mount Control; 0-10 VDC input; sensor sold separately
           MS2PM24V-11C                     MS2 Panel Mount Control; 0-10 VDC input; sensor sold separately
           HE-6300 Series                   Humidity Sensor, Wall Mount, 0-100% RH
           HE-6310 Series                   Humidity Sensor, Duct Mount, 0-100% RH
           P99V-1C                          P99 Pressure Transducer, 0-100 psig
         The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
         specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be
         liable for damages resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                             Printed in U.S.A
Milwaukee, WI 53201                                                                                              www.johnsoncontrols.com
                                                                          P—MS2 Two Stage Electronic Control Installation Bulletin                    5
6   P—MS2 Two Stage Electronic Control Installation Bulletin