FANs 125, 121
                                                                                    Temperature Controls Section          A
                                                                                             Installation Bulletin
                                                                                                       Issue Date         1199

                                              INSTALLATION BULLETIN

            MS1 One Stage Electronic Temperature Control

                                                               W iring
 IMPORTANT:            All MS1 controls are designed for
                       use only as operating controls.             ! WARNING: Risk of Electrical Shock.
                       Where an operating control                                   Disconnect power supply before
                       failure would result in personal                             making electrical connections to
                       injury or loss of property, it is the                        avoid possible electrical shock or
                       responsibility of the installer to                           equipment damage.
                       add devices (safety, limit
                       controls) or systems (alarm,
                       supervisory systems) that protect       Follow these wiring guidelines:
                       against, or warn of, control            •   All wiring must conform to the National Electric
                       failure.                                    Code and local regulations.
                                                               •   Make all wiring connections using adequate gauge
Refer to the MS Series Multi-Stage Electronic
                                                                   copper conductors only. Connectors are rated for
Temperature Controls Product Bulletin, LIT-125198, for
                                                                   14-22 AWG wiring.
necessary information on operation and performance
specifications for this product.                                                                  Alarm
                                                                                                                +
                                                                      Process       Sensor                      -
                                                                      Sensor        Common

M ounting                                                                       S1 SC                 A+   A-

                                                                         Terminal Not Used
The MS1 control is not position-sensitive but should be
                                                                                                      Internal to
mounted for convenient wiring and adjustment. To                                                      Control
mount the MR1 DIN Rail Mount, install the DIN rail                       V1 V2          C1   ➀
where appropriate. Snap the control onto the rail in                                              Refer to Rating Table
position.                                                                Power          Stage ➀   for more information.
                                                                         Supply

                                                                       Figure 1: MS1 DIN Rail Mount Wiring

© 1999 Johnson Controls, Inc.                                                                                                    1
  Part No. 24-7664-1733, Rev. A                                                                       www.johnsoncontrols.com
  Code No. LIT-125211
                                                               S etting Up the Stage Control
Use this table, with function So, to compensate for long       To lock/unlock the unit for programming
sensor leads.
                                                                                 Press the Enter, Up, and Down buttons in
                                                                                 sequence and hold until “- - -” is displayed. Hold
Table 1: Sensor Wire Size and Length                                             for about 10 seconds until the current
           Wire Size and Length                                                  temperature is displayed. This toggles the
                                                  Offset                         keypad between locked and unlocked.
 18 AWG          20 AWG       22 AWG
                                                               To run the self test procedure
 300-599 ft      190-374 ft   120 -239 ft         1F°
 91-183 m        58-114 m     36-73 m             1C°           IMPORTANT:         Disconnect loads before beginning self-test
                                                                                   procedure. Cycle power to resume normal
 600-899 ft      375-564 ft   240-349 ft          2F°                              operation.
 183-274 m       114-172 m    73-107 m            2C°
 900+ ft         565+ ft      350+ ft             3F°                            Press the Up and Down buttons in sequence,
 274+ m          172+ m       107+ m              3C°                            and hold for 5 seconds.

                                                               To select the mode of operation
Table 2: Rating Table                                                            1. Press and hold the Enter and Down buttons
 Rating Category               120          240          24                         simultaneously for approximately 7 seconds.
                               VAC          VAC         VDC
                                                                                 2. Press the Up or Down button until the
 Horsepower                     1/4         1/2            -                        desired setting is shown.
 Full Load Amperes              5.8         4.9            -                         1d = Direct (cool), 1r =     Reverse (heat)
 Locked Rotor Amperes          34.8         29.4           -                     3. Press the Enter button to save the new mode
                                                                                    of operation.
 Inductive (non-motor)           8           8             8
 Amperes
 Pilot Duty VA                 275          450            -   To change the setpoint
                                                                                 1. Hold the Enter button down for 3 seconds.
Alarm circuit rated at 40 VDC, 100 mA maximum.                                      The display will change to show the setpoint.
Power supply is 24 VAC.
                                                                                 2. Press the Up or Down button until you reach
Alarm requires separate power source.                                               the new setpoint.

                                                                                 3. Press the Enter button to save the new
                                                                                    setpoint.
                                                               Note:   If you do not press the Enter button after selecting the new
                                                                       setpoint, it is not saved. The control reverts to old setpoint.

                                                               To program other values
                                                                                 1. Hold the Enter button down for about
                                                                                    10 seconds. The display will change to HY.

                                                                                 2. Press the Up or Down button until the
                                                                                    desired setting is shown.

                                                                                 3. Press the Enter button. The setting’s current
                                                                                    value is displayed.

                                                                                 4. Press the Up or Down button until the
                                                                                    desired value is shown.

                                                                                 5. Press the Enter button to save the new
                                                                                    value. After 10 seconds of inactivity, the
                                                                                    display will return to its normal function.
                                                               Note: If you do not press the Enter button after selecting the new
                                                                     value, it is not saved. The control reverts to the old value.

2   A—MS1 One Stage Electronic Temperature Control Installation Bulletin
Table 3: Functions and Settings
Mode                             1d = Direct (Cool) 1r = Reverse (Heat)                                             d

Setting                                           Description                          Setting Range          Default
SI   Setpoint                    Relay cut-off point                              -40 to 99°F                 —
                                                                                  (-40 to 70°C)
HI   Differential (Hysteresis)   Temperature difference relative to setpoint at   1 to 9F° (1 to 9C°)         5
                                 which the load is switched On
LL Low Setpoint Stop             Lower limit of end-user setpoint adjustment      -40F° (-40C°) to HL         32
HL High Setpoint Stop            Upper limit of end-user setpoint adjustment      LL to 99°F (70°C)           90
Cc Anti-short Cycle Timer,       Time delay between equipment On cycles for       0 to 9 minutes              2
   Cool                          cooling stages
CH Anti-short Cycle Timer,       Time delay between equipment On cycles for       0 to 9 minutes              0
   Heat                          heating stages
rt   Soft Start                  Rate at which the process temperature            0 to 99 minutes/degrees     10
                                 approaches the setpoint
AH High Temperature Alarm        High temperature alarm setpoint relative to      0 to 50F° (0 to 50C°)       15
                                 main setpoint                                    above setpoint
AL Low Temperature Alarm         Low temperature alarm setpoint relative to       -50 to 0F° (-50 to 0C°)     -15
                                 main setpoint                                    below setpoint
Ad Alarm Differential            Temperature difference relative to high and low 1 to 9F° (1 to 9C°)          5
                                 alarms at which alarm output is switched Off
At Alarm Time Delay              Delay between alarm detection and activation     0 to 99 minutes             15
So Sensor Offset                 Compensate for long sensor leads or sensor       -20 to +20F° (-20 to +20C°) 0
                                 location
Un Units Used                    Temperature units used                           0 = °C   1 = °F             1
PU Display Refresh Rate          Time delay between display refreshes             1 to 99 seconds             1

R epair and Replacement                                         F CC Compliance
Field repair must not be made. In case of defective             This equipment has been tested and found to
or improperly functioning control, contact your                 comply with the limits for a Class A digital device
nearest authorized Johnson Controls/PENN                        pursuant to Part 15 of the FCC Rules. These limits
distributor. When requesting a replacement, refer to            are designed to provide reasonable protection
the model number found on the data plate of the                 against harmful interference when the equipment is
control.                                                        operated in a commercial environment. This
                                                                equipment generates, uses, and can radiate radio
C anadian DOC Compliance                                        frequency energy and, if not installed and used in
                                                                accordance with the instruction manual, may cause
This digital apparatus does not exceed the Class A              harmful interference to radio communications.
limits for radio noise emissions from digital                   Operation of this equipment in a residential area is
apparatus set out in the Radio Interference                     likely to cause harmful interference, in which case
Regulations of the Canadian Department of                       the user will be required to correct the interference at
Communications.                                                 his/her own expense.

                                       A—MS1 One Stage Electronic Temperature Control Installation Bulletin             3
F ault/Alarm Codes
Table 4: Fault/Alarm Codes
 Error Code (Flashing on Display)                                   System Status

 EE Program failure; control must be replaced.                      Alarm message displays, other outputs off.
 FI    Indicates an open or shorted process temperature             Alarm message displays. Correct problem and cycle power to
       sensor.                                                      reset.
 HI    Temperature has reached or exceeded                          Alarm message displays. Correct condition to reset.
       (setpoint + AH).
 LO Temperature has reached or fallen below                         Alarm message displays. Correct condition to reset.
    (setpoint - AL).

O rdering Information
Table 5: Specifications
 Power Requirements                3.7 VA @ 24 VAC, 50/60 Hz, Class 2 (20-30 VAC)
                                                                o              o
 Ambient Conditions                Operating:     +14 to +140 F (-10 to +60 C); 0 to 95% RH (non-condensing)
                                                             o             o
                                   Storage:       -22 to +176 F (-30 to +80 C); 0 to 95% RH (non-condensing)
                                           o      o
 Accuracy                          +1.8 F (+ 1C )

 Agency Listings                   UL Recognized: File E194024, CCN XAPX2
                                   Canadian UL Recognized: File E194024, CCN XAPX8
                                   FCC Compliant per Class A Digital Device, Part 15
                                   Canadian DOC Compliant per Class A, Radio Interference Regulations

Table 6: Ordering Information
 Item Code                         Description
 MS1DR24T-11C                      MS1 DIN Rail Mount Control; A99BB-200C sensor included
 A99BB-200C                        A99B Temperature Sensor, cable length: 6-1/2 ft (2 m)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be
liable for damages resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                              Printed in U.S.A.
Milwaukee, WI 53201                                                                                               www.johnsoncontrols.com

4     A—MS1 One Stage Electronic Temperature Control Installation Bulletin