Master Catalog    125
                                                                                 Temperature Controls Section   A
                                                                                             Product Bulletin   MS
                                                                                                  Issue Date    0618

    MS Series Multi-Stage Electronic Temperature Controls

The MS Series Controls are versatile,
microprocessor-based, multifunction, programmable
temperature controls. They are designed for single and
multiple stage temperature control applications.

Depending on the model selected, the MS Series
Controls can operate in the following modes:
   Direct mode
   Reverse mode
   Deadband mode
   Independent Setpoint mode

The MS Series Controls have large, easy-to-read,
red Light-Emitting Diode (LED) displays. These
compact controls are available in Panel Mount and               Figure 1: MS4 Panel Mount and DIN Rail
DIN Rail Mount models. MS Series Controls use the              Multi-Stage Electronic Temperature Controls
A99B temperature sensors, which allow remote
mounting of the display unit.

                                          Features and Benefits
                  Programmable Functions Allows adjustment of control settings to meet
                                                    application needs

                  Alarm Management                 Provides visible alarm codes on the display
                   Functions

                  Easily Readable LED              Displays temperature and functions quickly
                   Display                         and clearly

                  Programming Button               Allows user to disable programming buttons
                   Lockout                         and deter accidental or unauthorized changes

                  Accurate Sensors for             Provides accurate control performance with up to
                     Temperature                    300 feet of wiring (an adjustable offset is provided
                                                    for longer wiring)

                  Self-Test Procedure              Checks control operation by cycling all
                                                    outputs and testing all LEDs

© 2018 Johnson Controls                                                                                                1
  Code No. LIT-125198
O verview
 IMPORTANT:            All MS Series Controls are              Mode Selection
                       designed for use only as
                       operating controls. Where an            Mode Selection allows selection of one of several
                       operating control failure would         modes, depending on the model:
                       result in personal injury or loss of
                                                                  Direct mode for cooling applications
                       property, it is the responsibility of
                       the installer to add devices               Reverse mode for heating applications
                       (safety, limit controls) or systems
                                                                  Deadband mode for applications requiring cooling
                       (alarm, supervisory systems) that
                                                                   and heating with a common setpoint and a
                       protect against, or warn of,
                                                                   deadband
                       control failure.
                                                                  Independent Setpoint mode for applications
Refer to a specific model’s installation bulletin for the          requiring cooling and heating with an independent
necessary information on installation, use, and                    setpoint for each
servicing.
Table 1: Selected Applications                                 Stage Control Functions
    MS1    MS2      MS4     Application                        Adjustable Setpoint Stops restrict setpoint
                                                               adjustment to avoid extreme settings. The setpoint
                            Cooling tower pump and/or
                                                            cannot be changed to a value outside of these stops.
                            fan control
                            Rooftop heating or cooling         Soft Start controls the rate at which temperature
                                                            approaches the setpoint on power up, both initially and
                            units
                                                               when the binary input is configured as a remote
                            Boiler or pump control             shutoff.
                    
                                                               Anti-short Cycle Delay avoids situations where the
                            Space temperature control
                                                            equipment starts, stops, and restarts in a short period
                                                               of time. This feature determines the minimum time
                          Compressor or chiller staging      between two subsequent On cycles of the equipment.

                                                               Binary Input Functions
                                                               The MS2 and MS4 controls are equipped with a binary
                                                               input that can perform one of the following functions:
                                                                Shutoff and Alarm Signaling: When the binary
                                                                 input is open for a time longer than the binary input
                                                                 time delay, all outputs are shut off and an alarm
                                                                 message is displayed. Restart does not use the
                                                                 soft start feature.
                                                                Setback: When the binary input is open, the
                                                                 setpoints are shifted by a preset value in order to
                                                                 save energy.
                                                                Remote Shutoff: When the binary input is open for
                                                                 a time longer than the binary input time delay, all
                                                                 outputs are shut off and an alarm message is
                                                                 displayed. Restart uses the soft start feature.

2    MS Series Product Bulletin
Dual Sensor Temperature Reset                              Display Updating Time provides an adjustable
                                                           refresh rate to avoid displaying short duration
This feature resets the Setpoint based on the              fluctuations.
difference between temperature reading from the
Auxiliary Temperature Sensor (ATS) and the setpoint.       Units of Measurement for temperature measurement
This feature is available only on the MS4 Series and       can use either Fahrenheit or Celsius temperature
can only be used when the ATS is connected.                scales.

Alarm Management Functions                                 D imensions
High and Low Temperature Alarms have setpoints                              2 11/16                               1/4
relative to the main setpoint. If the temperature                             (68)                                    (6)
reaches or exceeds the alarm values, the display
flashes a specific alarm message. On the MS1, an                1 1/8                                1 3/8
alarm output circuit is energized. The MS2 and MS4              (28)                                  (35)
                                                                                                                  2
controls have no alarm output. Alarms are disabled for                                                          (50)
20 minutes after startup in addition to the alarm time                           2 5/16
delay.                                                                            (58)

Alarm Time Delay is used to avoid short-duration
events triggering the alarm.
                                                                2 3/4
Alarm Differential can be set to keep the alarm from            (70)                                   3
cycling rapidly on and off.                                                                          (75)       78 3/4
Sensor Failure is indicated by an alarm message on                                                              (2000)
the display.
Alarm codes are displayed by the LEDs and are used
to help troubleshoot errors. Alarm codes exist for these
conditions:
   process sensor failure                                          Figure 2: Panel Mount Control and
                                                                           A99 Sensor, in. (mm)
   high temperature alarm
                                                                         2 3/4
   low temperature alarm                                                (70)
                                                                                                             2 1/8
                                                                                                             (52.5)
   program failure
   binary input codes

Self-Test Procedure
The self-test procedure allows the user to verify that      1
                                                              13                                11
                                                              16                            4
the LEDs and outputs of an MS control are operating                                             16
correctly before the control is put into service.            (45)
                                                                                            (118)

Additional Features
Programming Button Lockout allows the
programming buttons to be deactivated, which deters
accidental or unauthorized modifications to the
settings.                                                       Figure 3: DIN Rail Mount Control, in. (mm)
Sensor Offset allows programming an offset of the
measured temperature for use with sensor leads
longer than 300 ft.

                                                                                          MS Series Product Bulletin        3
                                                             M odes of Operation
Display                                                      The MS1 Series Control performs temperature and
The display has two 7-segment LEDs and a minus (-)           alarm management for single-stage applications. It
indication to display temperatures from -40 to 99°F          operates in either Direct or Reverse modes.
(-40 to 70°C), with 1F° (C°) resolution. Three individual    The MS2 Series Control performs temperature
stage status LEDs display the relay status.                  management for 2-stage applications. In addition to
     LED  indicates Relay Output 1 is energized.           the MS1 modes, it has Deadband and Independent
                                                             Setpoint modes for applications that require both
     LED  indicates Relay Output 2 is energized.           cooling and heating.
     LED  indicates Relay Output 3 is energized.           The MS4 Series Control performs temperature
                                                             management for 4-stage applications. It has the same
The MS1 has one stage status LED. The MS2 has
                                                             mode selection as the MS2. It can automatically adjust
two stage status LEDs. The MS4 has three stage
                                                             the setpoint to save energy, based on readings from
status LEDs.
                                                             the auxiliary temperature sensor and the function
                         Stage Status LEDs
                                                             settings.
                                                             Table 2: Modes of Operation
                                                    Up
                                                    Button    MS1     MS2      MS4    Modes of Operation
       Enter
                                                    Down                      
       Button
                                                    Button                            Direct (Cooling)
                                                                                   Reverse (Heating)
                                                                                    Deadband (Cooling and
     Figure 4: Panel Mount Front Panel and Display                                    Heating)
                                                                                    Independent Setpoint
                                                                                      (Cooling and Heating)
                Stage Status LEDs
                                                             The illustrations on the following pages show the
                                                             modes that each MS Series Control is capable of
                                             Up Button       using.
                                             Down Button

    Figure 5: DIN Rail Mount Front Panel and Display

The MS1 has one stage status LED. The MS2 has
two stage status LEDs. The MS4 has three stage
status LEDs.

4     MS Series Product Bulletin
Direct Mode (Cooling)

             Temperature

                                                                                   Interstage
                                                                                      Time
                                                                                     Delay

                                                                                                On

                                                     Interstage
                                                        Time
                                                       Delay
                                                                                                     Stage 4       Differential 4
                                                                  On

                             Interstage                                                                    Off
                                Time                                   Stage 3
                               Delay                                                    Differential 3

                                          On
                                                                                 Off                                       Setpoint 4
                                                                                                                           (Offset from
                                           Stage 2         Differential 2                                                  Setpoint)

                                                                                                          Setpoint 3
              On                                  Off                                                     (Offset from
                                                                                                          Setpoint)

                                                                   Setpoint 2
                                                                  (Offset from
                   Stage 1         Differential                    Setpoint)

                         Off        Setpoint

                                                                                                                          Time

                                                        Figure 6: Direct Mode

Direct mode is used for cooling applications. The MS1                       Setpoint 3 is the offset from setpoint that activates
has one stage. The MS2 has two stages. The MS4                              Stage 3.
has four stages. Where desirable, stages may overlap
                                                                            Differential 3 is the operational range of Stage 3.
or have space between them.
                                                                            Setpoint 4 is the offset from setpoint that activates
Setpoint is the desired temperature.
                                                                            Stage 4.
Differential is the operational range of Stage 1.
                                                                            Interstage Time Delay is the minimum amount of time
Setpoint 2 is the offset from setpoint that activates                       between two successive stages when multiple stages
Stage 2.                                                                    are called for in rapid sequence.
Differential 2 is the operational range of Stage 2.

                                                                                                                  MS Series Product Bulletin   5
Reverse Mode (Heating)

                Temperature

                          Off              Setpoint

                                                                Setpoint 2
                    Stage 1       Differential                 (Offset from
                                                                Setpoint)
                                                      Off
                                                                                          Setpoint 3
               On                                                                        (Offset from
                                                                                          Setpoint)
                                            Stage 2
                                                            Differential 2
                                                                                                                 Setpoint 4
                                                                                                                (Offset from
                                           On                                   Off                              Setpoint)

                                                                                         Differential 3
                                                                       Stage 3
                                                                                                          Off
                              Interstage                             On
                                 Time
                                Delay
                                                                                                    Stage 4     Differential 4

                                                        Interstage
                                                           Time
                                                                                                   On
                                                          Delay

                                                                                      Interstage
                                                                                         Time
                                                                                        Delay

                                                                                                                     Time

                                                       Figure 7: Reverse Mode

Reverse mode is used for heating applications. The                           Setpoint 3 is the offset from setpoint that activates
MS1 has one stage. The MS2 has two stages. The                               Stage 3.
MS4 has four stages. Where desirable, stages may
                                                                             Differential 3 is the operational range of Stage 3.
overlap or have space between them.
                                                                             Setpoint 4 is the offset from setpoint that activates
Setpoint is the desired temperature.
                                                                             Stage 4.
Differential is the operational range of Stage 1.
                                                                             Differential 4 is the operational range of Stage 4.
Setpoint 2 is the offset from setpoint that activates
                                                                             Interstage Time Delay is the minimum amount of time
Stage 2.
                                                                             between two successive stages when multiple stages
Differential 2 is the operational range of Stage 2.                          are called for in rapid sequence.

6   MS Series Product Bulletin
Deadband Mode

               Temperature

                                          Interstage
                                         Time Delay

              Cooling
                                                            Stage 4                   Differential 4

                                                                            Setpoint 4
                             Stage 2       Differential 2                   (Offset from Stage 2)

                                       Setpoint + (1/2 Setpoint 2)
               Setpoint

                                       Setpoint - (1/2 Setpoint 2)

                                                                              Setpoint 3
                             Stage 1      Differential
                                                                              (Offset from Stage 1)

                                                             Stage 3                   Differential 3

               Heating

                                          Interstage
                                          Time Delay

                                                                                                        Time

                                               Figure 8: Deadband Mode

Deadband mode is used for applications requiring                     Setpoint 3 is the offset from the low end of the
cooling and heating. The MS2 has two stages. The                     deadband that activates Stage 3.
MS4 has four stages. Where desirable, stages may
                                                                     Differential 3 is the operational range of Stage 3.
overlap or have space between them.
                                                                     Setpoint 4 is the offset from the high end of the
Setpoint is the desired temperature.
                                                                     deadband that activates Stage 4.
Differential is the operational range of Stage 1.
                                                                     Differential 4 is the operational range of Stage 4.
Setpoint 2 is width of the deadband, which is centered
                                                                     Interstage Time Delay is the minimum amount of time
on setpoint.
                                                                     between two successive stages when multiple stages
Differential 2 is the operational range of Stage 2.                  are called for in rapid sequence.

                                                                                                        MS Series Product Bulletin   7
Independent Setpoint Mode

                Temperature

                                         Interstage
                                         Time Delay

               Cooling
                                                           Stage 4                        Differential 4

                              Stage 2     Differential 2                     Setpoint 4

                                                           Setpoint

                              Stage 1    Differential                        Setpoint 3

                                                             Stage 3                      Differential 3

                Heating

                                          Interstage
                                         Time Delay

                                                                                                           Time

                                        Figure 9: Independent Setpoint Mode

Independent Setpoint mode is used for applications                    Differential 2 is the operational range of Stage 2.
requiring cooling and heating. The MS2 has
                                                                      Setpoint 3 is the offset from Setpoint that activates
two stages. The MS4 has four stages. Where
                                                                      Stage 3.
desirable, stages may overlap or have space between
them.                                                                 Differential 3 is the operational range of Stage 3.
Setpoint is the desired heating temperature. It is the                Setpoint 4 is the offset from Setpoint 2 that activates
basis for the reverse stages.                                         Stage 4.
Differential is the operational range of Stage 1.                     Differential 4 is the operational range of Stage 4.
Setpoint 2 the desired cooling temperature                            Interstage Time Delay is the minimum amount of time
programmed by the user. It is the basis for the direct                between two successive stages when multiple stages
stages.                                                               are called for in rapid sequence.

8   MS Series Product Bulletin
F unction Definitions
The MS Series controls include a variety of                Anti-short Cycle Timer, Reverse establishes the
temperature and alarm management functions, which          minimum time in minutes between two subsequent On
are listed below. Not all of these functions are           cycles of reverse (heating) stages.
available on every model.
Refer to Table 3 for functions and setting ranges for                                                 Load Demand
specific models.
                                                                                                      Output Status

Temperature Management                                                    Anti-short Cycle
                                                                               Timer
Setpoint is the primary control point programmed by
the user.
                                                                      Figure 10: Anti-short Cycle Timer
Setpoint 2, Setpoint 3, Setpoint 4 depend on the
mode used. For information on function in each mode,       Interstage Time Delay is the minimum amount of time
see Modes of Operation.                                    between two successive stages when multiple stages
Differentials (or hysteresis) establishes the difference   are called for in rapid sequence.
between the value at which the output is switched Off      Soft Start controls the rate at which the process
and the value at which the output is switched On. For      temperature is allowed to approach the setpoint on
further information, see Modes of Operation.               power up, both initially and when the binary input is
Example: In Direct (cooling) mode, with the setpoint at    configured as remote shutoff. The setting is
40°F, and the differential at 4F°, the compressor is       minutes/temperature units, such as minutes/F°.
switched On when the temperature goes above 44°F,          Example:
and is turned Off when the temperature decreases to
below 40°F.                                                Process temperature = 20°
                                                           Setpoint =            30°
High and Low Setpoint Stops are temperature                Soft start =          2 minutes
settings (F or C) that define how high and low the
primary setpoint may be adjusted. Setpoint stops           Rate of Increase =
deter unauthorized or accidental overadjustment of         Soft start x (setpoint – sensor reading)
setpoint.                                                  Process setpoint increases by 1° every two minutes,
Anti-short Cycle Timer, Direct establishes the             until the setpoint temperature is reached. To go from
minimum time in minutes between two subsequent On          20° to 30° takes 10 minutes.
cycles of Direct (cooling) stages.                         Temperature Sensor Offset allows the user to
                                                           compensate for temperature differences between
                                                           actual and displayed temperature, such as those
                                                           experienced when using long sensor leads or when
                                                           the location of the sensor results in inaccurate
                                                           readings.
                                                           Temperature Units allows the user to select either the
                                                           Fahrenheit or Celsius temperature scale.
                                                           Display Refresh Rate establishes the time delay
                                                           (seconds) between updates of the temperature
                                                           display.

                                                                                             MS Series Product Bulletin   9
Heating Reset and Cooling Reset are used in                 Alarm Time Delay establishes the time delay
Deadband mode. The reset is an automatic shift of the       (minutes) between reaching an alarm condition
setpoint, based on the temperature at the Auxiliary         (high or low temperature) and activating the alarm.
Temperature Sensor (ATS).                                   This function reduces nuisance alarms caused by
                                                            transient changes that temporarily exceed alarm
Non-compensated Band establishes the temperature
                                                            setpoint temperatures. Conditions that would cause a
range (F or C) over which reset does not take place.      temperature alarm are disregarded by the unit during
                                                            the first 20 minutes after power up.
Alarm Management
High Temperature Alarm sets the temperature                 Binary Input
(F or C) relative to setpoint at which the control goes   Binary Input Function allows the user to select how
into a high temperature alarm condition.                    the binary input will activate the stage control contacts.
Example: If setpoint is 40°F and high temperature           The user can select to disengage this function or set
alarm is 15F°, the alarm message will be displayed at       one of three actions:
or above 55°F.                                                 Shutoff and Alarm Signaling - If the binary input
Low Temperature Alarm sets the temperature                      contact is open for a time longer than that set
(F or C) relative to setpoint at which the control goes       through the binary input time delay, the stage
into a low temperature alarm condition.                         control contacts are switched Off, and an alarm
                                                                message (A1) is displayed. On the MS1, the alarm
Example: If setpoint is 40°F and low temperature                is also activated.
alarm is -10F°, an alarm message will be displayed at
or below 30°F.                                                 Setback - If the binary input contact is open for a
                                                                time longer than that set through the binary input
Alarm Differential establishes the difference                   time delay, the setpoints are shifted by setback.
(F or C) between the temperature at which the alarm           Reverse setpoints (heating) decrease. Direct
is activated and the temperature at which the alarm is          setpoints (cooling) increase.
deactivated. On the MS1, alarm activation triggers an
external alarm and displays an alarm message. On the           Remote Shutoff of the outputs. - If the binary
MS2 and MS4, an alarm message is displayed.                     input contact is open for a time longer than that set
                                                                through the binary input time delay, the stage
Example (cooling):                                              control contacts are switched Off.
Setpoint = 40°F
High Temperature Alarm = 15F°                               If a set of stage control contacts are used to control an
Alarm Differential = 2F°                                    external alarm, this function should be disabled.
When the room temperature exceeds 40 + 15 = 55°F            Binary Input Time Delay establishes the time delay
for a time greater than the alarm time delay setting,       (minutes) between binary signal reaching the control
the alarm message is displayed; however, it will reset      and control’s response to the binary signal.
after the temperature drops below 40+15-2=53°F.             Setback determines the value of the setpoint shift
                                                            when the binary input is open and the binary input
                                                            function is set at setback.

10   MS Series Product Bulletin
Temperature Reset                                               Temperature Reset Examples
Heating reset, cooling reset, and Non-compensated               Heating Reset Example:
Band (NCB) are used only with the MS4. Heating reset            Setpoint = 70°
only affects the heating setpoint, and cooling reset            Auxiliary Temperature Sensor (ATS) = 42°
only affects the cooling setpoint. These functions              NCB = 20°
appear only when the Auxiliary Temperature Sensor               Heating Reset = 2°
(ATS) is connected.                                             Step 1
                                                                ATS–(setpoint–NCB) = differential
Heating Reset                                                   42 – (70 – 20) = -8

When the ATS reading is lower than the setpoint, and            Step 2
the difference exceeds the deadband, temperature                differential/heating reset = reset
reset will take place. The setpoint will be lowered.            -8/2 = -4
Degrees of reset are equal to:                                  Step 3
[ATS – (setpoint – NCB)] / heating reset                        setpoint + reset
                                                                70 + (-4) = 66

Cooling Reset                                                   Setpoint is reset to 66° to save energy.

When the Auxiliary Temperature Sensor (ATS) reading
is higher than the setpoint, and the difference exceeds         Cooling Reset Example:
the deadband, temperature reset will take place. The            Setpoint = 70°
setpoint will be raised. Degrees of reset are equal to:         Auxiliary Temperature Sensor (ATS) = 92°
[ATS – (setpoint + NCB)] / cooling reset                        NCB = 10°
                                                                Cooling Reset = 2°

Non-compensated Band (NCB)                                      Step 1
                                                                ATS–(setpoint + NCB) = differential
The temperature range over which reset does not take            92 – (70 + 10) = 12
place.
                                                                Step 2
                                                                differential/cooling reset = reset
                                                                12/2 = 6
                                                                Step 3
                                                                setpoint + reset
                                                                70 + 6 = 76
                                                                Setpoint is reset to 76° to save energy.

                          Heating Reset                                              Cooling Reset
                    Only Affects Heating Stages                                Only Affects Cooling Stages
                                                                       76°
                       1°
                                 Setpoint                  Process           Setpoint
                     Heating
                                                   70°   Temperature   70°
                      Reset
                                                                                                  1°
                                                   66°                                          Cooling
                                                                                                 Reset
                                      Deadband                                  Deadband
       Auxiliary                      NCB = 20°                                 NCB = 10°                          Auxiliary
     Temperature                                                                                                 Temperature
       Sensor       42°         50°               70°                    70°                 80°          92°      Sensor
        (ATS)                                                                                                       (ATS)

                                                                                                   MS Series Product Bulletin   11
                            Heating Reset                                              Cooling Reset
                      Only Affects Heating Stages                                Only Affects Cooling Stages
                                                                         76°
                        1°
                                   Setpoint                  Process           Setpoint
                      Heating
                                                     70°   Temperature   70°
                       Reset
                                                                                                    1°
                                                     66°                                          Cooling
                                                                                                   Reset
                                        Deadband                                  Deadband
       Auxiliary                        NCB = 20°                                 NCB = 10°                         Auxiliary
     Temperature                                                                                                  Temperature
       Sensor        42°          50°               70°                    70°                 80°          92°     Sensor
        (ATS)                                                                                                        (ATS)

                                        Figure 11: Temperature Reset Examples

12   MS Series Product Bulletin
Table 3: Functions and Settings
 MS1   MS2   MS4   Setting                           Setting Range

                                                  D = Direct (Cooling)
                                                  R = Reverse (Heating)
                   Mode Selection
                                                   B = Deadband (Direct and Reverse)
                                                   I = Independent Setpoint (Direct and Reverse)
                Setpoint                          -40 to 99°F (-40 to 70°C)
                Differential 1                    F°/1 to 9 C°
                                                     D, R modes         1 to 40F° (1 to 40C°)
                 Setpoint 2                        B mode             2 to 40F° (2 to 40C°)
                                                     I mode             Low to High Setpoint Stop
                 Differential 2                    1 to 9F° (1 to 9C°)
                  Setpoint 3                        1 to 40F° (1 to 40C°)
                  Differential 3                    1 to 9F° (1 to 9C°)
                  Setpoint 4                        1 to 40F° (1 to 40C°)
                  Differential 4                    1 to 9F° (1 to 9C°)
                Low Setpoint Stop                 -40° to High Setpoint Stop
                High Setpoint Stop                Low Setpoint Stop to 99°F (70°C)
                 Interstage Time Delay             3 to 90 seconds
                Anti-short Cycle Timer, Direct    0 to 9 minutes
                Anti-short Cycle Timer, Reverse   0 to 9 minutes
                Soft Start                        0 to 99 minutes/1F° (1C°)
                  Heating Reset                     0 to 6F° (0 to 6C°)
                  Cooling Reset                     0 to 6F° (0 to 6C°)
                  Non-compensated Band              0 to 20F° (0 to 20C°)
                Sensor Offset                     -20 to +20F° (-20 to +20C°)
                   Units Used                        0 = °C
            
                                                     1 = °F
                Display Refresh Rate              1 to 99 seconds
                High Temperature Alarm            0 to 50F° (0 to 50C°) above Setpoint
                Low Temperature Alarm             -50 to 0F° (-50 to 0C°) below Setpoint
                Alarm Differential                1 to 9F° (1 to 9C°)
                Alarm Time Delay                  0 to 99 minutes
                   Binary Input Function             0 = No binary input
                                                     1 = Shutoff and alarm signaling
             
                                                     2 = Setback
                                                     3 = Remote shutoff
                 Setback                           0 to 20F° (0 to 20C°)
                 Binary input Time Delay           0 to 99 minutes

                                                                       MS Series Product Bulletin    13
M S1 – One Stage Electronic
Temperature Control
The MS1 control is designed for 1-stage temperature              Modes of Operation
and alarm control applications. This model uses the
A99B Series temperature sensors.                                      Direct (Cooling)
                                     Alarm
                                                     +                Reverse (Heating)
        Process       Sensor                         -
        Sensor        Common
                  S1 SC                   A+   A-                Temperature Management Settings
           Terminal Not Used                                          Setpoint
                                          Internal to                 Differential (Hysteresis)
                                          Control
           V1 V2          C1                                         Low Setpoint Stop
                                     Refer to Rating Table
           Power          Stage     for more information.            High Setpoint Stop
           Supply
                                                                      Anti-short Cycle Timer
       Figure 12: MS1 DIN Rail Mount Wiring                           Soft Start
                                                                      Temperature Sensor Offset
Table 4: Rating Table
                                                                      Temperature Units Used
                                120            240        24
     Rating Category                                                  Display Refresh Rate
                                VAC            VAC       VDC
 Horsepower                         1/4         1/2          -
 Full Load Amperes
                                                                 Alarm Management Settings
                                    5.8         4.9          -
 Locked Rotor Amperes              34.8        29.4          -        High Temperature Alarm
 Inductive (non-motor)              8            8           8        Low Temperature Alarm
 Amperes
                                                                      Alarm Differential
 Pilot Duty VA                     275         450           -
                                                                      Alarm Time Delay
Alarm circuit is 40 VDC, 100 mA maximum.
Alarm requires separate power source.                            Table 5: Ordering Information
Power supply is 24 VAC.                                              Product Code           Description
                                                                     Number
                                                                     MS1DR24T-11C           MS1 DIN Rail Mount Control;
                                                                                            A99BB-200C sensor included;
                                                                                            shipping weight 0.75 lb (340 g)

14   MS Series Product Bulletin
M S2 – Two Stage Electronic
Temperature Control
The MS2 control is designed for 2-stage temperature                Modes of Operation
control applications. These models use the A99B
                                                                        Direct (Cooling)
Series temperature sensors.
      Sensor Common Binary
                                                                        Reverse (Heating)
                    Input
      Process                       Binary        Stage                Deadband (Cooling and Heating)
      Sensor                        Common
                                                                        Independent Setpoint (Cooling and Heating)
               S1 SC D CD                         C2 

                                   Internal to Control             Temperature Management Settings
           V1 V2          C1                                           Multiple Setpoints
                                      Terminal Not Used
            Power     Stage                                            Multiple Differentials (Hysteresis)
            Supply
               Refer to Rating Table for more information.              Low Setpoint Stop
                                                                        High Setpoint Stop
       Figure 13: MS2 DIN Rail Mount Wiring
                                                                        Interstage Time Delay
          Refer to Rating Table for more information.
                                                                        Anti-short Cycle Timers
       Internal to Control
                                         Terminal Not Used
                                                                        Soft Start
        C1               
                     C2            V1 V2 D SC                           Temperature Sensor Offset
                                         Binary                         Temperature Units Used
       Stage       Stage         Power Input    Process
                                   Supply         Sensor                Display Refresh Rate
                               Binary and Sensor Common

                                                                   Alarm Management Settings
        Figure 14: MS2 Panel Mount Wiring
                                                                        High Temperature Alarm
Table 6: Rating Table                                                   Low Temperature Alarm
 Rating Category                   120         240            24
                                                                        Alarm Differential
                                   VAC         VAC           VDC
                                                                        Alarm Time Delay
 Horsepower                        1/4          1/2           -
 Full Load Amperes                 5.8          4.9           -
                                                                   Binary Input Management Settings
 Locked Rotor Amperes              34.8         29.4          -
 Inductive (non-motor)                                                  Binary Input Function Selection
                                     8           8            8
 Amperes                                                                Binary Input Time Delay
 Pilot Duty VA                     275          450           -
                                                                        Setback
Power supply is 24 VAC.
                                                                   Table 7: Ordering Information
                                                                       Product Code           Description
                                                                       Number
                                                                       MS2DR24T-11C           MS2 DIN Rail Mount Control;
                                                                                              A99BB-200C sensor included;
                                                                                              shipping weight 0.79 lb (360 g)
                                                                       MS2PM24T-11C           MS2 Panel Mount Control;
                                                                                              A99BB-200C sensor included;
                                                                                              shipping weight 0.53 lb (240 g)

                                                                                                   MS Series Product Bulletin   15
M S4 – Four Stage Electronic
Temperature Control
The MS4 control is designed for 4-stage temperature                   Modes of Operation
control applications. These controls use the
Johnson Controls/PENN A99B temperature sensor.                             Direct (Cooling)
           Refer to Rating Table for more information.                     Reverse (Heating)
                                                                           Deadband (Cooling and Heating)
                                     Internal to Control                   Independent Setpoint (Cooling and Heating)
          C                    V1 V2 D S2 SC S1
                                                                      Temperature Management Settings
           Stage    Stage
                                 Power                                   Multiple Setpoints
                 Stage             Supply     Process
                               Binary         Sensor                      Multiple Differentials (Hysteresis)
       Common                    Input Binary / Sensor                     Low Setpoint Stop
         Auxiliary Temperature Sensor     Common
                                                                           High Setpoint Stop
         Figure 15: MS4 Panel Mount Wiring                                 Interstage Time Delay
                                                                           Anti-short Cycle Timers
                 Binary Input
       Sensor Common Binary and Sensor Common                              Soft Start
       Process                       Auxiliary                             Heating Reset
       Sensor                        Temperature Stage 
                                      Sensor                               Cooling Reset
                   SC D CD S2                       C2                    Non-compensated Band
          Internal to Control                                              Temperature Sensor Offset
          V1 V2          C1          C4               C3                 Temperature Units Used
                                                                           Display Refresh Rate
                         Stage       Stage        Stage 
        Power Supply
                                          See Rating Table            Alarm Management Settings
              Terminal Not Used           for more information.
                                                                           High Temperature Alarm
       Figure 16: MS4 DIN Rail Mount Wiring                                Low Temperature Alarm
                                                                           Alarm Differential
Table 8: Rating Table                                                      Alarm Time Delay
 Rating Category                   120           240            24
                                   VAC           VAC           VDC    Binary Input Management Settings
 Horsepower                         1/4           1/2             -        Binary Input Function Selection
 Full Load Amperes                  5.8           4.9             -        Binary Input Time Delay
 Locked Rotor Amperes               34.8         29.4             -        Setback
 Inductive (non-motor)               8             8              8
 Amperes                                                              Table 9: Ordering Information
 Pilot Duty VA                      275           450             -       Product Code      Description
                                                                          Number
Power supply is 24 VAC. Relay outputs must not exceed
                                                                          MS4DR24T-11C      MS4 DIN Rail Mount Control;
20 amperes total connected load.
                                                                                            includes one A99BB-200C sensor;
                                                                                            shipping weight 1.17 lb (530 g)
                                                                          MS4PM24T-11C      MS4 Panel Mount Control;
                                                                                            includes one A99BB-200C sensor;
                                                                                            shipping weight 0.90 lb (410 g)

16   MS Series Product Bulletin
Table 10: Replacement Sensor Ordering Information
 Product Code             Operating Range                                    Cable
 Number
 A99BB-200C                                                                  6-1/2 ft (2 m) PVC
 A99BB-300C                                                                  9-3/4 ft (3 m) PVC
 A99BB-500C               -40 to 212oF (-40 to 100oC)                        16-3/8 ft (5 m) PVC
 A99BB-600C                                                                  19-1/2 ft (6 m) PVC
 A99BA-200C                                                                  6-1/2 ft (2 m) Shielded

Table 11: Electrical Ratings of Contacts
 Rating Category                                                 120 VAC                     240 VAC                      24 VDC
 Horsepower                                                          1/4                         1/2                          ---
 Full Load Amperes                                                   5.8                         4.9                          ---
 Locked Rotor Amperes                                               34.8                        29.4                          ---
 Inductive (non-motor) Amperes                                        8                           8                           8
 Pilot Duty VA                                                      275                          450                          ---

Relay outputs must not exceed 20 amperes total connected load. Open collector transistors on the MS1 alarm circuits have a
maximum rating of 40 VDC, 100 mA. Alarm requires separate power source.

S pecifications
                       Product      MS Series One-and Multi-Stage Electronic Temperature Controls
        Power Requirements          3.7 VA @ 24 VAC, 50/60 Hz, Class 2 (20-30 VAC)
                     Accuracy        1.8F°( 1C°)
         Ambient Conditions         Operating:       +14 to +140°F (-10 to +60°C); 0 to 95 % RH (non-condensing)
                                    Storage:         -22 to +176°F (-30 to +80°C); 0 to 95 % RH (non-condensing)
             Agency Listings        UL Recognized: File E194024, CCN XAPX2
                                    Canadian UL Recognized: File E194024, CCN XAPX8
                                    FCC Compliant per Class A Digital Device, Part 15
                                    Canadian DOC Compliant per Class A, Radio Interference Regulations
    Dimensions (H x W x D)          Panel Mount: 1.38 x 2.95 x 2.68 in. (35 x 75 x 68 mm)
                                    DIN Rail:    4.65 x 2.76 x 2.07 in. (118 x 70 x 52.5 mm)
             Shipping Weight        See ordering information in Tables 5, 7, and 9.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls shall not be liable
for damages resulting from misapplication or misuse of its products.

                                                                                                                  www.penncontrols.com

                                                       ® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
                                          United States of America and/or other countries. All other trademarks used herein are the property
                                                      of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved.

                                                                                                          MS Series Product Bulletin      17