FANs 125, 121
                                                                                            Temperature Controls Section A
                                                                                                      Installation Bulletin
                                                                                                               Issue Date 1199

                                             INSTALLATION BULLETIN

           MR4 Refrigeration Temperature/Defrost Control

 IMPORTANT:            All MR4 controls are designed for
                       use only as operating controls.
                       Where an operating control
                                                               W iring
                                                                   !
                       failure would result in personal
                       injury or loss of property, it is the              WARNING: Shock Hazard. To avoid
                       responsibility of the installer to                          possible electrical shock or
                       add devices (safety, limit                                  damage to equipment,
                       controls) or systems (alarm,                                disconnect power supply before
                       supervisory systems) that protect                           wiring any connections.
                       against, or warn of, control
                       failure.                                Follow these wiring guidelines:
                                                                      All wiring must conform to the National Electric
Refer to the MR Series Refrigeration Temperature                       Code and local regulations.
Controls Product Bulletin, LIT-125199, for necessary
information on operation and performance                              Make all wiring connections using adequate gauge
specifications for this product.                                       copper conductors only. Connectors are rated for
                                                                       14-22 AWG wiring.

M ounting                                                                 Process Temperature Sensor
                                                                                Sensor Binary Input Binary Common
The MR4 control is not position-sensitive but should be                        Common
                                                                                                  Evaporator Alarm
mounted for convenient wiring and adjustment.                                                     Temperature
To mount the Panel Mount version, ensure that there                                               Sensor
                                                                               S1 SC D CD S2                  A1 A2
is at least 2 3/4 inches (70 mm) space behind the
                                                                          Terminal Not Used Internal to Control
panel. Make a cutout 1 3/16 x 2 13/16 inches
(29 x 71 mm). Remove retaining clip from the control.                         V1 V2        C1 Fr        C3 Fn         C2 Df
Insert the control into the hole. Install retaining clip and
adjust for tightness.                                                         Power       Compressor Evaporator       Defrost
To mount the DIN Rail Mount version, install the DIN                          Supply                    Fan
rail where appropriate. Snap the control onto the rail                                 Refer to Rating Table for more information.
into position.
                                                                          Figure 1: MR4 DIN Rail Mount Control

R epair and Replacement                                                         Refer to Rating Table for more information.

Field repair of the control should not be made. In case
                                                                                                                Internal to Control
of a defective or improperly functioning control, check
with your nearest authorized Johnson Controls/PENN                        C    Fr   A1 Df Fn           V1 V2     D   S1 SC S2
distributor. When contacting the supplier for
replacement, state the model number of the control.                Common          Defrost      Power Binary
This number can be found on the data plate.                                     Alarm EvaporatorSupply Input
                                                                         Compressor        Fan         Evaporator Temperature
                                                                            Process Temperature Sensor        Sensor

                                                                              Figure 2: MR4 Panel Mount Control

© 1999 Johnson Controls, Inc.                                                                                                         1
  Part No. 24-7664-1687, Rev. A                                                                               www.johnsoncontrols.com
  Code No. LIT-125193
Use Table 1 with function So to compensate for long
sensor leads.                                              P rogramming the Control
Table 1: Sensor Wire Size and Length                       To lock and unlock the unit for programming:
                                                                          Press the Enter, Up, and Down buttons
 18 AWG        20 AWG        22 AWG           Offset                      simultaneously and hold until “- - -” is
                                                                          displayed. Hold for about 10 seconds until the
 300-599 ft    190-374 ft    120 -239 ft      1F°
 91-183 m      58-114 m      36-73 m          1C°                         current temperature is displayed.
 600-899 ft    375-564 ft    240-349 ft       2F°          To change the setpoint:
 183-274 m     114-172 m     73-107 m         2C°                         1.   Hold the Enter button for approximately
 900+ ft       565+ ft       350+ ft          3F°                              3 seconds. The display will change to
 274+ m        172+ m        107+ m           3C°
                                                                               show the setpoint. Release the Enter
Table 2: Rating Table                                                          button.

 Rating Category               120         240      24                    2.   Press the Up or Down button until you
                               VAC         VAC      VDC                        reach the new setpoint.

 Horsepower                    1/4         1/2      -                     3.   Press the Enter button to save the new
 Full Load Amperes             5.8         4.9      -                          setpoint.
 Locked Rotor Amperes          34.8        29.4     -      Note:   If the Enter button is not pressed after selecting the new
 Inductive (non-motor)         8           8        8              setpoint, the new setpoint is not saved. The control reverts
 Amperes
                                                                   to the original setpoint.
 Pilot Duty VA                 275         450      -
                                                           To run the self-test procedure:
Relay outputs must not exceed 20 amperes total
connected load. Power source is 24 VAC. Alarms require      IMPORTANT:              Disconnect loads before self-test
                                                                                    procedure. Cycle power to resume
separate external power source.
                                                                                    normal operation.

F CC Compliance                                                           Press the Up and Down buttons in sequence,
                                                                          and hold for 5 seconds.
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to   To begin a manual defrost cycle:
Part 15 of the FCC Rules. These limits are designed to                    Hold the Defrost button for 3 seconds.
provide reasonable protection against harmful
interference when the equipment is operated in a
commercial environment. This equipment generates,          To begin a deep freeze cycle:
uses, and can radiate radio frequency energy and, if                      Press the Enter and Up buttons in sequence
not installed and used in accordance with the
                                                                          and hold both for 5 seconds. The compressor
instruction manual, may cause harmful interference to
                                                                          status LED will light.
radio communications. Operation of this equipment in
a residential area is likely to cause harmful              To program values other than setpoint:
interference, in which case the user will be required to                  1.   Hold the Enter button for about 10
correct the interference at his/her own expense.                               seconds. The display changes to HY.
                                                                          2.   Press the Up or Down button until the
C   anadian DOC Compliance                                                     desired parameter is displayed.
This digital apparatus does not exceed the Class A                        3.   Press the Enter button. The parameter’s
limits for radio noise emissions from digital apparatus                        current value is displayed.
set out in the Radio Interference Regulations of the
                                                                          4.   Press the Up or Down button until the
Canadian Department of Communications.
                                                                               desired value is shown.

D  isplay
Press Up and Down buttons to scroll through process
                                                                          5.   Press the Enter button to save the new
                                                                               value. After 10 seconds of inactivity, the
temperature, binary input status (On or OF), and                               display will return to its normal function.
auxiliary temperature sensor reading (F2 if none). After   Note:   If the Enter button is not pressed after selecting the new
15 seconds of inactivity, the display shows the process            value, the new value is not saved. The control reverts to the
temperature.                                                       previous value.

2   A—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin
Table 3: Functions and Settings
Function                              Description                                              Setting Range                    Default
SI:    Setpoint                       Primary temperature setpoint at which compressor         -40 to 158°F (-40 to 70°C)         ---
                                      control contacts open on temperature fall
HY: Hysteresis (Differential)         Temperature difference relative to setpoint at which     1 to 9 F° (1 to 9 C°)               5
                                      compressor control contacts close on temperature rise
LL:   Low Setpoint Stop               High setpoint adjustment limit                           -40°F (-40°C) to HL                -25

HL: High Setpoint Stop                Low setpoint adjustment limit                            LL to 158°F (70°C)                 40

CC: Anti-short Cycle Delay            Minimum time between two compressor On cycles            0 to 9 minutes                      1

Co: Deep Freezing Time                Time compressor forced On during deep freeze             0 to 99 minutes                    60

AH: High Temperature Alarm            Temperature above setpoint where alarm is initiated      0 to 50 F° (0 to 50 C°)            10

AL: Low Temperature Alarm             Temperature below setpoint where alarm is initiated      -50 to 0 F° (-50 to 0 C°)          -10

Ad: Alarm Differential                Temperature difference between alarm On and Off          1 to 9 F° (1 to 9 C°)               5

At:   Alarm Time Delay                Delay between alarm detection and activation             0 to 99 minutes                     3

dF: Defrost Type                      Select defrost type                                      0 = electric heater                 0
                                                                                               1 = hot gas
dE: Defrost End Mode                  Defrost termination type; note that defrost cycle always 0 = time                            1
                                      ends after time set for dd                               1 = temperature
dt:   Defrost Termination             Only used when dE = 1; defrost ends when                 32 to 68°F (0 to 20°C)             55
      Temperature                     temperature reaches dt
di:   Defrost Interval                Time between two subsequent defrost cycles; when         1 to 99 hours                       7
                                      di=1 hour, dd cannot exceed 40 min.
dd: Maximum Defrost Duration          Defrost ends after this time, even if defrost end        0 to 99 minutes                    45
                                      temperature has not been reached; 0 disables defrost
dC: Dripping Time                     Time compressor stopped after defrost so evaporator      0 to 99 minutes                     5
                                      can drip
dU: First Defrost After Power Up Time first defrost is delayed after power up                  OF, 0 to 99 minutes              OF (Off)
dP: Display During Defrost            Temperature displayed during defrost cycle               0 = last reading                    0
                                                                                               1 = setpoint
dr:   Display Delay After Defrost     Time after defrost before sensed temperature displays    1 to 99 minutes                    20

iF:   Binary Input Function           Configuration for normally closed binary input           0 = none                            0
                                                                                               1 = compres. off, alarm on
                                                                                               2 = alarm on
                                                                                               3 = fan off, alarm on, AH
                                                                                               and AL disabled.
id:   Binary Input Time Delay         Time between binary input detection and enabling of      0 to 99 minutes                     0
                                      the function set through iF
FF: Fan Operating Function            Fan operation; note that the fan is always Off during    0 = parallel with compres.          0
                                      the defrost cycle                                        1 = always on
Fd: Fan Start-up Delay (After         Time after defrost that fan is switched On, even if      0 to 99 minutes                     5
    Defrost)                          temperature set through Fr has not been reached
Fr: Fan Start Temperature After       Evaporator sensor temperature at which the fan is        -22 to 41°F (-30 to 5°C)           40
    Defrost End                       switched On after a defrost cycle
SF: Sensor Failure Operation          Control function after a sensor or sensor wire failure   0 = compressor on                   2
                                                                                               1 = compressor off
                                                                                               2 = based on last 4 cycles
So:   Temperature SensorOffset        Compensate for long sensor leads                         -20 to 20 F° (-20 to 20 C°)         0

Un: Temperature Units Used            Temperature units used                                   0 = °C                  1 = °F      1

PU: Display Refresh Rate              Time after which display is refreshed                    1 to 99 seconds                     1

                                          A—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin                            3
A larm and Fault Codes
Table 4: Error Codes and Status
 Error Code (Codes will flash on the display.)                    System Status

 F1 Open or shorted temperature sensor                            Alarm output On. Compressor runs according to SF. Cycle power
                                                                  to reset.
 F2 Open or shorted evaporator sensor                             Alarm output On. Defrost cycle controlled by di and dd. Correct
                                                                  problem to reset.
 A1 Binary input open for longer than id and iF = 1               Compressor output Off. Alarm output On. Correct problem to
                                                                  reset.
 A2 Binary input open for longer than id and iF = 2               Alarm output On. Correct problem to reset.
 A3 Binary input open for longer than id and iF = 3               Fan output Off. Alarm output On. AH and AL disabled. Correct
                                                                  problem to reset.
 HI    Temperature has reached or exceeded                        Alarm output On. Correct problem to reset.
       (setpoint + AH)
 LO Temperature has reached or fallen below                       Alarm output On. Correct problem to reset.
    (setpoint – AL)
 EE Program failure                                               Alarm output On. Other outputs Off. Replace control.

O rdering Information
Table 5: Specifications
 Power Requirements                3.7 VA @ 24 VAC 50/60 Hz, Class 2 (20-30 VAC)
 Ambient Conditions                Operating       14 to 140oF (-10 to 60oC); 0 to 95% RH (non-condensing)
                                   Storage         -22 to 176oF (-30 to 80oC); 0 to 95% RH (non-condensing)
 Accuracy                          +1.8 F (+ 1C)
 Agency Listings                   UL Recognized: File E194024, CCN XAPX2
                                   Canadian UL Recognized: File E194024, CCN XAPX8
                                   FCC Compliant per Class A Digital Device, Part 15
                                   Canadian DOC Compliant per Class A, Radio Interference Regulations

Table 6: Ordering Information
 Product Code Number               Description
 MR4PM24-12C                       MR4 Panel Mount Control; 2 A99BB-200C sensors included
 MR4DR24-12C                       MR4 DIN Rail Mount Control; 2 A99BB-200C sensors included
 A99BB-200C                        Replacement Sensor, lead length: 6-1/2 ft (2 m)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be
liable for damages resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                               Printed in U.S.A.
Milwaukee, WI 53201                                                                                                www.johnsoncontrols.com

4     A—MR4 Refrigeration Temperature/Defrost Control Installation Bulletin