                                             INSTALLATION BULLETIN

                    MR1 Refrigeration Temperature Control

 IMPORTANT:            All MR1 controls are designed for
                       use only as operating controls.
                       Where an operating control
                                                               W iring
                       failure would result in personal            !
                       injury or loss of property, it is the
                                                                          WARNING: Shock Hazard. To avoid
                       responsibility of the installer to
                                                                                   possible electrical shock or
                       add devices (safety, limit
                                                                                   damage to equipment,
                       controls) or systems (alarm,
                                                                                   disconnect power supply before
                       supervisory systems) that protect
                                                                                   wiring any connections.
                       against, or warn of, control
                       failure.
                                                               Follow these wiring guidelines:
Refer to the MR Series Refrigeration Temperature                      All wiring must conform to the National Electric
Controls Product Bulletin, LIT-125199, for necessary                   Code and local regulations.
information on application, operation and performance
specifications for this product.                                      Make all wiring connections using adequate gauge
                                                                       copper conductors only. Connectors are rated for
                                                                       14-22 AWG wiring.
M ounting                                                               Process
                                                                        Temperature
The MR1 control is not position sensitive but should be                 Sensor         Sensor
                                                                                                   Alarm
                                                                                                                +
mounted for convenient wiring and adjustment.                                                                   -
                                                                                      Common
To mount the DIN Rail Mount version, install the DIN                          S1 SC                   A1 A2
rail where appropriate. Snap the control onto the rail in
position.                                                                Terminal Not Used                          Internal to
                                                                                                                     Control
                                                                          V1 V2         C    Fr

                                                                                      Compressor           Refer to Rating Table
                                                                          Power                            for more information.
                                                                          Supply

                                                                          Figure 1: MR1 DIN Rail Mount Control

© 1999 Johnson Controls, Inc.                                                                                                      1
  Part No. 24-7664-1709, Rev. A                                                                             www.johnsoncontrols.com
  Code No. LIT-125196
Use Table 1 with function So to compensate for long
sensor leads.                                              P rogramming the Control
Table 1: Sensor Wire Size and Length                       To lock and unlock the unit for programming:
     Wire Size and Cable Length                                           Press the Enter, Up, and Down buttons
                                                  Offset                  simultaneously and hold until “- - -” is
 18 AWG          20 AWG       22 AWG                                      displayed. Hold for about 10 seconds until the
                                                                          current temperature is displayed.
 300-599 ft      190-374 ft   120 -239 ft          1F°
 91-183 m        58-114 m     36-73 m              1C°
                                                           To change the setpoint:

 600-899 ft      375-564 ft   240-349 ft           2F°                    1.   Hold the Enter button for approximately
 183-274 m       114-172 m    73-107 m             2C°                         3 seconds. The display will change to
                                                                               show the setpoint. Release the Enter
 900+ ft         565+ ft      350+ ft              3F°
                                                                               button.
 274+ m          172+ m       107+ m               3C°
                                                                          2.   Press the Up or Down button until you
Table 2: Rating Table                                                          reach the new setpoint.

 Rating Category                 120        240      24
                                 VAC        VAC      VDC                  3.   Press the Enter button to save the new
                                                                               setpoint.
 Horsepower                      1/4        1/2      ---
 Full Load Amperes               5.8        4.9      ---   Note:   If the Enter button is not pressed after selecting the new
 Locked Rotor Amperes            34.8       29.4     ---           setpoint, the new setpoint is not saved. The control reverts
 Inductive (non-motor)                                             to the original setpoint.
                                 8          8        8
 Amperes                                                   To run the self-test procedure:
 Pilot Duty VA                   275        450      ---
                                                            IMPORTANT:              Disconnect loads before self-test
Open collector transistors on MR1 alarms have a                                     procedure. Cycle power to resume
maximum rating of 40 VDC 100 mA. Alarms require                                     normal operation.
separate power source. Power source is 24 VAC.
                                                                          Press the Up and Down buttons in sequence,
                                                                          and hold for 5 seconds.
F CC Compliance                                            To begin a deep freeze cycle:
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to                  Press the Enter and Up buttons in sequence
Part 15 of the FCC Rules. These limits are designed to                    and hold both for 5 seconds. The compressor
provide reasonable protection against harmful                             status LED will light.
interference when the equipment is operating in a          To program values other than setpoint:
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if                      1.   Hold the Enter button for about 10
not installed and used in accordance with the                                  seconds. The display changes to HY.
instruction manual, may cause harmful interference to                     2.   Press the Up or Down button until the
radio communications. Operation of this equipment in
                                                                               desired parameter is displayed.
a residential area is likely to cause harmful
interference, in which case the user will be required to                  3.   Press the Enter button. The parameter’s
correct the interference at his/her own expense.
                                                                               current value is displayed.
                                                                          4.   Press the Up or Down button until the
C   anadian DOC Compliance                                                     desired value is shown.

This digital apparatus does not exceed the Class A                        5.   Press the Enter button to save the new
limits for radio noise emissions from digital apparatus                        value. After 10 seconds of inactivity, the
set out in the Radio Interference Regulations of the                           display will return to its normal function.
Canadian Department of Communications.                     Note:     If the Enter button is not pressed after selecting the new
                                                                     value, the new value is not saved. The control reverts to
                                                                     the previous value.

2   A—MR1 Refrigeration Temperature Control Installation Bulletin
Table 3: Functions and Settings
 Function                      Description                               Setting Range                Default
 SI:   Setpoint                Primary temperature setpoint at which     -40 to 158°F (-40 to 70°C)     ---
                               compressor control contacts open on
                               temperature fall
 HY: Hysteresis                Temperature difference relative to        1 to 9 F°(1 to 9 C°)            5
     (Differential)            setpoint at which compressor control
                               contacts close on temperature rise
 LL: Low Setpoint Stop         Low setpoint adjustment limit             -40°F(-40°C) to HL             -25
 HL: High Setpoint Stop        High setpoint adjustment limit            LL to 158°F (70°C)             40
 CC: Anti-Short Cycle Delay    Minimum time between two compressor       0 to 9 minutes                  1
                               On cycles
 Co: Deep Freezing Time        Time compressor forced On during deep     0 to 99 minutes                60
                               freeze
 AH: High Temperature          Temperature above setpoint where alarm 0 to 50 F°(0 to 50 C°)            10
     Alarm                     is initiated
 AL: Low Temperature           Temperature below setpoint where alarm    -50 to 0 F°(-50 to 0 C°)       -10
     Alarm                     is initiated
 Ad: Alarm Differential        Temperature difference between alarm      1 to 9 F°(1 to 9 C°)            5
                               On and Off
 At:   Alarm Time Delay        Delay between alarm detection and         0 to 99 minutes                 3
                               activation
 SF: Sensor Failure            Control function after a temperature      0 = compressor on               2
     Operation                 sensor failure                            1 = compressor off
                                                                         2 = based on last
                                                                             four cycles
 So: Temperature Sensor        Compensate for long sensor leads          -20 to 20 F°(-20 to 20 C°)      0
     Offset
 Un: Temperature Units         Temperature units used                    0 = °C                          1
     Used                                                                1 = °F
 PU: Display Refresh Rate      Time after which display is refreshed     1 to 99 seconds                 1

R    epair and Replacement
Field repair must not be made. In case of defective or          When requesting a replacement, reference the model
improperly functioning control, contact your nearest            number found on the data plate of the control.
authorized Johnson Controls/PENN distributor.

                                                 A—MR1 Refrigeration Temperature Control Installation Bulletin       3
A larm and Fault Codes
Table 4: Error Codes and Status
 Error Code (Codes will flash on the display.)                    System Status

 F1 Open or shorted temperature sensor                            Alarm output On. Compressor runs according to SF. Cycle
                                                                  power to reset.
 HI    Temperature has reached or exceeded                        Alarm output On. Correct problem to reset.
       (setpoint + AH)
 LO Temperature has reached or fallen below                       Alarm output On. Correct problem to reset.
    (setpoint – AL)
 EE Program failure                                               Alarm output On. Other outputs Off. Replace control.

O rdering Information
Table 5: Specifications
 Power Requirements            3.7 VA @ 24 VAC, 50/60 Hz, Class 2 (20-30 VAC)
 Ambient Conditions            Operating       14 to 140oF (-10 to 60oC); 0 to 95% RH (non-condensing)
                               Storage         -22 to 176oF (-30 to 80oC); 0 to 95% RH (non-condensing)
 Accuracy                      +1.8 F (+1 C)
 Agency Listings               UL Recognized: File E194024, CCN XAPX2
                               Canadian UL Recognized: File E194024, CCN XAPX8
                               FCC Compliant per Class A Digital Device, Part 15
                               Canadian DOC Compliant per Class A, Radio Interference Regulations

Table 6: Ordering Information
 Product Code                  Description
 Number
 MR1DR24-11C                   MR1 DIN Rail Mount Control; A99BB-200C sensor included
 A99BB-200C                    Replacement Sensor, cable length: 6-1/2 ft (2 m)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be
liable for damages resulting from misapplication or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                               Printed in U.S.A.
Milwaukee, WI 53201                                                                                                www.johnsoncontrols.com

4     A—MR1 Refrigeration Temperature Control Installation Bulletin