Technical Bulletin          Medium User Interface (MUI)
                                                                                 Issue Date           October 21, 2009

                                   Medium User Interface (MUI)
                                           Version 3

Introduction to MUI................................................................................3

    Introduction .........................................................................................................3

    Key Concepts ......................................................................................................4
    MUI Features .................................................................................................................... 4

Installation..............................................................................................7

    Introduction .........................................................................................................7
    North American Emissions Compliance ........................................................................... 8

    Key Concepts ......................................................................................................9
    MUI Dimensions ............................................................................................................... 9

    Detailed Procedures .........................................................................................10
    Mounting the MUI on a Wall or Surface.......................................................................... 10
    Mounting the MUI in a Panel .......................................................................................... 12
    Connecting the MUI to the FX Controller ........................................................................ 14
    Connecting the MUI to an FXVMA Controller ................................................................. 16

Operation..............................................................................................17

    Introduction .......................................................................................................17

    Key Concepts ....................................................................................................18

    Detailed Procedures .........................................................................................19
    Page Navigation ............................................................................................................. 19
    Accounts ......................................................................................................................... 22
    Data Points ..................................................................................................................... 25
    System Data ................................................................................................................... 26
    Event Notification and Management ............................................................................... 27
    Trend .............................................................................................................................. 31
© 2009 Johnson Controls, Inc.
  Code No. LIT-12011577                                                                                   www.johnsoncontrols.com
2                                            Medium User Interface (MUI) Version 3 Technical Bulletin

    Scheduler and Calendar ................................................................................................. 33
    Communication Resources............................................................................................. 37
    FXVMA Support.............................................................................................................. 41
    Downloading the Display Configuration to the MUI ........................................................ 42

    Troubleshooting................................................................................................44

Technical Specifications.....................................................................45

    Ordering Codes.................................................................................................45

    Technical Specifications ..................................................................................46
Medium User Interface (MUI) Version 3 Technical Bulletin                                  3

Introduction to MUI

Introduction

                                                      Figure 1: MUI
                       The MUI is a remote user interface device for the FX Platform that
                       supports FX06, FX07, FX14, FX15, FX16, and FXVMA controllers.
                       You can use the MUI as a portable hand held unit, or permanently
                       mount it in a panel or on the wall.
                       The MUI provides an easy way for the building operator or
                       maintenance engineer to monitor and adjust the operation of the FX
                       field controller. You can configure the MUI to receive event and alarm
                       messages, to change time schedules, and to display event and trend log
                       data. Access to data and operating commands are controlled by
                       passwords.
                       With the FXVMA, the MUI functions as an airflow balancing tool to
                       support the commissioning of Variable Air Volume (VAV) units.
                       The MUI presents data in a text format on a 4-line x 26-character
                       backlit Liquid Crystal Display (LCD) and on an array of Light-Emitting
                       Diodes (LEDs) for quick recognition of equipment operating status.
                       The format of the MUI is fully configurable using the FX Builder
                       software package.
                       The MUI is a cost-effective solution for monitoring, commissioning,
                       and servicing your building control system installation.
4                        Medium User Interface (MUI) Version 3 Technical Bulletin

Key Concepts
MUI Features

                                       Figure 2: MUI Features

               Features
               The MUI has the following features:
               •   Provides a configurable user interface with a 4-line x 26-character
                   LCD backlit display, 10 status LEDs, 6 control keys, and an integral
                   buzzer.
               •   Manages passwords for up to eight user profiles and three levels of
                   access to provide protection against unauthorized use.
               •   Uses menu-driven navigation for easy and intuitive operation –
                   select from a list of functions and data point names to monitor and
                   control the system.
               •   Allows the customization of the control key functions to create
                   short-cut access to the most commonly viewed pages or control and
                   system parameters, and to set key combinations for frequently used
                   actions such as alarm acknowledge.
               •   Provides ten configurable front panel LEDs that indicate status of
                   equipment, alarms, and operating modes.
               •   Provides access to the time schedulers and calendars in the FX
                   controller, and allows you to modify start and stop times, associated
                   days of the week, exception days, and holidays.
               •   Sends immediate notification of events and alarms on the LCD
                   screen with a dedicated LED alarm indicator and buzzer. Press any
                   key to clear the screen and silence the buzzer. Access to the
                   acknowledgement function for events and alarms normally requires
                   password clearance.
               •   Maintains an Event Summary of data points currently in the active
                   or alarm state, or inactive but not acknowledged.
               •   Maintains an Event History of the events, both to the active or alarm
                   state and to the inactive state, with a record of the acknowledgement
                   details.
Medium User Interface (MUI) Version 3 Technical Bulletin                                       5

                       •   Shows the Trend data that the controller is collecting for
                           monitoring, trouble-shooting, and diagnostic purposes.
                       •   Allows you to view and modify parameters and destinations for
                           remote communication functions of the FX controller.
                       •   Allows you to view and modify parameters for the airflow balancing
                           feature of the FXVMA controller.
                       •   Allows customization of the menus, pages, and display format of the
                           data using the FX Builder software.

                       Connection to FX Controller
                       The MUI connects to the FX controller through the Remote Display
                       port of the FX controller, or the Remote Sensor Port on the FXVMA
                       controller. In FXVMA applications, you can also connect the MUI to a
                       Network Room Module (NRM) with a MUI type service port
                       connection.
                       The MUI is a slave network display unit of the FX controller and
                       receives its configuration database and active control data directly from
                       the controller over the remote display or sensor bus.
                       Use the keypads and menu navigation system on the LCD display to
                       access the data stored locally on the MUI, such as the Event History,
                       and the active data and configuration parameters that are available in
                       the connected FX controller.

                       Display Configuration
                       You can configure the MUI’s display layout for the specific control
                       application in the controller.
                       The display configuration is built using a set of dedicated windows and
                       templates (commonly called plug-ins) in the FX Builder software.
                       With the display configuration plug-in, the user:
                       •   creates and formats the display pages
                       •   associates the pages to items on the entry menu for easy navigation
                           and control
                       •   defines the keypad button tasks used as short-cut access paths to
                           pages, or to acknowledge alarms
                       •   defines the use of the LED indicators
                       •   maps controller data points and parameters to the display pages
                           describing them by point names (or tags), units of measure
                           (numeric) or logical (binary), or multi-state state names
6              Medium User Interface (MUI) Version 3 Technical Bulletin

    •   defines which specific points can be commanded (adjusted or
        overridden) by the user with specific editing ranges and password
        levels
    •   configures events and alarms by defining the alarm messages,
        triggering conditions, setting priority levels, and defining the events
        that require acknowledgement before an active event or alarm can
        be reset
    •   defines the names of schedulers and calendars
    •   defines the trend logs that are displayed
    •   defines user account profiles for password entry and authorization to
        acknowledge events, change parameters, and issue commands
    The FX controller stores the display configuration database. When you
    connect a MUI to an FX controller, the controller downloads the display
    configuration part of the control application to the display unit.
    FX Builder designs the FX control application, including the MUI’s
    display configuration. The control application and display configuration
    are then downloaded to the FX controller through its network
    communication interface, which may use the N2 Open, LON, or
    BACnet® protocol.
    When you download a pre-configured standard application for the
    FXVMA, the MUI display application is already built-in; therefore, the
    MUI provides the airflow balancing data and command functions when
    it is connected to the FXVMA controller. Refer to the Single Duct
    Variable Air Volume (VAV-SD) Box Controller Application Note
    (LIT-12011436) for information on using the MUI to monitor and
    commission the FXVMA controller, and air balance the VAV box.
Medium User Interface (MUI) Version 3 Technical Bulletin                                           7

Installation

Introduction
                       IMPORTANT: Use this Medium User Interface only as an operating control.
                       Where failure or malfunction of the MUI could lead to personal injury or
                       property damage to the controlled equipment or other property, additional
                       precautions must be designed into the control system. Incorporate and
                       maintain other devices, such as supervisory or alarm systems or safety or limit
                       controls, intended to warn of or protect against failure or malfunction of the
                       MUI.

                       IMPORTANT: The installation of electrical wiring must conform to local
                       codes and should be carried out by authorized personnel only. Users should
                       ensure that all Johnson Controls® products are used safely and without risk to
                       health or property.

                       IMPORTANT: Cables and wiring at Safety Extra-Low Voltage (SELV) and
                       Class 2 wiring (North America) must be separated from power line voltage
                       wiring. A minimum separation distance of 30 cm (12 in.) is recommended. Do
                       not run extra low voltage cables parallel to power line voltage cables for long
                       distances greater than 3 m (9.8 ft). Do not run extra low voltage wiring close to
                       transformers or high frequency generating equipment.

                       The MUI connects to the FX06, FX07, FX14, FX15, FX16, and
                       FXVMA controllers. An FX Controller with an integral display
                       (2 X 4 LCD or integral MUI) supports one additional MUI—either the
                       local panel mount version, or the remote mount version. An FX
                       controller without an integral display supports one or two MUI units.
                       One of the MUIs can be the local panel version and be powered by the
                       controller.
                       The local panel mount MUI has the ordering code LP-DIS60P20-0C
                       and mounts in a panel up to 3 m (9.8 ft) from the controller using one of
                       the pre-assembled cable kits:
                       •   LP-KIT007-005C – for the FX06 controller
                       •   LP-KIT007-000C – for the other FX controllers
                       •   For FXVMA – see Connecting the MUI to an FXVMA Controller
8                       Medium User Interface (MUI) Version 3 Technical Bulletin

              The cable provides power and communication from the controller to the
              MUI.
              The remote wall mount MUI has the ordering code LP-DIS60P21-0C
              and mounts on the wall or in a panel up to 300 m (1,000 ft) from the
              controller. The remote MUI requires a local power supply; the
              communications cable must be supplied by the installer. For this MUI,
              the communication interface is isolated from the power supply to
              provide reliable operation at the remote location.
              This chapter describes how to:
              •   mount the MUI on a wall
              •   mount the MUI in a panel
              •   install the cable and connect the panel and wall mount versions of
                  the MUI
North American Emissions Compliance
              United States
              This equipment has been tested and found to comply with the limits for
              a Class A digital device pursuant to Part 15 of the FCC Rules. These
              limits are designed to provide reasonable protection against harmful
              interference when this equipment is operated in a commercial
              environment. This equipment generates, uses, and can radiate radio
              frequency energy, and if not installed and used in accordance with the
              instruction manual, may cause harmful interference to radio
              communications. Operation of this equipment in a residential area is
              likely to cause harmful interference, in which case the user is required
              to correct the interference at his/her own expense.

              Canada
              This Class (A) digital apparatus meets all the requirements of the
              Canadian Interference-Causing Equipment Regulations.
              Cet appareil numérique de la Classe (A) respecte toutes les exigences
              du Règlement sur le matériel brouilleur du Canada.
Medium User Interface (MUI) Version 3 Technical Bulletin                                                             9

Key Concepts
MUI Dimensions
                       Figure 3 shows the overall dimensions of the MUI. For panel cut-out
                       dimensions or wall bracket drill hole spacing, see
                       Detailed Procedures in this chapter.

                       Minimum Required Mounting Clearance
                       Wall mounting requires a minimum of 45 mm (1.8 in.) free space in
                       front of the mounting surface for clearance from nearby objects, such as
                       sliding doors or movable panels, or for clearance within a protective
                       enclosure or cover.
                       Panel mounting requires a minimum of 45 mm (1.8 in.) free depth
                       behind the panel for the plug-in connectors at the rear.

                                                                                           .5 7)
                                                                                  4 0 (1

                            72 (2.83)

                                                                             )
                                                                       7. 28
                                                              1 85 (

                                                            Wall Mounting

                                                                                               7)
                                                                                      40 ( 1. 5

                                                                                   58 (2.28)

                            72 (2.83)

                                                                                               FIG: mui_dimensions
                                                                    (7    .64 )
                                                               19 4

                                                            Panel Mounting

                                         Figure 3: MUI Dimensions, mm (in.)
10                         Medium User Interface (MUI) Version 3 Technical Bulletin

Detailed Procedures
Mounting the MUI on a Wall or Surface
               The MUI remote wall mount version has the ordering code
               LP-DIS60P21-0C. This version has an isolated power supply and can
               be mounted up to 300 m (1,000 ft) from the controller. The MUI
               requires an independent power supply of 12 to 24 VAC at 3.5 VA, or
               9 to 48 VDC at 200 mA maximum.
               1. Carefully remove the MUI panel mount bezel (if fitted): release the
                  b tabs (see Figure 8) and pull the bezel away from the MUI unit.
               2. To open the MUI, press the two retaining lugs (indicated by the
                  arrows in Figure 4) and pull the MUI cover away from the base.

                                                                                                      FIG: mui_w_02

                                            Figure 4: Opening the MUI
                3. Drill holes and insert plugs (anchors) as necessary, and mount the
                   base to the wall or surface with a minimum of two screws located
                   on opposite sides of the center of the base. Ensure that the base is
                   correctly positioned over the cable entry. The mounting hole
                   locations and dimensions are shown in Figure 5.
                                                                155 (6.10)

                                                                83.4 (3.3)

                                                                60 (2.4)

                                                                 4 (.16)

                                               4.5 (.18)

                      42 (1.65)

                                  6 (.24)                                             FIG: mui_w_03

                                             Cable Entry Area

                           Figure 5: MUI Wall Mount Dimensions, mm (in.)
Medium User Interface (MUI) Version 3 Technical Bulletin                                              11

                          !   CAUTION:          Risk of Electric Shock. Disconnect power supply
                       before making electrical connections to avoid electric shock.

                        4. Connect the power and communication cables to the terminal block
                           as shown in Figure 6.
                        5. Replace the MUI cover on the base by first inserting the two lugs
                           on the right side of the cover below the corresponding lips of the
                           base. Then close the MUI pushing on the left side as indicated by
                           the arrow in Figure 6. Make sure that the pins on the circuit board
                           in the cover engage correctly into the terminal block in the base.

                                      V Com (-)

                                      V   /~ (+)

                                      RT Com

                                      RT-

                                      RT+

                                                                                            FIG: mui_w_04

                                      Figure 6: Wiring and Reassembly Details
12                        Medium User Interface (MUI) Version 3 Technical Bulletin

Mounting the MUI in a Panel
               The panel mounting kit is supplied with both the panel mount version
               with ordering code LP-DIS60P20-0C, and the remote wall mount
               version with ordering code LP-DIS60P21-0C.
               The panel mount version is non-isolated and can be mounted up to 3 m
               (9.8 ft) from the controller. Available to order are cables that connect
               power and communications from the controller. See Ordering Codes.
               The remote wall mount version can also be mounted in a panel up to
               300 m (1,000 ft) from the controller. The MUI has an isolated power
               supply and requires an independent power supply of
               12 to 24 VAC at 3.5 VA, or 9 to 48 VDC at 200 mA maximum.
               Note:     When mounting the remote wall mount version in a panel, the
               wiring must be completed before fixing the display in the panel. Follow
               the instructions for Mounting the MUI on a Wall or Surface, but omit
               step 3.

               1. Carefully remove the panel mount bezel: release the b tabs
                  (see Figure 8) and pull the bezel away from the MUI unit. Fit the
                  two gaskets into the bezel (if not already installed).
               2. Use the cut-out dimensions shown in Figure 7 and insert the panel
                  mount bezel from the front side of the panel, and the MUI unit from
                  the other side.

                                                                                                                         )
                                                                                                                 0 2-0. 0
                                                                                                             + 0.
                                                                                                   (7 .3 2
                                                                                          - 0 .0
                                                                                    + 0 .5
                                                                             1 86

                                      50 + 0.5-0.0 (1.97 + 0.02-0.0)

                                                                       Maximum Panel Thickness = 5 mm (0.20 in.)             FIG: mui_p_02

                           Figure 7: Panel Cut-out Dimensions, mm (in.)
               3. Hold the MUI firmly against the back of the panel and press the
                  bezel until it clicks into place at the six points (a and b) indicated by
                  the arrows in Figure 8. Ensure that the b tabs are engaged with the
                  lugs on the display base.
Medium User Interface (MUI) Version 3 Technical Bulletin                                                                 13

                                                                                                         FIG: mui_p_03
                                                                                 a

                                                                                                                         b

                                          Figure 8: Fitting the MUI in a Panel
                       4. Hold the panel mount bezel of the MUI firmly against the front of
                          the panel and insert the four locking clips as indicated in Figure 9.
                          Ensure that the side clips are pressed firmly against the panel.

                                                                                         FIG: mui_p_04

                                        Figure 9: Securing the MUI in a Panel
                       To assure IP54 enclosure protection, verify that:
                       •   The cut-out dimensions are within tolerances.
                       •   The panel surface is clean and flat.
                       •   The two gaskets are properly fitted to the MUI panel mount bezel.
                       For the local panel mount version, use the appropriate cable kit to
                       connect the MUI to the FX controller (see Table 5).
                       For the remote mount version, wire the MUI to the controller as
                       described in Connecting the MUI to the FX Controller.
14                                    Medium User Interface (MUI) Version 3 Technical Bulletin

Connecting the MUI to the FX Controller

                           !    CAUTION:          Risk of Electric Shock. Disconnect power supply
                         before making electrical connections to avoid electric shock.

                         An FX Controller with an integral display (2X4 LCD or integral MUI)
                         supports one additional MUI. An FX controller without an integral
                         display supports one or two MUIs, but only one panel mount MUI. Two
                         MUIs operate in parallel with the same data presentation format.
                         Figure 10 shows the cabling of a panel mount MUI with the cable kit,
                         and the cabling of a second remote MUI with field prepared cables.
                         Figure 11 shows the cabling of two remote wall mount MUIs with field
                         prepared cables.
                                       MUI (1)

                                                                               MUI (2)

                            Max 3 m (9.8 ft)               Max 300 m (1,000 ft)

         FX Controller

                                                                      To Power Supply
                                                                       9 ÷ 48 VDC
                                                                      12 ÷ 24 VAC

                                                                            To MUI (1)

         FX Controller                                   To MUI (2)
                                                                                         V Com (-)
                                                                                         V     /~ (+)

                                                                                                        FIG: mui_007_remote_wall
                                Com
                                                                                         RT Com
                                RT-
                                                                                         RT-
     Com +16V LL- LL+           RT+                                                      RT+

                               Figure 10: Installation of a Local Panel Mount and a
                                             Remote Wall Mount MUI
Medium User Interface (MUI) Version 3 Technical Bulletin                                                         15

                              !   CAUTION:          Risk of Electric Shock. Disconnect power supply
                           before making electrical connections to avoid electric shock.

                                          Max 300 m (1,000 ft) Total Length

                                          MUI (1)                              MUI (2)

        FX Controller

                                    To Power Supply                           To Power Supply
                                     9 ÷ 48 VDC                                9 ÷ 48 VDC
                                    12 ÷ 24 VAC                               12 ÷ 24 VAC

        FX15 Universal

       m
       ocV9+-LL+LL

    LL+ LL- +9V Com
             (not used)

        FX Controller              To FX Controller        To MUI (2)         To MUI (1)

                                                                                   V Com (-)
                                                                                   V /~(+)

                                                                                                FIG: mui_008_two_remote
                                                                                   RT Com
    Com +16V LL- LL+                                                               RT-
                                                                                   RT+
       (not used)

                          Figure 11: Installation of Two Remote Wall Mount MUIs
16                            Medium User Interface (MUI) Version 3 Technical Bulletin

Connecting the MUI to an FXVMA Controller
               The MUI connects to the Remote Sensor Port on the FXVMA
               controller. You can purchase a cable, or assemble field-prepared cables.
               Use a 6-conductor (26-28 AWG stranded copper wire) cable with
               6-position modular plugs (RJ-12) at each end wired according to
               Figure 13.

                                                          Tool Port

                                                 Pin Number Assignment for
                                                   Straight-Through Cable
                                                    6 5 4 3 2 1

                                                     Printed Circuit Board

                                                                                     FIG: tool_port
                                                        R  +
                                                RT  Un T -
                                                       us
                                                    Un ed
                                                   C use
                                                    om d
                                                       m
                                                   +1 on
                                                     5 VD C

                                       Figure 12: MUI Tool Port Socket
                                       (6-pin Modular Jack Connector)

                                                                                                      65
                                                                                                           43
                                                                                                                2
                                                                                                                    1
                                        Pinout connections from
                                            MUI to FXVMA
                                               6 to 1
                                               5 to 2
                                               4 to 3
                                               3 to 4
                                               2 to 5
                                               1 to 6

                                                              Max 3 m (9.8 ft)

                                                                                     FIG: 6-pin_cbl

               12               RJ-12 Modular Plugs on each end
                    34
                         56

                Figure 13: 6-conductor (26-28 AWG stranded copper wire) Cable
                       with 6-position Modular Plugs (RJ-12) at Each End
Medium User Interface (MUI) Version 3 Technical Bulletin                                17

Operation

Introduction
                       The MUI uses a simple menu system interface on its LCD screen, and
                       six control keys to provide easy, intuitive access to the data and
                       parameters stored in the FX controller. The MUI provides password
                       protection for changing data or for operating functions in the
                       FX controller, such as acknowledging events, overriding outputs,
                       modifying setpoints, and editing trend data collection or communication
                       parameters.

                       This section describes how to:
                       •   establish communication with an FX controller
                       •   display the Home Page
                       •   navigate the Menu
                       •   enter a password
                       •   view application and system points
                       •   adjust configuration parameters
                       •   view the Event Summary
                       •   view the Event History
                       •   view Trend data
                       •   work with communication resource editing options
                       •   refer to the Single Duct Variable Air Volume (VAV-SD) Box
                           Controller Application Note (LIT-12011436) for information on
                           how to use the FXVMA functions
18                   Medium User Interface (MUI) Version 3 Technical Bulletin

Key Concepts
          •    page navigation: display screen, control keys, home page, and menu
               page
          •    password entry
          •    data point display: adjusting and overriding
          •    system data
          •    event notification and management
          •    trend display and settings
          •    scheduler and calendar display and modification
          •    communication resources configuration: modem, Short Message
               Service (SMS), e-mail, and Web page
          •    monitor and commission the FXVMA controller, and air balance the
               VAV box
Medium User Interface (MUI) Version 3 Technical Bulletin                                                 19

Detailed Procedures
Page Navigation
                        The MUI front panel is a 4-line x 26-character backlit LCD display,
                        with 10 status LEDs, and 6 control keys (or buttons).

                  Status LEDs     LCD Display      Cursor and Scroll Keys       Action Buttons

                                                Figure 14: MUI Front Panel

                        Status LEDs
                        The status LEDs indicate important information from the controller and
                        the control application (see Table 1).

                       Table 1: Status LEDs

                        Name           Symbol     Description

                                                  Normally configured in FX Builder to indicate the
                                                  power supply status of the FX controller. The Power
                        Power
                                                  Supply LED is ON when the FX controller is
                        Supply LED
                                                  connected to its power supply and properly powered
                                                  up.
                                                  Normally configured in FX Builder to blink when an
                                                  active event (alarm) condition is present in the FX
                                                  controller, and steady ON when all active events
                        Alarm Active
                                                  have been acknowledged. The OFF condition
                        LED
                                                  indicates that there are no active events in the FX
                                                  controller, and that all events have been
                                                  acknowledged.
                                                  Configurable in FX Builder to indicate the status of
                                                  any value or parameter in the control application in
                        Status LEDs      1–8      the FX controller. The LEDs can be configured to
                                                  blink or be steady ON for any one or more of the
                                                  states of the selected value or parameter.
20                      Medium User Interface (MUI) Version 3 Technical Bulletin

              Keypad
              The control keys      ,     ,    ,     ,     , and       have fixed
              functions that are related to the contents and selected items on the
              displayed page.

     Table 2: Control Key Actions
      Name            Symbol        Description
                                    Moves the cursor between menu items and between
      Left/Right
                                    pages horizontally.
                                    Moves the cursor between menu items and between
                                    pages vertically. When in EDIT mode, changes the
      Up/Down                       value of the selected parameter.

                                    Toggles between the Home Page and the Main Menu,
      Escape                        or aborts the selection of a menu/submenu or
                                    adjust/command procedure.
                                    Confirms an action or command when selecting a menu
      Enter
                                    option, or commanding or adjusting a value.

              In FX Builder you configure each key, or a combination of keys, to
              create customized short-cut access to commonly viewed pages or
              parameters, or to perform system tasks such as the acknowledgement of
              alarms and events. You can also configure a key action to perform the
              auto-repeat function on continued pressure for faster navigation.

              Home Page
              When you connect the MUI to an FX controller, the user interface
              configuration automatically downloads from the controller to the MUI.
              The download operation can take a few minutes and a progress bar
              appears on the MUI screen. When complete, the Home Page
              automatically appears as the default screen.

              The Home Page is also shown when the Menu Page times out, or if you
              press the  key when the Menu Page is displayed.
              You can configure the Home Page to show fixed text (such as
              Welcome, or the job name) or selected active information (such as time
              and date), or the value of special data points from the FX controller with
              descriptive text and units of measure. If you map more information to
              the Home Page than can be shown in four lines, you can scroll up to 16
              lines using the      and      keys, and select points using the     key.
              Use the Home Page to display the most important parameters of the
              connected FX. From the Menu Page, press the      key to select the
              Home Page.
Medium User Interface (MUI) Version 3 Technical Bulletin                                     21

                                       10/12/2009   16:20:04
                                       Johnson Controls FX16
                                              Welcome

                                      Figure 15: Home Page Shown on the MUI
                       Press the      key when the Home Page displays to view the Menu
                       Page.
                       This section describes the Data Points and System Data that can appear
                       on the Home Page.

                       Menu Page
                       To access the Menu Page from the Home Page, press the          key.
                       If you press the      key when the Menu page is displayed, or if the
                       page timeout expires, the Home page appears.
                       Use FX Builder to configure the Menu Page. The Menu Page contains
                       the menu links that makes the MUI pages accessible. Access to some
                       pages are via sub-menu pages under a Main Menu page.
                       Each menu link opens a MUI page (such as Event Summary, Event
                       History, or Accounts management), or opens user defined pages
                       containing data points from the control application in the FX controller.
                       You can limit access to pages by account passwords. If the user does
                       not have the required level of access to a linked page, the Menu link
                       item is hidden and access is denied.
                                       - - - MAIN MENU - - -
                                   ►Events
                                    Trends
                                    Schedulers               ↓
                                   Figure 16: Main Menu Page Shown on the MUI
                       The navigation keys        ,    ,    ,    ,    , and      have specific
                       functions that are independent from the application downloaded into the
                       MUI. The function of the keys is related to the operational mode of the
                       page shown.
                       For example, when the Main Menu Page is in IDLE mode, the arrow
                       keys    and      allow you to scroll through the displayed menu tags.

                       When you press the enter key        , the page goes to ACTIVE mode and
                       the cursor appears as a reverse video character.
22                      Medium User Interface (MUI) Version 3 Technical Bulletin

           Press the enter key again to view the page associated with the menu tag
           where the cursor is positioned.
           When a page appears, the keys are used as follows:
           •   Press        key to set page from IDLE mode to ACTIVE mode and
               display the cursor.
           •   Use the arrow keys         ,    ,     , and      to move the cursor
               through the modifiable parameter values.
           •   Press the       key to set the selected parameter into EDIT mode as
               shown by the blinking parameter value.
           •   Use the up and down arrow keys            and      to edit (modify) the
               value. Numeric values increase and decrease within the allowable
               range, logic (binary) values toggle, and multistate values show the
               possible states.
           •   Press        key to confirm the change, or       to restore the original
               value.
           •   Press the       key to open the previous page in IDLE mode.

           Arrow symbols ↓↑on the right side of a page indicate additional
           information exists outside the area currently displayed. Use the
           Up/Down control keys to scroll through the additional information.
           If a page is configured without tags that you can select, or values that
           you can edit, the page can only remain in IDLE mode.
           A page may appear directly in EDIT mode where you can immediately
           adjust the single value field which is blinking.

Accounts
           The MUI implements an Accounts (password) system, definable in FX
           Builder, to control access to pages and data points, to limit the editing
           and event acknowledgement functions, and to limit the use of key or
           multiple-key associations. To access a page or modify a parameter that
           is account protected, you must log-in with a password at the same or
           higher access level than the account access level required.
           By default, FX Builder provides a link to the Accounts page in the Main
           Menu structure. This Main Menu page must be set with the lowest user
           access priority level. If you do not have the required privilege to access
           a linked page or parameter, the link is hidden and access is denied.
           If you modify a password from one of two MUIs connected to the same
           controller, this action is notified to the other MUI with the following
           message that appears on the display: Pwd Updated by Net.
Medium User Interface (MUI) Version 3 Technical Bulletin                                       23

                       Three Account password levels are defined as follows:
                       • A Level 3 password has the maximum priority, is allowed to access
                          pages or parameters protected by any other password of the system,
                          and is allowed to change passwords.
                       •   A Level 2 password can access pages or parameters protected by
                           passwords of Level 2 or Level 1.
                       •   A Level 1 password can only access pages or parameters protected
                           by a password of Level 1.
                       An additional level is defined as Level 0 and means that a password is
                       not required.
                       Define the passwords with a 4-digit number, where each digit is a
                       numeric character (0-9). The passwords are defined in FX Builder
                       during the MUI user interface design process, and stored in the display
                       configuration within the control application.
                       Through the MUI you can enter and, if allowed by configuration,
                       modify your password. These actions are done using the Log-In and
                       User Account pages.

                       Account Entry Pages
                       The Accounts page is accessible either through the Accounts tag in the
                       Main Menu, or via special key combination shortcuts.
                                                       MENU
                                 ►Log-In

                                              Figure 17: Password Page
                       Press the enter key       to login with your password. The Log-In page
                       also appears when you attempt an action which requires a valid
                       password.
                                             LOG-IN REQUIRED

                                 User: Supervisor
                                 Code: ****
                                                Figure 18: Log-In Page
                       Scroll using the      and       keys to select your user name and then
                       press the enter key      . Then enter your password code.
                       The blinking cursor is positioned on the first digit to edit with a 0
                       default value. Select the correct number (0 – 9) using the        and
                       keys, and confirm with the enter key       .
24               Medium User Interface (MUI) Version 3 Technical Bulletin

     The blinking cursor moves to the next digit. Enter all the required digits.
     When you confirm the last required digit, if the password is valid, the
     MUI allows you to proceed. If no action is in progress, the Main Menu
     page appears again with the appropriate menu links for your password
     level.
     If the password is not valid, the Wrong Password message appears and
     any other active access level is cancelled.

                            WRONG PASSWORD

                      Figure 19: Wrong Password Message

     Press the       key to return to the previous Log-In Required page.

     User Account Page
     If configured through FX Builder, the MUI allows you to change
     passwords directly from the user interface unit without having to
     modify the control application.
     To open the User Account page to modify passwords you have to map
     the Change the Password feature to the Main Menu, or to a key or
     multiple key combination during the control application configuration.
     The User Account page contains the list of the configured password
     users (maximum eight users).

          USER_ID               Password Code (hidden)            Password Level

                         USER ACCOUNT
                 ►Administrator    ****                           3
                  Supervisor       ****                           2
                  Operator         ****                           1 ↓
                  UserName4        ****                           2
                  UserName5        ****                           1
          Figure 20: User Account Page, User Password Level 1 – 3
     Navigate the User Account list using the            and      keys. When the
     desired user name appears, press the enter key            to access the
     password change session. This feature is normally protected by the
     Level 3 password.
Medium User Interface (MUI) Version 3 Technical Bulletin                                  25

                       The password entering procedure is the same as the account entry
                       (see Account Entry Pages). When you confirm the last digit, the
                       Confirm Password screen appears (Figure 21).
                                            Confirm Password

                                                        ****

                                         Figure 21: Confirm Password Page
                       Enter the password again using the same procedure and press the enter
                       key      to confirm.

                       If the passwords entered match, the message Password Saved appears,
                       and the password is modified.
                       If the passwords entered do not match, the Wrong Password message
                       (Figure 19) appears on the screen. Press the   key to return to the
                       previous page.

                       Log-Off
                       There are two ways to log off:
                       •   Open the Accounts page, select Log-Off, and press the enter key.
                       •   Press the specific key combination defined at design time in FX
                           Builder, as the log-off shortcut.
                       As a security feature, password access automatically expires after
                       15 minutes of inactivity, and the User Logged-Off message appears.
                       Press any key to remove this message and return to the Main Menu.
Data Points
                       You can map application data points to the MUI screen for monitoring,
                       adjusting, commanding, or overriding purposes. The display
                       configuration is defined during the control application configuration
                       using FX Builder.
                       These data points represent variables (Network Variable Inputs,
                       Network Variable Outputs, and Application Points), and working
                       parameters and setpoints (Configuration Parameters) that are defined for
                       the specific control application. Data points can represent numeric,
                       logic (binary), and multistate values.
26                      Medium User Interface (MUI) Version 3 Technical Bulletin

              All the fields of structured variables and configuration parameters can
              be mapped to the display application.
              Each Data Point page and each data point on the page has a name (tag)
              to relate the data information to the monitored application.
                                SETPOINTS
                       ►Entrance Hall     19.0°C
                        Conference Room   20.5°C
                        Offices Floor 1   21.0°C ↓
                        Offices Floor 2   20.5°C
                        Offices Floor 3   21.5°C
                              Figure 22: Setpoints Data Point Page
              Depending on the source of the point represented, the data is read-only
              or can be adjusted or modified (write-enabled). Write-enabled points
              have a defined Edit Range to limit the adjustment range.
              To view, adjust, or override a data point:
              1. Go to the Data Point screen using the page navigation with menu
                 pages.
              2. To adjust or override a data value, press the      key to set the page
                 into the ACTIVE mode. The cursor appears.
              3. Use the       and       keys to select the data point that you want to
                 modify, and press the       key again to enter the EDIT mode. A
                 blinking cursor highlights the value to be changed.
              4. Use the       and       keys to modify the value. For numeric values,
                      increases the value and       decreases the value. For logic and
                 multistate points, the keys step through the possible states of the
                 value.
              5. Press the      key to confirm the change or        to restore the
                 original value. The cursor returns to the data point description field.
System Data
              The Data Point pages may contain System Data as well as Data Points.
              System Data relates to the internal controller operating system and
              includes Real-Time Clock information (date and time), Unit of Measure
              (SI or U.S.), Language of display, and others.
Medium User Interface (MUI) Version 3 Technical Bulletin                                      27

Event Notification and Management
                       When an event with an alarm condition occurs, the Event Notification
                       page pops-up and displays the details of the event. This pop-up page
                       shows only the message for the first event in a series of events.
                       When the event pop-up appears, press the         key to access the Event
                       Summary Point Detail and view details, such as the date and time when
                       the event occurred or the event priority level (see Figure 26).
                       Press the     key to cancel the pop-up page and silence the buzzer (if it
                       sounds), and the next new active event in a series appears (if any).
                       Otherwise, the previous page is shown again.
                                       EVENT SUMMARY
                                 O♪Zone Supply_Fan   Fail

                                     Figure 23: Event Notification Pop-up Page
                       The maximum of number of Events that can be managed by the MUI is
                       dependent on the FX controller. The FX06, FX07, FX14, and FX15
                       controllers handle up to 20 events, while the FX16 Master Controller
                       handles up to 250 events. Refer to the Technical Bulletin of the relevant
                       controller for details.
                       Events and alarms are stored in the Event History and are viewed in the
                       Event Summary as long as they are active or not acknowledged.
                       To acknowledge an event, press and hold the specific key or key
                       combination defined at design time in FX Builder, until the event is
                       acknowledged (see Figure 25 and Table 3).
                       Use the page navigation from the Events tag in the Main Menu page
                       (default configuration) to view the Event History and Event Summary
                       pages.
                       The default Events Menu page (Figure 24) enables you to select the
                       Event History or Event Summary pages using the     ,     , and
                       keys to select the page that you want to view.
                                            MENU
                                 ►Event Summary
                                  Event History

                                             Figure 24: Events Menu Page
28                Medium User Interface (MUI) Version 3 Technical Bulletin

     Event Summary
     The event with the highest priority displays at the top of the
     list. System