M9210-AGx-3 Floating Electric Spring Return Actuators
Installation Instructions
                                                                                      Part No. 34-636-1654, Rev. B
                                                                                                 Issued May 13, 2011
                                                                                             Supersedes June 20, 2006

Applications                                                  Installation
The M9210-AGx-3 Floating Actuators are                        The M9210-AGx-3 Floating Electric Spring Return
direct-mount, spring return electric actuators that           Actuators mount directly to the surface in any
operate on AC/DC 24 V power. These bidirectional              convenient orientation using two M3 x 9.5 mm
actuators do not require a damper linkage, and are            self-drilling sheet metal screws and the anti-rotation
easily installed on dampers with 1/2 to 3/4 in. or 12 to      bracket (parts included with the actuator). No additional
19 mm round shafts, or 3/8 and 1/2 in. or 10, 12, and         linkages or couplers are required. Electrical
14 mm square shafts using the standard shaft clamp            connections are color-coded and identified with
included with the actuator. An optional M9220-600             numbers permanently marked on the actuator cable.
Jackshaft Coupler Kit is available for 3/4 to 1-1/16 in. or   A tag on the actuator cable identifies the electrical
19 to 27 mm round shafts, or 5/8 and 3/4 in. or 16, 18,       connections, and wiring details are also included on the
and 19 mm square shafts.                                      actuator housing.
The M9210-AGx-3 Floating Electric Spring Return                   IMPORTANT: Do not install or use this
Actuators provide running and spring return torques of            M9210 AGx-3 Floating Electric Spring Return
89 lb·in (10 N·m). Integral line voltage auxiliary                Actuator in or near environments where corrosive
switches are available on the AGC model to indicate               substances or vapors could be present. Exposure of
end-stop position, or to perform switching functions              the electric actuator to corrosive environments may
within the selected rotation range.                               damage the internal components of the device, and
                                                                  will void the warranty.
 IMPORTANT: Use this M9210-AGx-3 Floating
 Electric Spring Return Actuator only to control              Parts Included
 equipment under normal operating conditions.
                                                              •     floating electric spring return actuator with coupler
 Where failure or malfunction of the electric actuator
 could lead to personal injury or property damage to          •     anti-rotation bracket
 the controlled equipment or other property,
                                                              •     manual override crank
 additional precautions must be designed into the
 control system. Incorporate and maintain other               •     two M3 x 9.5 mm self-drilling sheet metal mounting
 devices, such as supervisory or alarm systems or                   screws
 safety or limit controls, intended to warn of or protect
                                                              •     two No. 10-32 x 9/16 in. thread-forming conduit
 against failure or malfunction of the electric actuator.
                                                                    screws
                                                              Special Tools Needed
                                                              •     torque wrench with 3/8 in. (10 mm) socket
                                                              •     digital voltmeter or M9000-200 Commissioning
                                                                    Tool
                                                              •     flat blade screwdriver

                              M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions           1
Dimensions

                                            4
                                          (102)
                                                       2
                                                      (51)
                                                                                           3-3/16
                                    1-19/32       1-19/32
                                                                                            (81)
                                      (40)          (40)                      1/8                        3/4
                                                                              (3)                       (19)

                                              A
                                                             2-3/16
              1-19/32                                         (56)
                (40)

                           1-1/16
                            (27)

    10-5/16                                                            10
     (262)                                                            (254)

              6-15/16
               (176)

                        1/4 (6.5)
                  Mounting Hole
                   (6 Locations)

                                                                                     1         2-3/16
                                              1-3/4                                 (25)        (56)
                                              (44)

     Figure 1: M9210-AGx-3 Floating Electric Spring Return Actuator Dimensions, in. (mm)

2   M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
Accessories
Table 1: Accessories and Replacement Parts (Order Separately)
 Code Number             Description
 DMPR-KC0031             7 in. (178 mm) Blade Pin Extension (without Bracket) for Johnson Controls® Direct-Mount Damper
                         Applications (quantity 5)
 M9000-153               Crank arm (quantity 1)
 M9000-170               Remote Mounting Kit, Horizontal. Kit includes Mounting Bracket, M9000-153 Crank Arm, Ball Joint,
                         and Mounting Bolts (quantity 1)
 M9000-171               Remote Mounting Kit, Vertical. Kit includes Mounting Bracket, M9000-153 Crank Arm, Ball Joint, and
                         Mounting Bolts (quantity 1)
 M9000-200               Commissioning Tool that Provides a Control Signal to Drive 24 V On/Off, Floating, Proportional,
                         and/or Resistive Electric Actuators (quantity 1)
 M9000-320               Weather Shield Enclosure - NEMA 3R enclosure for protecting a single M9210/20 actuator from rain,
                         sleet, or snow (quantity 1)
 M9000-400               Jackshaft Linkage Kit. Open-ended design enables clamping onto a jackshaft without requiring
                         access to the ends of the jackshaft (quantity 1)
 M9000-604               Replacement Anti-rotation Bracket Kit (with Screws) for M9210-AGx-3 Floating Electric Spring
                         Return Actuators (quantity 1)
 M9200-100               Threaded Conduit Adapter, 1/2 NPSM, for M9210(20) and M(VA)9208 Series Actuators (quantity 5)
 M9220-600               1 in. (25 mm) Jackshaft Coupler Kit (with Locking Clip) for Mounting M9210-AGx-3 Floating Electric
                         Spring Return Actuators on Dampers with 3/4 to 1-1/16 in. or 19 to 27 mm Round Shafts, or
                         5/8 and 3/4 in. or 16, 18, and 19 mm Square Shafts (quantity 1)
 M9220-601               Replacement Coupler Kit (with Locking Clip) for Mounting M9210-AGx-3 Floating Electric Spring
                         Return Actuators on Dampers with 1/2 to 3/4 in. or 12 to 19 mm Round Shafts, or 3/8 and 1/2 in. or
                         10, 12, and 14 mm Square Shafts (quantity 1)
 M9220-602               Replacement Locking Clips for M9210-AGx-3 Floating Electric Spring Return Actuators
                         (Five per Bag)
 M9220-603               Adjustable Stop Kit for M9210-AGx-3 Floating Electric Spring Return Actuators (quantity 1)
 M9220-604               Replacement Manual Override Cranks for M9210-AGx-3 Floating Electric Spring Return Actuators
                         (Five per Bag)
 M9220-610               Replacement Shaft Gripper, 10 mm Square Shaft with Locking Clip (quantity 1)
 M9220-612               Replacement Shaft Gripper, 12 mm Square Shaft with Locking Clip (quantity 1)
 M9220-614               Replacement Shaft Gripper, 14 mm Square Shaft with Locking Clip (quantity 1)

1.   Furnished with the damper and may be ordered separately.

Mounting
The M9210-AGx-3 Floating Electric Spring Return
Actuators can be easily installed on dampers with
1/2 to 3/4 in. or 12 to 19 mm round shafts, or 3/8 and
1/2 in. or 10, 12, and 14 mm square shafts. An
M9220-600 Jackshaft Coupler Kit is available for 3/4 to
1-1/16 in. or 19 to 27 mm round shafts, or 5/8 and
3/4 in. or 16, 18, and 19 mm square shafts; see Table 1
for more details. If the damper shaft extends less than
3-19/32 in. (91 mm), see the Removable Coupler
section for further instructions. If the damper shaft
extends less than 1-5/32 in. (29 mm), install an
extension recommended by the damper manufacturer.

M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions                                               3
Counterclockwise (CCW) Spring Return                                                                                               Removable Coupler
Direction – Clockwise (CW) Powered                                                                                                 The coupler may be installed on either side of the
Operation                                                                                                                          output hub. If the damper shaft is less than 3-19/32 in.
For CCW spring return direction, mount the actuator to                                                                             (91 mm) long, insert the coupler in the face of the
the damper shaft so that Side A of the actuator is away                                                                            actuator closest to the damper. If the damper shaft is
from the damper as illustrated in Figure 2. With power                                                                             shorter than 1-5/32 in. (29 mm) long, a shaft extension
applied, the actuator drives CW from the 0° position,                                                                              is required to mount the actuator.
and spring returns CCW.
                                                                                                                                                             U-Bolt Nut
                                                                                                                                                            and Washer
           Side A: CCW Spring Return Direction                                                                                                               (Qty Two)
                                    A                                                                                                                      Shaft Coupler
                                                                       Auxiliary Switch
                                                                       Adjuster Located                                                                       Pointer
                                                                       on the Right

                                                                       Pointer Showing
                80
               90    70
                          60   50   40   30
                                              20
                                                   10
                                                        -5             Actuator in the
                                                                       Spring Return
                                                                       Position                                                                               U-Bolt

                                                                                                                                                            Locking Clip
                                                                                                                                                                        Assembled View
                                                                       Manual                                                                                              of Coupler
                                                                       Override                                                                                          Subassembly

                                                                                                                                                                                     FIG:chpos
                                                                                                           FIG:sidea

                                                                                                                                    Figure 4: Changing the Position of the Coupler
            Figure 2: Side A of Actuator

                                                                                                                                   To change the position of the coupler, see Figure 4 and
Clockwise (CW) Spring Return Direction –
                                                                                                                                   proceed as follows:
Counterclockwise (CCW) Powered Operation
To change the spring return direction to CW, mount the                                                                             1. Mount the coupler on either Side A or Side B of the
actuator to the damper shaft so that Side B of the                                                                                    actuator, as determined by the shaft length.
actuator is away from the damper as illustrated in                                                                                 2. Snap the locking clip securely into the coupler
Figure 3. With power applied, the actuator now drives                                                                                 retention groove to retain the coupler.
CCW from the 0° position, and spring returns CW.
                                                                                                                                   Manual Override
                                                  Side B:                                                                          Use only the supplied manual override crank to
                                         CW Spring Return Direction
                                                                                                                                   reposition the actuator hub when using the manual
                                                                                 B                                                 override feature.
           Auxiliary Switch
          Adjuster Located
                 on the Left                                                                                                        IMPORTANT: Applying excessive torque to the
                                                                                                                                    manual override or running the manual override with
           Pointer Showing                                                                                                          a power tool may damage the internal components
            Actuator in the
                                                                                                                                    of the actuator and cause premature failure.
                                                                  10                                 80
                                                             -5        20
                                                                            30   40   50   60
                                                                                                70    90
             Spring Return
                   Position
                                                                                                                                   To reposition the actuator hub, proceed as follows:
                                                                                                                                   1. De-energize the actuator.
                      Manual                                                                                                       2. Insert the hex end of the manual override crank
                     Override                                                                                                         into the manual override adjustment point on the
                                                                                                                                      face of the actuator.
                                                                                                                       FIG:sideb
                                                                                                                                   3. Rotate the manual override crank in the direction
            Figure 3: Side B of Actuator                                                                                              indicated by the arrow on the label.

4     M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
    Note: The actuator requires 27 rotations of the                  2. Bend or cut the anti-rotation bracket to fit the
    manual override crank from the fully spring return                  damper frame or duct as illustrated in Figure 6.
    position to fully reposition the actuator hub. At the                Note: The anti-rotation bracket can be bent to fit a
    end of travel, the rotational resistance increases;                  round damper.
    do not force the actuator hub past this point.
                                                                                                            Anti-rotation Bracket
4. Rotate the manual override crank a half turn in the
   opposite direction to lock the actuator hub in place.
    Note: To unlock the actuator hub, rotate the
                                                                                                            Slot for Mounting the
    manual override crank in the direction indicated by                                                     Anti-rotation Bracket
    the arrow on the label. The actuator hub
    automatically unlocks when power is applied to the
    actuator, and returns the actuator to normal drive
    and spring return operation.                                                                             Anti-rotation Bracket
                                                                         Actuator Shown with Anti-rotation Bracket
Mounting the Actuator                                                     Assembled to Both the Top and Bottom
                                                                                    Anti-rotation Slots
To mount the actuator, proceed as follows:                                                                         M3 x 9.5 mm
                                                                                                                   Self-Drilling
1. See the dimensions in Figure 5 and Table 2 to                                                                   Sheet Metal Screws
   ensure the correct positioning of the anti-rotation                                                             (Two Locations)
   bracket.

                   A                  A

                                                                                    Anti-rotation Bracket

  Dimension
                                                  Dimension                                                                         FIG:brfit
     B
                                                     A                                                      Damper Frame

                                                                      Figure 6: Fitting the Anti-rotation Bracket on the
                                                                                    Damper Frame or Duct
                                                         FIG:brpos

                                                                     3. Drill mounting holes in the damper frame or duct
  Figure 5: Positioning the Anti-rotation Bracket
                                                                        using the anti-rotation bracket as a guide (based
                   (See Table 2.)
                                                                        on the measurements obtained in Table 2 and
                                                                        Figure 5).
Table 2: Dimensions from Anti-rotation Bracket to
         Shaft Center                                                4. Secure the anti-rotation bracket to the damper
                                                                        frame or duct using the two M3 x 9.5 mm
 Shaft Diameter        Dimension A,       Dimension B,
                                                                        self-drilling sheet metal screws provided and a
                       in. (mm)           in. (mm)
                                                                        1/4 in. (6 mm) blade screwdriver or 5/16 in. (8 mm)
 1/2 to 9/16 in.       8-9/32             7                             nut driver.
 (12 to 14 mm)         (210)              (178)
 5/8 to 3/4 in.        8-5/32             6-29/32                     IMPORTANT: Do not overtighten the mounting
 (16 to 19 mm)         (207)              (175)                       screws to avoid stripping the threads. Be certain that
                                                                      the tab on the anti-rotation bracket remains properly
 IMPORTANT: The tab on the anti-rotation bracket                      positioned in the slot on the actuator, and that the
 must fit midpoint in the actuator slot. Positioning the              actuator remains parallel to the mounting surface.
 tab midpoint in the slot prevents actuator binding
                                                                     5. Slide the actuator onto the damper shaft, and
 and premature wear, and makes actuator removal
                                                                        position the tab of the anti-rotation bracket into the
 easier.
                                                                        slot at the bottom of the actuator as illustrated in
                                                                        Figure 6.

M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions                                                                 5
6. Rotate the damper blades to the desired position if             Note: If two stroke limiting stops are applied, use
   the power is lost. To ensure a tight seal, insert the           the manual override crank to position and lock the
   manual override crank and turn it in the direction              actuator in a mid-stroke position to gain access to
   indicated by the arrow on the label five turns; the             both stroke limiting stop mounting positions.
   position indicator should be near the 0° position on
                                                               3. Mount the stroke limiting stops in the desired
   the scale. Quickly rotate the manual override crank
                                                                  position using the two M4 x 10 mm self-tapping
   a half turn in the opposite direction to temporarily
                                                                  screws provided. Tighten the screws to a torque of
   lock the actuator hub in place.
                                                                  35 lb·in (4 N·m).
7. Evenly hand tighten each clamp nut onto the
                                                               4. Manually reposition the coupler so that the coupler
   U-bolt, keeping the actuator flat. Secure the U-bolt
                                                                  set screw aligns with the nodule guide that
   to the damper shaft and tighten to a torque of 100
                                                                  corresponds to the value determined in Step 2.
   to 125 lb·in (11 to 14 N·m).
                                                                   Example:
8. To release the spring, turn the manual override
   crank in the direction indicated on the label; the              For a rotation range of 65°, mount one stroke
   actuator spring returns to its starting position. If this       limiting stop in the minimum stroke position as
   step is omitted, the spring releases automatically              illustrated in Figure 8.
   when power is applied to the actuator.
                                                                                                                           Stroke Limiting
9. Remove the manual override crank and store it in                                                                        Stop (Qty Two)
   an unused mounting hole.                                                                       A                        Lock Screw
                                                                                                                           (Qty Two)
10. Apply power long enough for the actuator to travel                                                                     Adjustment Holes
    a full stroke, and verify that the actuator rotates                                                                    (Qty Two Groups
    freely throughout the range.                                                                                           of Eight)
                                                                                                                           Shaft Position
    Note: If electric power is not available, complete                      90
                                                                              80
                                                                                   70
                                                                                        60   50   40   30
                                                                                                            20
                                                                                                                 10
                                                                                                                      -5   Pointer
    this verification by reinserting the manual override                                                                   Sweep Angle
    crank and turning it in the direction indicated to                                                                     Indicated in 5°   FIG:range65
                                                                                                                           Increments
    rotate the coupler to the fully open position.
Rotation Range Using Optional                                        Figure 8: One Stroke Limiting Stop
                                                                 Mounted in the Minimum Stroke Position for a
M9210-603 Adjustable Stop Kit
                                                                            Rotation Range of 65°
The actuator is factory set for 90° rotation, and its
rotation range is limited in 5° increments to a minimum
of 30°. Stroke limiting stops are attached in the field to     Wiring
the shaft coupler side of the actuator to reduce the           The M9210-AGx-3 Floating Electric Spring Return
rotation range. Attaching a stroke limiting stop in the        Actuator provides reliable, integrated damper control.
farthest mounting position reduces the rotation range of       When AC 24 V at 50/60 Hz or DC 24 V power is
the actuator by 5°. Each progressive mounting position         applied between the black and red wires, and power is
reduces the rotation range an additional 5°.                   applied to a gray or orange control wire, the output hub
                                                               rotates from -5 to 90°, based on the Reverse Acting
1. Check that the damper blade is accessible or that           (RA)/Direct Acting (DA) setting (unless an external
   its position is permanently marked on the end of            mechanical limit is reached).
   the damper shaft as illustrated in Figure 7.
                                                               Once the command to rotate is removed, the actuator
                                                               holds its position until either another command to
                                             FIG:dampos
                                                               rotate is applied or until all power is removed. When
                                                               power is removed, the actuator spring returns to its -5°
                                                               position (unless an external mechanical limit is
           Figure 7: Damper Position Icons                     reached). A stall condition while driving between -5 to
                                                               90° causes the output hub to stop motion and hold its
2. Determine the desired rotation range. If a                  position until power is removed. Rotation is
   65 to 90° rotation range is desired, add one stroke         mechanically limited to the -5 and 90° positions by
   limiting stop. If a 35 to 60° rotation range is             integral end-stops. Optional end-stops are available to
   desired, add two stroke limiting stops.                     limit the output hub travel. An anti-rotation bracket
                                                               prevents rotational movement of the actuator body.

6      M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
See Figures 9 and 10 for proper wiring of the
M9210-Bxx-3 Series On/Off Electric Spring Return                     Floating Control,                 Open/Close,
                                                                        Four Wire                   Single Wire Control
Actuator.
                                                                         RA RA                         RA RA
            CAUTION: Risk of Electric Shock.                            DA   DA                       DA   DA
            Disconnect the power supply before
    !       making electrical connections to avoid
                                                                BLK RED GRY ORN
                                                                 1   2   3   4
                                                                                              BLK RED GRY ORN
                                                                                               1   2   3   4
            electric shock.

            CAUTION: Risk of Property Damage.
            Do not apply power to the system before
    !       checking all wiring connections. Short
            circuited or improperly connected wires
            may result in permanent damage to the
                                                                         ~         AC 24 V              ~        AC 24 V
            equipment.
                                                                 -       +         DC 24 V      -       +        DC 24 V

 IMPORTANT: Make all wiring connections in
 accordance with local, national, and regional                                    On/Off Control, Two Wire
 regulations. Do not exceed the electrical ratings of
                                                                                            RA RA
 the M9210-AGx-3 Floating Electric Spring Return
                                                                                           DA   DA
 Actuator.                                                                         BLK RED GRY ORN
                                                                                    1   2   3   4

                S1               S2
                     21               24
                          22               25

                                                                                                                      FIG:M9210AGx_cntrlwir
                          23               26
                     21               24

             BLK/ BLK/ BLK/ WHT/ WHT/ WHT/
             RED BLU GRY RED BLU GRY
              21   22   23   24   25   26
                                                                                          ~      AC 24 V
                                                                                  -       +      DC 24 V
                                                                      Figure 10: Control Wiring Diagrams

                                                FIG:auxswtch
             COM     NC   NO COM      NC   NO

   Figure 9: Auxiliary Switch Wiring Diagram for
                     AGC Model

M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions                                                               7
Setup and Adjustments                                                                                Auxiliary Switches (AGC Model Only)
Direction of Action                                                                                  The AGC model includes two integral auxiliary
                                                                                                     switches with a switch adjuster accessible on either
The M9210-AGx Floating Electric Spring Return                                                        face of the actuator (as illustrated in Figure 2 and
Actuators are factory set for Direct Acting operation,                                               Figure 3). The nominal factory setting for Auxiliary
but may also be switched to Reverse Acting operation.                                                Switch No. 1 is 11° closing, and the nominal factory
A control input drives the actuator.                                                                 setting for Auxiliary Switch No. 2 is 81° opening
Figure 11 and Figure 12 indicate how the drive                                                       (relative to a 0 to 90° rotation range). See the
direction for the actuator depends on the spring return                                              Technical Specifications table for the auxiliary switch
direction and the position of the mode selection switch.                                             ratings.

                                     A                                     B                                     WARNING: Risk of Electric Shock.
                                                                                                                 Disconnect or isolate all power supplies
                                                                                                          !      before making electrical connections.
    Control Inputs                                                                                               More than one disconnect or isolation
                                CCW Face            CW Face                                                      may be required to completely
                                of Actuator        of Actuator
                                                                                                                 de-energize equipment. Contact with
                                         Mode Selection                                                          components carrying hazardous voltage
                                         Switch Setting                                                          can cause electric shock and may result
    GRY         ORN
                 4              DA        RA      RA                           DA                                in severe personal injury or death.
     3

                                                                                                     The switch point of Auxiliary Switch No. 1 is fixed. The
                                                                                                     switch point of Auxiliary Switch No. 2 is independently
                                                                                                     and continuously adjustable from 25 to 95°. See

                                                                                    FIG:DRVPOS_AGx
                                         Holds Position                                              Figure 13 and use the method in the following example
                                                                                                     for the most accurate positioning of Auxiliary Switch
                                                                                                     No. 2.
       Figure 11: Settings for Drive Direction                                                       To change the switch point of Auxiliary Switch No. 2:
                                                                                                     1. Move the actuator to the full spring return position.
Mode Selection Switch
The M9210-AGx-3 Floating Electric Spring Return                                                          Note: Auxiliary Switch No. 2 is factory set to trip
Actuators are factory set at DA, 90° of travel as                                                        when the actuator reaches the 81° position
illustrated in Figure 12. To reverse the rotation, either                                                (approximately).
move the mode selection switch from Direct Acting                                                    2. Rotate the switch adjuster until it points to the
(DA) to Reverse Acting (RA), or reverse the control                                                     desired switch point.
input wiring to GRY 3 and ORN 4 (as illustrated in
Figure 10).                                                                                                                 A
                                                                                                                                       Switch

                                                          FIG:AGx_modsel
                                                                                                                                       Adjuster

                                                                                                                                             FIG:swpnt
           Side A of Actuator        Side B of Actuator
              Figure 12: Mode Selection                                                                        Figure 13: Switch Point Settings

                                                                                                     3. Connect Auxiliary Switch No. 2 to a power source
                                                                                                        or an ohmmeter, and apply power to the actuator.
                                                                                                        The actuator moves to the fully open position and
                                                                                                        holds while power is applied.
                                                                                                     4. Observe the switch point. If required, repeat
                                                                                                        Steps 2 and 3.

8     M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
Repairs and Replacement
A number of replacement parts are available; see
Table 1 for more details. If the M9210-AGx-3 Floating
Electric Spring Return Actuator fails to operate within
its specifications, replace the unit. For a replacement
electric actuator, contact the nearest
Johnson Controls® representative.
Technical Specifications
M9210-AGx Floating Electric Spring Return Actuators (Part 1 of 2)
 Power Requirements                             AC 24 V (19.2 to 30 V) at 50/60 Hz: Class 2 (North America) or SELV
                                                (Europe), 9.6 VA Running,
                                                6 VA Holding Position;
                                                DC 24 V (21.6 to 26.4 V); Class 2 (North America) or SELV
                                                (Europe), 3.9 W Running, 2.1 W Holding Position
 Transformer Sizing Requirements                15 VA Minimum per Actuator
 Input Signal                                   AC 19.2 to 30 V at 50/60 Hz or DC 24 V ±10%, Class 2 (North America) or
                                                SELV (Europe), 500ms minimum pulse width
 Auxiliary Switch Rating       AGC Model        Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with
                                                Gold Flash Contacts:
                                                AC 24 V, 50 VA Pilot Duty;
                                                AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;
                                                AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
 Spring Return                                  Direction is Selectable with Mounting Position of Actuator:
                                                Side A, Actuator Face Away from Damper for CCW Spring Return;
                                                Side B, Actuator Face Away from Damper for CW Spring Return
 Running and Spring Return Torque               89 lb·in (10 N·m)
 Rotation Range                                 Adjustable from 30 to 90° CW or CCW with Optional
                                                M9210-603 Adjustable Stop Kit; Mechanically Limited to 90°
 Rotation Time                 Power On         150 Seconds for 0 to 89 lb·in (0 to 10 N·m) at All Operating Conditions
                               (Running)
                               Power Off        26 Seconds for 0 to 89 lb·in (0 to 10 N·m) at Room Temperature
                               (Spring
                               Returning)
 Cycles                                         60,000 Full Stroke Cycles; 1,500,000 repositions
 Audible Noise Rating          Power On         <40 dBA at 39-13/32 in. (1 m)
                               (Running)
                               Power On         <20 dBA at 39-13/32 in. (1 m)
                               (Holding)
                               Power Off        <55 dBA at 39-13/32 in. (1 m)
                               (Spring
                               Returning)
 Electrical Connections        Actuator         48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm2) Wire Leads
                               (All Models)
                               Auxiliary        48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm2) Wire Leads
                               Switches
                               (AGC Model)
 Conduit Connections                            Integral Connectors for 3/8 in. Flexible Metal Conduit

M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions                                           9
M9210-AGx Floating Electric Spring Return Actuators (Part 2 of 2)
 Mechanical Connections               Standard              1/2 to 3/4 in. or 12 to 19 mm Diameter Round Shafts, or
                                      Shaft Clamp           3/8 and 1/2 in. or 10, 12, and 14 mm Square Shafts
                                      Included with
                                      Actuator
                                      Optional              3/4 to 1-1/16 in. or 19 to 27 mm Diameter Round Shafts, or
                                      M9220-600             5/8 and 3/4 in. or 16, 18, and 19 mm Square Shafts
                                      Jackshaft
                                      Coupler Kit
 Aluminum Enclosure                                         NEMA 2 (IP54) for All Mounting Orientations
 Ambient Conditions                   Operating             -40 to 131°F (-40 to 55°C); 90% RH Maximum, Noncondensing
                                      Storage               -85 to 185°F (-65 to 85°C); 95% RH Maximum, Noncondensing
 Dimensions                                                 See Figure 1.
 Compliance                           United States         UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
                                                            Automatic Electrical Controls for Household and Similar Use; and
                                                            UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for
                                                            Electric Actuators. (Models: All)
                                      Canada                UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA:
                                                            July 2002, 3rd Ed., Automatic Electrical Controls for Household and
                                                            Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and
                                                            Regulating Equipment (Models: All).
                                      Europe                CE Mark – Johnson Controls, Inc., declares that this product is in
                                                            compliance with the essential requirements and other relevant provisions
                                                            of the EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.
                                      Australia and         C-Tick Mark, Australia/NZ Emissions Compliant (Models: All)
                                      New Zealand
 Shipping Weight                                            6.4 lb (2.9 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                    All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.

10      M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions

Published in U.S.A.                                                                                                 www.johnsoncontrols.com

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.