| Вид документа | Інструкція з монтажу |
|---|---|
| Виробник | JCI |
| Код документа | m9210-agx-3-floating-electric-spring-return-actuators-installation-guide |
| Група обладнання | M9210 |
| Сторінок | 10 |
| Мова документа | англійська |
| Розмір файлу | 0.3 МБ |
Текст документа
M9210-AGx-3 Floating Electric Spring Return Actuators
Installation Instructions
Part No. 34-636-1654, Rev. B
Issued May 13, 2011
Supersedes June 20, 2006
Applications Installation
The M9210-AGx-3 Floating Actuators are The M9210-AGx-3 Floating Electric Spring Return
direct-mount, spring return electric actuators that Actuators mount directly to the surface in any
operate on AC/DC 24 V power. These bidirectional convenient orientation using two M3 x 9.5 mm
actuators do not require a damper linkage, and are self-drilling sheet metal screws and the anti-rotation
easily installed on dampers with 1/2 to 3/4 in. or 12 to bracket (parts included with the actuator). No additional
19 mm round shafts, or 3/8 and 1/2 in. or 10, 12, and linkages or couplers are required. Electrical
14 mm square shafts using the standard shaft clamp connections are color-coded and identified with
included with the actuator. An optional M9220-600 numbers permanently marked on the actuator cable.
Jackshaft Coupler Kit is available for 3/4 to 1-1/16 in. or A tag on the actuator cable identifies the electrical
19 to 27 mm round shafts, or 5/8 and 3/4 in. or 16, 18, connections, and wiring details are also included on the
and 19 mm square shafts. actuator housing.
The M9210-AGx-3 Floating Electric Spring Return IMPORTANT: Do not install or use this
Actuators provide running and spring return torques of M9210 AGx-3 Floating Electric Spring Return
89 lb·in (10 N·m). Integral line voltage auxiliary Actuator in or near environments where corrosive
switches are available on the AGC model to indicate substances or vapors could be present. Exposure of
end-stop position, or to perform switching functions the electric actuator to corrosive environments may
within the selected rotation range. damage the internal components of the device, and
will void the warranty.
IMPORTANT: Use this M9210-AGx-3 Floating
Electric Spring Return Actuator only to control Parts Included
equipment under normal operating conditions.
• floating electric spring return actuator with coupler
Where failure or malfunction of the electric actuator
could lead to personal injury or property damage to • anti-rotation bracket
the controlled equipment or other property,
• manual override crank
additional precautions must be designed into the
control system. Incorporate and maintain other • two M3 x 9.5 mm self-drilling sheet metal mounting
devices, such as supervisory or alarm systems or screws
safety or limit controls, intended to warn of or protect
• two No. 10-32 x 9/16 in. thread-forming conduit
against failure or malfunction of the electric actuator.
screws
Special Tools Needed
• torque wrench with 3/8 in. (10 mm) socket
• digital voltmeter or M9000-200 Commissioning
Tool
• flat blade screwdriver
M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions 1
Dimensions
4
(102)
2
(51)
3-3/16
1-19/32 1-19/32
(81)
(40) (40) 1/8 3/4
(3) (19)
A
2-3/16
1-19/32 (56)
(40)
1-1/16
(27)
10-5/16 10
(262) (254)
6-15/16
(176)
1/4 (6.5)
Mounting Hole
(6 Locations)
1 2-3/16
1-3/4 (25) (56)
(44)
Figure 1: M9210-AGx-3 Floating Electric Spring Return Actuator Dimensions, in. (mm)
2 M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
Accessories
Table 1: Accessories and Replacement Parts (Order Separately)
Code Number Description
DMPR-KC0031 7 in. (178 mm) Blade Pin Extension (without Bracket) for Johnson Controls® Direct-Mount Damper
Applications (quantity 5)
M9000-153 Crank arm (quantity 1)
M9000-170 Remote Mounting Kit, Horizontal. Kit includes Mounting Bracket, M9000-153 Crank Arm, Ball Joint,
and Mounting Bolts (quantity 1)
M9000-171 Remote Mounting Kit, Vertical. Kit includes Mounting Bracket, M9000-153 Crank Arm, Ball Joint, and
Mounting Bolts (quantity 1)
M9000-200 Commissioning Tool that Provides a Control Signal to Drive 24 V On/Off, Floating, Proportional,
and/or Resistive Electric Actuators (quantity 1)
M9000-320 Weather Shield Enclosure - NEMA 3R enclosure for protecting a single M9210/20 actuator from rain,
sleet, or snow (quantity 1)
M9000-400 Jackshaft Linkage Kit. Open-ended design enables clamping onto a jackshaft without requiring
access to the ends of the jackshaft (quantity 1)
M9000-604 Replacement Anti-rotation Bracket Kit (with Screws) for M9210-AGx-3 Floating Electric Spring
Return Actuators (quantity 1)
M9200-100 Threaded Conduit Adapter, 1/2 NPSM, for M9210(20) and M(VA)9208 Series Actuators (quantity 5)
M9220-600 1 in. (25 mm) Jackshaft Coupler Kit (with Locking Clip) for Mounting M9210-AGx-3 Floating Electric
Spring Return Actuators on Dampers with 3/4 to 1-1/16 in. or 19 to 27 mm Round Shafts, or
5/8 and 3/4 in. or 16, 18, and 19 mm Square Shafts (quantity 1)
M9220-601 Replacement Coupler Kit (with Locking Clip) for Mounting M9210-AGx-3 Floating Electric Spring
Return Actuators on Dampers with 1/2 to 3/4 in. or 12 to 19 mm Round Shafts, or 3/8 and 1/2 in. or
10, 12, and 14 mm Square Shafts (quantity 1)
M9220-602 Replacement Locking Clips for M9210-AGx-3 Floating Electric Spring Return Actuators
(Five per Bag)
M9220-603 Adjustable Stop Kit for M9210-AGx-3 Floating Electric Spring Return Actuators (quantity 1)
M9220-604 Replacement Manual Override Cranks for M9210-AGx-3 Floating Electric Spring Return Actuators
(Five per Bag)
M9220-610 Replacement Shaft Gripper, 10 mm Square Shaft with Locking Clip (quantity 1)
M9220-612 Replacement Shaft Gripper, 12 mm Square Shaft with Locking Clip (quantity 1)
M9220-614 Replacement Shaft Gripper, 14 mm Square Shaft with Locking Clip (quantity 1)
1. Furnished with the damper and may be ordered separately.
Mounting
The M9210-AGx-3 Floating Electric Spring Return
Actuators can be easily installed on dampers with
1/2 to 3/4 in. or 12 to 19 mm round shafts, or 3/8 and
1/2 in. or 10, 12, and 14 mm square shafts. An
M9220-600 Jackshaft Coupler Kit is available for 3/4 to
1-1/16 in. or 19 to 27 mm round shafts, or 5/8 and
3/4 in. or 16, 18, and 19 mm square shafts; see Table 1
for more details. If the damper shaft extends less than
3-19/32 in. (91 mm), see the Removable Coupler
section for further instructions. If the damper shaft
extends less than 1-5/32 in. (29 mm), install an
extension recommended by the damper manufacturer.
M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions 3
Counterclockwise (CCW) Spring Return Removable Coupler
Direction – Clockwise (CW) Powered The coupler may be installed on either side of the
Operation output hub. If the damper shaft is less than 3-19/32 in.
For CCW spring return direction, mount the actuator to (91 mm) long, insert the coupler in the face of the
the damper shaft so that Side A of the actuator is away actuator closest to the damper. If the damper shaft is
from the damper as illustrated in Figure 2. With power shorter than 1-5/32 in. (29 mm) long, a shaft extension
applied, the actuator drives CW from the 0° position, is required to mount the actuator.
and spring returns CCW.
U-Bolt Nut
and Washer
Side A: CCW Spring Return Direction (Qty Two)
A Shaft Coupler
Auxiliary Switch
Adjuster Located Pointer
on the Right
Pointer Showing
80
90 70
60 50 40 30
20
10
-5 Actuator in the
Spring Return
Position U-Bolt
Locking Clip
Assembled View
Manual of Coupler
Override Subassembly
FIG:chpos
FIG:sidea
Figure 4: Changing the Position of the Coupler
Figure 2: Side A of Actuator
To change the position of the coupler, see Figure 4 and
Clockwise (CW) Spring Return Direction –
proceed as follows:
Counterclockwise (CCW) Powered Operation
To change the spring return direction to CW, mount the 1. Mount the coupler on either Side A or Side B of the
actuator to the damper shaft so that Side B of the actuator, as determined by the shaft length.
actuator is away from the damper as illustrated in 2. Snap the locking clip securely into the coupler
Figure 3. With power applied, the actuator now drives retention groove to retain the coupler.
CCW from the 0° position, and spring returns CW.
Manual Override
Side B: Use only the supplied manual override crank to
CW Spring Return Direction
reposition the actuator hub when using the manual
B override feature.
Auxiliary Switch
Adjuster Located
on the Left IMPORTANT: Applying excessive torque to the
manual override or running the manual override with
Pointer Showing a power tool may damage the internal components
Actuator in the
of the actuator and cause premature failure.
10 80
-5 20
30 40 50 60
70 90
Spring Return
Position
To reposition the actuator hub, proceed as follows:
1. De-energize the actuator.
Manual 2. Insert the hex end of the manual override crank
Override into the manual override adjustment point on the
face of the actuator.
FIG:sideb
3. Rotate the manual override crank in the direction
Figure 3: Side B of Actuator indicated by the arrow on the label.
4 M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
Note: The actuator requires 27 rotations of the 2. Bend or cut the anti-rotation bracket to fit the
manual override crank from the fully spring return damper frame or duct as illustrated in Figure 6.
position to fully reposition the actuator hub. At the Note: The anti-rotation bracket can be bent to fit a
end of travel, the rotational resistance increases; round damper.
do not force the actuator hub past this point.
Anti-rotation Bracket
4. Rotate the manual override crank a half turn in the
opposite direction to lock the actuator hub in place.
Note: To unlock the actuator hub, rotate the
Slot for Mounting the
manual override crank in the direction indicated by Anti-rotation Bracket
the arrow on the label. The actuator hub
automatically unlocks when power is applied to the
actuator, and returns the actuator to normal drive
and spring return operation. Anti-rotation Bracket
Actuator Shown with Anti-rotation Bracket
Mounting the Actuator Assembled to Both the Top and Bottom
Anti-rotation Slots
To mount the actuator, proceed as follows: M3 x 9.5 mm
Self-Drilling
1. See the dimensions in Figure 5 and Table 2 to Sheet Metal Screws
ensure the correct positioning of the anti-rotation (Two Locations)
bracket.
A A
Anti-rotation Bracket
Dimension
Dimension FIG:brfit
B
A Damper Frame
Figure 6: Fitting the Anti-rotation Bracket on the
Damper Frame or Duct
FIG:brpos
3. Drill mounting holes in the damper frame or duct
Figure 5: Positioning the Anti-rotation Bracket
using the anti-rotation bracket as a guide (based
(See Table 2.)
on the measurements obtained in Table 2 and
Figure 5).
Table 2: Dimensions from Anti-rotation Bracket to
Shaft Center 4. Secure the anti-rotation bracket to the damper
frame or duct using the two M3 x 9.5 mm
Shaft Diameter Dimension A, Dimension B,
self-drilling sheet metal screws provided and a
in. (mm) in. (mm)
1/4 in. (6 mm) blade screwdriver or 5/16 in. (8 mm)
1/2 to 9/16 in. 8-9/32 7 nut driver.
(12 to 14 mm) (210) (178)
5/8 to 3/4 in. 8-5/32 6-29/32 IMPORTANT: Do not overtighten the mounting
(16 to 19 mm) (207) (175) screws to avoid stripping the threads. Be certain that
the tab on the anti-rotation bracket remains properly
IMPORTANT: The tab on the anti-rotation bracket positioned in the slot on the actuator, and that the
must fit midpoint in the actuator slot. Positioning the actuator remains parallel to the mounting surface.
tab midpoint in the slot prevents actuator binding
5. Slide the actuator onto the damper shaft, and
and premature wear, and makes actuator removal
position the tab of the anti-rotation bracket into the
easier.
slot at the bottom of the actuator as illustrated in
Figure 6.
M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions 5
6. Rotate the damper blades to the desired position if Note: If two stroke limiting stops are applied, use
the power is lost. To ensure a tight seal, insert the the manual override crank to position and lock the
manual override crank and turn it in the direction actuator in a mid-stroke position to gain access to
indicated by the arrow on the label five turns; the both stroke limiting stop mounting positions.
position indicator should be near the 0° position on
3. Mount the stroke limiting stops in the desired
the scale. Quickly rotate the manual override crank
position using the two M4 x 10 mm self-tapping
a half turn in the opposite direction to temporarily
screws provided. Tighten the screws to a torque of
lock the actuator hub in place.
35 lb·in (4 N·m).
7. Evenly hand tighten each clamp nut onto the
4. Manually reposition the coupler so that the coupler
U-bolt, keeping the actuator flat. Secure the U-bolt
set screw aligns with the nodule guide that
to the damper shaft and tighten to a torque of 100
corresponds to the value determined in Step 2.
to 125 lb·in (11 to 14 N·m).
Example:
8. To release the spring, turn the manual override
crank in the direction indicated on the label; the For a rotation range of 65°, mount one stroke
actuator spring returns to its starting position. If this limiting stop in the minimum stroke position as
step is omitted, the spring releases automatically illustrated in Figure 8.
when power is applied to the actuator.
Stroke Limiting
9. Remove the manual override crank and store it in Stop (Qty Two)
an unused mounting hole. A Lock Screw
(Qty Two)
10. Apply power long enough for the actuator to travel Adjustment Holes
a full stroke, and verify that the actuator rotates (Qty Two Groups
freely throughout the range. of Eight)
Shaft Position
Note: If electric power is not available, complete 90
80
70
60 50 40 30
20
10
-5 Pointer
this verification by reinserting the manual override Sweep Angle
crank and turning it in the direction indicated to Indicated in 5° FIG:range65
Increments
rotate the coupler to the fully open position.
Rotation Range Using Optional Figure 8: One Stroke Limiting Stop
Mounted in the Minimum Stroke Position for a
M9210-603 Adjustable Stop Kit
Rotation Range of 65°
The actuator is factory set for 90° rotation, and its
rotation range is limited in 5° increments to a minimum
of 30°. Stroke limiting stops are attached in the field to Wiring
the shaft coupler side of the actuator to reduce the The M9210-AGx-3 Floating Electric Spring Return
rotation range. Attaching a stroke limiting stop in the Actuator provides reliable, integrated damper control.
farthest mounting position reduces the rotation range of When AC 24 V at 50/60 Hz or DC 24 V power is
the actuator by 5°. Each progressive mounting position applied between the black and red wires, and power is
reduces the rotation range an additional 5°. applied to a gray or orange control wire, the output hub
rotates from -5 to 90°, based on the Reverse Acting
1. Check that the damper blade is accessible or that (RA)/Direct Acting (DA) setting (unless an external
its position is permanently marked on the end of mechanical limit is reached).
the damper shaft as illustrated in Figure 7.
Once the command to rotate is removed, the actuator
holds its position until either another command to
FIG:dampos
rotate is applied or until all power is removed. When
power is removed, the actuator spring returns to its -5°
position (unless an external mechanical limit is
Figure 7: Damper Position Icons reached). A stall condition while driving between -5 to
90° causes the output hub to stop motion and hold its
2. Determine the desired rotation range. If a position until power is removed. Rotation is
65 to 90° rotation range is desired, add one stroke mechanically limited to the -5 and 90° positions by
limiting stop. If a 35 to 60° rotation range is integral end-stops. Optional end-stops are available to
desired, add two stroke limiting stops. limit the output hub travel. An anti-rotation bracket
prevents rotational movement of the actuator body.
6 M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
See Figures 9 and 10 for proper wiring of the
M9210-Bxx-3 Series On/Off Electric Spring Return Floating Control, Open/Close,
Four Wire Single Wire Control
Actuator.
RA RA RA RA
CAUTION: Risk of Electric Shock. DA DA DA DA
Disconnect the power supply before
! making electrical connections to avoid
BLK RED GRY ORN
1 2 3 4
BLK RED GRY ORN
1 2 3 4
electric shock.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
! checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
~ AC 24 V ~ AC 24 V
equipment.
- + DC 24 V - + DC 24 V
IMPORTANT: Make all wiring connections in
accordance with local, national, and regional On/Off Control, Two Wire
regulations. Do not exceed the electrical ratings of
RA RA
the M9210-AGx-3 Floating Electric Spring Return
DA DA
Actuator. BLK RED GRY ORN
1 2 3 4
S1 S2
21 24
22 25
FIG:M9210AGx_cntrlwir
23 26
21 24
BLK/ BLK/ BLK/ WHT/ WHT/ WHT/
RED BLU GRY RED BLU GRY
21 22 23 24 25 26
~ AC 24 V
- + DC 24 V
Figure 10: Control Wiring Diagrams
FIG:auxswtch
COM NC NO COM NC NO
Figure 9: Auxiliary Switch Wiring Diagram for
AGC Model
M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions 7
Setup and Adjustments Auxiliary Switches (AGC Model Only)
Direction of Action The AGC model includes two integral auxiliary
switches with a switch adjuster accessible on either
The M9210-AGx Floating Electric Spring Return face of the actuator (as illustrated in Figure 2 and
Actuators are factory set for Direct Acting operation, Figure 3). The nominal factory setting for Auxiliary
but may also be switched to Reverse Acting operation. Switch No. 1 is 11° closing, and the nominal factory
A control input drives the actuator. setting for Auxiliary Switch No. 2 is 81° opening
Figure 11 and Figure 12 indicate how the drive (relative to a 0 to 90° rotation range). See the
direction for the actuator depends on the spring return Technical Specifications table for the auxiliary switch
direction and the position of the mode selection switch. ratings.
A B WARNING: Risk of Electric Shock.
Disconnect or isolate all power supplies
! before making electrical connections.
Control Inputs More than one disconnect or isolation
CCW Face CW Face may be required to completely
of Actuator of Actuator
de-energize equipment. Contact with
Mode Selection components carrying hazardous voltage
Switch Setting can cause electric shock and may result
GRY ORN
4 DA RA RA DA in severe personal injury or death.
3
The switch point of Auxiliary Switch No. 1 is fixed. The
switch point of Auxiliary Switch No. 2 is independently
and continuously adjustable from 25 to 95°. See
FIG:DRVPOS_AGx
Holds Position Figure 13 and use the method in the following example
for the most accurate positioning of Auxiliary Switch
No. 2.
Figure 11: Settings for Drive Direction To change the switch point of Auxiliary Switch No. 2:
1. Move the actuator to the full spring return position.
Mode Selection Switch
The M9210-AGx-3 Floating Electric Spring Return Note: Auxiliary Switch No. 2 is factory set to trip
Actuators are factory set at DA, 90° of travel as when the actuator reaches the 81° position
illustrated in Figure 12. To reverse the rotation, either (approximately).
move the mode selection switch from Direct Acting 2. Rotate the switch adjuster until it points to the
(DA) to Reverse Acting (RA), or reverse the control desired switch point.
input wiring to GRY 3 and ORN 4 (as illustrated in
Figure 10). A
Switch
FIG:AGx_modsel
Adjuster
FIG:swpnt
Side A of Actuator Side B of Actuator
Figure 12: Mode Selection Figure 13: Switch Point Settings
3. Connect Auxiliary Switch No. 2 to a power source
or an ohmmeter, and apply power to the actuator.
The actuator moves to the fully open position and
holds while power is applied.
4. Observe the switch point. If required, repeat
Steps 2 and 3.
8 M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
Repairs and Replacement
A number of replacement parts are available; see
Table 1 for more details. If the M9210-AGx-3 Floating
Electric Spring Return Actuator fails to operate within
its specifications, replace the unit. For a replacement
electric actuator, contact the nearest
Johnson Controls® representative.
Technical Specifications
M9210-AGx Floating Electric Spring Return Actuators (Part 1 of 2)
Power Requirements AC 24 V (19.2 to 30 V) at 50/60 Hz: Class 2 (North America) or SELV
(Europe), 9.6 VA Running,
6 VA Holding Position;
DC 24 V (21.6 to 26.4 V); Class 2 (North America) or SELV
(Europe), 3.9 W Running, 2.1 W Holding Position
Transformer Sizing Requirements 15 VA Minimum per Actuator
Input Signal AC 19.2 to 30 V at 50/60 Hz or DC 24 V ±10%, Class 2 (North America) or
SELV (Europe), 500ms minimum pulse width
Auxiliary Switch Rating AGC Model Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with
Gold Flash Contacts:
AC 24 V, 50 VA Pilot Duty;
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Spring Return Direction is Selectable with Mounting Position of Actuator:
Side A, Actuator Face Away from Damper for CCW Spring Return;
Side B, Actuator Face Away from Damper for CW Spring Return
Running and Spring Return Torque 89 lb·in (10 N·m)
Rotation Range Adjustable from 30 to 90° CW or CCW with Optional
M9210-603 Adjustable Stop Kit; Mechanically Limited to 90°
Rotation Time Power On 150 Seconds for 0 to 89 lb·in (0 to 10 N·m) at All Operating Conditions
(Running)
Power Off 26 Seconds for 0 to 89 lb·in (0 to 10 N·m) at Room Temperature
(Spring
Returning)
Cycles 60,000 Full Stroke Cycles; 1,500,000 repositions
Audible Noise Rating Power On <40 dBA at 39-13/32 in. (1 m)
(Running)
Power On <20 dBA at 39-13/32 in. (1 m)
(Holding)
Power Off <55 dBA at 39-13/32 in. (1 m)
(Spring
Returning)
Electrical Connections Actuator 48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm2) Wire Leads
(All Models)
Auxiliary 48 in. (1.2 m) Halogen-Free Cable with 18 AWG (0.75 mm2) Wire Leads
Switches
(AGC Model)
Conduit Connections Integral Connectors for 3/8 in. Flexible Metal Conduit
M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions 9
M9210-AGx Floating Electric Spring Return Actuators (Part 2 of 2)
Mechanical Connections Standard 1/2 to 3/4 in. or 12 to 19 mm Diameter Round Shafts, or
Shaft Clamp 3/8 and 1/2 in. or 10, 12, and 14 mm Square Shafts
Included with
Actuator
Optional 3/4 to 1-1/16 in. or 19 to 27 mm Diameter Round Shafts, or
M9220-600 5/8 and 3/4 in. or 16, 18, and 19 mm Square Shafts
Jackshaft
Coupler Kit
Aluminum Enclosure NEMA 2 (IP54) for All Mounting Orientations
Ambient Conditions Operating -40 to 131°F (-40 to 55°C); 90% RH Maximum, Noncondensing
Storage -85 to 185°F (-65 to 85°C); 95% RH Maximum, Noncondensing
Dimensions See Figure 1.
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1,
Automatic Electrical Controls for Household and Similar Use; and
UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for
Electric Actuators. (Models: All)
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA:
July 2002, 3rd Ed., Automatic Electrical Controls for Household and
Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and
Regulating Equipment (Models: All).
Europe CE Mark – Johnson Controls, Inc., declares that this product is in
compliance with the essential requirements and other relevant provisions
of the EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.
Australia and C-Tick Mark, Australia/NZ Emissions Compliant (Models: All)
New Zealand
Shipping Weight 6.4 lb (2.9 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.
10 M9210-AGx-3 Floating Electric Spring Return Actuators Installation Instructions
Published in U.S.A. www.johnsoncontrols.comПозиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.