M9106-AGx-5 Series floating Electric Non-Spring Return Actuators Installation Guide

Вид документаІнструкція з монтажу
ВиробникJCI
Код документаm9106-agx-5-series-floating-electric-non-spring-return-actuators-installation
Група обладнанняM9106
Сторінок4
Мова документаанглійська
Розмір файлу0.1 МБ

Текст документа

34- 636- 1336, Rev. C

                                                                       Installation Instructions        M9106-AGx-x
                                                                                     Issue Date         March 2016

                            M9106-AGx-5 Series Floating Electric
                               Non-Spring Return Actuators
                                                                                                           Coupler Set
Installation                                                     End-stop                                    Screw
                                                                Set Screws
 IMPORTANT: Use this M9106-AGx-5 Series                             (2)                                     End-stops (2)
                                                                                     90
 Electric Non-Spring Return actuator only to control                                    60 30 0            Damper
                                                                 Stop Gear       0                90       Shaft
 equipment under normal operating conditions.                                         30   60
 Where failure or malfunction of this M9106-AGx-5
 actuator could lead to personal injury or property                Figure 1: Setting the Rotation Range
 damage to the controlled equipment or other
 property, additional precautions must be designed         Use the center of the coupler set screw as a pointer to
 into the control system. Incorporate and maintain         observe the position on the scale when rotating the
 other devices, such as supervisory or alarm systems       coupler from one side to the other.
 or safety or limit controls, intended to warn of or
 protect against failure or malfunction of the this
 M9106-AGx-5 actuator.                                      IMPORTANT:          Do not remove the end-stop
                                                            set screws, as this could interfere with the
 IMPORTANT: Utiliser ce M9106-AGx-5 Series
                                                            actuator’s operation.
 Electric Non-Spring Return actuator uniquement
 pour commander des équipements dans des
 conditions normales de fonctionnement. Lorsqu'une
 défaillance ou un dysfonctionnement du
 M9101-AGx-5 actuator risque de provoquer des              Setup and Adjustments
 blessures ou d'endommager l'équipement contrôlé           Direction of Action
 ou un autre équipement, la conception du système
 de contrôle doit intégrer des dispositifs de protection   In the Direct Acting (DA) mode, a minimum control
 supplémentaires. Veiller dans ce cas à intégrer de        signal drives the actuator to the full CCW position, and
 façon permanente d'autres dispositifs, tels que des       a maximum control signal drives it fully CW. For
 systèmes de supervision ou d'alarme, ou des               Reverse Acting (RA) operation, a minimum control
 dispositifs de sécurité ou de limitation, ayant une       signal drives the actuator to the full CW position, and a
 fonction d'avertissement ou de protection en cas de       maximum control signal drives it fully CCW.
 défaillance ou de dysfonctionnement du                    For CW rotation and RA operation, apply 24 VAC to
 M9101-AGx-5 actuator.                                     the Common (COM) and CW Terminals. For CCW
                                                           rotation and DA operation, apply 24 VAC to the COM
Parts Included                                             and CCW Terminals. (See Figure 2.)
•   M9106-AGx-5 actuator
•   spade terminals

Special Tools Needed
•   wire/terminal crimper
                                                                                     CCW
Mounting                                                                              CW
                                                                                     COM
The actuators are not position sensitive, and may be
mounted in any convenient orientation onto VG1000
Series Ball Valves by the means of the M9000-520-5                    Figure 2: Direction of Action on
linkage kit.                                                                     AGx Model
For more details refer to th M9000-520-5 Ball Valve
Linkage Kit Mounting Instructions (P/N 14-1297-13).

© 2016 Johnson Controls, Inc.                                                                                               1
  Part No. 34-636-1336, Rev. C                                                                         www.johnsoncontrols.com
Wiring
                                                          Note: To avoid excessive wear or drive time on the
    !     CAUTION: Risk of Property Damage.
                                                          motor for the AGx models, use a controller and/or
                                                          software that provides a time-out function to remove
Do not apply power to the system before checking          the signal at the end of rotation (stall).
all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to         Through the Conduit Openings
the equipment.
                                                          Depending on the M9106 model selected, one or both
MISE EN GARDE: Risque de dégâts matériels.
                                                          conduit openings are used.
Ne pas mettre le système sous tension avant d'avoir
vérifié tous les raccords de câblage. Des fils formant    1. Loosen the cover screw and remove the actuator
un court-circuit ou connectés de façon incorrecte            cover.
risquent d'endommager irrémédiablement
                                                          2. Push the plastic conduit plug out of the
l'équipement.
                                                             conduit opening with fingertip. (See Figure 4.)
                                                                                     Cover
                                                                                     Screw
                                                                         Cover
MPORTANT:           Make all wiring connections in
accordance with the National Electrical Code and all
local regulations.                                                      Gear
                                                                       Release

                                                                                 Plugs
                                                                           (Conduit Openings)
                     Floating Control
                       Models: AGx                            Figure 4: Location of the Conduit Openings
                   CCW       ~
                                                          3. Use the Phillips No. 1 screwdriver to puncture a
                   CW        ~
                                  24 VAC                     hole through the center of the plastic conduit plug.
                   COM       <
                                                             Reinsert the plug into the conduit opening.
                  Auxiliary Switches                      Note: For applications requiring metal conduit,
                    Models: All AGC                       thread the conduit fitting into the conduit opening and
                 S1                  S2
                                           80°            hand tighten.
                NC1          NC2
             C1      NO1
                             NO2                          4. Insert the cable wires through the plastic plug,
                               C2                            compression fitting, or conduit fitting, and connect
                                                             to the terminals using the appropriate wiring
             10°                                             diagram in Figure 3.
        Figure 3: Wiring for M9106-AGx Models              IMPORTANT:          Install all quick-connect
                                                           terminals in the same direction to prevent shorting.
                                                           (See Figure 5.)

                                                                   Figure 5: Orientation of Terminals
                                                          Note: If using optional pluggable terminal blocks
                                                          (M9000-105 or M9000-106), insert the cable wires
                                                          through the conduit opening, and then connect the
                                                          wires to the terminals.

2   M9106-AGx-5 Series Electric Non-Spring Return Actuators Installation Instructions
Auxiliary Switches (AGC Model)                            Switch S2
The M9106-AGC-5 models has two built-in                   To change the angle of Switch S2 to 70°, refer to
auxiliary switches that may be set for any angle          Figure 13 and proceed as follows:
between 0 and 90° (factory set for 10 and 80°,
                                                          1. Press and hold the gear release. Using the
nominal). Refer to the Technical Data section for
                                                             0 to 90° nodule guides, rotate the coupler until the
auxiliary switch ratings.
                                                             center of the coupler set screw is at 70°.
The following procedures serve as examples to
                                                          2. Rotate Switch S2 CW, and align the edge of the
change the position of the auxiliary switch angles
                                                             switch with the plunger until the plunger rises.
when starting at full CCW position.
                                                             (See Figure 6.)
Switch S1                                                 Note: At this point, the normally closed contact
To change the angle of Switch S1 to 20°, refer to         opens, and the normally open contact closes. (See
Figure 6 and proceed as follows:                          Auxiliary Switches in Figure 3.)
                                                          3. Press and hold the gear release. Rotate the
                                          Coupler
                                                             coupler until the center of the coupler set screw is
       Nodule Guides                     Set Screw           back to 0°.
      (10° Increments)
                         90°   0°                         4. Check all the wiring and system settings, and
                            CW            Edge of
                                          Switch             apply power to the controller. Provide signals to
        Plunger             CW                               the actuator to drive it at least one complete cycle
                                                             open and closed to verify proper operation.
            Gear
           Release                                        Repairs and Replacement
                                                          Field repairs must not be made. For a replacement or
                                                          an accessory, refer to the Ordering Information section
           Figure 6: Switch Angle Settings                in the M9106-xxx-5 Series Electric Non-spring Return
1. Press and hold the gear release. Using the             Actuators Product Bulletin (10.862E).
   0 to 90° nodule guides, rotate the coupler until the
   center of the coupler set screw is at 20°.
2. Rotate Switch S1 CW, and align the edge of the
   switch with the plunger until the plunger rises.
   (See Figure 6.)
Note: At this point, the normally closed contact
closes, and the normally open contact opens. (See
Auxiliary Switches in Figure 3.)

                            M9106-AGx-5 Series Electric Non-Spring Return Actuators Installation Instructions   3
Technical Data
    Product                           M9106-AGx-5 Series Electric Non-Spring Return Actuators
    Power Requirements                20 to 30 VAC at 50/60 Hz; 2.5 VA supply, Class 2
    Input Signal                      20 to 30 VAC at 50/60 Hz
    Input Signal Adjustments          CW and COM Terminals, CW rotation
                                      CCW and COM Terminals, CCW rotation
                                      Action is jumper selectable Direct (CW) or Reverse (CCW) with signal increase.
    Input Impedance                   200 ohms, nominal
    Auxiliary Switch Rating           AGC:                Two Single-Pole, Double-Throw (SPDT) switches rated at 24 VAC,
                                                          1.5 A inductive, 3.0 A resistive, 35 VA maximum per switch, Class 2
    Mechanical Output                 Running Torque: 6 Nm
    Cycles                            100,000 full cycles; 2,500,000 repositions rated at 6 Nm
    Audible Noise Rating              35 dBA maximum at 1 m
    Rotation Range                    Adjustable from 30 to 90°, CW or CCW
    Rotation Time                     Nominal 60 seconds at 60 Hz and 72 seconds at 50 Hz for 90°
    Electrical Connection             1/4 in. spade terminals (Optional pluggable terminal blocks are available.)
    Conduit Connection                M16 Threaded
    Mechanical Connection             10 to 3 mm round shaft or 10 mm square shaft
    Enclosure                         NEMA 2, IP32
    Ambient Operating                 -20 to 52 °C; 90% RH maximum, non-condensing
    Conditions
    Ambient Storage                   -40 to 80 °C; 90% RH maximum, non-condensing
    Conditions
    Dimensions (H x W x D)            150 x 107 x 67 mm
    Shipping Weight                   1.1 kg
    Agency Compliance                 CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
                                      essential requirements and other relevant provisions of the EMC Directive

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

European Single Point of Contact:               NA/SA Single Point of Contact:                    APAC Single Point of Contact:
JOHNSON CONTROLS                                JOHNSON CONTROLS                                  JOHNSON CONTROLS
WESTENDHOF 3                                    507 E MICHIGAN ST                                 C/O CONTROLS PRODUCT
45143 ESSEN                                     MILWAUKEE WI 53202                                MANAGEMENT
GERMANY                                         USA                                               NO. 22 BLOCK D NEW DISTRICT
                                                                                                  WUXI JIANGSU PROVINCE 214142
                                                                                                  CHINA

                                                                                                               Building Efficiency
                                                                                      507 E. Michigan Street, Milwaukee, WI 53202
                                              Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                     All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

4     M9106-AGx-5 Series Electric Non-Spring Return Actuators Installation Instructions