34- 636- 1077, Rev. C

                                                                       Installation Instructions    M9106AGx-2N0x
                                                                                     Issue Date     March 2016

                                 M9106-AGx-2N0x Series Electric
                                  Non-Spring Return Actuators
                                                         must be accessible and protected from moisture and
Installation                                             corrosive fumes.
 IMPORTANT: Use this M9106-AGx-2N0x Series
            Actuator only to control equipment           Parts Included
            under normal operating conditions.           •   M9106-AGx-2N0x Actuator
            Where failure or malfunction of the
                                                         •   CBL-2000-1 Wiring Harness and DPT-2015-0
            actuators could lead to personal
                                                             Differential Pressure Transmitter (included with the
            injury or property damage to the
                                                             M9106-AGS-2N02)
            controlled equipment or other
            property, additional precautions must        •   No. 10 self-drilling sheet metal screw
            be designed into the control system.
            Incorporate and maintain other               Special Tools Needed
            devices, such as supervisory or alarm
                                                         •   5/16 in. (8 mm) square socket
            systems or safety or limit controls,
            intended to warn of or protect against       •   3/8 in. (10 mm) 12-point socket
            failure or malfunction of the
            actuators.                                   •   drill with a 5/16 in. hex nut driver

 IMPORTANT : Utiliser ce M9106-AGx-2N0x Series           •   digital voltmeter (for troubleshooting the
             Actuator uniquement pour                        transmitter)
             commander des équipements dans
             des conditions normales de                  Mounting
             fonctionnement. Lorsqu'une                  To mount the actuator to a damper:
             défaillance ou un dysfonctionnement
             du actuators risque de provoquer des        1. Position the actuator on the damper shaft so the
             blessures ou d'endommager                      damper shaft protrudes through the actuator
             l'équipement contrôlé ou un autre              coupler as shown in Figure 1.
             équipement, la conception du                                             Damper
             système de contrôle doit intégrer des
             dispositifs de protection
             supplémentaires. Veiller dans ce cas
             à intégrer de façon permanente
             d'autres dispositifs, tels que des
             systèmes de supervision ou d'alarme,
             ou des dispositifs de sécurité ou de
                                                                                                          Damper
             limitation, ayant une fonction                                                                Shaft
             d'avertissement ou de protection en
             cas de défaillance ou de
             dysfonctionnement du actuators.

The actuator may be mounted in any convenient
orientation. When installing the DPT-2015 Differential
Pressure Transmitter on the actuator, mount it so the
tubing connecting the flow pick-up device to the               Figure 1: Mounting on the Damper Shaft
DPT-2015 creates a moisture trap. This will prevent
condensation from entering the sensor.                   2. Make sure the actuator is in the desired mounting
                                                            position, parallel to the mounting surface as shown
No extra mounting brackets, linkage, or couplers are        in Figure 2.
required for standard mounting, but wiring terminals

© 2016 Johnson Controls, Inc.                                                                                      1
  Part No. 34-636-1077, Rev. C                                                              www.johnsoncontrols.com
           Approximately
              an 1/8 in.
           (3.2 mm) Gap

                                                                                Figure 4: Damper Position Icons
              Mounting
              Surface                                                 To set the actuator stroke, proceed as follows:
                                                 DPT-2015
                                                                      1. Grasp the damper shaft firmly with pliers and
                                                                         rotate the damper fully closed. (See Figure 5.)
                  Gear
                 Release                                                          Damper
                  Lever

                                                                                                                Damper
                                                                                                                 Shaft

             Figure 2: Actuator Position
3. Verify that the shoulder washer is centered
   between the plastic ribs of the actuator housing to                                                 Damper
   allow actuator movement during rotation.                                                             Blade
   (See Figure 3.)

                                                                             CCW to                CW to
                                                                              Close                Close

                                                                                   Figure 5: Damper Rotation
                                  LO                  Self-drilling
                         5    (-)
                                                      Sheet Metal
                                                                      2. Press and hold the gear release lever shown in
                       -2
                   PT
                         01
                                                       Screw             Figure 2, and rotate the actuator coupler to the
                 O
               G UT
                N
                                                                         fully closed position.
              IN D
                   D
                                                                      3. Make a note of the rotation travel and direction,
               CCW COM                                                   either Clockwise (CW) or Counterclockwise
                      CW                              Shoulder           (CCW), required to close the damper.
                                                      Washer
                                                                      If rotation is less than 90°, proceed to Less Than
                                  Plastic Ribs
                                                                      90 Degrees section.
        Figure 3: Shoulder Washer Position
                                                                       IMPORTANT:           Do not remove the sheet metal
4. Hold the actuator in place on the damper shaft,                     screw and force the damper blade closed by rotating
   and insert the self-drilling sheet metal screw                      the actuator. This puts additional stress on the gear
   through the shoulder washer. (See Figure 3.)                        train and could reduce the life of the actuator.
5. Place a 5/16 in. (8 mm) socket on the screw and
   using a drill and extension, drill the screw into the              90 Degrees
   mounting surface until tight against the washer.                   1. Release the gear release lever.
 IMPORTANT:           Do not overtighten the mounting                 2. Secure the coupler to the shaft using a crescent
 screw to avoid stripping the threads.                                   wrench or one of the tools from the Special Tools
                                                                         Needed section to tighten the coupler set screw
                                                                         against the damper shaft. (See Figure 6.)
Rotation Range
Make sure that the damper blade is visually accessible
or its position is permanently marked on the end of the
damper shaft as shown in Figure 4.

2   M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions
                                 90°
                                                               IMPORTANT:           Do not remove the end-stop
                       30°             60°                     set screws, as this could interfere with the actuator’s
      End-stop
    Set Screws on     10°              45°                     operation.
     End Stops
       (2 each)                                               4. Hand tighten the set screw so it remains in this
                                               Coupler Set
                                                 Screw
                                                                 position.
                                               Damper         5. Secure the coupler to the shaft by using a crescent
        Stop Gear                               Shaft            wrench or one of the tools from the Special Tools
                                                                 Needed section to tighten the coupler set screw
          Figure 6: Setting the Rotation Range                   against the damper shaft. (See Figure 6.)

3. Keeping the actuator parallel to the mounting              6. Keeping the actuator parallel to the mounting
   surface, continue tightening the coupler set screw            surface, continue tightening the coupler set screw
   approximately 1/2 turn to achieve 150 to 180 lb∙in            approximately 1/2 turn to achieve 150 to 180 lb∙in
   (17 to 20 N∙m) torque.                                        (17 to 20 N∙m) torque.

4. Press and hold the gear release lever, and turn the        7. Repeat Steps 1 through 3 to set the desired
   coupler by hand to ensure the damper rotates from             maximum rotation position.
   end to end.                                                8. Use the Phillips screwdriver to tighten both
Proceed to the DPT-2015 section if needed.                       end-stop set screws to a minimum of 25 lb∙in
                                                                 (2.8 N∙m).
Less Than 90 Degrees                                          9. Press and hold the gear release lever, and turn the
If the damper shaft rotation is less than 90°, the stroke        coupler by hand to ensure the damper rotates from
of the actuator has to be adjusted using the scale on            end to end.
the actuator. (See Figure 6.)
                                                              DPT-2015
Use the center of the coupler set screw as a pointer to
observe the position on the scale when rotating the           The M9106-AGx-2N housing has two mounting bosses
coupler from one side to the other.                           for the DPT-2015. (See Figure 7.) Follow the
                                                              procedure in the installation instructions included with
Examples:                                                     the DPT-2015, DPT-2015 Differential Pressure
                                                              Transmitter for VAV Box Applications Installation
•     For a rotation range of 90°, set both end-stop
                                                              Instructions (Part No. 24-7547-18).
      set screws fully up as shown in Figure 6.
•     For a rotation range of 60°, leave one end-stop
      set screw fully up, and adjust the other one, so the
      coupler rotates between the 30 and 90° indicator
      marks on the scale.
•     For a rotation range of 45°, adjust both end-stop
      set screws, so the coupler rotates between 30 and                             Mounting
      75°.                                                                          Bosses

•     For a rotation range of 30°, move both end-stop
      set screws, so the coupler rotates between the
      30 and 60° indicator marks on the scale.                                 CCWCOM
                                                                                     CW
To accurately set the end-stops:
1. Press and hold the gear release lever, and turn the
   actuator coupler to the minimum rotation position               Figure 7: Location of the Mounting Bosses
   for the minimum ventilation flow required.
2. Release the gear release lever.
3. Use a Phillips screwdriver to loosen the end-stop
   set screw that is closest to the stop gear. Move the
   end-stop set screw in its slot until it is tight against
   the stop gear. (See Figure 6.)

                             M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions        3
Wiring                                                     The plenum-rated 20 in. (0.5 m) CBL-2000-2 and
                                                           72 in. (1.8 m) CBL-2000-3 Wiring Harnesses are also

    !
                                                           available. (See Table 1.)
        CAUTION: Risk of Electric Shock.
Disconnect the power supply before making                  Setup and Adjustments
electrical connections to avoid electric shock.
                                                           Air Pressure (M9106-AGS-2N02)
MISE EN GARDE : Risque de décharge
électrique. Débrancher l'alimentation avant de             The flow pickup device provided with the Variable Air
                                                           Volume (VAV) box must be connected to the
réaliser tout raccordement électrique afin d'éviter tout
                                                           DPT-2015 using field-supplied tubing as follows:
risque de décharge électrique.
                                                           1. Cut two lengths of tubing, and connect them to the
                                                              flow pickup device.
    !   CAUTION: Risk of Property Damage.                   IMPORTANT:            Make sure the tubing is properly
Do not apply power to the system before checking all        sized and made of an elastic material, such as
wiring connections. Short circuited or improperly           silicone rubber, to ensure airtight connections and
connected wires may result in permanent damage to           minimize flow measurement errors.
the equipment.
                                                           2. Connect the tubing from the flow pickup device to
MISE EN GARDE : Risque de dégâts matériels.                   the corresponding barbed high and low pressure
Ne pas mettre le système sous tension avant d'avoir           ports on the DPT-2015. (See Figure 9.)
vérifié tous les raccords de câblage. Des fils formant     Note: The upper port is the low pressure port and
un court-circuit ou connectés de façon incorrecte          indicated as (-)LO on the transmitter.
risquent d'endommager irrémédiablement
l'équipement.                                                                1/4 in. Barbed Ports (2)
                                                                            for Field-supplied Tubing

IMPORTANT:           All wiring must be in accordance
with the National Electrical Code and local electrical
regulations.
                                                                                           Upper Port
                                                                                             (-)LO
The actuator requires a 24 VAC control signal and is
compatible with a variety of controllers. Refer to
Figure 8 for the wiring configuration.                                                     DPT-2015
          M9106-AGx-2N0x          DPT-2015
        CCW COM      CW        IN   GND OUT

                           14.5 to 17       0.5 to 4.5
        24 Common 24          VDC              VDC
        VAC       VAC         (+)       (-)    (+)

                                                            Figure 9: M9106-AGS-2N02 with Wiring Harness

               CBL-2000-x Wiring Harness                   3. Route the tubing so a portion of it is lower than the
                                                              DPT-2015. This creates a trap that prevents any
              Figure 8: Wiring Diagram                        condensation from entering the sensor. Avoid
                                                              making any sharp bends in the tubing.
Note: To avoid excessive wear or drive time on the
motor, use a controller and/or software that provides a     IMPORTANT:           Overpressure limit is 15 in. W.C.
time-out function to remove the signal at the end of        (3.74 kPa). Do not blow into ports to test their
rotation (stall).                                           operation, as this could damage the sensing
The 20 in. (0.5 m) CBL-2000-1 Wiring Harness,               element.
accepted by Underwriters Laboratories, Inc.® (UL) for
plenum use, is pre-wired with the M9106-AGS-2N02 or
may be ordered separately.

4   M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions
Commissioning                                                  (Part No. 24-7547-18), to ensure proper operation
                                                               of the transmitter.
M9106-AGx-2N0x
After wiring is completed, apply power to the controller   IMPORTANT:            Perform commissioning when
and provide signals to the actuator to drive it at least   the transmitter is permanently mounted and
one complete cycle open and closed.                        operating at normal temperatures.

                                                           2. Set up and zero using HVAC PRO software
DPT-2015
                                                              when using a DPT-2015 with a Johnson Controls
To commission the transmitter:                                VAV Series controller. Refer to the Variable Air
1. Perform the checkout procedure provided in the             Volume Controller Technical Bulletin
   controller installation instructions, DPT-2015             (LIT-6363040) for details.
   Differential Pressure Transmitter for VAV Box
   Applications Installation Instructions
                                                           •   Verify that the air lines on the DPT-2015 are
Troubleshooting                                                connected to their respective high and low ports
                                                               with no kinks in the tubing.
M9106-AGx-2N0x
If the actuator is not responding or working properly:     •   Check the supply voltage to ensure it is within the
                                                               14.5 to 17 VDC range and the polarity is correct.
•   Verify that the actuator assembly is properly
    secured to the duct.                                   •   Disconnect the air lines from the high and low
                                                               ports, and place a voltmeter across the OUT and
•   Check that all electrical connections are complete         GND terminals on the DPT-2015. If the output is
    and power is applied.                                      not between 0.4 and 0.6 volts with power applied
•   Verify that the damper fully opens and closes,             to the DPT-2015 in the vertical position, the
    using the gear release lever on the actuator.              transmitter is defective and should be replaced.
                                                           Note: Voltage readings may vary by 0.1 volt if the
•   Check that the actuator stroke is set for the
                                                           transmitter is in the horizontal position.
    desired application.

DPT-2015                                                   Repairs and Replacement
The DPT-2015 must be auto zeroed by a                      Field repairs must not be made. For a replacement
Johnson Controls VAV controller. If the DPT-2015 is        product or an accessory, refer to the M9106-AGx-2N0x
not operating properly:                                    Series Electric Non-Spring Return Actuators Product
                                                           Bulletin (LIT-2681126).

                         M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions        5
Technical Data
    Product                           M9106-AGx-2N0x Series Electric Non-Spring Return Actuators
    Power Requirements                M9106-AGA-2N01:           20 to 30 VAC at 50/60 Hz, 2.5 VA supply, Class 2
                                      M9106-AGx-2N02:           20 to 30 VAC at 50/60 Hz, 2.1 VA supply, Class 2
                                      DPT-2015:                 15 VDC (14.5 to 17 VDC) unregulated; 15 mA maximum
    Input Signal                      M9106-AGx-2N0x:           24 VAC (20 to 30 VAC) at 50 or 60 Hz
    Motor Input Impedance             M9106-AGA-2N01:           200 ohms, nominal
                                      M9106-AGx-2N02:           250 ohms, nominal
    DPT-2015-0                        Pressure Range:           0 to 1.5 in. W.C. (0 to 374 Pa)
                                      Over Pressure Limit:      15 in. W.C. (3.74 kPa)
                                      Output Voltage:           0.5 to 4.5 VDC with 25,000 ohm minimum load impedance
    Mechanical Output                 Running Torque:           53 lb∙in (6 N∙m)
    Cycles                            100,000 full cycles; 2,500,000 repositions rated at 53 lb∙in (6 N∙m)
    Audible Noise Rating              35 dBA maximum at 1 m
    Rotation Range                    Adjustable from 30 to 90°, CW or CCW
    Rotation Time                     M9106-AGx-2N01:           Nominal 60 seconds at 60 Hz and 72 seconds at 50 Hz for 90°
                                      M9106-AGS-2N02:           Nominal 120 seconds at 60 Hz and 144 seconds at 50 Hz for 90°
    Electrical Connection             No. 6-32 screw terminals on the M9106 actuator; 1/4 in. spade terminals on the DPT-2015
    Pressure Connection               6 in. (152 mm) length of silicone tubing with barbed fittings for 1/4 in. (6.35 mm)
                                      O.D. tubing
    Enclosure                         NEMA1, IP30
    Ambient Operating                 M9106-AGA-2N0x:           32 to 125°F (0 to 52°C); 90% RH maximum, non-condensing
    Conditions                        M9106-AGS-2N02:           32 to 125°F (0 to 52°C); 90% RH maximum, non-condensing
                                                                60 to 100°F (16 to 38°C); 90% RH maximum, non-condensing
                                          For DPT rated accuracy, see DPT-2015 Differential Pressure Transmitter for VAV Box
                                          Applications Installation Instructions (Part No. 24-7547-18).
    Ambient Storage                   -20 to 150°F (-29 to 66°C); 90% RH maximum, non-condensing
    Conditions
    Dimensions (H x W x D)            M9106-AGA-2N01:     5.95 x 4.2 x 2.15 in. (151.2 x 107.3 x 54.6 mm)
                                      M9106-AGx-2N02: 5.95 x 4.2 x 2.32 in. (151.2 x 107.3 x 58.9 mm) with the DPT-2015
    Shipping Weight                   M9106-AGA-2N0x:           2.0 lb (0.91 kg)
                                      M9106-AGS-2N02:           2.2 lb (0.99 kg) with the DPT-2015
    Agency Compliance                 UL 873 Listed, File E27734, CCN XAPX
    (M9106 Actuator)                  CSA C22.2 No. 139 Certified, File LR85083, Class 3221 02
                                      CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
                                      essential requirements and other relevant provisions of the EMC Directive

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.

6     M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions
European Single Point of Contact:      NA/SA Single Point of Contact:            APAC Single Point of Contact:
JOHNSON CONTROLS                       JOHNSON CONTROLS                          JOHNSON CONTROLS
WESTENDHOF 3                           507 E MICHIGAN ST                         C/O CONTROLS PRODUCT
45143 ESSEN                            MILWAUKEE WI 53202                        MANAGEMENT
GERMANY                                USA                                       NO. 22 BLOCK D NEW DISTRICT
                                                                                 WUXI JIANGSU PROVINCE 214142
                                                                                 CHINA

                                                                                             Building Efficiency
                                                                   507 E. Michigan Street, Milwaukee, WI 53202

                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                    All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

                        M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions         7