Submittal Bulletin
                                                                                  Issue Date      January 13, 2003

       M9104-AGx-2N Electric Non-spring Return Actuators

The M9104-AGA-2N synchronous motor-driven
actuator provides floating (3-wire) control and is easily
installed on a Variable Air Volume (VAV) box, or a
small- or medium-sized damper with a round shaft up
to 1/2 inch (13 mm) in diameter or a 3/8 inch (10 mm)
square shaft.

This compact, non-spring return actuator has a 35 lb·in
(4 N·m) running torque and 40 lb·in (4.5 N·m) minimum
stall torque in a compact easy-to-install package. It
has a nominal 90-second travel time at 60 Hz
(108 seconds at 50 Hz) for 90° of rotation.

The M9104-AGS-2N Actuator/Transmitter combines
an M9104-AGA-2N with a prewired DPT-2015
Differential Pressure Transmitter that has a 0 to
1.5 inch W.C. (0 to 374 Pa) differential pressure range.

                                                                 Figure 1: M9104-AGS-2N Non-spring Return
                                                                                  Actuator

                                               Features and Benefits
                  ❑ 30 dBA Rating                     Meets audible requirements for open ceilings

                  ❑ Synchronous Drive                 Provides constant rotation time independent
                                                      of load

                  ❑ 100,000 Cycle Rating              Extends actuator life due to improved
                                                      technology

                  ❑ Direct Shaft Mount with           Simplifies installation and provides three-point
                       Single-Screw Coupler           shaft gripping

                  ❑ Magnetic Clutch                   Provides torque protection for the actuator
                                                      gear train and damper

                  ❑ Adjustable Rotation Stops         Allow application versatility with 30 to 90°
                                                      Clockwise (CW) or Counterclockwise (CCW)
                                                      rotation

                  ❑ Manual Gear Release               Simplifies setup and field adjustments

                  ❑ Screw Terminal Connection         Makes wiring easy

© 2003 Johnson Controls, Inc.                                                                                          1
  Code No. LIT- 1201445                                                                           www.johnsoncontrols.com
Application
 IMPORTANT:           This device is not designed or        The actuator rotates at a nominal rate of 1° per second
 intended to be used in or near environments where          (90° in 1.5 minutes). The actuator rotation is field
 explosive vapors or gases could be present, or             adjustable from 30 to 90°. Determine the actual
 environments where substances corrosive to the             rotation time for actuators using less than 90° rotation,
 device's internal components could be present.             and use that value with the controller software. For
                                                            example, use 1 minute for 60° rotation.
The M9104-AGx-2N actuator is used to position               The M9104-AGS-2N includes the 20 in. (0.5 m)
balancing, control, round, and zone dampers in typical      CBL-2000-1 Wiring Harness and the DPT-2015, which
Heating, Ventilating, and Air Conditioning (HVAC)           is connected to the airflow pickup device of the
applications. It is also used to position the blades in a   VAV box. The DPT-2015 measures differential
VAV box.                                                    pressure and generates a proportional 0.5 to 4.5 VDC
The actuator mounts directly to the surface of a            signal. The voltage signal from the DPT-2015 is read
VAV box, round damper, or small rectangular damper          by the VAV controller and converted to airflow in cubic
with a single No. 10 self-drilling sheet metal screw        feet per minute (cfm). The wiring harness is used to
(included). There are no additional linkages or             connect the transmitter and actuator to the VAV Series
couplers required. Clearly labeled electrical terminals     controller for simplified installation.
simplify installation. Refer to the damper or VAV box       Only zero calibration is required, which is performed
manufacturer’s information to select the proper timing      within the controller. The VAV controller must be
for the actuator.                                           provided with the correct “K” factor and VAV box size
                                                            to perform the calculations. Refer to the HVAC PRO
Operation                                                   User's Guide, Appendix B: VAV Controller Flow
                                                            Calculation Constants (LIT-6375185).
 IMPORTANT: The M9104-AGx-2N Series actuators
 are intended to control equipment under normal
 operating conditions. Where failure or malfunction of
                                                            Dimensions
 an M9104-AGx-2N actuator could lead to an                  See Figure 2 for the actuator and differential pressure
 abnormal operating condition that could cause              transmitter.
 personal injury or damage to the equipment or other                                     4.0
 property, other devices (limit or safety controls), or                                 101.6                           1.7
                                                                                                                       43.2
 systems (alarm or supervisory) intended to warn of,             1.25
 or protect against, failure or malfunction of the               31.8
 M9104-AGx-2N actuator must be incorporated into
 and maintained as part of the control system.
                                                                  4.33                                  5.95
When combined with a VAV controller, the actuator                110.0         -2
                                                                                        (-)
                                                                                           LO
                                                                                                        151.2
provides reliable, integrated damper control. See the                       O
                                                                                 01
                                                                                    5
                                                                          G UT
M9104-AGx-2N Electric Non-spring Return Actuators                          N
                                                                         IN D
                                                                              DPT
Application Note (LIT-2681110) for various
configurations with and without the DPT-2015                              CCW
                                                                             COMCW
differential pressure transmitter.
A 24 VAC signal from the controller to the CW or                                                 0.26
                                                                                                 6.6                   2.05
CCW terminal of the actuator causes the motor to                              2.0                                      52.1
rotate in the proper direction, and moves the damper                          50.8               4.2                    0.1
blades open or closed. When the controller stops                                                107.3                  2.54
sending the signal, the actuator remains in place.
                                                                                                                1.00
Note: To avoid excessive wear or drive time on the                                                              25.4
motor, use a controller and/or software that provides a            2.15                                                 2.32
                                                                   54.6                                            1.1 58.9
time-out function to remove the signal at the end of
                                                                                                                   28.3
rotation (stall).
                                                                Note: All dimensions are nominal unless otherwise specified.

                                                                        Figure 2: M9104-AGS-2N, in. (mm)

2   M9104-AGx-2N Electric Non-spring Return Actuators Submittal Bulletin
Ordering Information
Table 1: Products Available
  Product Code                                                 Description
     Number
 M9104-AGA-2N       35 lb in (4 N m) Electric non-spring return actuator with floating control
 M9104-AGS-2N       35 lb in (4 N m) Electric non-spring return actuator with floating control (includes the DPT-2015
                    and CBL-2000-1)
 CBL-2000-1         20 in. (0.5 m) wiring harness, Underwriters Laboratories®, Inc. (UL) accepted for plenum use,
                    supplied with the M9104-AGS-2N and may be ordered separately; connects the M9104 and
                    DPT-2015 to the VAV controller
 CBL-2000-2         20 in. (0.5 m) plenum-rated wiring harness
 CBL-2000-3         72 in. (1.8 m) plenum-rated wiring harness
 DPT-2015-0         0 to 1.5 in. W.C. (0 to 374 Pa) differential pressure transmitter supplied with the M9104-AGS-2N
                    and may be ordered separately
 DMPR-KC003         Blade Pin Extension without Bracket supplied with D-1300 dampers and may be ordered
                    separately
 DMPR-KR003         Sleeve Pin Kit supplied with round dampers that have a 5/16 in. (8 mm) shaft and may be
                    ordered separately
 M9000-200          Commissioning Tool provides a control signal to drive on/off, floating, proportional, or
                    resistive actuators.

                                      M9104-AGx-2N Electric Non-Spring Return Actuators Submittal Bulletin              3
Technical Specifications
    Product                           M9104-AGx-2N Electric Non-spring Return Actuators
    Power Requirements                M9104-AGx-2N:                20 to 30 VAC at 50/60 Hz, 2.1 VA supply, Class 2
                                      DPT-2015:                    15 VDC (14.5 to 17 VDC) unregulated; 15 mA maximum
    Input Signal                      M9104-AGx-2N:                24 VAC (20 to 30 VAC) at 50/60 Hz
    Motor Input Impedance             M9104-AGx-2N:                250 ohms, nominal
    DPT-2015-0                        Pressure Range:              0 to 1.5 in. W.C. (0 to 374 Pa)
                                      Over Pressure Limit:         15 in. W.C. (3.74 kPa)
                                      Output Voltage:              0.5 to 4.5 VDC with 25,000 ohm minimum load impedance
    Mechanical Output                 Running Torque:              35 lb·in (4 N·m)
    Cycles                            100,000 full cycles; 2,500,000 repositions rated at 35 lb·in (4 N·m)
    Audible Noise Rating              30 dBA maximum at 1 m
    Rotation Range                    Adjustable from 30 to 90°, CW or CCW
    Rotation Time                     Nominal 90 seconds at 60 Hz for 90°
                                      Nominal 108 seconds at 50 Hz for 90°
    Electrical Connection             No. 6-32 screw terminals on the M9104 actuator; 1/4 in. spade terminals on the DPT-2015
    Pressure Connection               6 in. (152 mm) length of silicone tubing with barbed fittings for 1/4 in. (6.35 mm) O.D. tubing
    Enclosure                         NEMA 1, IP30
    Ambient Operating                 M9104-AGA-2N:                32 to 125°F (0 to 52°C); 90% RH maximum, noncondensing
    Conditions                        M9104-AGS-2N:                32 to 125°F (0 to 52°C); 90% RH maximum, noncondensing
                                                                   60 to 100°F (16 to 38°C); 90% RH maximum, noncondensing for
                                                                   DPT rated accuracy, see DPT-2015 Differential Pressure
                                                                   Transmitter for VAV Box Applications Installation Instructions
                                                                   (Part No. 24-7547-18).
    Ambient Storage                   -20 to 150°F (-29 to 66°C); 90% RH maximum, noncondensing
    Conditions
    Dimensions (H x W x D)            M9104-AGA-2N:                5.95 x 4.2 x 2.15 in. (151.2 x 107.3 x 54.6 mm)
                                      M9104-AGS-2N:                5.95 x 4.2 x 2.32 in. (151.2 x 107.3 x 58.9 mm) with the DPT-2015
    Shipping Weight                   M9104-AGA-2N:                2.0 lb (0.91 kg)
                                      M9104-AGS-2N:                2.2 lb (0.99 kg) with the DPT-2015
    Agency Compliance                 UL 873 Listed, File E27734, CCN XAPX
    (M9104)                           CSA Certified C22.2 No. 139, File LR85083, Class 3221 02
                                      CE Mark, EMC Directive 89/336/EEC

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                                 Published in U.S.A.
Milwaukee, WI 53201                                                                                                    www.johnsoncontrols.com

4     M9104-AGx-2N Electric Non-spring Return Actuators Submittal Bulletin

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.