14- 1330- 18, Rev . B

M9000-310 and M9000-320 Series Weather Shield
Enclosures
Installation Instructions                                                           Part No. 14-1330-18, Rev. B
                                                                                               Issued June 2016

Applications                                                Installation
The M9000-310 and M9000-320 Weather Shield                  Refer to the following documentation for more
Enclosures are cost-effective and durable weather           information on the M9000 Series Electric Actuators and
shields designed to provide a degree of protection for a    Valve Linkages used with the M9000-310 and M9000-
single Johnson Controls® M9000 Series Electric              320 Weather Shield Enclosures:
Actuator used in either control damper or iron flanged
                                                            •   M9106-xGx-2 Series Electric Non-Spring Return
valve applications. These weather shield enclosures
                                                                Actuators Installation Instructions (Part No. 34-
are manufactured to National Electrical Manufacturers’
                                                                636-1085)
Association (NEMA) 3R specifications and protect the
electric actuator from corrosion, rain, freezing rain,      •   M9108, M9116, M9124, and M9132 Series Electric
sleet, and snow. The enclosure can be mounted                   Non-Spring Return Actuators Installation
indoors or outdoors; however, it may not prevent                Instructions (Part No. 34-636-399)
externally formed ice from restricting the motion of the
                                                            •   M9109 Series Electric Non-spring Return
rotary shaft.
                                                                Actuators Installation Instructions (Part No. 34-
Each enclosure is constructed of impact-grade ABS               636-1190)
plastic that provides excellent impact resistance. The
                                                            •   M9220-AGx-3 Floating Electric Spring Return
cover features ultraviolet inhibitors that extend service
                                                                Actuators Installation Instructions (Part No. 34-
life by preventing the cover from becoming brittle or
                                                                636-1689)
damaged by the sun or other environmental elements.
The transparent cover provides an unobstructed view         •   M9220-Bxx-3 On/Off Electric Spring Return
of the electric actuator without having to disassemble          Actuators Installation Instructions (Part No. 34-
the enclosure. An appliance cord enables installation of        636-1239)
control wiring, and a form-fitting seal prevents water or
                                                            •   M9220-GGx-3 Proportional Electric Spring Return
moisture from entering the unit and damaging the
                                                                Actuators Installation Instructions (Part No. 34-
actuator.
                                                                636-1697)
 IMPORTANT: The M9000-310 and M9000-320                     •   M9000-53x Cast Iron Flanged Valve Linkage Kit for
 Weather Shield Enclosures only provide protection              Mounting a Single M9000 Series Electric Actuator
 for the Johnson Controls M9000 Series Electric                 Installation Instructions (Part No. 14-1298-18)
 Actuator used in control damper and iron flanged
 valve applications. To ensure proper operation,            •   M9000-53x Series Cast Iron Flanged Valve
 check that all associated equipment used in the                Linkage Kit for Tandem Mounting of M9000 Series
 application is suitable for the surrounding                    Electric Actuators Installation Instructions
 environment.                                                   (Part No. 14-1298-26)

                          M9000-310 and M9000-320 Series Weather Shield Enclosures
                                          Installation Instructions
                                                      1
Parts Included

                                                                                            Mounting
                                                                                            Brackets

                         Anti-Rotation
                              Bracket

                                                                                                         No. 12-24 x 1/2 in.
                                                                                                         Hex-Head Screws
                                                                                                         (Eight Locations)
                                                                                   Threaded
                                                                                   Hex Nuts

                                                                                          Enclosure Base and
                                                                                          Seal Assembly

             Cover Screws
           (Four Locations)                                                           Strain Relief
                                                                                      Conduit Fittings
                                                         M3 x 8 mm                    (Two Locations)
                                                         Phillips Screws and
                                                         M4 Washers (Two Locations)
                                                                                                                          FIG:prts_incl
                                                     Cover and
                                                     Gasket

     Figure 1: Parts Included in M9000-310 and M9000-320 Weather Shield Enclosure Kits (See Table 1)

Table 1: Parts Included in M9000-310 and M9000-320 Weather Shield Enclosure Kits
 Quantity           Description
 1                  Enclosure Base and Seal Assembly
 1                  Cover and Gasket
 4                  Cover Screws
 2                  Mounting Brackets
 8                  No. 12-24 x 1/2 in. Hex-Head Screws with Nitrile Patch
 1                  Anti-Rotation Bracket
 2                  M3 x 8 mm Phillips Screws
 2                  M4 Washers
 2                  Strain Relief Conduit Fittings with 1/2 in. National Pipe Straight Mechanical (NPSM) Exit1
 1                  Cap Plug
 2                  Threaded Hex Nuts
 1                  Appliance Cord - 6 Conductor, 18 AWG Wire Gauge, 43 in. (109 cm)
 1                  Shaft Extender with Set Screw (M9000-320 Kit Only)

1.   It is recommended that 1/2 in. liquid-tight conduit and 1/2 in. National Pipe Thread (NPT) liquid-tight fittings (purchased
     locally) be used to terminate the control wiring to the weather shield enclosure strain relief conduit fittings.

                M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

                                                                 2
Dimensions

                                                                                                 FIG:dmns

                       Figure 2: Weather Shield Enclosure Dimensions, in. (mm)
                                            (See Table 2.)

Table 2: Weather Shield Enclosure Dimensions, in. (mm)
Dimension              Weather Shield Enclosure
                       M9000-310                                 M9000-320
A                      7-7/8 (200)                               13-3/8 (340)
B                      4-23/32 (120)                             5-29/32 (150)
C                      3-17/32 (90)                              4-23/32 (120)
D                      4-27/32 (123)                             6-1/32 (153)
E                      5-13/32 (137)                             6-9/16 (167)

            M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

                                                    3
Mounting                                                                4. Orient the two mounting brackets onto the
                                                                           enclosure base as illustrated in Figure 4.
The M9000-310 and M9000-320 Weather Shield
Enclosure Kits are shipped from the factory partially
assembled, with the cover held in place using the four
cover screws included with the kit. The remainder of
the parts required for mounting can be found inside the
enclosure.
Control Damper Applications
Mount the weather shield enclosure onto a control
damper as follows:
1. Loosen the four cover screws using a No.1 Phillips
   screwdriver and remove the cover and gasket
   assembly from the enclosure base.
2. Orient the anti-rotation bracket onto the enclosure
   as illustrated in Figure 3.
Note: The anti-rotation bracket must be oriented
properly for the anti-rotation tab to align with the slot on                                                                  FIG:mntbrkt
                                                                                M9000-310                     M9000-320
the electric actuator.
                                                                              Figure 4: Proper Orientation of the
                                                                           Mounting Brackets onto the Enclosure Base

                                                                        5. Secure the mounting brackets to the enclosure
                                                                           base using four No. 12-24 x 1/2 in. hex-head
                                                                           screws (included with the kit).
                                                                        Note: Each hex-head screw should be inserted from
                                                                        the inside of the enclosure so that the nitrile patch
                                                                        seals the mounting hole in the base.
                                                                        6. Install the enclosure and mounting bracket
                                                                           assembly onto the damper shaft extension. Orient
                                    Anti-Rotation                          the assembly so that the flanges of the mounting
                                      Bracket
       Anti-Rotation                                                       brackets are flush with the mounting surface.
         Bracket
                                                                        7. Using the mounting brackets as a template, mark
                                                                           the mounting hole locations with a ball-peen
                                                                           hammer and punch.
        M9000-310                    M9000-320         FIG:rtbrkt
                                                                        8. Remove the enclosure and mounting bracket
 Figure 3: Proper Orientation of the Anti-Rotation                         assembly from the damper shaft extension.
                     Bracket                                            9. Drill pilot holes at each of the marked spots using a
                                                                           drill and a No. 10 drill bit.
3. Secure the anti-rotation bracket to the threaded                     10. Reinstall the enclosure and mounting bracket
   brass inserts of the enclosure base using two                            assembly onto the damper shaft extension. Orient
   M3 x 8 mm Phillips screws and M4 washers                                 the assembly so that the flanges of the mounting
   included with the kit. Tighten the Phillips screws to                    brackets are flush with the mounting surface and
   a torque of 15 to 20 lb·in (1.7 to 2.3 N·m).                             the holes in the mounting brackets align with the
                                                                            pilot holes drilled in Step 9.
 IMPORTANT: Do not overtighten the Phillips
 screws. Overtightening may cause the threaded                          11. Secure the enclosure and mounting bracket
 inserts located in the enclosure base to become                            assembly to the mounting surface using four
 dislodged, resulting in damage to the enclosure.                           No. 12-24 x 1/2 in. hex-head screws included with
                                                                            the kit. Tighten the hex-head screws to a torque of
                                                                            20 to 25 lb·in (2.3 to 2.8 N·m).

               M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

                                                                    4
12. Install the two conduit fittings included with the kit       3. Secure the anti-rotation bracket to the threaded
    into the enclosure base and secure them in place                brass inserts of the enclosure base using two
    using the threaded hex nuts.                                    M3 x 8 mm Phillips screws and M4 washers
                                                                    included with the kit. Tighten the Phillips screws to
 IMPORTANT: The conduit fittings must be installed                  a torque of 15 to 20 lb·in (1.7 to 2.3 N·m).
 properly to ensure a tight seal. Water or moisture
 may damage or affect the operation of the electric               IMPORTANT: Do not overtighten the Phillips
 actuator within the enclosure.                                   screws. Overtightening may cause the threaded
                                                                  inserts located in the enclosure base to become
13. Insert the appliance cord into one of the conduit             dislodged, resulting in damage to the enclosure.
    fittings so that the cable wrapping is visible inside
    the enclosure. Tighten the conduit fitting to a              4. Orient the two mounting brackets onto the primary
    torque of 10 to 15 lb·in (1.1 to 1.7 N·m) to secure             side of the M9000-53x Series Valve Linkage (for
    the appliance cord in place.                                    single-mount applications) as illustrated in
                                                                    Figure 5.
14. Install the electric actuator onto the damper shaft
    extension and the enclosure anti-rotation bracket.
Note: Refer to the documentation included with the                                                                  FIG:mntbrkt53x

electric actuator for complete installation instructions.
15. Reinstall the cover and gasket assembly and
    secure it in place using the four cover screws
    included with the kit. Tighten the cover screws to a
    torque of 5 to 8 lb·in (0.6 to 0.9 N·m) maximum.

 IMPORTANT: The cover and gasket assembly
 must be installed properly to ensure a tight seal.
 Water or moisture may damage or affect the
 operation of the electric actuator within the
                                                                            Primary Side of     Secondary Side of
 enclosure.                                                                M9000-53x Series     M9000-53x Series
                                                                            Valve Linkage         Valve Linkage
16. If one of the conduit fittings remains unused, seal
    the fitting using the cap plug included with the                     Figure 5: Proper Orientation of the
    enclosure kit.                                                       Mounting Brackets onto the M9000-
                                                                             53x Series Valve Linkage
Iron Flanged Valve Applications
Mount the weather shield enclosure onto the M9000-               5. Secure the mounting brackets to the M9000-
53x Series Valve Linkage as follows:                                53x Series Valve Linkage using four No. 12-24 x 1/
1. Loosen the four cover screws using a No. 1 Phillips              2 in. hex-head screws (included with the kit).
   screwdriver and remove the cover and gasket                   6. Install the enclosure onto the input shaft of the
   assembly from the enclosure base.                                M9000-53x Series Valve Linkage. Orient the
2. Orient the anti-rotation bracket onto the enclosure              enclosure so that the flanges of the mounting
   as illustrated in Figure 3.                                      brackets are flush with the surface of the enclosure
                                                                    base.
Note: The anti-rotation bracket must be oriented
properly in order for the anti-rotation tab to align with        7. Secure the enclosure to the mounting brackets
the slot on the electric actuator.                                  using four No. 12-24 x 1/2 in. hex-head screws
                                                                    included with the kit. Tighten the hex-head screws
                                                                    to a torque of 20 to 25 lb·in (2.3 to 2.8 N·m).
                                                                 Note: Each hex-head screw should be inserted from
                                                                 the inside of the enclosure so that the nitrile patch
                                                                 seals the mounting hole in the base.

               M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

                                                             5
8. Install the two conduit fittings included with the kit                      11. Using a flat blade screwdriver, remove and save
   into the enclosure base and secure them in place                                the spring clip from the M9220 actuator hub and
   using the threaded hex nuts.                                                    gripper assembly. Remove the actuator gripper
                                                                                   assembly from the actuator and retain.
 IMPORTANT: The conduit fittings must be installed
                                                                               12. Insert the appliance cord(s) for the actuator
 properly to ensure a tight seal. Water or moisture
                                                                                   through the conduit fittings.
 may damage or affect the operation of the electric
 actuator within the enclosure.                                                13. Install the actuator into the enclosure/linkage
                                                                                   assembly. Insert the actuator anti-rotation slots
Steps 9 and 11 apply only to the M9000-320 kit when                                over the anti-rotation tab of the bracket from
used with the M9220 Series actuators. For the M9000-                               Step 3.
310 kit, proceed to Step 12.
                                                                               14. Center the shaft or shaft extension in the actuator
9. For the M9000-320 kit used with the M9220 Series                                hub. For the M9220, reinstall the actuator gripper
   actuators, install the shaft extension onto the input                           assembly and secure in place using the spring clip.
   shaft of the valve linkage. Ensure that the set                                 Secure the actuator coupler assembly to the shaft
   screws located on the shaft extension are oriented                              following the actuator mounting instructions.
   perpendicular to the flat surfaces on the input shaft.
                                                                               Note: Refer to the documentation included with the
   (See Figure 6.) To reduce friction, ensure that the
                                                                               electric actuator and valve linkage for complete
   shaft extension and the seal assembly are not in
                                                                               installation instructions.
   contact. A gap of no more than 1/8 in. is
   recommended between these two components.                                   15. Tighten the conduit fitting to a torque of 10 to
                                                                                   15 lb·in (1.1 to 1.7 N·m) to secure the appliance
                                                                                   cord in place.
                                                                               16. Reinstall the cover and gasket assembly and
                                                                                   secure it in place using the four cover screws
                                                                                   included with the kit. Tighten the cover screws to a
                                                                                   torque of 5 lb·in (0.6 N·m) maximum.
                                                                               17. If the valve application is a tandem configuration,
                                                                                   repeat Steps 11 through 16 on the secondary side
                                                                                   of the M9000-53x Series Valve Linkage.

                                                                                IMPORTANT: The cover and gasket assembly
                                                                                must be installed properly to ensure a tight seal.
                                                                                Water or moisture may damage or affect the
                                                                                operation of the electric actuator within the
                                                                                enclosure.

                                                                               18. If one of the conduit fittings remains unused, seal
                                                                                   the fitting using the cap plug included with the
                                                                                   enclosure kit.
                                                            FIG:mntg_pos
                                                                               Repair Information
   Figure 6: Proper Mounting Position for Shaft                                If the M9000-310 or M9000-320 Series Weather Shield
                    Extension                                                  Enclosure fails to operate within its specifications,
                                                                               replace the unit. For a replacement weather shield,
10. Secure the shaft extension to the input shaft of the                       contact the nearest Johnson Controls representative.
    valve linkage using the supplied set screws and 5/
    16 in. (8 mm) wrench. The recommended torque
    applied to the set screws is 100 in·lb (11 N·m).
    Tighten the screws evenly.

              M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

                                                                           6
Technical Specifications
M9000-310 and M9000-320 Weather Shield Enclosures
 Materials                      Enclosure                 Impact-Grade ABS Plastic
                                Enclosure Seal            Nitrile
                                Cover                     Transparent Impact-Grade ABS Plastic with Ultraviolet Inhibitors
                                Cover Gasket              Neoprene
 Weather Shield Rating                                    NEMA 3R, IP32
 Actuator Ambient               M9106 and M9109           -4 to 122°F (-20 to 50°C)
 Operating                      (M9000-310 Only)
 Temperature Limits
                                M9108, M9116,             -4 to 122°F (-20 to 50°C)
                                M9124, and M9132
                                M9220                     -40 to 131°F (-40 to 55°C)
 Weather Shield Enclosure Ambient Storage                 -40 to 176°F (-40 to 80°C)
 Temperature Limits
 Electrical Connections                                   Strain Relief Conduit Fittings with 1/2 in. National Pipe Straight Mechanical
                                                          (NPSM) Exit
 Shipping Weight                M9000-310                 2.0 lb (0.9 kg)
                                M9000-320                 3.3 lb (1.5 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

European Single Point of Contact:             NA/SA Single Point of Contact:               APAC Single Point of Contact:
JOHNSON CONTROLS                              JOHNSON CONTROLS                             JOHNSON CONTROLS
WESTENDHOF 3                                  507 E MICHIGAN ST                            C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN                                   MILWAUKEE WI 53202                           NO. 22 BLOCK D NEW DISTRICT
GERMANY                                       USA                                          WUXI JIANGSU PROVINCE 214142
                                                                                           CHINA

                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                    All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

                 M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions

Published in U.S.A.                                                     7                                           www.johnsoncontrols.com

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.