14- 1330- 18, Rev . B
M9000-310 and M9000-320 Series Weather Shield
Enclosures
Installation Instructions Part No. 14-1330-18, Rev. B
Issued June 2016
Applications Installation
The M9000-310 and M9000-320 Weather Shield Refer to the following documentation for more
Enclosures are cost-effective and durable weather information on the M9000 Series Electric Actuators and
shields designed to provide a degree of protection for a Valve Linkages used with the M9000-310 and M9000-
single Johnson Controls® M9000 Series Electric 320 Weather Shield Enclosures:
Actuator used in either control damper or iron flanged
• M9106-xGx-2 Series Electric Non-Spring Return
valve applications. These weather shield enclosures
Actuators Installation Instructions (Part No. 34-
are manufactured to National Electrical Manufacturers’
636-1085)
Association (NEMA) 3R specifications and protect the
electric actuator from corrosion, rain, freezing rain, • M9108, M9116, M9124, and M9132 Series Electric
sleet, and snow. The enclosure can be mounted Non-Spring Return Actuators Installation
indoors or outdoors; however, it may not prevent Instructions (Part No. 34-636-399)
externally formed ice from restricting the motion of the
• M9109 Series Electric Non-spring Return
rotary shaft.
Actuators Installation Instructions (Part No. 34-
Each enclosure is constructed of impact-grade ABS 636-1190)
plastic that provides excellent impact resistance. The
• M9220-AGx-3 Floating Electric Spring Return
cover features ultraviolet inhibitors that extend service
Actuators Installation Instructions (Part No. 34-
life by preventing the cover from becoming brittle or
636-1689)
damaged by the sun or other environmental elements.
The transparent cover provides an unobstructed view • M9220-Bxx-3 On/Off Electric Spring Return
of the electric actuator without having to disassemble Actuators Installation Instructions (Part No. 34-
the enclosure. An appliance cord enables installation of 636-1239)
control wiring, and a form-fitting seal prevents water or
• M9220-GGx-3 Proportional Electric Spring Return
moisture from entering the unit and damaging the
Actuators Installation Instructions (Part No. 34-
actuator.
636-1697)
IMPORTANT: The M9000-310 and M9000-320 • M9000-53x Cast Iron Flanged Valve Linkage Kit for
Weather Shield Enclosures only provide protection Mounting a Single M9000 Series Electric Actuator
for the Johnson Controls M9000 Series Electric Installation Instructions (Part No. 14-1298-18)
Actuator used in control damper and iron flanged
valve applications. To ensure proper operation, • M9000-53x Series Cast Iron Flanged Valve
check that all associated equipment used in the Linkage Kit for Tandem Mounting of M9000 Series
application is suitable for the surrounding Electric Actuators Installation Instructions
environment. (Part No. 14-1298-26)
M9000-310 and M9000-320 Series Weather Shield Enclosures
Installation Instructions
1
Parts Included
Mounting
Brackets
Anti-Rotation
Bracket
No. 12-24 x 1/2 in.
Hex-Head Screws
(Eight Locations)
Threaded
Hex Nuts
Enclosure Base and
Seal Assembly
Cover Screws
(Four Locations) Strain Relief
Conduit Fittings
M3 x 8 mm (Two Locations)
Phillips Screws and
M4 Washers (Two Locations)
FIG:prts_incl
Cover and
Gasket
Figure 1: Parts Included in M9000-310 and M9000-320 Weather Shield Enclosure Kits (See Table 1)
Table 1: Parts Included in M9000-310 and M9000-320 Weather Shield Enclosure Kits
Quantity Description
1 Enclosure Base and Seal Assembly
1 Cover and Gasket
4 Cover Screws
2 Mounting Brackets
8 No. 12-24 x 1/2 in. Hex-Head Screws with Nitrile Patch
1 Anti-Rotation Bracket
2 M3 x 8 mm Phillips Screws
2 M4 Washers
2 Strain Relief Conduit Fittings with 1/2 in. National Pipe Straight Mechanical (NPSM) Exit1
1 Cap Plug
2 Threaded Hex Nuts
1 Appliance Cord - 6 Conductor, 18 AWG Wire Gauge, 43 in. (109 cm)
1 Shaft Extender with Set Screw (M9000-320 Kit Only)
1. It is recommended that 1/2 in. liquid-tight conduit and 1/2 in. National Pipe Thread (NPT) liquid-tight fittings (purchased
locally) be used to terminate the control wiring to the weather shield enclosure strain relief conduit fittings.
M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions
2
Dimensions
FIG:dmns
Figure 2: Weather Shield Enclosure Dimensions, in. (mm)
(See Table 2.)
Table 2: Weather Shield Enclosure Dimensions, in. (mm)
Dimension Weather Shield Enclosure
M9000-310 M9000-320
A 7-7/8 (200) 13-3/8 (340)
B 4-23/32 (120) 5-29/32 (150)
C 3-17/32 (90) 4-23/32 (120)
D 4-27/32 (123) 6-1/32 (153)
E 5-13/32 (137) 6-9/16 (167)
M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions
3
Mounting 4. Orient the two mounting brackets onto the
enclosure base as illustrated in Figure 4.
The M9000-310 and M9000-320 Weather Shield
Enclosure Kits are shipped from the factory partially
assembled, with the cover held in place using the four
cover screws included with the kit. The remainder of
the parts required for mounting can be found inside the
enclosure.
Control Damper Applications
Mount the weather shield enclosure onto a control
damper as follows:
1. Loosen the four cover screws using a No.1 Phillips
screwdriver and remove the cover and gasket
assembly from the enclosure base.
2. Orient the anti-rotation bracket onto the enclosure
as illustrated in Figure 3.
Note: The anti-rotation bracket must be oriented
properly for the anti-rotation tab to align with the slot on FIG:mntbrkt
M9000-310 M9000-320
the electric actuator.
Figure 4: Proper Orientation of the
Mounting Brackets onto the Enclosure Base
5. Secure the mounting brackets to the enclosure
base using four No. 12-24 x 1/2 in. hex-head
screws (included with the kit).
Note: Each hex-head screw should be inserted from
the inside of the enclosure so that the nitrile patch
seals the mounting hole in the base.
6. Install the enclosure and mounting bracket
assembly onto the damper shaft extension. Orient
Anti-Rotation the assembly so that the flanges of the mounting
Bracket
Anti-Rotation brackets are flush with the mounting surface.
Bracket
7. Using the mounting brackets as a template, mark
the mounting hole locations with a ball-peen
hammer and punch.
M9000-310 M9000-320 FIG:rtbrkt
8. Remove the enclosure and mounting bracket
Figure 3: Proper Orientation of the Anti-Rotation assembly from the damper shaft extension.
Bracket 9. Drill pilot holes at each of the marked spots using a
drill and a No. 10 drill bit.
3. Secure the anti-rotation bracket to the threaded 10. Reinstall the enclosure and mounting bracket
brass inserts of the enclosure base using two assembly onto the damper shaft extension. Orient
M3 x 8 mm Phillips screws and M4 washers the assembly so that the flanges of the mounting
included with the kit. Tighten the Phillips screws to brackets are flush with the mounting surface and
a torque of 15 to 20 lb·in (1.7 to 2.3 N·m). the holes in the mounting brackets align with the
pilot holes drilled in Step 9.
IMPORTANT: Do not overtighten the Phillips
screws. Overtightening may cause the threaded 11. Secure the enclosure and mounting bracket
inserts located in the enclosure base to become assembly to the mounting surface using four
dislodged, resulting in damage to the enclosure. No. 12-24 x 1/2 in. hex-head screws included with
the kit. Tighten the hex-head screws to a torque of
20 to 25 lb·in (2.3 to 2.8 N·m).
M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions
4
12. Install the two conduit fittings included with the kit 3. Secure the anti-rotation bracket to the threaded
into the enclosure base and secure them in place brass inserts of the enclosure base using two
using the threaded hex nuts. M3 x 8 mm Phillips screws and M4 washers
included with the kit. Tighten the Phillips screws to
IMPORTANT: The conduit fittings must be installed a torque of 15 to 20 lb·in (1.7 to 2.3 N·m).
properly to ensure a tight seal. Water or moisture
may damage or affect the operation of the electric IMPORTANT: Do not overtighten the Phillips
actuator within the enclosure. screws. Overtightening may cause the threaded
inserts located in the enclosure base to become
13. Insert the appliance cord into one of the conduit dislodged, resulting in damage to the enclosure.
fittings so that the cable wrapping is visible inside
the enclosure. Tighten the conduit fitting to a 4. Orient the two mounting brackets onto the primary
torque of 10 to 15 lb·in (1.1 to 1.7 N·m) to secure side of the M9000-53x Series Valve Linkage (for
the appliance cord in place. single-mount applications) as illustrated in
Figure 5.
14. Install the electric actuator onto the damper shaft
extension and the enclosure anti-rotation bracket.
Note: Refer to the documentation included with the FIG:mntbrkt53x
electric actuator for complete installation instructions.
15. Reinstall the cover and gasket assembly and
secure it in place using the four cover screws
included with the kit. Tighten the cover screws to a
torque of 5 to 8 lb·in (0.6 to 0.9 N·m) maximum.
IMPORTANT: The cover and gasket assembly
must be installed properly to ensure a tight seal.
Water or moisture may damage or affect the
operation of the electric actuator within the
Primary Side of Secondary Side of
enclosure. M9000-53x Series M9000-53x Series
Valve Linkage Valve Linkage
16. If one of the conduit fittings remains unused, seal
the fitting using the cap plug included with the Figure 5: Proper Orientation of the
enclosure kit. Mounting Brackets onto the M9000-
53x Series Valve Linkage
Iron Flanged Valve Applications
Mount the weather shield enclosure onto the M9000- 5. Secure the mounting brackets to the M9000-
53x Series Valve Linkage as follows: 53x Series Valve Linkage using four No. 12-24 x 1/
1. Loosen the four cover screws using a No. 1 Phillips 2 in. hex-head screws (included with the kit).
screwdriver and remove the cover and gasket 6. Install the enclosure onto the input shaft of the
assembly from the enclosure base. M9000-53x Series Valve Linkage. Orient the
2. Orient the anti-rotation bracket onto the enclosure enclosure so that the flanges of the mounting
as illustrated in Figure 3. brackets are flush with the surface of the enclosure
base.
Note: The anti-rotation bracket must be oriented
properly in order for the anti-rotation tab to align with 7. Secure the enclosure to the mounting brackets
the slot on the electric actuator. using four No. 12-24 x 1/2 in. hex-head screws
included with the kit. Tighten the hex-head screws
to a torque of 20 to 25 lb·in (2.3 to 2.8 N·m).
Note: Each hex-head screw should be inserted from
the inside of the enclosure so that the nitrile patch
seals the mounting hole in the base.
M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions
5
8. Install the two conduit fittings included with the kit 11. Using a flat blade screwdriver, remove and save
into the enclosure base and secure them in place the spring clip from the M9220 actuator hub and
using the threaded hex nuts. gripper assembly. Remove the actuator gripper
assembly from the actuator and retain.
IMPORTANT: The conduit fittings must be installed
12. Insert the appliance cord(s) for the actuator
properly to ensure a tight seal. Water or moisture
through the conduit fittings.
may damage or affect the operation of the electric
actuator within the enclosure. 13. Install the actuator into the enclosure/linkage
assembly. Insert the actuator anti-rotation slots
Steps 9 and 11 apply only to the M9000-320 kit when over the anti-rotation tab of the bracket from
used with the M9220 Series actuators. For the M9000- Step 3.
310 kit, proceed to Step 12.
14. Center the shaft or shaft extension in the actuator
9. For the M9000-320 kit used with the M9220 Series hub. For the M9220, reinstall the actuator gripper
actuators, install the shaft extension onto the input assembly and secure in place using the spring clip.
shaft of the valve linkage. Ensure that the set Secure the actuator coupler assembly to the shaft
screws located on the shaft extension are oriented following the actuator mounting instructions.
perpendicular to the flat surfaces on the input shaft.
Note: Refer to the documentation included with the
(See Figure 6.) To reduce friction, ensure that the
electric actuator and valve linkage for complete
shaft extension and the seal assembly are not in
installation instructions.
contact. A gap of no more than 1/8 in. is
recommended between these two components. 15. Tighten the conduit fitting to a torque of 10 to
15 lb·in (1.1 to 1.7 N·m) to secure the appliance
cord in place.
16. Reinstall the cover and gasket assembly and
secure it in place using the four cover screws
included with the kit. Tighten the cover screws to a
torque of 5 lb·in (0.6 N·m) maximum.
17. If the valve application is a tandem configuration,
repeat Steps 11 through 16 on the secondary side
of the M9000-53x Series Valve Linkage.
IMPORTANT: The cover and gasket assembly
must be installed properly to ensure a tight seal.
Water or moisture may damage or affect the
operation of the electric actuator within the
enclosure.
18. If one of the conduit fittings remains unused, seal
the fitting using the cap plug included with the
enclosure kit.
FIG:mntg_pos
Repair Information
Figure 6: Proper Mounting Position for Shaft If the M9000-310 or M9000-320 Series Weather Shield
Extension Enclosure fails to operate within its specifications,
replace the unit. For a replacement weather shield,
10. Secure the shaft extension to the input shaft of the contact the nearest Johnson Controls representative.
valve linkage using the supplied set screws and 5/
16 in. (8 mm) wrench. The recommended torque
applied to the set screws is 100 in·lb (11 N·m).
Tighten the screws evenly.
M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions
6
Technical Specifications
M9000-310 and M9000-320 Weather Shield Enclosures
Materials Enclosure Impact-Grade ABS Plastic
Enclosure Seal Nitrile
Cover Transparent Impact-Grade ABS Plastic with Ultraviolet Inhibitors
Cover Gasket Neoprene
Weather Shield Rating NEMA 3R, IP32
Actuator Ambient M9106 and M9109 -4 to 122°F (-20 to 50°C)
Operating (M9000-310 Only)
Temperature Limits
M9108, M9116, -4 to 122°F (-20 to 50°C)
M9124, and M9132
M9220 -40 to 131°F (-40 to 55°C)
Weather Shield Enclosure Ambient Storage -40 to 176°F (-40 to 80°C)
Temperature Limits
Electrical Connections Strain Relief Conduit Fittings with 1/2 in. National Pipe Straight Mechanical
(NPSM) Exit
Shipping Weight M9000-310 2.0 lb (0.9 kg)
M9000-320 3.3 lb (1.5 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN MILWAUKEE WI 53202 NO. 22 BLOCK D NEW DISTRICT
GERMANY USA WUXI JIANGSU PROVINCE 214142
CHINA
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
M9000-310 and M9000-320 Series Weather Shield Enclosures Installation Instructions
Published in U.S.A. 7 www.johnsoncontrols.comПозиції каталогу з цим документом