FANs 268.1, 1628.3
                                                                                            Product Bulletin   M100E
                                                                                                Issue Date     0800

             M100E Economizer Series Actuator with
    R81EAA-2 Interface Board for Thermistor Sensor Applications

The M100E Economizer Series Actuators are used to
control outdoor air, return air, and exhaust air dampers
to maintain the M100E mixed air temperature setpoint.
The R81EAA-2 electronics in the actuator allow
economical use of outdoor air for natural or free
cooling and reduce energy consumption by minimizing
compressor run time.
The M100E economizer actuator has changeover and
refrigeration programming relays, minimum position,
mixed air setpoint, mixed air proportional band, and
actuator travel adjustments.
The internal changeover relay and refrigeration
programming relay can be wired in various ways that
provide control sequences utilizing available natural
cooling. For these cooling options, use the M100E with
A19, A319, or A419 Temperature Controls (sensible
changeover) or an enthalpy changeover control.
The R81EAA-2 is compatible with Johnson Controls
thermistor-type sensors. Use A91 Thermistor Sensors
for direct mixed air control or T91 Thermistor Room
Thermostats for ventilation only systems.                              Figure 1: M100E Series Actuator

                                             Features and Benefits
                  ❑ Output Versatility               Allows linkage connections on both ends of
                                                     output shaft for dampers and full power in
                                                     both directions

                  ❑ Load Versatility                 Available in torques of 25, 35, 50, 75, and
                                                     150 lb∙in (2.8, 4.0, 5.6, 8.5, and 17.0 N∙m)

                  ❑ Top Cover Mounted Circuit        Provides adjustment of proportional band and
                      Board                          minimum position potentiometers without
                                                     removing the cover

                  ❑ R81 Plug-in Electronics          Allows faster installation or conversions and
                      Interface Board                when necessary, shorter service times;
                                                     reduces inventory

                  ❑ Special Oil Mixture in           Provides the longest life cycle cost/benefits in
                      Gear Case                      the industry

© 2000 Johnson Controls, Inc.                                                                                        1
  Code No. LIT-2681114                                                                          www.johnsoncontrols.com
O peration
 IMPORTANT:        M100E actuators are intended to          When outdoor air can provide natural or free cooling,
                   control equipment under normal           the first stage of cooling enables control of outdoor air
                   operating conditions. Where failure      dampers. When outdoor air is not available for cooling
                   or malfunction of M100E actuators        (as determined by changeover status), the mechanical
                   could lead to an abnormal                cooling stages are enabled.
                   operating condition that could           When the outdoor air parameters are below the
                   cause personal injury or damage to       changeover setpoint, the changeover control contacts
                   the equipment or other property,         close, energizing the changeover relay. On a signal for
                   other devices (limit or safety           cooling from the room thermostat, the actuator is
                   controls) or systems (alarm or           modulated to maintain the mixed air setpoint.
                   supervisory) intended to warn of, or
                   protect against, failure or              Should the outdoor air parameters rise too high for
                   malfunction of M100E actuators           natural cooling, the contacts of the changeover control
                   must be incorporated into and            open. The changeover relay de-energizes, and the
                   maintained as part of the control        actuator returns to its minimum position, which
                   system.                                  positions the outdoor air dampers for minimum
                                                            ventilation.
Refer to Figure 2 and the following description to find     The refrigeration programming relay is used when
out how the M100E accomplishes greater energy               two stages of cooling are needed. When outside
savings than a non-economizer actuator.                     conditions are low enough for natural cooling, the
                                                            outside air changeover control energizes the
    Exhaust                                     Return      refrigeration programming relay, which switches the
      Air                                        Air
                                                            first stage of cooling to outside air. The second stage
                                                            of cooling becomes the first stage of mechanical
                     Mixed Air F C H                        cooling.
                               i o e     Fan
     Outdoor                   l ol at                      Refer to the M100E Economizer Series Actuator with
       Air           Mixed Air t i i                        R81EAA-2 Interface Board for Thermistor Sensor
    Changeover        Sensor e n n             Discharge
                                                            Applications Application Note (LIT-2681130 in
      Control                  r g g              Air
                                                            FAN 268.1 or 1628.3) for wiring configurations.

                                                 Room
     Cooling           M100E
                                               Thermostat
     Lockout         Economizer
     Control          Actuator

      Figure 2: Typical Installation Flow Diagram

2    M100E Economizer Series Actuator with R81EAA-2 Interface Board Product Bulletin
D imensions
Figure 3 shows the dimensions for an M100E actuator
with a switch kit. Figure 4 shows the dimensions for a
CVR83A-600R Weather Cover Kit. Figure 5 shows the                                5.05
dimensions for a standard M100E spring return                       0.5 Diameter 128
actuator.                                                           12.7 Hole

                         1.90            5.13
           7.10                                                         5.03               5.03
                          48             130    4.25                               0.25
           180                  0.80                                    127.7             127.7
                                 20             108                                6.35

                                0.92                                             5.05
                                 23                                              128
                                  5.80
                                  147

                                                                                 3.15
                                                                      LOAD END    80

  Figure 3: M100E Spring Return with Switch Kit,             Figure 4: CVR83A-600R Weather Cover Kit,
                    in. (mm)                                                 in. (mm)

                          M100E Economizer Series Actuator with R81EAA-2 Interface Board Product Bulletin   3
                                                 0.56            3.96
                                                  14             101

                                                                                     0.27 (4 Mounting Slots)
                                5.64                                                   7
                                143
                                       4.88
                                       124 2.44                                        0.37 (Square Both Ends)
                                            62                                          9
                  4.38
                  111                                                              0.97
                                              1.08               4.94               25
                  2.50                         28                125
                   64
                                                                           0.88 (4 Holes)
                    1.25                       0.50      1.47 1.31                                             5.13
                                                                            22
                     32                         13        37 33                                                130

                                                                                                 2.50
                             0.16                                                  1.69           64
                               4                                                    43
                                       6.23
                                       158
                               1.75                                                              3.31
                                45                                                                84

               LOAD END                                        Side View
                                                                 4.65                0.51                 Auxiliary End
                                                                 118                  13           0.38
                                                        0.29
                                                                                                    10
                                                         7        7.68
                                                                  195

                         Figure 5: M100E Spring Return Actuator Dimensions, in. (mm)

4   M100E Economizer Series Actuator with R81EAA-2 Interface Board Product Bulletin
R epair and Replacement                                   O rdering Information
The drive motor and gear train are immersed in oil and    Table 1: Actuators and Electronics Kits
sealed in a die cast case, so maintenance is not
necessary.                                                    Product Code
                                                                                              Description
                                                                 Number
Make no field repairs, except for replacement of the
R81E electronics kit. Refer to the Ordering Information        M110EGA-1       25 lb∙in (2.8 N∙m) Torque, Spring
section for the desired product code number, and                               Return Economizer Actuator
contact the nearest Johnson Controls representative.           M130EGA-1       50 lb∙in (5.6 N∙m) Torque, Spring
                                                                               Return Economizer Actuator
                                                                R81EAA-2       Thermistor Sensor Input Economizer
                                                                               Control Electronics Kit
                                                               M110XGA-1*      25 lb∙in (2.8 N∙m) Torque, Spring
                                                                               Return Actuator
                                                               M120XGA-1*      35 lb∙in (4.0 N∙m) Torque, Non-spring
                                                                               Return Actuator
                                                               M130XGA-1*      50 lb∙in (5.6 N∙m) Torque, Spring
                                                                               Return Actuator
                                                               M140XGA-1*      75 lb∙in (8.5 N∙m) Torque, Non-spring
                                                                               Return Actuator
                                                               M150XGA-1*      150 lb∙in (17 N∙m) Torque, Non-spring
                                                                               Return Actuator
                                                          *    Requires R81 Electronics Kit

                          M100E Economizer Series Actuator with R81EAA-2 Interface Board Product Bulletin              5
Table 2: Accessories
    Product
     Code                                                     Description
    Number
Y68AA-1         Transformer, 120/24 VAC, 40 VA, 60 Hz, Class 2
Y68DA-1         Transformer, 240/24 VAC, 40 VA, 60 Hz, Class 2
Y68HA-1         Transformer, 24/24 VAC, 40 VA, 60 Hz, Class 2
S91DJ-1         Auxiliary switch kit with one Single-Pole, Double-Throw (SPDT) switch
S91EJ-1         Auxiliary switch kit with two SPDT switches
S91PT-1         Auxiliary potentiometer kit, 1000 ohm, 1/3 watt
CVR83A-600R     Weather cover kit
Y20DAA-2        Mounts the actuator to the top of a duct or any flat surface. Contains the LVR27A-602, LVR27A-600,
                ROD16-3, and SWL10A-603Y (2).
Y20DAB-2        Mounts the actuator to the side of a duct or wall. Contains all items in the Y20DAA-2 plus
                one BKT22A-602.
Y20EBA-1        Valve linkage kit for mounting Honeywell® valves with 1/4-28 stem connection to M120 or
                M130 actuators
Y20EBA-2        Valve linkage kit for mounting Honeywell valves with 1/4-28 stem connection to M150 actuators
Y20EBA-3        Valve linkage kit for mounting Barber-Colman® valves with 1/4-28 stem connection to M120 or
                M130 actuators
Y20EBA-4        Valve linkage kit for mounting Barber-Colman valves with 1/4-28 stem connection to M150 actuators
Y20EBD-1        Linkage kit for M120 or M130 actuators and 1-1/4 in. (DN 32) valves, produces 75 lb (334 N) seating
                force
Y20EBD-2        Linkage kit for M140 actuators and 1-1/4 in. (DN 32) valves, produces 150 lb (607 N) seating force
Y20EBD-3        Linkage kit for M150 actuators and 1-1/4 in. (DN 32) valves, produces 270 lb (1202 N) seating force
Y20EBD-5        Linkage kit for M110 actuators and 1-1/4 in. (DN 32) valves, produces 40 lb (178 N) seating force
Y20EBD-6        Linkage kit for M120 or M130 actuators and 1-1/4 in. (DN 32) valves, produces 100 lb (449 N)
                seating force
Y20EBE-1        Coupling adaptor to convert valves with a 5/16 in. stem and a hold down nut for Johnson Controls
                1/2 to 3 in. valves manufactured prior to March 1969
Y20EBE-2        Stem adaptor and centerpiece collar to adapt VT Series valves with slotted stems. (Y20EBD-5 also
                required.)
Y20EBE-3        Hold down nut for cast iron and VB Series 2-1/2 to 4 in. valves and yoke nut for Barber-Colman
                1/2 to 2 in. valves
Y20EBE-4*       Stem connector for Barber-Colman 2-1/2 to 4 in. valves, 5 per package. (Use with Y20EBD-3 or -6.)
Y20EBE-11       Valve Linkage Adaptor Kit for VG7000 valves. (Y20EBD Series kit also required.)
VG7000-M110     Mounting Kit for M110 actuator and 1/2 through 2 in. (DN15 through DN50) valves
VG7000-M130     Mounting Kit for M130 actuator and 1/2 through 2 in. (DN15 through DN50) valves
VG7000-M140     Mounting Kit for M140 actuator and 1/2 through 2 in. (DN15 through DN50) valves
VG7000-M150     Mounting Kit for M150 actuator and 1/2 through 2 in. (DN15 through DN50) valves
Y20DFC-1        Damper linkage kit for mounting the actuator to CD-1300 dampers only (includes a universal mounting
                bracket for inside or outside damper frame mounting)

6   M100E Economizer Series Actuator with R81EAA-2 Interface Board Product Bulletin
                        Notes

M100E Economizer Series Actuator with R81EAA-2 Interface Board Product Bulletin   7
S pecifications
                         Product      M100E Economizer Series Actuator with R81EAA-2 Interface Board
         Power Requirements           24 VAC, Class 2, (20 to 30 VAC) at 50/60 Hz, 25 VA spring return, 20 VA non-spring return
                    Input Signal      Proportional control, thermistor sensor input using A91 or T91 sensors
    Input Signal Adjustments          Mixed air setpoint 40 to 90°F (5 to 32°C)
                                      Adjustable proportional band 2 to 20F° (1.1 to 11C°)
                                      Adjustable minimum position 0 to 70% of full travel
      Mechanical Connection           3/8 in. (9.5 mm) square shaft (both ends)
                                      Maximum dead weight on output shaft:              200 lb (91 kg) on load end;
                                                                                        10 lb (4.5 kg) on auxiliary end
           Mechanical Output                    Running Torque                          Breakaway and Stall (minimum)
                                      M110      25 lb∙in (2.8 N∙m) spring return        100 lb∙in (11 N∙m)
                                      M120      35 lb∙in (4.0 N∙m)                      70 lb∙in (7.9 N∙m)
                                      M130      50 lb∙in (5.6 N∙m) spring return        200 lb∙in (23 N∙m)
                                      M140      75 lb∙in (8.5 N∙m)                      150 lb∙in (17 N∙m)
                                      M150      150 lb∙in (17 N∙m)                      300 lb∙in (34 N∙m)
               Rotation Range         Fixed zero, adjustable full travel 65 to 270°, factory set at 90°
               Rotation Timing        60 seconds for 160° travel nominal, 60 Hz
               (at Rated Load)        38 seconds for 90° travel nominal, 60 Hz
                                      75 seconds for 90° spring return
                      Cycle Life      M110EGA-1, M130EGA-1: 150,000 cycles at rated load. Duty cycle, 25%
        Electrical Connection         1/4 in. spade terminals
                           Action     CW rotation on temperature increase (fixed)
              Factory Settings        Setpoint 65°F (18°C); Proportional band 2F° (1.1C°); Minimum position 0%
          Programming Relay           Contacts: SPDT, Class 2 circuit          Coil: 24 VAC, 1 VA, Class 2 circuit
            Changeover Relay          24 VAC, 1 VA, Class 2 circuit (contacts connected internally)
           Ambient Operating          Non-spring Return:       -40 to 125°F (-40 to 52°C), 90% RH
                 Conditions           Spring Return:           -35 to 125°F (-37 to 52°C), 90% RH
              Ambient Storage         -40 to 140°F (-40 to 60°C), 90% RH
                   Conditions
                      Enclosure       NEMA 2, IP32
     Dimensions (H x W x D)           Spring Return:           6.23 x 5.64 x 7.68 in. (158 x 143 x 195 mm)
                                      Non-spring Return:       6.23 x 5.64 x 4.94 in. (158 x 143 x 125 mm)
              Shipping Weight         Spring Return:           9 lb (4.1 kg)
                                      Non-spring Return:       6.5 lb (2.9 kg)
          Agency Compliance           UL:      M110EGA-1, M130EGA-1:             UL 916 Listed, File 107041, CCN PAZX
                                                                                 UL 873 Recognized, File E27734, CCN XAPX2
                                               M100X and R81:                    No UL Listing
                                      CSA:     M110EGA-1, M130EGA-1:             C22.2 No. 24 Certified, File LR948, Class 4813 02
                                               M100X and R81:                    No CSA Certification
    EU Directive Compliance           89/336/EEC (CE Mark)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication
or misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                                  Printed in U.S.A.
Milwaukee, WI 53201                                                                                                   www.johnsoncontrols.com

8   M100E Economizer Series Actuator with R81EAA-2 Interface Board Product Bulletin

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.