Code No. LIT-1900459
                                                                                                                                                  Issued May 16, 2012

LN-VAVLF-2, LN-VAVLN-2, and LN-VVTLF-2
LN Series VAV and VVT Controllers
Description                                                          Configured device complies with
                                                                     LONMARK® Space Comfort Control (SCC)
The LN Series LN-VAVLF-2, LN-VAVLN-2,
                                                                     profile for interoperability with other
and LN-VVTLF-2 controllers use the latest
                                                                     LONMARK devices.
technology to provide you with more flexibility
and reliability of control. The LN VAV/VVT                      •    robust hardware - allows you to use any
controllers are designed to meet the                                 commerically available thermistor type
requirements of single duct Variable Air                             (100 ohms to 100k ohms) and setpoint
Volume (VAV) or Variable Air Volume and                              potentiometer type. Features an extremely
Temperature (VVT) applications.                                      accurate onboard airflow sensor for
                                                                     pressure independent single duct VAV
The LN-VAVLF-2, LN-VAVLN-2, and                                      applications. The controller can read
LN-VVTLF-2 controllers are based on                                  differential pressure as small as 0.04
LONWORKS® technology for interoperability                            milli-inches.
and peer-to-peer communication between                          •    wireless functionality - features an optional                              LN-VAVLF-2 Controller
controllers without any intermediary, but also                       EnOcean® wireless receiver
integrate seamlessly into the Metasys®                               (LN-WMOD315-0 or LN-WMOD868-0) that
system.                                                              you can use with a variety of wireless                      Repair Information
For additional information, see the LN Series                        sensors and switches. The wireless                          If the LN-VAVLF-2, LN-VAVLN-2 or
Variable Air Volume (VAV) and Variable Air                           receiver (LN-WMODxxx-0) supports up to                      LN-VVTLF-2 controller fails to operate within
Volume and Temperature (VVT) Controllers                             14 wireless inputs, which allow you to                      its specifications, replace the unit. For a
Product Bulletin (LIT-12011298).                                     create wire-free installations.                             replacement, contact the nearest
                                                                •    powerful control options - perform Demand                   Johnson Controls® representative.
Features                                                             Control Ventilation based on CO2 sensor
•    configurable software - features an LNS                         readings to ensure high indoor air quality in
     plug-in which provides the ability to easily                    an efficient manner. Provides you with the
     configure inputs, outputs, and sequence                         ability to link VAV occupancy status with
     options.                                                        local lighting control.

Selection Chart
 Code Number                  Description
 LN-VAVLF-2                   Configurable VAV controller, acutator with feedback, flow sensor, 10 I/O (4 UIs, 4 triac DOs, 2 UO) and LNS® plug-in.
 LN-VAVLN-2                   Configurable VAV controller, flow sensor, 10 I/O (4 UIs, 4 triac DOs, 2 UO) and LNS Plug-in. No actuator.
 LN-VVTLF-2                   Configurable VAV controller, actuator with feedback, 10 I/O (4 UIs, 4 triac DOs, 2 UO) and LNS Plug-in. No flow sensor.

Selection Chart
    Controller Features                                   LN-VAVLF-2                                      LN-VVTLF-2                             LN-VAVLN-2
    Points                                                10-Point VAV                                    10-Point VAV                           10-Point VAV
    Universal Inputs                                      4                                               4                                      4
    Ability to use Spare Inputs
    Built-in Flow Sensor
    (0 to 1 in. W.C)

    Wireless Inputs1                                      6                                               6                                      6

    Digital (triac) Outputs                               4                                               4                                      4
    Universal Outputs                                     2                                               2                                      2
    Network Outputs (using NVOs)                          6                                               6                                      6
    Ability to Use Spare Outputs
    Built-in Actuator
1. Available when optional wireless receiver module (LN-WMODxxx-0) is connected to the controller.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       1 of 3
LN Series VAV and VVT Controllers (Continued)
Technical Specifications
LN-VAVLF, LN-VAVLN, and LN-VVTLF (Part 1 of 2)
 Product Codes                                         LN-VAVLF-2, LN-VAVLN-2, and LN-VVTLF-2
 Power Requirement                                     Voltage: 24 VAC/DC; +/- 15%, 50/60 Hz, Class 2
                                                       Protection: 3 A user-replaceable fuse for triac when using the internal power supply
                                                       Consumption: 18 VA
                                                       Maximum Consumption: 70 VA if internal power supply is used
 Ambient Storage Conditions                            Ambient Operating Temperature: 0 to 50°C, (32 to 122°F)
                                                       Ambient Storage Temperature: -20 to 50°C, (-4 to 122°F)
                                                       Ambient Relative Humidity: 0 to 90% noncondensing
 General                                               LONMARK Functional Profile: Space Comfort Controller (SCC) VAV #8502
                                                       Processor: Neuron® 3150™, 8 bits, 10 MHz
                                                       Memory: Nonvolatile Flash 64k (APB application)
                                                       Media Channel: TP/FT-10; 78 Kbps
                                                       Communication: LonTalk® protocol
                                                       LONMARK Interoperability Guidelines: Version 3.4
 Enclosure                                             Material: FR/ABS Resin
                                                       Dimensions (with screws):
                                                       LN-VAVLN-2: 4.8 x 5.9 x 2.5 in. (122.7 x 149.1 x 63 mm)
                                                       LN-VAV-LF-2/LN-VVT-LF-2: 4.8 x 8.4 x 2.5 in. (122.7 x 214.3 x 63 mm)
                                                       Shipping Weight:
                                                       LN-VAVLN-2: 0.92 lb (0.42 kg)
                                                       LN-VAV-LF-2/LN-VVT-LF-2: 2.30 lb (1.05 kg)
 Inputs                                                Universal software configurable
                                                       Input Types:
                                                       Digital: Dry Contact
                                                       Analog Voltage: 0 to 10 VDC
                                                       Analog current: 4 to 20 mA with 249 Ohms external resistor (wired in parallel)
                                                       Pulse: Dry contact; 500 milliseconds minimum ON/OFF
                                                       Resistor Support:
                                                       Thermistor: 10k Ohms Type 2, Type 3 (10k Ohms at 25°C [77°F])
                                                         Range: -40° to 153°C (-40° to 302°F)
                                                       Platinum: PT1000 (1k ohms at 0°C [32°F])
                                                         Range: -40 to 150°C (-40 to 302°F)
                                                         PT100 (100 ohms at 0°C [32°F])
                                                         Range: -40 to 135°C (-40 to 275°F)
                                                       Potentiometer: Translation table configurable on several points
                                                       Input Resolution: 16-bit analog/digital converter
                                                       Differential: Range 0 to 250 Pa (0 to 1 in. H20)
                                                       Resolution 0.000162 milli-inches H20, Accuracy ±0.3% full scale
 Outputs                                               Digital: 24 VAC Triac, digital (on/off), Pulse Width Modulation (PWM), or floating
                                                       0.5 A continuous
                                                       PWM control: adjustable period from 2 seconds to 15 minutes
                                                       Floating control: requires two consecutive outputs
                                                         Minimum pulse on/off: 500 milliseconds
                                                         Adjustable drive time period
                                                       External or internal power supply (jumper selectable)
                                                       Digital LED Occupancy: 0 to 10 VDC dedicated output for occupancy sensor LED,
                                                         Maximum 20 mA
                                                       Universal: 0 to 10 VDC, digital 0 to 12 VDC (on/off), floating for PWM
                                                       PWM control: adjustable period from 2 seconds to 15 minutes
                                                       Floating control: requires two consecutive outputs
                                                         Minimum pulse on/off: 500 milliseconds
                                                         Adjustable drive time period
                                                       20 mA maximum at 12 VDC
                                                       Minimum load resistance 600 ohms
                                                       Output Resolution: 10-bit digital/analog converter
 Damper Actuator                         Torque: 35 in·lb, 4 N·m
 (LN-VAVLF-2 and LN-VVTLF-2 Models Only) Angle of Rotation: 95º adjustable
                                         Fits Shaft Diameter: 5/16 to 3/4 in. (8.5 to 18.2 mm)
                                         Power Supply: from controller
 Agency                                                UL Listed: UL916 Energy management equipment
                                                       Material: UL94-5VA1

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       2 of 3
LN Series VAV and VVT Controllers (Continued)

LN-VAVLF, LN-VAVLN, and LN-VVTLF (Part 2 of 2)
 Electromagnetic Compatibility                         CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and light-industrial environments.
                                                       CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and light-industrial environments.
 Wireless2                                             Communication: EnOcean® Wireless standard
                                                       Number of Wireless Inputs3: 14 (some sensors may require more than one wireless input)
                                                       Supported Wireless Receivers: Wireless Receiver 315 (LN-WMOD315-0) and Wireless Receiver 868
                                                       (LN-WMOD868-0)
                                                       Cable: Connector: 4P4C modular jack, Length: 3 ft (0.91 m)
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
   directive.
2. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more than one wireless input from the
   controller.
3. Some wireless sensors may use more than one wireless input from the controller.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc.                  www.johnsoncontrols.com