Installation Instructions
                                                                                                   Issue Date September 1, 2009
                                                                                                 Supersedes December 1, 2004

                                           LN Series Sensors

                                                               Installation
Application Requirements
                                                               Note:     Wall surface must be flat and clean.
The LN Series Sensor analog wall sensor family is
specifically designed to interface with fan coil, heat         1. Remove security screw on the bottom of
pump, rooftop and other terminal unit building                    thermostat cover.
automation controls. The units provide precise indoor
                                                               2. Pull the bottom side of thermostat to open
local temperature sensing. Local setpoint adjustment
                                                                  (Figure 1).
with various scales is available.
                                                               3. Pull cables 6 inches out of the wall.
The modern, attractive, low profile enclosure is
suitable for classrooms, hotels, executive areas, office       4. Insert cable in the central hole of the base.
spaces, and other commercial areas.
                                                               5. Align the base and mark the location of the two
                                                                  mounting holes on the wall. Install proper side of
Mounting                                                          base up.
Location Consideration                                         6. Install anchors in the wall.
Install the sensor away from any heat source.                  7. Insert screws in mounting holes on each side of
Do not install the sensor:                                        the base. Do not overtighten.

•   on an outside wall                                         8. Strip each wire 1/4 inch.

•   near an air discharge grill                                9. Insert each wire according to wiring diagram.
                                                               10. Gently push excess wiring back into the hole in wall.
•   in a location affected by direct sun radiation
                                                               11. Press printed circuit board into place.
•   in a location that restrains vertical air circulation to
    the thermostat                                             12. Install the cover, top side.
                                                               13. Install security screw.

                                                                                                                         Wall Anchor

                                                                                                                  Pull on plastic tab
                                                                                                                  to release the
                                                                                                                  printed circuit board

                                                                     Flip printed circuit
                                                                     board to access                 Security Screw
                                                                     mounting hole

              Figure 1: LN Series Sensor
                                                                                 Figure 2: Sensor Installation

© 2009 Johnson Controls, Inc.                                                                                                             1
  Code No. LIT-1201871                                                                                      www.johnsoncontrols.com
Wiring                                                        CN1
Figure 3 shows the terminals. Generic Sensor wiring is
in Figure 4; please check Table 1 and Table 2 to verify             1   Normally open                        10K type 2 NTC thermistor
                                                                        Momentarily closed                       5% precision
models.                                                                 Override button
                                                                    2
                                                                    3                          10K DA setpoint potentiometer
                                                                                                     20% tolerance
                                                                                                Resistance increases on CW
                                                                    4                                     rotation

                                                                    5                        24 Vac / Vdc externally powered LED
                                                                                              for occupied / unoccupied system
                                                                    6                                       status

                                                                        7
                                                                        8

                                                                                 1/8 inch LONWORKS Network Port Connnection

                                                              CN2
                                                                    1                            LONWORKS Network Terminals 1-2 TP-FT10
                                                                                                 or Smart Sensor +/- remote connection via
                                                                                                         LONWORKS Network Port
                                                                    2
                                                                          3
                 Figure 3: Terminals                                      4
                                                                        Figure 4: Sensor Wiring

Table 1: Sensor Functions
 Part Number        Sensor       Temperature        ± Scale    C. Scale        F. Scale                   Terminals
                                 Override
 LN-SENSOR-0             X                                                                                1, 2, 7, 8
 LN-SENSLO-0             X               X                                                                1, 2, 5, 6, 7, 8
 LN-SENOCW-0             X               X                X                                               1, 2, 3, 4, 5, 6, 7, 8
 LN-SENOSC-0             X               X                          X                                     1, 2, 3, 4, 5, 6, 7, 8
 LN-SENOSF-0             X               X                                              X                 1, 2, 3, 4, 5, 6, 7, 8

2   LN Series Sensors Installation Instructions
Table 2: Sensor Models
 Part Number      Description
 LN-SENSOR-0      Room sensor – no setpoint
 LN-SENSLO-0      Room sensor with LED, override push button
 LN-SENOCW-0      Room sensor with LED, override push button, and setpoint adjustment (cool/warm)
 LN-SENOSC-0      Room sensor with LED, override push button, and setpoint adjustment (°C)
 LN-SENOSF-0      Room sensor with LED, override push button, and setpoint adjustment (°F)
 LN-SENAV1-0      Room sensor containing four thermistors. Jumper configurable for averaging up to maximum of for
                  sensors connected in parallel. No setpoint.
 LN-SENAV2-0      Room sensor containing four thermistors. Jumper configurable for averaging up to a maximum of four
                  sensors connected in parallel. With LED and Override push button. No setpoint.

Averaging Sensors Wiring Examples

Single Remote Room Sensor
                                      1 x LN-SENAV2-0                               LN-SENAV1-0
                                       Wiring 1 Sensor                             Wiring 1 Sensor
                                   S2 -1 = ON / S2 -2 = ON                     S2 -1 = ON / S2 -2 = ON
                                      Scom
                                                                  Scom                                 Scom
                                                                                     OR
                                      RS                            RS                                  RS
                                                                   Aux
                                      AU
                                                                    C
                                       C                            DI

                                 D2 D1

                                                                                 Dip switch     ON    S2-1 = ON
                                                                                 setting for:         S2-2 = ON
                                                                                  1 sensor      1 2

                          Figure 5: Single Remote Room Sensor Wiring Example

Two Room Sensors for Averaging Applications
                                    2 x LN-SENAV2-0
                                    Wiring 2 sensors
                                                                                               2 x LN-SENAV1-0
                                S2 -1 = OFF / S2 -2 = ON
                                                                                               Wiring 2 sensors
                         Scom
                                              Scom     Scom                                S2 -1 = OFF / S2 -2 = ON
                         RS                    RS          RS
                                                                              Scom
                                              Aux          Aux                                          Scom          Scom
                         AU
                                               C           C
                          C
                                                                              RS                         RS           RS
                                               DI          DI

                      D2 D1                                                   AU
                                    1 x LN-SENAV1-0 and
                                       1 x LN-SENAV2-0                         C
                                       Wiring 2 sensors
                                   S2 -1 = OFF / S2 -2 = ON               D2 D1                 Dip switch ON S2-1 = OFF
                                                                                                setting for:  S2-2 = ON
                         Scom
                                              Scom     Scom                                     2 sensors 1 2
                         RS                    RS          RS
                                              Aux
                         AU
                                               C
                          C                    DI                Notes for averaging applications:
                      D2 D1
                                                                 LN-SENAV-1 and LN-SENAV2-0 can be mixed matched.
                                                                 Wire LN-SENAV-1 and LN-SENAV2-0 in parallel.
                                                                 Request the dip switch setting in each remote sensor.

               Figure 6: Two Remote Sensors for Averaging Applications Wiring Example

                                                                                           LN Series Sensors Installation Instructions   3
Three Room Sensors for Averaging Applications
                               2 x LN-SENAV1-0 and 1 x LN-SENAV2-0                    1 x LN-SENAV1-0 and 2 x LN-SENAV2-0
                                           Wiring 3 sensors                                       Wiring 3 sensors
                                      S2 -1 = OFF / S2 -2 = OFF                              S2 -1 = OFF / S2 -2 = OFF
                        Scom
                                                Scom      Scom       S com
                                                                               Scom
                        RS                       RS        RS         RS                               Scom
                                                                                                       Scom               Scom         Scom
                                                Aux
                        AU
                                                 C
                                                                               RS                        RS                RS          RS
                         C                       DI                                                      Aux              Aux
                                                                               AU
                  D2    D1                                                                               C                 C
                                                                                C                        DI                DI

                                                                             D2 D1

                                                                                                  Dip switch     ON       S2-1 = OFF
                                                                                                  setting for:            S2-2 = OFF
                                                                                                  3 sensors      1    2

                       Figure 7: Three Room Sensors for Averaging Application Wiring Example

Temperature versus Resistance Chart for 10 K ohm NTC Thermistor
    ºC   ºF K ohm                ºC     ºF K ohm             ºC      ºF K ohm                ºC     ºF K ohm                           ºC     ºF K ohm
-20      -4 87.1310              -10    14 51.3490              0    32 31.1410              10     50 19.4020                         20     68 12.3980

-19      -2   82.5330             -9    16   48.7820            1    34    29.6670           11     52       18.5320                   21     70   11.8710
-18       0   78.2010             -8    18   46.3570            2    36    28.2700           12     54       17.7050                   22     72   11.3690
-17       1   74.1190             -7    19   44.0650            3    37    26.9460           13     55       16.9190                   23     73   10.8900
-16       3   70.2710             -6    21   41.8990            4    39    25.6910           14     57       16.1720                   24     75   10.4340
-15       5   66.6420             -5    23   39.8490            5    41    24.5000           15     59       15.4620                   25     77   10.0000
-14      7    63.2200             -4    25 37.9110              6    43 23.3710              16     61 14.7870                         26     79 9.5858
-13      9 59.9910                -3    27 36.0770              7    45 22.3000              17     63 14.1450                         27     81 9.1909
-12      10 56.9430               -2    28 34.3410              8    46 21.2840              18     64 13.5330                         28     82 8.8143
-11      12 54.0660               -1    30 32.6970              9    48 20.3190              19     66 12.9520                         29     84 8.4549

                                                                                                                       Building Efficiency
                                                                                              507 E. Michigan Street, Milwaukee, WI 53202

                                                Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.