LN Series Input/Output (I/O) Extension Modules
Subnetwork for LN-PRG6x0-2 Code No. LIT-12011706
Application Note Issued August 6, 2012
LN-IOE400-0, LN-IOE410-0, LN-IOE420-0, LN-PRG6x0-2 Supersedes May 13, 2011
Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Subnetwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Topology and EOL Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Subnetwork Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical Specifications and Cable Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LN Series Input/Output (I/O) Extension Modules Subnetwork for LN-PRG6x0-2 1
Application Note
2 LN Series Input/Output (I/O) Extension Modules Subnetwork for LN-PRG6x0-2 Application Note
LN Series Input/Output (I/O) Extension Modules
Subnetwork for LN-PRG6x0-2
Application Note
Document Introduction
This document describes the subnetwork for the LN Series Input/Output Extension
Modules used with the LN Free Programmable PRG 600 Series Controllers. The
LN Free Programmable PRG 600 Series Controllers use the subnetwork to support
one or more extension modules with structural cabling. This document does not
describe how to set up a LONWORKS® network. For information on setting up your
LONWORKS® network, refer to the LONWORKS LN-Series Network Communication
and Interface Guide Technical Bulletin (LIT-12011253).
Related Documentation
Table 1: Related Documentation
For Information On See Document LIT or Part
Number
Setting Up a LONWORKS Network LONWorks LN-Series Network LIT-12011253
Communication and Interface Guide
Technical Bulletin
Installing LN Free Programmable LN Free Programmable PRG 600 LIT-12011691
PRG 600 Series Controllers Series Controllers Installation
Instructions
Installing LN Series Input/Output LN Series Input/Output (I/O) LIT-12011693
(I/O) Extension Modules Extension Modules Installation
Instructions
LN Free Programmable PRG 600 LN Free Programmable PRG 600 LIT-12011656
Series Controllers and LN I/O and LN Input/Output Extension
Extension Modules Features and Modules Product Bulletin
Benefits
LN Series Input/Output (I/O) Extension Modules Subnetwork for LN-PRG6x0-2 Application Note 3
Subnetwork
Figure 1 shows the LN Series Input/Output Extension modules on the
subnetwork with the proper End-of-Line (EOL) terminations.
Figure 1: EOL Terminations Settings on Subnetwork
Topology and EOL Terminations
Set the EOL terminations on the LN Free Programmable PRG 600 Series
Controller and the last LN I/O Extension Module to ON. All other extension
modules must have their EOL termination set to OFF (Figure 1).
Note: In Figure 1, the EOL jumpers are located on the inside of the controller and
modules.
Subnetwork Length
The total maximum length of the subnetwork is 300 meters (1,000 feet). The
polarity of the LN Series I/O Extension Modules must be configured as shown in
Figure 2. All terminals identified as SUBNET+ must be connected to the same
conductor. Similarly, all terminals identified as SUBNET- must be connected to the
same conductor.
Figure 2: LN-PRG6x0 Controllers Subnetwork Shielding
4 LN Series Input/Output (I/O) Extension Modules Subnetwork for LN-PRG6x0-2 Application Note
Use properly grounded, shielded cable for the best protection against interference
on the LN Series I/O Extension Module subnetwork. Use the daisy-chain
configuration with the cable shield twisted together and isolated with electrical
tape at each extension module.
When you use an LN Free Programmable PRG 600 Series Controller, connect the
shielding of the extension modules on the subnetwork to the electrical system
ground at one point only (Figure 2).
Physical Specifications and Cable Requirements
Use cables composed of stranded conductors, instead of solid conductors, for the
best breakage resistance during pulling operations. Table 2 describes the physical
specifications and cable requirements for an LN Series I/O Extension Module
subnetwork.
Table 2: Physical Specifications and Cable Requirements
Specification Description
Maximum Number of LN Series I/O 2 LN Series I/O Extension Modules
Extension Modules
Media Shielded, Twisted Pair
Characteristic Impedance 100–130 ohm
Distributed Capacitance Less than 100 pF per meter (30 pF per foot)
Maximum Length of the LN Series I/O 300 meters (1,000 ft.) Maximum
Extension Modules Subnetwork
Polarity Polarity Sensitive
Multi-Drop Daisy-chain (No Routers)
End-of-Line (EOL) Terminations Built-in and set (enabled) on the last extension
module only.
Shield Grounding See Figure 2.
LN Series Input/Output (I/O) Extension Modules Subnetwork for LN-PRG6x0-2 Application Note 5
Addressing
Each LN Series I/O Extension Module on the subnetwork must have a unique
address. The current valid addresses are 1 or 2. Figure 3 shows an example of how
to set a DIP switch. Table 3 shows the DIP switch settings.
Figure 3: DIP Switch Set to 2
Table 3: DIP Switch Settings
Switch Position Value
1 2 3
OFF OFF OFF Invalid
ON OFF OFF 1
OFF ON OFF 2
ON ON OFF Invalid
OFF OFF ON Invalid
ON OFF ON Invalid
OFF ON ON Invalid
ON ON ON Invalid
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2012 Johnson Controls, Inc.
LN Series Input/Output (I/O) Extension Modules Subnetwork for LN-PRG6x0-2 Application Note 6
Published in U.S.A. www.johnsoncontrols.comПозиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.