LN Series Input/Output (I/O) Extension Modules
Installation Instructions
LN-IOE400-0, LN-IOE410-0, LN-IOE420-0 Code No. LIT-12011693
Issued April 24, 2014
Supersedes January 30, 2013
Application Note: The I/O Extension Module’s plastic enclosure
has a back plate that is separate from the front plate
The LN Series Input/Output (I/O) Extension Module
allowing the back plates to be shipped directly to the
product line is compatible with the LN-PRG600-2 and
installation site while all the engineering is done
LN-PRG600-12 Series controllers. These devices are
elsewhere.
microprocessor-based and designed to control various
HVAC equipment, such as roof top units, large air IMPORTANT: Prevent any static electric discharge
handling units, central plant applications, including to the controller. Static discharge can damage the
chillers and boilers. controller and void the warranties.
The LN PRG600 Series Controllers are built on a
platform compatible with the LN Series I/O Extension North American Emissions Compliance
Modules, but have different numbers of inputs and Canada
outputs. Each LN Series I/O Extension Module also
has different numbers of digital outputs or universal Industry Canada Statement
outputs. The LN Series I/O Extension Modules provide
additional hardware point capacity for the LN PRG600 The term IC before the certification/registration
Series controllers. number only signifies that the Industry Canada
technical specifications were met.
Follow these recommendations for proper installation
and operation of each I/O Extension Module: Le terme C » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est
• Inspect the I/O Extension Module for shipping conforme aux spécifications techniques d'Industry
damages. Do not install damaged I/O Extension Canada.
Module.
• Keep the I/O Extension Module at room United States
temperature for at least 24 hours prior to
This equipment has been tested and found to
installation to allow any condensation that may
comply with the limits for a Class A digital device
have accumulated during shipping to evaporate.
pursuant to Part 15 of the FCC Rules. These limits
• If the I/O Extension Module is used in a manner not are designed to provide reasonable protection
specified by Johnson Controls, the functionality against harmful interference when this equipment is
and the protection provided by the I/O Extension operated in a commercial environment. This
Module may become impaired. equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
• Avoid areas where corroding, deteriorating, or
accordance with the instruction manual, may cause
explosive vapors, fumes, or glass may be present.
harmful interference to radio communications.
• Do not drop the I/O Extension Module or subject it Operation of this equipment in a residential area
to physical shock. may cause harmful interference, in which case the
users will be required to correct the interference at
their own expense.
LN Series Input/Output (I/O) Extension Modules Installation Instructions 1
Figure 1: LN Series I/O Extension Module Dimensions, mm (in.)
Installation • Ensure proper ventilation of each I/O Extension
Module and avoid areas where corroding,
Observe these guidelines when installing an I/O
deteriorating, or explosive vapors, fumes, or gases
Extension Module:
may be present.
• Transport the I/O Extension Module in the original
container to minimize vibration and shock damage. Mounting
You can mount the I/O Extension Module on a DIN
• Verify that all parts shipped with the I/O Extension
Rail, on a wall, or in a panel. The I/O Extension Module
Module.
is equipped with two mounting holes 0.25 x 0.165 in.
• Do not drop the I/O Extension Module or subject it (6.35 x 4.191 mm).
to physical shock.
DIN Rail
Location Considerations To mount the module on a DIN rail:
• Allow for proper clearance around the I/O
1. Ensure the DIN rail is properly mounted on the
Extension Module’s enclosure, wiring terminals,
wall.
and address switch to provide easy access for
hardware configuration and maintenance. 2. Clip the module onto the DIN rail.
• Orient I/O Extension Module with the ventilation Wall Mount
slots and power supply/output terminal block To mount the module on a wall:
connector towards the top to permit proper heat
dissipation. 1. Press on the side clips to separate the module’s
front and back plates.
• Do not mount the I/O Extension Module on
surfaces prone to vibration, such as duct work, or 2. Use the holes on the back plate to mark the wall
in areas where electromagnetic emissions from location.
other devices or wiring can interfere with controller 3. Drill the holes.
communication.
4. Clean the surface and mount the module using the
appropriate screws.
2 LN Series Input/Output (I/O) Extension Modules Installation Instructions
Typical Air Handling Unit Application
Wiring Diagram
Figure 2 shows a typical Air Handling Unit (AHU)
application wiring diagram.
Figure 2: Typical Power and Network Connections for Air Handling Unit Application
Wiring Follow these wiring recommendations:
• Remove the front plate from the back plate to
CAUTION: Risk of Electric Shock.
facilitate in the wiring process. Use a small flat
Disconnect the power supply before
! making electrical connections to avoid
screwdriver to tighten the terminal connector
screws once the wires are inserted.
electric shock.
• Keep power cables apart from other types of wiring
MISE EN GARDE : Risque de décharge
to avoid ambient noise transmission to other wires
électrique.
(for example, for power, 3-wire voltage, and current
Débrancher l'alimentation avant de
inputs and outputs).
réaliser tout raccordement électrique afin
d'éviter tout risque de décharge • Use wires or flat cables ranging from 22 to 14 AWG
électrique. (0.644 to 1.630 mm diameter) per pole. Power
cables must remain between 18 to 14 AWG
(1.024 to 1.630 mm) diameter.
LN Series Input/Output (I/O) Extension Modules Installation Instructions 3
• Do not connect the universal inputs, analog/digital Use an external fuse on the 24 VAC/DC side
outputs or common terminals to earth or chassis (secondary side) of the transformer to protect all
ground unless otherwise stated. controllers against power link spikes (Figure 3 and
Figure 4).
• Keep all wires away from high speed data
transmission cables (for example, Ethernet cable).
• Keep input and output wires in conduits, trays, or
close to the building frame whenever possible.
Power Wiring
IMPORTANT: This is a Class 2 Product. Use a
Class 2 transformer only (rated at 100 VA or less at Figure 4: Power Wiring – DC
24 VAC) to power the controller.
IMPORTANT: Maintain consistent polarity when
Device power requirements for the LN Series I/O
you connect the controllers and devices to the
Extension Module is 24 VAC +15%, Class 2.
transformer.
For more information and requirements for powering an
LN Series I/O Extension Module, refer to the IMPORTANT: One terminal on the secondary side
LONWORKS® LN-Series Network Communication and of the transformer must be connected to the
Interface Guide Technical Bulletin (LIT-12011253). building’s ground. All 24 V COM terminals of all
We recommend wiring only one controller per 24 VAC controllers and peripherals throughout the LAN or
transformer. When only one transformer is available, the subnetwork must be connected to the grounded
determine the maximum number of controllers that can transformer as shown in Figure 3 and Figure 4. This
be supplied using the following method for calculating ensures that the 24 V COM terminals of all devices
the required power transformer capacity: connected to any LAN or subnetwork in the building
are at the same potential.
1. Add up the maximum power consumption of all
controllers, including external loads, and multiply IMPORTANT: The COM terminals of the controller
this sum by 1.3. are internally wired to the 24 V COM terminal of the
2. If the resulting number is higher than 100 VA, use power supply. Connecting a peripheral or another
multiple transformers controller to the same transformer without
maintaining polarity between these devices will
cause a short circuit.
IMPORTANT: A mechanical ground is
unacceptable. Do not use a pipe, conduit, or duct
work for a ground. The power supply must have a
dedicated ground wire that comes from the main
electrical supply panel.
Input Wiring
Figure 3: Power Wiring – AC
Each I/O Extension Module has physical connections
for inputs (marked Ulx), which are software
configurable from within the device’s LNS® plug-in or
wizard. Each input can be configured for digital,
resistive, current, or voltage signals. You must
configure the input types properly in the software
plug-in or wizard to ensure proper input readings. The
physical connections for inputs are marked as Ulx.
IMPORTANT: Before you connect input equipment
to the extension module, refer to the installation
instructions from the equipment manufacturer.
4 LN Series Input/Output (I/O) Extension Modules Installation Instructions
Note: For wire length less than 75 feet (23 m), use a Wiring Current Inputs
shielded or unshielded 18 AWG wire. Current inputs have a range of 0 to 20 mA. Set the
Note: For a wire up to 200 feet (61 m) long, a shielded jumper to the 0 to 20mA position for all current inputs.
18 AWG wire is recommended. This setting provides the required 249 ohm resistance
for the controller’s current inputs. Depending on the
Note: The wire should be shielded on the I/O transducer power requirements, you may use any of
Extension Module side and the shield length should be the following input configurations. Use Figure 8 for the
kept as short as possible. 2-wire, 0 to 20 mA transducer powered by the
Wiring Digital Inputs controller’s internal 15 VDC power supply.
Use this input configuration to monitor digital dry
contacts, as well as pulsed contacts.
Figure 5: Digital Input – Digital Dry Contact
(N.O. and N.C.) Figure 8: Current Input – 2-Wire Transducer
Powered by the Controller
Wiring Resistive Inputs
Use the Figure 9 configuration for a 2-wire, 0 to 20 mA
Use this input configuration to monitor Resistance transducer powered by an external 24 AC/DC power
Temperature Detectors (RTD), thermistors, such as supply.
1,000 ohm RTDs to 10k ohm Type II and Type III
thermistors, and potentiometers, such as 10k ohm and
100k ohm.
Figure 6: Resistive Input – RTD/Thermistor Figure 9: Current Input – 2-Wire
Input Transducer, Externally Powered
Use the Figure 10 configuration for a 3-wire, 0 to 20
mA transducer powered by an external 24 AC/DC
power supply.
Figure 7: Resistive Input – 10k ohm
Potentiometer Input
Figure 10: Current Input – 3-Wire Transducer,
Externally Powered
LN Series Input/Output (I/O) Extension Modules Installation Instructions 5
Use the Figure 11 configuration for a transducer Output Wiring
powered by its own power source. Each extension module has physical connections for
universal outputs. These outputs are all software
configurable.
IMPORTANT: Before you connect output
equipment to the extension module, refer to the
installation instructions from the equipment
manufacturer.
Figure 11: Current Input – Transducer with Its
Own Power Source Output Wiring Recommendations
Output wiring recommendations include:
Wiring Voltage Inputs • For a wire length less than 75 feet (23 m) long, use
Voltage inputs have a range of 0 to 10 VDC or either a shielded or unshielded 18 AWG wire.
0 to 5 VDC. Connect the voltage input according to
• For a wire length up to 200 feet (61 m) long, use a
Figure 12 if you are using a 3-wire 0 to 10 V or 0 to 5 V
shielded 18 AWG wire.
transducer.
• The shield of the wire should be grounded on the
controller side and the shield length should be kept
as short as possible.
Wiring Universal Outputs (UOx)
Figure 12: Voltage Input – 3-Wire Transducer You can configure universal outputs to provide either a
discrete signal of 0 or 12 VDC, a linear signal ranging
from 0 to 10 VDC, or a 0 to 20 mA signal. The discrete
Connect the voltage input according to Figure 13 if the
signal can be used to generate a pulse wave
transducer is powered by its own power source.
modulation (PWM) signal or a simple two-state signal.
These outputs are protected by an auto-reset fuse.
Wiring Discrete Outputs
If a 12 VDC relay is being controlled, connect it to a
Figure 13: Voltage Input – Transducer with Its universal output according to Figure 15.
Own Power Source
Wiring Pulse Inputs
The pulse inputs support a maximum input frequency
of 1 Hz (500 ms minimum ON/OFF) or 50 Hz (10 ms Figure 15: Discrete 0 or 12 VDC Universal
minimum ON/OFF). Connect the pulse input according Output – Relay
to Figure 14 for a pulse meter that can pull down a +5
VDC supply with a 10k ohm pull-up resistor (internal
supply type). Wiring Current Outputs
The 0 to 20 mA signal is configurable by jumper
(Figure 16).
Figure 16: 0 to 20 mA Universal Output and
Jumper Configuration
Figure 14: Internal Supply, 2-wire Pulse Meter
6 LN Series Input/Output (I/O) Extension Modules Installation Instructions
Voltage Outputs • Connect the shield of the data bus to the electrical
Connect the 0 to 10 VDC as shown in Figure 17. system ground at only one point, usually at one
end of the bus as shown in Figure 19
As shown in Figure 20, Figure 21, and Figure 22:
• The first and last daisy-chained subnetwork device
must have its EOL resistors enabled. All other
devices must have their EOL resistor disabled.
Figure 17: Voltage 0 to 10 VDC Universal Output
• The I/O Extension Module and the LN-SVSENx-0
share the same subnetwork.
If you are controlling an analog actuator, connect the 0
Refer to the LN Series Input/Output (I/O) Extension
to 10 VDC output, along with an external 24 VAC
Modules Subnetwork Application Note (LIT-12011706)
power source, to the analog actuator (Figure 18).
for additional information.
About the Subnetwork Bus
The LN Free Programmable PRG 600 Series
controllers use the Subnetwork bus to support the
LN-IOE400 Series Extension Modules through 2-wire
shielded cable.
Figure 18: Voltage 0 to 10 VDC Universal
Output – Analog Actuator The LN-PRG6x0-xx Controllers also use the
subnetwork bus to support one or more LN-SVSENx-0
Subnetwork Communications Wiring with the Communicating Sensors using standard structural
cabling.
LN-PRG6x0-xx Controller
LN-IOE400 Series I/O Extension Modules are Subnetwork Bus Total Length
connected to the Subnet- and Subnet+ terminals of The total maximum length of all subnetwork buses,
the LN-PRG6x0-xx controllers. including both the length of the LN-SVSENx-0 Sensors
subnetwork bus and the LN-IOE4x0-0 subnetwork bus
For optimal performance, use 24 AWG (0.65 mm)
is 1,000 ft (300 m). The maximum length of the
stranded, twisted pair shielded cable. The subnetwork
LN-SVSENx-0 subnetwork bus is 650 ft (200 m). The
communication wire is polarity sensitive and the only
maximum length of the LN-IOE4x0-0 subnetwork bus is
acceptable topology is to daisy-chain the cable from
1,000 ft (300 m). See Figure 20.
one I/O Extension Module to the next.
Subnetwork Bus Topology and EOL Terminations
For more information on subnetworks for the
with the LN-PRG6x0-xx Controllers
LN-IOE400 Series Extension Modules and
LN-PRG6x0-xx controllers, refer to the LONWORKS When the LN-IOE400 Series Extension Modules are
LN Series Network Communication and Interface installed with LN-PRG6x0-xx controllers, only the EOL
Guide Technical Bulletin (LIT-12011253) and the terminations of LN-PRG6x0-xx controller and the last
LN Series Input/Output Extension Modules and I/O Extension Module are set to ON. All other I/O
Communicating Sensors Subnetwork for Extension Modules must have their EOL terminations
LN-VAVCF-12 and LN-PRGxxx-12 Application Note set to OFF. See Figure 21.
(LIT-12011815). When the LN-IOE400 Series Extension Modules are
Subnet Bus Shielding Recommendations installed with an LN-PRG6x0-xx controller and with
LN-SVSENx-0 sensor(s), only the EOL terminations on
• When the subnetwork data bus is connected to a
the last I/O Extension Module and the last
following device, twist data bus shields together.
LN-SVSENx-0 sensor are set to ON. The
• Isolate all shields with electrical tape so there is no LN-PRG6x0-xx controller and all other I/O Extension
exposed metal that can touch ground or other Modules and LN-SVSENx-0 sensors must have their
conductors. EOL terminations set to OFF. See Figure 22.
LN Series Input/Output (I/O) Extension Modules Installation Instructions 7
Figure 19: Subnetwork Bus Shielding
Figure 20: Subnetwork Bus Overview Showing the LN-SVSENx-0 Subnetwork Bus and the
LN-IOE4x0-0 Subnetwork Bus
8 LN Series Input/Output (I/O) Extension Modules Installation Instructions
Figure 21: Setting the EOL Terminations on the Subnetwork Bus
Figure 22: Setting the EOL Terminations on the LN-IOE4x0-0 Subnetwork Bus When LN-SVSENx-0
Sensors Are Used
LN Series Input/Output (I/O) Extension Modules Installation Instructions 9
If you are inserting multiple wires in the terminals, The address is the sum of the numbers set to ON. For
properly twist wires together prior to inserting them in example, if the second DIP switch is set to ON, the I/O
the terminal connectors. For more information on Extension Module address is 2. You must power cycle
network topology and wire length restrictions, refer to the I/O Extension Module after the Subnet ID DIP
The LONWORKS LN-Series Network Communication Switch change.
and Interface Guide Technical Bulletin (LIT-12011253).
Strain Relief and Terminal Block Cover
Setup and Adjustments In certain jurisdictions, terminal block covers are
I/O Extension Module Addressing required to meet local safety regulations. Strain reliefs
and terminal block covers are available for controllers
Using the DIP switch located on the faceplate, you
housed in large enclosures and are used to relieve
must set the Subnet ID Address 1 or 2. Figure 23
tension on the wiring and conceal the controllers’ wire
shows an example of how to set the device’s Subnet ID
terminals. Strain reliefs and terminal block covers are
Address DIP switch.
optional and are sold separately.
ON
Subnet ID
Figure 23: Typical I/O Extension Module
DIP Switch Set to 2
Figure 24: Large Enclosure Strain Relief and Terminal Block Cover Installation
10 LN Series Input/Output (I/O) Extension Modules Installation Instructions
Maintenance • verify the tension of all wires and cables each time
you service the controller.
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
Disposal
! making any electrical connections to The Waste Electrical and Electronic Equipment
(WEEE) Directive sets regulations for the recycling and
avoid electric shock.
disposal of products. The WEEE 2002/96/EG Directive
MISE EN GARDE : Risque de décharge applies to stand-alone products that can function on
électrique. their own and are not a part of another system or piece
Débrancher l'alimentation avant de of equipment. For this reason, Johnson Controls®
réaliser tout raccordement électrique afin products are exempt from the WEEE Directive.
d'éviter tout risque de décharge
électrique. Nevertheless, they are marked with the WEEE symbol,
indicating the devices are not disposed with municipal
Each controller requires minimal maintenance, but it is waste.
important to: Dispose of products at the end of their useful life
• clean the outside of the front plate and the inside of according to local regulations and the WEEE Directive.
the back plate with a dry cloth.
Troubleshooting
Table 1 describes some troubleshooting scenarios.
Table 1: Troubleshooting (Part 1 of 2)
Problem Possible Solution
Controller is powered but does not turn on.
Fuse Is Blown Disconnect power from the controller and check the fuse integrity.
Reconnect power.
Power Supply Polarity Verify that consistent polarity is maintained between all controllers and
the transformer. Ensure that the COM terminal of each controller is
connected to the same terminal on the secondary side of the
transformer. See Figure 3 and Figure 4.
I/O Extension Module cannot communicate on the subnetwork.
Absent or Incorrect Supply Voltage 1. Check power supply voltage between 24 VAC/DC ±15% and COM
pins, and ensure that it is between acceptable limits.
2. Check for tripped fuse or circuit breaker.
Overloaded Power Transformer Verify the transformer is powerful enough to supply all controllers. See
Power Wiring.
Network Not Wired Properly Check that the wire connections are correct.
Absent or Incorrect Network Termination Check the network terminations. Only the last LN-IOE4x0-0 Extension
Module must have it EOL termination set to ON. See Figure 21. When
one or more LN-SVSENx-0 sensors are connected to the controller, only
the last LN-SVSENx-0 must have its EOL termination set to ON. See
Figure 22.
There is another controller with the same Each I/O Extension Module on the subnetwork must have a unique
Subnet ID on the subnetwork Subnet ID. Look at the Subnet ID DIP switch on the faceplate of each I/O
Extension Module.
Network length Check that the total wire length does not exceed specifications. Refer to
the LN Series Input/Output (I/O) Extension Modules Subnetwork
Application Note (LIT-12011706).
Wire type Check that the wire type agrees with specifications. Refer to the LN
Series Input/Output (I/O) Extension Modules Subnetwork Application
Note (LIT-12011706).
Hardware input is not reading the correct value.
Input Wiring Problem Check that the wiring is correct according to this manual and according
to the peripheral device's manufacturer.
LN Series Input/Output (I/O) Extension Modules Installation Instructions 11
Table 1: Troubleshooting (Part 2 of 2)
Problem Possible Solution
Open Circuit or Short Circuit Using a voltmeter, check the voltage on the input terminal. A short circuit
has a 0 V value and an open circuit has a 5 V value.
Configuration Problem Check the configuration of the input using the controller configuration
plug-in or wizard. Refer to the online help for more information.
Over Voltage or Over Current at an Input An over voltage or over current at one input can affect the reading of
other inputs. Observe the allowed voltage/current range limits for all
inputs.
Hardware output is not operating correctly.
Fuse has blown (auto reset fuse) Disconnect the power and outputs terminals. Then wait a few seconds to
allow the auto-reset fuse to cool down. Check the power supply and the
output wiring if necessary. Reconnect the power.
Output Wiring Problem Check that the wiring is correct according to this manual and according
to the peripheral device's manufacturer.
Configuration Problem Using the controller configuration wizard (LN-GPI), check the
configuration of the input. Refer to the controller's user guide for more
information.
0 to 10 V Output, 24 VAC Powered Check the polarity of the 24 VAC power supply connected to the actuator
Actuator is Not Moving while connected to the controller. Reverse the 24 VAC wire if necessary.
Rx/Tx LEDs
Rx LED not Blinking Data is not being received from the Subnetwork bus.
Tx LED not Blinking Data is not being transmitted onto the Subnetwork bus.
Status LED Operation
Table 2: Status LED Operation Guide – Normal Operation
Operation Service
Fast Blink Continuous • Initialization: the device is starting up.
• Firmware upgrade in is progress and the controller operation is
temporarily unavailable. The new firmware is being loaded into
(150 ms On, 150 ms Off, Continuous) memory and the process takes a few seconds. Do not interrupt
power to the device during this time.
Solid ON Firmware upgrade in is progress and the controller operation is
temporarily unavailable. The new firmware is being loaded into
memory and the process takes a few seconds. Do not interrupt power
to the device during this time.
The Status LED is Always OFF The controller is operating normally.
Table 3: Status LED Operation Guide – Repeats every 2 seconds (highest priority first)
Operation Service
Long blink continuous The controller is not configured.
(1s On, 1s Off, Continuous) Appropriate action: Commission the controller.
Long Long Long Blink The controller is offline.
(800 ms On, 300 ms Off, 800 ms On, 300 ms Off, 800 ms Appropriate action: Verify that the:
Off) • I/O Extension Module’s Subnet ID Address is correctly
set. See Setup and Adjustments.
• Subnetwork bus cable is not cut, short-circuited, or too
long. See Subnetwork Communications Wiring with the
LN-PRG6x0-xx Controller.
• Associated LN-PRG6x0-12 controller has power.
12 LN Series Input/Output (I/O) Extension Modules Installation Instructions
Repair Information
If the LN Series I/O Extension Module fails to operate
within its specifications, replace the unit. For a
replacement controller, contact the nearest
Johnson Controls® representative.
Technical Specifications
LN-IOE4x0-0 Series (Part 1 of 2)
Product Code LN-IOE400-0, LN-IOE410-0, LN-IOE420-0
Power Requirements Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
Protection: 3.0 A user-replaceable fuse
Power Consumption: 22 VA typical plus all output loads; LN-IOE400-0, LN-IOE410-0:
50 VA maximum; LN-IOE420-0: 16 VA maximum; 10 VA typical on all loads
Communication Communication Bus: RS-485
Baud Rate: 38, 400 bps
Addressing: DIP switch
Environmental Operating Temperature: 0 to 50°C, (32 to 122°F)
Storage Temperature: -20 to 50°C, (-4 to 122°F)
Relative Humidity: 0 to 90% noncondensing
General Processor: STM32 (ARM Cortex™ M3) MCU, 32 bit
Processor Speed: 64 MHz
Clock: Real-time clock chip
Battery for Clock: CR2032 lithium battery
Memory: 64 KB Nonvolatile Flash (applications and storage); 20 KB RAM
Status Indicator: Green LED – power status and subnetwork TX, Orange LED – service
and subnetwork RX
Enclosure Material: FR/ABS
Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
Shipping Weight: 1.17 lbs (0.53 kg)
Inputs Number of Inputs: 12
LN-SVSENx-0 Sensors: 12
Input Types: universal software configurable
Voltage: 0 to 10 VDC (40k ohm input impedance)
0 to 5 VDC (high input impedance)
Current: 0 to 20 mA with 249 ohmjumper configurable internal resistor
Digital: dry contact
Pulse: 1 Hz maximum, 500 ms On/500 ms off; dry contact
Resistor Support: 0 to 350k ohms. All thermistor types that operate within this range are
supported. The following temperature sensors are pre-configured:
Thermistor:
Type 2 and Type 3 10k ohm (10k ohm at 25°C [77°F])
Platinum:
PT1000 1k ohm (1k ohm at 0°C [32°F])
Nickel:
RTD Ni1000 (1k ohm at 0°C [32°F])
RTD Ni1000 (1k ohm at 21°C [69.8°F])
Input Resolution: 16-bit analog/digital converter
Power Supply Output: 15 VDC; maximum 200 mA (16 inputs x 20 mA each)
LN Series Input/Output (I/O) Extension Modules Installation Instructions 13
LN-IOE4x0-0 Series (Part 2 of 2)
Outputs Universal Outputs: 12
Universal Output Characteristics:
0 to 10 VDC linear; digital 0 to12 VDC (on/off), PWM, floating, or 0 to 20 mA (jumper
configurable); software configurable.
PWM control: adjustable period from 2 to 15 minutes
Floating control:
minimum plus on/off: 500 ms
adjustable drive time period
HOA: Hands-Off-Auto switch (when equipped)
Hand position potentiometer range: 0 – 12.5 VDC
60 mA maximum at 12 VDC (60°C; 140°F)
Load Resistance: minimum resistance 200 ohms for 0 to 10 VDC and
0 to 12 VDC, maximum 500 ohm for 0 to 20 mA output
Auto reset fuse
60 mA at 60°C (140°F)
100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/analog converter
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and
light-industrial environments (pending).
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
light-industrial environments (pending).
Compliance:
United States UL Listed, File E107041, CCN PAZX,
Under UL 916, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7,
Under CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that the products are in compliance with the
essential requirements and other relevant provisions of the EMC Directive 2004/108/EC.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.
14 LN Series Input/Output (I/O) Extension Modules Installation Instructions