LN Series Input/Output (I/O) Extension Modules and LN
Communicating Sensors Subnetwork for
LN-VAVCF-12 and LN-PRGxxx-12                      Code No. LIT-12011815
                                                                                                                 Software Release 6.0
Application Note                                                                                               Issued January 30, 2013
LN-IOE400-0, LN-IOE410-0, LN-IOE420-0, LN-VAVCF-12, LN-PRGxxx-12

Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Subnetwork Bus Total Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Subnetwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
    Topology and EOL Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Connecting to the LONWORKS Network Through an
    LN Communicating Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Enabling the Net to Subnet Port Settings Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Configuring the LN Communicating Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Connecting to the LON USB Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Subnetwork Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Physical Specifications and Cable Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

                            LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors                                         1
                                         Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note
2   LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-
    VAVCF-12 and LN-PRGxxx-12 Application Note
LN Series Input/Output (I/O) Extension Modules and LN
Communicating Sensors Subnetwork for
LN-VAVCF-12 and LN-PRGxxx-12
Application Note

Document Introduction
  This document describes the subnetwork for the LN Series Input/Output Extension
  Modules and LN Series Communicating Sensors. The LN-VAVCF0-12 and
  LN-PRGxxx-12 Series Controllers are equipped with an RJ-45 subnetwork port to
  quickly connect with subnetwork devices such as the LN Communicating Sensors
  using a Cat 5e cable (standard patch Ethernet cable). In addition, the
  LN-PRG6x0-12 Series controllers can also link to the LN-IOE-4x0 I/O Extension
  Modules through the subnetwork. The subnetwork for the LN-IOE-4x0 I/O
  Extension Modules uses a standard screw-type terminal block connector and
  twisted pair shielded cable.
  This document does not describe how to set up a LONWORKS® network. For
  information on setting up your LONWORKS® network, refer to the LONWORKS®
  LN-Series Network Communication and Interface Guide Technical Bulletin
  (LIT-12011253).

Related Documentation
  Table 1: Related Documentation
   For Information On                  See Document                        LIT Number
   Setting Up a LONWORKS Network       LONWorks LN-Series Network          LIT-12011253
                                       Communication and Interface Guide
                                       Technical Bulletin
   Setting Up a Subnetwork with LN     LN Series Input/Output (I/O)        LIT-12011706
   Series Input/Output Extension       Extension Modules Subnetwork for
   Modules Subnetwork for              LN-PRG6x0-2 Application Note
   LN-PRG6x0-2
   Installing LN Free Programmable     LN Free Programmable PRG 600        LIT-12011691
   PRG 600 Series Controllers          Series Controllers Installation
                                       Instructions
   Installing LN Series Input/Output   LN Series Input/Output (I/O)        LIT-12011693
   (I/O) Extension Modules             Extension Modules Installation
                                       Instructions
   LN Free Programmable PRG 600        LN Free Programmable PRG 600        LIT-12011656
   Series Controllers and LN I/O       and LN Input/Output Extension
   Extension Modules Features and      Modules Product Bulletin
   Benefits
   LN Series Communicating Sensors     LN Series Communicating Sensors     LIT-12011779
   Features and Benefits               Product Bulletin

 LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-   3
                                                    VAVCF-12 and LN-PRGxxx-12 Application Note
Subnetwork Bus Total Length
    The total maximum length of all subnetwork buses, including both the length of
    the LN Series I/O Extension Modules subnetwork bus and the LN Series
    Communicating Sensors subnetwork bus is 300 m (1,000 ft). The maximum length
    of the LN Series I/O Extension Modules subnetwork bus is 300 m (1,000 ft)
    (Figure 1). The maximum length of the LN Series Communicating Sensors
    subnetwork bus is 200 m (650 ft) (Figure 2).

           Figure 1: Maximum Length of the LN I/O Extension Modules
                              Subnetwork Bus

         Figure 2: Maximum Length of the LN Communicating Sensors
               Subnetwork Bus with an LN-VAVCF-12 Controller

4     LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-
      VAVCF-12 and LN-PRGxxx-12 Application Note
  Since the total maximum length of all subnetwork buses cannot exceed
  300 m (1,000 ft), the length of one subnetwork bus affects the length of other
  subnetwork buses. Figure 3 shows that if the LN Series Communicating Sensors
  subnetwork is 150 m (500 ft), then the LN Series I/O Extension Modules
  subnetwork length can only be a maximum of 150 m (500 ft).

      Figure 3: Example of Distribution and Total Maximum Length of
                         Subnetwork Bus Length

Subnetwork
  Figure 4 shows the LN Series Input/Output Extension modules on the
  subnetwork with the proper End-of-Line (EOL) terminations.

               Figure 4: EOL Terminations Settings on Subnetwork

  Note: In Figure 4, the EOL jumpers are located on the inside of the controller and
        modules.

 LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-   5
                                                    VAVCF-12 and LN-PRGxxx-12 Application Note
    When LN-IOE4x0 modules are installed with an LN-PRG6x0 controller and with
    LN Communicating Sensors, only the EOL terminations of the last LN-IOE4x0
    and the last LN Communicating Sensor are set to ON. All other LN-IOE4x0
    modules and LN Communicating Sensors must have their EOL terminations set to
    OFF (Figure 5).

    Figure 5: Setting the EOL Terminations on the LN-IOE4x0 Subnetwork
            Bus When the LN Communicating Sensors Are Used

Topology and EOL Terminations
    Set the EOL terminations on the LN Free Programmable PRG 600 Series
    Controller and the last LN I/O Extension Module to ON. All other extension
    modules must have their EOL termination set to OFF (Figure 4).

Connecting to the LONWORKS Network Through an
LN Communicating Sensor
    The subnetwork bus extends the LONWORKS network to the LN Communicating
    Sensors to provide convenient network access for maintenance and
    troubleshooting purposes (Figure 6).

6     LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-
      VAVCF-12 and LN-PRGxxx-12 Application Note
 This section explains how to enable the LONWORKS network with the LN
 Communicating Sensors. A LONWORKS network has a limited number of enabled
 controllers.

   Figure 6: LN Communicating Sensors Subnetwork with LONWORKS
                             Network

 To provide LONWORKS network access, jumpers on both the controller and the
 LN Communicating Sensor must be enabled.
 All LONWORKS controllers have Net to Subnet Port Settings jumpers, which
 (when enabled) connect the LONWORKS network to the LN Communicating
 Sensor.
 Note: Only a limited number of controllers on the LONWORKS network segment
       should have their Net to Subnet Port Settings jumpers enabled. Enabling
       too many LN Communicating Sensors with network access may cause
       communication issues.

LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-   7
                                                   VAVCF-12 and LN-PRGxxx-12 Application Note
    Figure 7 shows a typical LONWORKS network bus topology with only a few
    controllers enabled for network access at the LN Communicating Sensor.

                 Figure 7: LONWORKS Network Bus Topology

    For maximum cable lengths and cable specifications for LONWORKS network bus
    topology, see Table 2.
    The length of the LN Communicating Sensor subnetwork bus must also comply
    with the restrictions shown in Figure 1 and Figure 2.

Enabling the Net to Subnet Port Settings Jumper
    To connect the main LONWORKS network to the LN Communicating Sensor
    subnetwork Cat5e cable, set the two Net to Subnet Port Settings jumpers inside
    the LN-PRG6x0 controller to Enable (Figure 8). The factory default for the Net to
    Subnet Port Settings jumpers is set to Disable.

        Figure 8: Jumpers Set to Enabled on the LN-PRG6x0 Controller

8     LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-
      VAVCF-12 and LN-PRGxxx-12 Application Note
  To connect the main LONWORKS network to the LN Communicating Sensor
  subnetwork Cat5e cable, set the two Net to Subnet Port Settings jumpers inside
  the LN-VAVCF-12 controller to Enable (Figure 9). The factory default for the Net
  to Subnet Port Settings jumpers is set to Disable.

     Figure 9: Jumpers Set to Enabled on the LN-VAVCF-12 Controller

Configuring the LN Communicating Sensor
  On each LN Communicating Sensor, ensure that the BAC/LON jumper is set to the
  LON position (Figure 10). Use this setting for all LN Communicating Sensors, in
  case you wish to enable the network in the future.

                 Figure 10: LN Communicating Sensor BAC/LON
                               Jumper Set to LON

 LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-   9
                                                    VAVCF-12 and LN-PRGxxx-12 Application Note
Connecting to the LON USB Interface
     To temporarily access the LONWORKS network for commissioning and
     maintenance purposes, connect a LON USB Network Interface to the stereo audio
     plug located on the lower edge of the LN Communicating Sensor. You can then
     wire a standard 3.5 mm (1/8 in.) three-conductor (stereo jack) or two-conductor
     (mono jack) as shown in Figure 11.

        Figure 11: Connecting to LONWORKS Network via Stereo Jack on LN
                             Communicating Sensor

Subnetwork Length
     The total maximum length of the subnetwork is 300 meters (1,000 feet). The
     polarity of the LN Series I/O Extension Modules must be configured as shown in
     Figure 12. All terminals identified as SUBNET+ must be connected to the same
     conductor. Similarly, all terminals identified as SUBNET- must be connected to the
     same conductor.

          Figure 12: LN Free Programmable PRG 600 Series Controllers
                              Subnetwork Shielding

10     LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-
       VAVCF-12 and LN-PRGxxx-12 Application Note
   Use properly grounded, shielded cable for the best protection against interference
   on the LN Series I/O Extension Module subnetwork. Use the daisy-chain
   configuration with the cable shield twisted together and isolated with electrical
   tape at each extension module.
   When you use an LN Free Programmable PRG 600 Series Controller, connect the
   shielding of the extension modules on the subnetwork to the electrical system
   ground at one point only (Figure 12).

Physical Specifications and Cable Requirements
   Use cables composed of stranded conductors, instead of solid conductors, for the
   best breakage resistance during pulling operations. Table 2 describes the physical
   specifications and cable requirements for an LN Series I/O Extension Module
   subnetwork.
   Table 2: Physical Specifications and Cable Requirements
    Specification                            Description
    Maximum Number of LN Series I/O          2 LN Series I/O Extension Modules
    Extension Modules
    Media                                    Shielded, Twisted Pair
    Characteristic Impedance                 100–130 ohm
    Distributed Capacitance                  Less than 100 pF per meter (30 pF per foot)
    Maximum Length of the LN Series I/O      300 meters (1,000 ft) Maximum
    Extension Modules Subnetwork
    Polarity                                 Polarity Sensitive
    Multi-Drop                               Daisy-chain (No Routers)
    End-of-Line (EOL) Terminations           Built-in and set (enabled) on the last extension
                                             module only.
    Shield Grounding                         See Figure 12.

 LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-   11
                                                    VAVCF-12 and LN-PRGxxx-12 Application Note
Addressing
     Each LN Series I/O Extension Module on the subnetwork must have a unique
     address. The current valid addresses are 1 or 2. Figure 13 shows an example of
     how to set a DIP switch. Table 3 shows the DIP switch settings.

                                Figure 13: DIP Switch Set to 2

     Table 3: DIP Switch Settings
                      Switch Position                                       Value
            1               2                    3
          OFF             OFF                  OFF                          Invalid
           ON             OFF                  OFF                             1
          OFF              ON                  OFF                             2
           ON              ON                  OFF                          Invalid
          OFF             OFF                   ON                          Invalid
           ON             OFF                   ON                          Invalid
          OFF              ON                   ON                          Invalid
           ON              ON                   ON                          Invalid

                                                                                                Building Efficiency
                                                                       507 E. Michigan Street, Milwaukee, WI 53202
                                Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                       All other marks herein are the marks of their respective owners. © 2013 Johnson Controls, Inc.

12     LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-
       VAVCF-12 and LN-PRGxxx-12 Application Note
Published in U.S.A.                                                                        www.johnsoncontrols.com