Текст документа
Code No. LIT-1900464
Issued November 5, 2012
LN-PRG203-2, LN-PRG300-2, LN-PRG4x0-2, LN-PRG5x0-2
LN Series Free Programmable Controllers
Description • robust hardware - features a fire retardant
plastic enclosure, a 128K Flash memory
The LN Series Free Programmable
for the configuration and trending of up to
Controllers are microprocessor-based free
12,000 events, and a status indicator on
programmable controllers, designed to control
each output.
various Heating, Ventilating, and Air
Conditioning (HVAC) applications. • powerful control option - allows you to
easily configure all features, including,
The Metasys® system LN Series Free input types, output types, heating and
Programmable controllers product family is cooling stages, variable airflow, and
built to meet rigorous quality standards. The Proportional plus Integral plus Derivative
complete family of Metasys system LN Series (PID) loops. The controller supports four
controllers is designed for use with any input types: space temperature; setpoint
LONWORKS® network open and interoperable adjustment; duct temperature; and
system. occupancy, bypass, or window contacts.
• wireless functionality - features an optional LN-PRG510 Controller
Features EnOcean® wireless receiver
• configurable software - features LNS® (LN-WMOD315-0 or LN-WMOD868-0) that
plug-in that provides the ability to easily you can use with a variety of wireless Repair Information
configure and program inputs, outputs, and sensors and switches. The wireless If the LN Series Free Programmable controllers
sequence options. Configured device receiver (LN-WMODxxx-0) supports up to fail to operate within their specifications,
complies with LONMARK® Space Comfort 14 wireless inputs which allow you to replace the unit. For a replacement, contact the
Control (SCC) profile for interoperability create wire-free installations. nearest Johnson Controls® representative.
with other LONMARK devices. Also features
more than 60 network variables.
Selection Chart
Code Number Description
LN-PRG203-2 LONMARK certified Programmable Controller with 6 Universal Inputs (UIs), 5 Digital Outputs (DOs), 3 Universal Outputs (UOs), and LNS
plug-in, 24 VAC, wireless enabled.
LN-PRG300-2 LONMARK certified Programmable Controller with 10 UI, 8 UO, and LNS plug-in, 24 VAC, wireless option.
LN-PRG400-2 LONMARK certified Programmable Controller with 12 UI, 12 UO, and LNS plug-in, 24 VAC, wireless option.
LN-PRG410-2 LONMARK certified Programmable Controller with 12 UI, 12 UO, Hands-Off-Auto (HOA) Switches, and LNS plug-in, 24 VAC, wireless option.
LN-PRG500-2 LONMARK certified Programmable Controller with 16 UI, 12 UO, and LNS plug-in, 24 VAC, wireless option.
LN-PRG510-2 LONMARK certified Programmable Controller with 16 UI, 12 UO, HOA Switches, and LNS plug-in, 24 VAC, wireless option.
Technical Specifications
LN-PRG203 (Part 1 of 2)
Product Code LN-PRG203-2
Power Requirement Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
Protection: 1.85 A auto-reset fuse
Typical Consumption: 18 VA with 2 triac outputs ON and 2 outputs with 20 mA load at 12 VDC
Maximum Consumption: 25 VA
Ambient Storage Conditions Ambient Operating Temperature: 0 to 70°C (32 to 158°F)
Ambient Storage Temperature: -20 to 70°C (-4 to 158°F)
Ambient Relative Humidity: 0 to 90% noncondensing
General Processor: Neuron® 3150™, 8 bits, 10 MHz
Memory: Nonvolatile Flash 64k (APB application); Nonvolatile Flash 128k (storage)
Media Channel: TP/FT-10; 78 Kbps
Communication: LonTalk® protocol
Status Indicator: Green LED - power status and LON TX, Orange LED - service and LON RX
Communication Jack: LON audio jack mono 1/8 in (3.5 mm)
LONMARK Interoperability: Version 3.4
Device Class: Multi I/O Module
LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
Open-Loop Sensor #3
Enclosure Material: ABS type PA-765A
Dimensions (with screws): 5.7 x 4.7 x 2.0 in. (144.8 x 119.4 x 50.8 mm)
Shipping Weight: 0.97 lb (0.44 kg)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
7
LN Series Free Programmable Controllers (Continued)
LN-PRG203 (Part 2 of 2)
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and
light-industrial environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
light-industrial environments.
FCC: This device complies with FCC rules part 15, subpart B, class B
Agency UL Listed: UL916 Energy management equipment
Material: UL94-5VA
Inputs Universal software configurable
Input Types:
Digital: Dry Contact
Pulse: Dry Contact; 500 milliseconds minimum ON/OFF
Voltage: 0 to 10 VDC,
Current: 4 to 20 mA with 249 ohms external resistor (wired in parallel),
Resistor Support:
Thermistor:
Type 2 and Type 3 10k ohms (10k ohms at 25°C [77°F])
Range: -40 to 150°C (-40 to 302°F)
Platinum:
PT1000 1k ohm (1k ohms at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
PT100: 100 ohms (100 ohms at 0°C [32°F])
Range: -40 to 135°C (-40 to 275°F)
Nickel:
RTD Ni1000 (1k ohm at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
Potentiometer:
Translation table configurable on several points
Input Resolution: 16-bit analog/digital converter
Outputs Digital: 24 VAC Triac, digital (on/off), PWM, or floating
software configurable
0.5 A continuous
1.0 A at 15% duty cycle for a 10-minute period
PWM control: adjustable period from 2 seconds to 15 minutes
Floating control: requires two consecutive outputs
minimum plus on/off: 500 milliseconds
adjustable drive time period
External or internal power supply (jumper selectable)
Universal: 0-10 VDC, digital 0-12 VDC (on/off), PWM, or floating
PWM control: adjustable period from 2 seconds to 15 minutes
Floating control: requires two consecutive outputs
minimum plus on/off: 500 milliseconds
adjustable drive time period
60 mA maximum at 12 VDC (60°C [140°F})
minimum resistance 200 ohms
Auto reset fuse
60 mA at 60°C (140°F)
100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/analog converter
Wireless1 Communication: EnOcean® Wireless standard
Number of Wireless Inputs: 14 (some sensors may require more than one wireless input)
Supported Wireless Receivers: Wireless Receiver 315 (LN-WMOD315-0) and Wireless Receiver 868 (LN-WMOD868-
0)
Cable: Connector: 4P4C modular jack, Length: 3 ft (1 m)
1. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more than one wireless input from the
controller.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
8
LN Series Free Programmable Controllers (Continued)
LN-PRG300 (Part 1 of 2)
Product Code LN-PRG300-2
Power Requirement Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
Protection: 1.85 A auto-reset fuse
Typical Consumption: 18 VA, all outputs with 20 mA load at 12 VDC
Maximum Consumption: 33 VA
Ambient Storage Conditions Ambient Operating Temperature: 0 to 70°C, (32 to 158°F)
Ambient Storage Temperature: -20 to 70°C, (-4 to 158°F)
Ambient Relative Humidity: 0 to 90% noncondensing
General Processor: Neuron 3150, 8 bits, 10 MHz
Memory: Nonvolatile Flash 64k (APB application), Nonvolatile Flash 128k (storage)
Media Channel: TP/FT-10; 78 Kbps
Communication: LonTalk protocol
Clock: Real-time clock chip, CR2032 lithium battery (for clock)
Status Indicator: Green LED - power status and LON TX, Orange LED - service and
LON RX
Communication Jack: LON audio jack mono 1/8 in (3.5 mm)
LONMARK Interoperability: Version 3.4
Device Class: Multi I/O Module
LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
Open-Loop Sensor #3
Enclosure Material: ABS type PA-765-A
Dimensions (with screws): 5.7 x 4.7 x 2.0 in. (144.8 x 119.4 x 50.8 mm)
Shipping Weight: 0.86 lb (0.39 kg)
Agency UL Listed: UL916 Energy management equipment
Material: UL94-5VA
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and light-industrial
environments.
CE Immunity: EN61000-6-1: 2007 Generic standards for residential, commercial, and light-industrial
environments.
Inputs Universal software configurable
Input Types:
Digital: Dry Contact
Pulse: Dry Contact, 500ms minimum ON/OFF
Analog Voltage: 0 to 10 VDC,
Analog current: 4 to 20 mA with 249 ohms external resistor (wired in parallel),
Resistor Support:
Thermistor: Type 2, Type 3 10k ohms (10k ohms at 25°C [77°F])
Range: -40 to 150°C (-40 to 302°F)
Platinum:
Pt1000 (1k ohm at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
PT100: 100 ohms 1k ohm at 0°C [32°F])
Range: -40 to 135°C (-40 to 275°F)
Nickel: Ni1000 (1k ohm at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
Potentiometer: Translation table configurable on several points,
Input Resolution: 16-bit analog/digital converter
Outputs Quantity: 8 (software configurable)
0 to 10 VDC, digital 0 to12 VDC (on/off), PWM, or Floating
PWM output: adjustable period from 2 seconds to 15 minutes
Floating control: requires two consecutive outputs
minimum pulse on/off: 500 milliseconds
adjustable drive time period
60 mA maximum at 12 VDC (60°C [140°F])
Minimum load 200 ohms
Auto reset fuse
60 mA at 60°C (140°F)
100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/analog converter
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
9
LN Series Free Programmable Controllers (Continued)
LN-PRG300 (Part 2 of 2)
Wireless1 Communication: EnOcean® Wireless standard
Number of Wireless Inputs: 14 (some sensors may require more than one wireless input)
Supported Wireless Receivers: Wireless Receiver 315 (LN-WMOD315-0) and Wireless Receiver 868 (LN-
WMOD868-0)
Cable: Connector: 4P4C modular jack, Length: 3 ft (1 m)
1. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more than one wireless input from the
controller.
LN-PRG410 and LN-PRG400 (Part 1 of 2)
Product Codes LN-PRG410-2 and LN-PRG400-2
Power Requirement Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
Protection: 3.0 A user-replaceable fuse
Typical Consumption: 25 VA
Maximum Consumption: 50 VA
Power Supply: 15 VDC output used to power 4 to 20 mA inputs
Ambient Storage Conditions Ambient Operating Temperature: 0 to 70°C (32 to 158°F)
Ambient Storage Temperature: -20 to 70°C (-4 to 158°F)
Ambient Relative Humidity: 0 to 90% noncondensing
General Standard: LONMARK Functional Profile: SCC-VAV Controller #8502
Processor: Neuron 3150, 8 bits, 10 MHz
Memory: Nonvolatile Flash 64k (APB application), Nonvolatile Flash 128k (storage)
Media Channel: TP/FT-10; 78 Kbps
Communication: LonTalk protocol
Clock: Real-time clock chip, CR2032 lithium battery (for clock)
Status Indicator: Green LED - power status and LON TX, Orange LED - service and
LON RX
Communication Jack: LON audio jack mono 1/8 in (3.5 mm)
LONMARK Interoperability: Version 3.4
Device Class: Multi I/O Module
LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
Open-Loop Sensor #3
Enclosure Material: ABS type PA-765A
Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
Shipping Weight: 1.17 lb (0.53 kg)
Agency UL Listed: UL916 Energy management equipment
Material: UL94-5VA
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and light-industrial
environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and light-industrial
environments.
Inputs Universal software configurable
Input Types:
Digital: Dry Contact
Pulse: Dry Contact (500 milliseconds minimum ON/OFF)
Analog Voltage: 0 to 10 VDC,
Analog current: 4 to 20 mA with 249 ohms external resistor (wired in parallel),
Resistor Support:
Thermistor: Type 2, Type 3 10k ohms (10k ohms at 25°C [77°F])
Range: -40 to 150°C (-40 to 302°F)
Platinum:
Pt1000 (1k ohm at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
PT100: 100 ohms 1k ohm at 0°C [32°F])
Range: -40 to 135°C (-40 to 275°F)
Nickel: Ni1000 (1k ohm at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
Potentiometer: Translation table configurable on several points,
Input Resolution: 16-bit analog/digital converter
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
10
LN Series Free Programmable Controllers (Continued)
LN-PRG410 and LN-PRG400 (Part 2 of 2)
Outputs Software and jumper configurable)
0 to 10 VDC, digital 0 to12 VDC (on/off), PWM, or Floating1
PWM output: adjustable period from 2 seconds to 15 minutes
Floating control: requires two consecutive outputs
minimum pulse on/off: 500 milliseconds
adjustable drive time period
60 mA maximum at 12 VDC (60°C [140°F])
Minimum load 200 ohms
Auto reset fuse
60 mA at 60°C (140°F)
100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/analog converter
Power Supply Output: 15 VDC, maximum 240 mA
Wireless2 Communication: EnOcean® Wireless standard
Number of Wireless Inputs: 14 (some sensors may require more than one wireless input)
Supported Wireless Receivers: Wireless Receiver 315 (LN-WMOD315-0) and Wireless Receiver 868 (LN-
WMOD868-0)
Cable: Connector: 4P4C modular jack, Length: 3 ft (1 m)
1. Available when programmed with LN GPI software.
2. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more than one wireless input from the
controller.
LN-PRG510 and LN-PRG500 Controllers (Part 1 of 2)
Product Codes LN-PRG510-2 and LN-PRG500-2
Power Requirement Voltage: 24 VAC/DC; +/- 15%, 50/60 Hz, Class 2
Protection: 3.0 A user-replaceable fuse
Typical Consumption: 25 VA all outputs with 20mA load at 12 VDC and 15 VDC output 80mA (4 x 20 mA)
Maximum Consumption: 50 VA
Ambient Storage Conditions Ambient Operating Temperature: 0 to 70°C, (32 to 158°F)
Ambient Storage Temperature: -20 to 70°C, (-4 to 158°F)
Ambient Relative Humidity: 0 to 90% noncondensing
General Standard: LONMARK Functional Profile: SCC-VAV Controller #8502
Processor: Neuron 3150, 8 bits, 10 MHz
Memory: Nonvolatile Flash 64k (APB application), Nonvolatile Flash 64k (storage)
Media Channel: TP/FT-10; 78 Kbps
Communication: LonTalk protocol
Transceiver: FTX-1
LONMARK Interoperability: Version 3.4
Device Class: Multi I/O Module
LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
Open-Loop Sensor #3
Enclosure Material: LEXAN® 500R (GE)
Dimensions (with screws): 3.74 x 7.68 x 2.82 in. (95 x 195 x 72 mm)
Shipping Weight: 1.76 lb (0.80 kg)
Agency UL Listed: UL916 Energy management equipment
Material: UL94-5VA
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and light-industrial
environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and light-industrial
environments.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
11
LN Series Free Programmable Controllers (Continued)
LN-PRG510 and LN-PRG500 Controllers (Part 2 of 2)
Inputs Universal software configurable
Input Types:
Digital: Dry Contact
Pulse: Dry Contact
Analog Voltage: 0 to 10 VDC, Accuracy: ±0.5%,
Analog current: 4 to 20 mA with 249 ohms external resistor (wired in parallel),
Resistor Support:
Thermistor: Type 2, Type 3 10k ohms (10k ohms at 25°C [77°F])
Range: -40 to 150°C (-40 to 302°F)
Platinum:
Pt1000 (1k ohm at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
PT100: 100 ohms 1k ohm at 0°C [32°F])
Range: -40 to 135°C (-40 to 275°F)
Nickel: Ni1000 (1k ohm at 0°C [32°F])
Range: -40 to 150°C (-40 to 302°F)
Potentiometer: Translation table configurable on several points
Input Resolution: 16-bit analog/digital converter
Outputs Universal 0 to10 VDC, digital 0 to12 VDC (on/off), 0-20 mA, PWM, or floating1
PWM output: adjustable period from 2 seconds to 15 minutes
Floating control: requires two consecutive outputs
minimum pulse on/off: 500 milliseconds
adjustable drive time period
60 mA maximum at 12 VDC (60°C; 140°F)
Minimum load 200 ohms
Auto reset fuse
60 mA at 60°C (140°F)
100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/analog converter
Power Supply Output: 15 VDC, maximum 240 mA
Wireless2 Communication: EnOcean® Wireless standard
Number of Wireless Inputs: 14 (some sensors may require more than one wireless input)
Supported Wireless Receivers: Wireless Receiver 315 (LN-WMOD315-0) and Wireless Receiver 868 (LN-
WMOD868-0)
Cable: Connector: 4P4C modular jack, Length: 3 ft (1 m)
1. Available when programmed with LN GPI software.
2. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more than one wireless input from the
controller.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2012 Johnson Controls, Inc. www.johnsoncontrols.com
12Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.