Code No. LIT-1900695
Issued May 13, 2011
LN-PRG600-2, LN-PRG610-2, LN-IOE400-0, LN-IOE410-0, LN-IOE420-0
LN Free Programmable PRG 600 Series Controller and Input/Output
(I/O) Extension Modules
Description
The LN Free Programmable PRG 600 Series Controllers are
microprocessor-based free programmable controllers, designed to
control various building systems, such as multi-zone air handing units
and central plant applications. The 600 Series controllers use the
LonTalk® communication protocol.
The PRG 600 Series controllers support up to 2 Input/Output extension
modules that operate on a separate sub-network, providing the PRG
600 Series controller with up to 40 universal inputs and 36 universal
outputs.
The LN Series Free Programmable controllers product family is built to
meet rigorous quality standards. The complete family of Metasys®
system LN Series controllers is designed for use with any LONWORKS®
network open and interoperable system.
Refer to the LN Free Programmable PRG 600 Series Controllers and LN-PRG610 Controller and I/O Extension Module
Input/Output (I/O) Extension Modules Product Bulletin (LIT-12011656).
Features
Repair Information
• configurable software
If the LN Series Controllers fail to operate within its specifications,
• robust hardware
replace the unit. For a replacement valve, contact the nearest
• powerful control options
Johnson Controls® representative.
• wireless functionality
Controller Models
Controller Features LN-PRG600-2 LN-PRG610-2 LN-IOE400-0 LN-IOE410-0 LN-IOE420-0
Points 28 28 24 24 24
Universal Inputs 161 161 12 12 12
Wireless Inputs2 28 28 14 14 14
15 VDC Power Supply X X X X X
HOA Switch and Potentiometer X X
Number of I/O extension Modules 2 2
Universal Outputs 12 12 12 12 0
1. The first four inputs are software configurable for pulse counting up to 50 Hz and are compatible with an SO rate (optically-isolated) output.
2. Available when optional Wireless Receiver is connected to the controller.
Selection Chart
Code Number Description
LN-PRG600-2 LONMARK® Certified Programmable Controller with 16 Universal Inputs (UI), 12 Universal Outputs (UO), and LNS Plug-in, 24 VAC, Wireless
Option
LN-PRG610-2 LONMARK Certified Programmable Controller with 16 UI, 12 UO, Hands-off-Auto (HOA) Switches, and LNS Plug-in, 24 VAC, Wireless Option
LN-IOE400-0 I/O Extension Module for LN-PRG6x0-2 with 12 UI, 12 UO, 24 VAC
LN-IOE410-0 I/O Extension Module for LN-PRG6x0-2 with 12 UI, 12 UO, 24 VAC, HOA Switches
LN-IOE420-0 I/O Extension Module for LN-PRG6x0-2 with 12 UI, 24 VAC
Technical Specifications
LN Free Programmable PRG 600 Series Controllers (Part 1 of 3)
Product Code LN-PRG600-2 and LN-PRG610-2
Power Requirement Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
Protection: 3.0A user-replaceable fuse
Power Consumption: 22 VA typical plus all output loads
Maximum Consumption: 65 VA
Ambient Storage Conditions Ambient Operating Temperature: 0 to 50°C, (32 to 122°F)
Ambient Storage Temperature: -20 to 50°C, (-4 to 122°F)
Ambient Relative Humidity: 0 to 90% noncondensing
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc. www.johnsoncontrols.com
1 of 4
LN Free Programmable PRG 600 Series Controller and Input/Output (I/O) Extension
Modules (Continued)
LN Free Programmable PRG 600 Series Controllers (Part 2 of 3)
General Processor: STM32 (ARM Cortex™ M3) MCU, 32 bit
Processor Speed: 72 MHz
Memory: 1 MB Nonvolatile Flash (applications), 2 MB Nonvolatile Flash (storage)
96 kB RAM
Media Channel: TP/FT-10; 78 Kbps
Communication: LonTalk® protocol
Status Indicator: Green LED - power status and LAN TX, Orange LED - service and LAN RX
Communication Jack: TP/FT-10; 78 Kbps, 1/8 in (3.5 mm)
LONMARK Interoperability: Version 3.4
Device Class: Static Programmable Device
LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1,
Output Objects: Open - Loop Sensor #3, Real Time Clock: Real Time Keeper #3300, Scheduler: Scheduler
#20020, Calendar: Calendar #20030, Programmable Device: Static Programmable Device #410
Enclosure Material: FR/ABS
Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
Shipping Weight: 1.17 lb (0.53 kg)
Inputs Input Types: universal software configurable
Voltage: 0 to 10 VDC (40k ohm input impedance)
0 to 5 VDC (high input impedance)
Current: 0 to 20 mA with 249 ohm jumper configurable internal resistor,
Digital: dry contact
Pulse: UI1 to UI4; 50 Hz maximum; Minimum 10 ms On/10 ms Off, dry contact
UI5 to UI6: 1 Hz maximum; Minimum 500 ms On/500 ms Off, dry contact
Resistor Support: 0 to 350k ohms. All thermistor types that operate within this range are supported. The
following temperature sensors are pre-configured:
Thermistor:
Type 2 and Type 3 10k ohm (10k ohm at 25°C [77°F])
Platinum:
PT1000 1k ohm (1k ohm at 0°C [32°F])
Nickel:
RTD Ni1000 (1k ohm at 0°C [32°F])
RTD Ni1000 (1k ohm at 21°C [69.8°F])
Input Resolution: 16-bit analog/digital converter
Power Supply Output: 15 VDC; maximum 320 mA (16 inputs x 20 mA each)
Outputs Universal: 0-10 VDC linear, digital 0 to12 VDC (on/off), PWM, floating, or
0 to 20 mA (jumper configurable to 4 to 20 mA); software configurable. Built-in snubbing diode to protect
against back EMF, for example when used with a 12 VDC relay.
PWM control: adjustable period from 2 seconds to 15 minutes
Floating control:
minimum plus on/off: 500 ms
adjustable drive time period
Hands-off-Auto (HOA) Switch (when equipped): hand position potentiometer range: 0 to 12.5 VDC
60 mA maximum at 12 VDC (60°C; 140°F)
Load Resistance: minimum resistance 200 ohms for 0 to 10 VDC and
0 to 12.5 VDC, maximum 500 ohm for 0 to 20 mA output
Auto reset fuse
60mA at 60°C (140°F)
100mA at 20°C (68°F)
Output Resolution: 10-bit digital/does analog converter
Wireless Receiver1 Communication: EnOcean® Wireless standard
Number of Wireless Inputs: 282
Supported Wireless Receivers: LN-WMOD315-0 and LN-WMOD868-0
Telephone Cord Cable: Connector: 4P4C modular jack, Length: 3 ft (1 m)
Enclosure Material: UL94-5VA
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and light-industrial
environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and light-industrial
environments.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc. www.johnsoncontrols.com
2 of 4
LN Free Programmable PRG 600 Series Controller and Input/Output (I/O) Extension
Modules (Continued)
LN Free Programmable PRG 600 Series Controllers (Part 3 of 3)
Compliance United UL Listed, File E107041, CCN PAZX,
States Under UL 916, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7,
Under CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that the products are in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC.
1. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more than one wireless input from the
controller.
2. Some wireless modules may use more than one wireless input from the controller.
LN Input/Output (I/O) Extension Modules (Part 1 of 2)
Product Code LN-IOE400-0, LN-IOE410-0, LN-IOE420-0
Power Requirement Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
Protection: 3.0A user-replaceable fuse
Power Consumption: 400/410: 50 VA maximum, 22 VA typical on all loads
420: 16 VA maximum, 10 VA typical on all loads
Ambient Storage Conditions Ambient Operating Temperature: 0 to 50°C, (32 to 122°F)
Ambient Storage Temperature: -20 to 50°C, (-4 to 122°F)
Ambient Relative Humidity: 0 to 90% noncondensing
Hardware Processor: STM32 (ARM Cortex M3) MCU, 32 bit, 64 MHz
Memory: 64 kB non-volatile Flash (applications and storage), 20 kB RAM
Status Indicator: Green LEDs - power status and Sub-Network TX, Orange LEDs - service and Sub-Network
RX
Enclosure Material: FR/ABS
Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
Shipping Weight: 1.17 lb (0.53 kg)
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and light-industrial
environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and light-industrial
environments.
Enclosure Material: UL94-5VA
Inputs Input Types: universal; software configurable
Voltage: 0 to 10 VDC (40k ohms input impedance),
0 to 5 VDC (high input impedance)
Current: 0 to 20 mA with 249 ohms jumper configurable internal resistor
Digital: dry contact
Pulse: 1 Hz maximum 500 ms On/500 ms Off, dry contact
Resistor Support: 0 to 350k ohms. All thermistor types that operate in this range are supported. The following
temperature sensors are pre-configured:
Thermistor:
Type II and Type III 10k ohm (10k ohm at 25°C [77°F])
Platinum:
PT1000 1k ohm (1k ohms at 0°C [32°F])
Nickel:
RTD Ni1000 (1k ohm at 0°C [32°F])
RTD Ni1000 (1k ohms at 21°C [69.8°F])
Input Resolution: 16-bit analog/digital converter
Power Supply Output: 15 VDC; maximum 240 mA (12 inputs x 20 mA each)
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc. www.johnsoncontrols.com
3 of 4
LN Free Programmable PRG 600 Series Controller and Input/Output (I/O) Extension
Modules (Continued)
LN Input/Output (I/O) Extension Modules (Part 2 of 2)
Outputs Universal: 0 to 10 VDC linear, digital 0 to 12 VDC (on/off), PWM, floating, or
(LN-IOE400-0 and LN-IOE410-0 Modules 0 to 20 mA (jumper configurable); software configurable
Only) PWM control or 0 to 20 mA (jumper configurable): 4 to 20 mA software configurable. Built-in snubbing diode to
protect against back EMF, for example when used with a 12 VDC relay.
PWM control: adjustable period from 2 seconds to 15 minutes
Floating control:
minimum plus on/off: 500 ms
adjustable drive time period
Hands-Off-Auto (HOA) switch (when equipped): hand position potentiometer range 0 to 12.5 VDC
60 mA maximum at 12 VDC (60°C; 140°F)
Load Resistance: minimum resistance 200 ohms for 0 to 10 VDC and 0 to 12 VDC outputs, maximum
500k Ohms for 0 to 20 mA output
Auto reset fuse:
60 mA at 60°C (140°F)
100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/analog converter
Compliance United States UL Listed, File E107041, CCN PAZX,
Under UL 916, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7,
Under CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that the products are in compliance with the essential requirements
and other relevant provisions of the EMC Directive 2004/108/EC.
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc. www.johnsoncontrols.com
4 of 4Позиції каталогу з цим документом