LN Free Programmable PRG 600 Series Controllers
Installation Instructions
LN-PRG600-2, LN-PRG610-2                                                                      Code No. LIT-12011691
                                                                                                   Issued July 17, 2014

Applications                                                  North American Emissions Compliance
The LN Free Programmable PRG 600 Series                       Canada
Controllers are microprocessor-based free
programmable controllers designed to control various              The term IC before the certification/registration
building automation systems, such as multi-zone air               number only signifies that the Industry Canada
handing units and central plant applications. The                 technical specifications were met.
PRG 600 Series controllers use the LonTalk®
                                                                  Industry Canada Statement
communication protocol.
                                                                  Le terme « IC » précédant le numéro d'accréditation/
The PRG 600 Series controllers support up to 2 Input/
                                                                  inscription signifie simplement que le produit est
Output extension modules that operate off of a
                                                                  conforme aux spécifications techniques d'Industry
separate sub-bus, providing the PRG 600 Series
                                                                  Canada.
controller with up to 40 universal inputs and
36 universal outputs.
                                                              United States
Follow these recommendations for proper installation
and subsequent operation of each controller:                      This equipment has been tested and found to
                                                                  comply with the limits for a Class A digital device
•     Inspect the controller for shipping damages. Do not         pursuant to Part 15 of the FCC Rules. These limits
      install damaged controllers.                                are designed to provide reasonable protection
•     Keep the controller at room temperature for at least        against harmful interference when this equipment is
      24 hours prior to installation to allow any                 operated in a commercial environment. This
      condensation that may have accumulated during               equipment generates, uses, and can radiate radio
      shipping to evaporate.                                      frequency energy and, if not installed and used in
                                                                  accordance with the instruction manual, may cause
•     Record the 12-digit Neuron® ID located on either            harmful interference to radio communications.
      end of the device (shown on the sticker below the           Operation of this equipment in a residential area
      barcode) for commissioning.                                 may cause harmful interference, in which case the
Note: The controller’s plastic enclosure has a back               users will be required to correct the interference at
plate that is separate from the front plate allowing the          their own expense.
back plates to be shipped directly to the installation site
while all the engineering is done elsewhere.                  Installation
                                                              Observe these guidelines when installing an LN Free
•     If the controller is used in a manner not specified
      by Johnson Controls, the functionality and the          Programmable PRG 600 Series Controller:
      protection provided by the controller may become        •     Transport the controller in the original container to
      impaired.                                                     minimize vibration and shock damage.

    IMPORTANT: Prevent any static electric discharge          •     Verify that all parts shipped with the controller.
    to the controller. Static discharge can damage the        •     Do not drop the controller or subject it to physical
    controller and void the warranties.                             shock.
                                                              •     Allow for proper clearance around the controller’s
                                                                    enclosure, wiring terminals, and service pin to
                                                                    provide easy access for hardware configuration
                                                                    and maintenance.

                                  LN Free Programmable PRG 600 Series Controllers Installation Instructions                1
Dimensions

                          Figure 1: LN PRG600 Series Controller Dimensions, mm (in.)

Mounting                                                    You can mount each controller on a DIN rail, in a panel,
                                                            or on a wall. The controllers are equipped with two
Observe these guidelines when mounting an LN Free
                                                            mounting holes 0.25 x 0.165 in. (6.35 x 4.191 mm).
Programmable PRG 600 Series Controller:
•   Provide for sufficient space around the controller      DIN Rail
    for cable and wire connections, easy cover              To mount the controller on a DIN rail:
    removal, and good ventilation through the               1. Ensure the DIN rail is properly mounted on the
    controller.                                                wall.
•   Ensure proper ventilation of each controller and        2. Clip the controller onto the DIN rail.
    avoid areas where corroding; deteriorating; or
    explosive vapors, fumes, or gases may be present.       Wall Mount
                                                            To mount the controller on a wall:
•   Orient each controller with the ventilation slots and
    power supply/output terminal block connector            1. Press on the side clips to separate the controller’s
    towards the top to permit proper heat dissipation.         front and back plates.
•   Do not mount the controller on surfaces prone to        2. Use the holes on the back plate to mark the wall
    vibration, such as duct work, or in areas where            location.
    electromagnetic emissions from other devices or
                                                            3. Drill the holes.
    wiring can interfere with controller communication.
                                                            4. Clean the surface and mount the controller using
                                                               the appropriate screws.

2     LN Free Programmable PRG 600 Series Controllers Installation Instructions
Wiring
            CAUTION: Risk of Electric Shock.
            Disconnect power supply before making
     !      electrical connections to avoid electric
            shock.
            MISE EN GARDE : Risque de décharge
            électrique.
            Débrancher l'alimentation avant de                         Figure 2: Power Wiring - AC
            réaliser tout raccordement électrique afin
            d'éviter tout risque de décharge                IMPORTANT: Maintain consistent polarity when
            électrique.                                     you connect the controllers and devices to the
                                                            transformer. Connect the COM terminal of each
Follow these wiring recommendations:
                                                            controller and each peripheral to the same terminal
•   Remove the front plate from the back plate to           on the secondary side of the transformer. One
    facilitate in the wiring process. Use a small flat      terminal on the secondary side of the transformer
    screwdriver to tighten the terminal connector           must be connected to the building’s ground.
    screws once the wires are inserted.
•   Keep power cables apart from other types of wiring
    to avoid ambient noise transmission to other wires
    (for example, for power, 3-wire voltage, and current
    inputs and outputs).
•   Use wires or flat cables ranging from 22 to 14 AWG
    (0.644 to 1.630 mm diameter) per pole. Power
    cables must remain between 18 to 14 AWG
    (1.024 to 1.630 mm) diameter.
•   Do not connect the universal inputs, analog/digital
                                                                       Figure 3: Power Wiring - DC
    outputs or common terminals to earth or chassis
    ground unless otherwise stated.
                                                           Input Wiring
•   Keep all wires away from high speed data               Each controller has physical connections for inputs that
    transmission cables (for example, Ethernet cable).     are software configurable from within the LN Graphical
•   Keep input and output wires in conduits, trays, or     Programming Interface (GPI) software. You can
    close to the building frame whenever possible.         configure each input in the software plug-in to ensure
                                                           proper input readings. The physical connections for
Power Wiring                                               inputs are marked as UIx.
We recommend wiring only one controller per 24 VAC
                                                           Wiring Digital Inputs
transformer. When only one transformer is available,
determine the maximum number of controllers that can       Use this input configuration to monitor digital dry
be supplied using the following method for calculating     contacts, as well as pulsed contacts.
the required power transformer capacity:
1. Add up the maximum power consumption of all
   controllers, including external loads, and multiply
   this sum by 1.3.
2. If the resulting number is higher than 100 VA, use
                                                               Figure 4: Digital Input - Digital Dry Contact
   multiple transformers.
                                                                             (N.O. and N.C.)
Use an external fuse on the 24 VAC/DC side
(secondary side) of the transformer to protect all
controllers against power link spikes (Figure 2 and

LN Free Programmable PRG 600 Series Controllers Installation Instructions                                         3
Wiring Resistive Inputs                                     Use the Figure 8 configuration for a 2-wire, 0 to 20 mA
Use this input configuration to monitor Resistance          transducer powered by an external 24 AC/DC power
Temperature Detectors (RTD); thermistors, such as           supply.
1,000 ohm RTDs to 10k ohm Type II and Type III
thermistors; and potentiometers, such as 10k ohm and
100k ohm.

     Figure 5: Resistive Input - RTD/Thermistor                      Figure 8: Current Input - 2-Wire
                        Input                                        Transducer, Externally Powered

                                                            Use the Figure 9 configuration for a 3-wire, 0 to 20 mA
                                                            transducer powered by an external 24 AC/DC power
                                                            supply.

         Figure 6: Resistive Input - 10k ohm
                Potentiometer Input

Wiring Current Inputs
Current inputs have a range of 0 to 20 mA. Set the
jumper to the 0 to 20 mA position for all current inputs.
This setting provides the required 249 ohm resistance          Figure 9: Current Input - 3-Wire Transducer,
for the controller’s current inputs. Depending on the                      Externally Powered
transducer power requirements, you may use any of
the following input configurations. Use Figure 7 for the    Use the Figure 10 configuration for a transducer
2-wire, 0 to 20 mA transducer powered by the                powered by its own power source.
controller’s internal 15 VDC power supply.

    Figure 7: Current Input - 2-Wire Transducer
            Powered by the Controller
                                                               Figure 10: Current Input - 3-Wire Transducer,
                                                                           Externally Powered

4     LN Free Programmable PRG 600 Series Controllers Installation Instructions
 Wiring Voltage Inputs                                       Connect the pulse input according to Figure 13 for a
 Voltage inputs have a range of 0 to 10 VDC or               pulse meter that can pull down a +5 VDC supply with a
 0 to 5 VDC. Connect the voltage input according to          10k ohm pull-up resistor (internal supply type).
 Figure 11 if you are using a 3-wire 0 to 10 V or 0 to 5 V
 transducer.

     Figure 11: Voltage Input - 3-Wire Transducer                 Figure 13: All Pulse Input Types - Internal
                                                                         Supply, 2-wire Pulse Meter

 Connect the voltage input according to Figure 12 if the     When you use a pulse meter that requires more than
 transducer is powered by its own power source.              5 VDC to operate, you must use a Fast Pulse Input
                                                             type (Table 1). An external power supply is required to
                                                             operate the pulse meter. You may use the controller’s
                                                             built-in power supply (Figure 14).

   Figure 12: Voltage Input - Transducer with Own
                    Power Source

 Wiring Pulse Inputs
 The input must be wired according to the requirements
                                                                 Figure 14: Fast Pulse Input Type - External
 of the connected pulse meter (for example, fast pulse
                                                               Supply, 2-wire Pulse Meter, Built-in Power Used
 or slow pulse and internal or external supply type).
 Table 1 outlines the PRG 600 Series controller pulse
 input support.
 Table 1: Pulse Input Support
  Controller                   Pulse Inputs
                  50 Hz: 10 ms        1 Hz: 500 ms
                  Minimum ON/         Minimum ON/
                  OFF (Fast           OFF (Slow Pulse)
                  Pulse)
  LN-PRG600-2         UI1 to UI4          UI5 to UI16           Figure 15: Fast Pulse Input Type - External
                                                                        Supply, 2-wire Pulse Meter
  LN-PRG610-2         UI1 to UI4          UI5 to UI16
                                                             Output Wiring
 Configure the Pulse Input Types in the software to          Each controller has physical connections for universal
 verify the pulse meter is powered correctly.                outputs. These outputs are all software configurable.
                                                             Table 2 shows the controller outputs.
                                                             Table 2: Controller Outputs
                                                              Controller      Universal    Jumper
                                                                              Outputs      0–10 VDC/0–20 mA
                                                              LN-PRG600-2          12                 Yes
                                                              LN-PRG610-2          12                 Yes

LN Free Programmable PRG 600 Series Controllers Installation Instructions                                         5
Note: Before you connect output equipment to the              Voltage Outputs
controller, refer to the installation instructions from the   Connect the 0 to 10 VDC as shown in Figure 17.
equipment manufacturer.
Output Wiring Recommendations
Output wiring recommendations include:
•   For a wire length less than 75 feet (23 m) long, use
    either a shielded or unshielded 18 AWG wire.
•   For a wire length up to 200 feet (61 m) long, use a
    shielded 18 AWG wire.                                          Figure 18: Voltage 0 to 10 VDC Universal
•   The shield of the wire should be grounded on the                                Output
    controller side and the shield length should be kept
    as short as possible.                                     If you are controlling an analog actuator, connect the
                                                              0 to 10 VDC output, along with an external 24 VAC
Wiring Universal Outputs (UOx)                                power source, to the analog actuator (Figure 19).
You can configure universal outputs to provide either a
linear signal ranging from 0 to 10 VDC or a 0 to 20 mA
signal or a discrete signal of 0 or 12 VDC. You can use
the discrete signal to generate a Pulse Wave
Modulation (PWM) or a simple two-state signal. The
outputs are protected by an auto-reset fuse.
Discrete Outputs
If a 12 VDC relay is being controlled, connect it to a
universal output according to Figure 16.
                                                                   Figure 19: Voltage 0 to 10 VDC Universal
                                                                           Output - Analog Actuator

                                                              Communications Wiring
                                                              The recommended cable type for LONWORKS®
                                                              communications is 22 AWG (0.65 mm), twisted pair,
                                                              unshielded wire. The LONWORKS communication wire
    Figure 16: Discrete 0 or 12 VDC Universal                 is polarity insensitive and when laid out in a bus, star,
                  Output - Relay                              or free topology. For loop topology, take special care to
                                                              maintain the polarity when connecting the LONWORKS
Current Outputs
                                                              network to avoid a short circuit.
The 0 to 20 mA signal is configurable by jumper
(Figure 17).                                                  Note: We recommend you use the bus topology
                                                              network configuration for all LONWORKS communication
                                                              wiring. This configuration allows you to troubleshoot
                                                              the network easily.

    Figure 17: 0 to 20 mA Universal Output and
               Jumper Configuration

6      LN Free Programmable PRG 600 Series Controllers Installation Instructions
Connect both wires to the LON1 or LON2 terminals of        Regardless of the mounting method, the wireless
the controller. When you insert multiple wires into the    receiver should be 16 inches (41 cm) or more away
terminals, ensure you properly twist the wires together    from the controller or any other network cables.
prior to inserting them into the terminal connectors.
                                                           Connecting the Wireless Receiver
           LON Network              Controller 1           Connect the wireless receiver to the controller with the
                                     LON1                  included telephone cable (4P4C modular connectors).
                                     LON2                  Locate the telephone socket inside the device
                                                           (Figure 21).

                                    Controller 2
                                     LON1
                                     LON2

          Figure 20: Communications Wiring

For more information and detailed explanations on
network topology and wire length restrictions, refer to
the LONWORKS LN-Series Network Communication
and Interface Guide (LIT-12011253) or Echleon
Corporation’s Junction Box and Wiring Guideline for
Twisted Pair LONWORKS® Networks.

    IMPORTANT: Use the proper network terminators
    for the network topology. Failure to use the correct
    network terminators may result in communication
    errors between controllers. Do not use multiple                       Figure 21: Telephone Socket
    gauges of cable on the same communication bus.                                  Location
Two network terminators are required for the bus           Connecting to the Controller Wireless Port
topology network configuration. Place one network
                                                           The wireless-option controllers have a wireless port
terminator at each end of the bus topology channel.
                                                           where you connect the telephone cable. Locate the
One network terminator is required for the free            wireless port on the bottom of the controller.
topology network configuration. You can put the
                                                           Maintenance
network terminator anywhere on the channel.
Wireless Installation                                                  CAUTION: Risk of Electric Shock.
                                                                       Disconnect the power supply before
The LN Free Programmable PRG 600 Series
controllers can receive input signals from wireless
                                                                !      making any electrical connections to
devices when connected to a wireless receiver and                      avoid electric shock.
programmed with LN GPI software. Compatible                            MISE EN GARDE : Risque de décharge
wireless devices include temperature sensors, duct                     électrique.
sensors, window/door contacts, and light switches.                     Débrancher l'alimentation avant de
For information on selecting mounting locations for the                réaliser tout raccordement électrique afin
LN Series wireless controllers, refer to the LN Series                 d'éviter tout risque de décharge
Wireless Solution Guide Technical Bulletin                             électrique.
(LIT-12011628).
                                                           Each controller requires minimal maintenance, but it is
Mounting the Wireless Receiver                             important to:
You have three mounting options: on a wall or ceiling      •   clean the outside of the front plate an/or the inside
with double-sided tape, on a wall or ceiling with              of the back plate with a dry cloth.
mounting screws, or on a metal enclosure using a
1/2 inch National Pipe Thread (NPT) hub.                   •   verify the tension of all wires and cables each time
                                                               you service the controller.

7        LN Free Programmable PRG 600 Series Controllers Installation Instructions
Disposal
The Waste Electrical and Electronic Equipment
(WEEE) Directive sets regulations for the recycling and
disposal of products. The WEEE 2002/96/EG Directive
applies to stand-alone products that can function on
their own and are not a part of another system or piece
of equipment. For this reason, Johnson Controls®
products are exempt from the WEEE Directive.
Nevertheless, they are marked with the WEEE symbol,
indicating the devices are not disposed with municipal
waste.
Dispose of products at the end of their useful life
according to local regulations and the WEEE Directive.
Troubleshooting
Table 3 describes some troubleshooting scenarios.
Table 3: Troubleshooting (Part 1 of 3)
 Problem                                   Possible Solution
 Controller is powered but does not turn on.
 Fuse Is Blown                             Disconnect power from the controller and check the fuse integrity.
                                           Reconnect power.
 Power Supply Polarity                     Verify that consistent polarity is maintained between all controllers and
                                           the transformer. Ensure that the COM terminal of each controller is
                                           connected to the same terminal on the secondary side of the
                                           transformer. See Figure 2 and Figure 3.
 Controller cannot communicate on the LONWORKS network.
 Absent or Incorrect Supply Voltage        1. Check power supply voltage between 24 VAC/DC ±15% and COM
                                              pins, and ensure that it is between acceptable limits.
                                           2. Check for tripped fuse or circuit breaker.
 Overloaded Power Transformer              Verify the transformer is powerful enough to supply all controllers.
 Network Not Wired Properly                Check that the wire connections are correct.
 Absent or Incorrect Network Termination   Check the network terminations.

8     LN Free Programmable PRG 600 Series Controllers Installation Instructions
Table 3: Troubleshooting (Part 2 of 3)
 Problem                                    Possible Solution
 Controller communicates well over a short network but does not communicate on large network.
 Network Length                             Check that the total wire length does not exceed the specifications of the
                                            Junction Box and Wiring Guideline for Twisted Pair LONWORKS
                                            Networks.
 Wire Type                                  Check that the wire type agrees with the specification of the LONWORKS
                                            LN-Series Network Communications and Interface Guide (LIT-1201235)
                                            or Junction Box and Wiring Guideline for Twisted Pair LONWORKS
                                            Networks.
 Network Wiring Problem                     Check that the wire connections are correct.
 Absent or Incorrect Network Termination    Check the termination(s). Incorrect or broken termination(s) make the
                                            communication integrity dependent upon a controller's position on the
                                            network.
 Extra Capacitance                          Ensure no extra capacitance is connected to the network other than the
                                            standard FTT circuit, and a maximum of a 3 meter stub (in bus topology).
 Number of Devices on Network Segment       The number of controllers on a channel should never exceed 64. Use a
 Exceeded                                   router or a repeater in accordance with LONWORKS LN-Series Network
                                            Communications and Interface Guide (LIT-1201235) or Junction Box and
                                            Wiring Guideline for Twisted Pair LONWORKS Networks.
 Network Traffic                            Query node statistic to check errors.
                                            Use a LONWORKS protocol analyzer to check network traffic.
 Hardware input is not reading the correct value.
 Input Wiring Problem                       Check that the wiring is correct according to this manual and according
                                            to the peripheral device's manufacturer.
 Open Circuit or Short Circuit              Using a voltmeter, check the voltage on the input terminal. A short circuit
                                            has a 0 V value and an open circuit has a 5 V value.
 Configuration Problem                      Check the configuration of the input using the controller configuration
                                            plug-in or wizard. Refer to the online help for more information.
 Over Voltage or Over Current at an Input   An over voltage or over current at one input can affect the reading of
                                            other inputs. Observe the allowed voltage/current range limits for all
                                            inputs.
 Hardware output is not operating correctly.
 Output Wiring Problem                      Check that the wiring is correct according to this manual and according
                                            to the peripheral device's manufacturer.
 Configuration Problem                      Using the controller configuration wizard (LN-GPI), check the
                                            configuration of the input. Refer to the controller's user guide for more
                                            information.
 0 to 10 V Output, 24 VAC Powered           Check the polarity of the 24 VAC power supply connected to the actuator
 Actuator is Not Moving                     while connected to the controller. Reverse the 24 VAC wire if necessary.
 Wireless devices not working correctly.
 Device not associated to controller        Using the device configuration wizard, check the configuration of the
                                            input.
 Power discharge                            Recharge the device with light (if solar powered) or replace the battery.
                                            Ensure sufficient light intensity (200lx for 4 hours per day)

LN Free Programmable PRG 600 Series Controllers Installation Instructions                                                 9
Table 3: Troubleshooting (Part 3 of 3)
 Problem                                     Possible Solution
 Device too far from the Wireless Receiver   Reposition the device to be within the range of the Wireless Receiver.
                                             For information on typical transmission ranges, refer to the LN Series
                                             Wireless Solution Technical Bulletin (LIT-12011628).
 Configuration Problem                       Check the configuration of the input using the device configuration
                                             plug-in or wizard.
 Rx/Tx LEDs
 Rx LED not Blinking                         Data is not being received from the LONWORKS data bus.
 Tx LED not Blinking                         Data is not being transmitted onto the LONWORKS data bus.

Service Light LED Operation
Table 4: Service LED Operation Guide
 Operation                                             Service
 Normal Operation
 Fast Blink Continuous                                 Initialization: The device is starting up.
                                                       Firmware upgrade in is progress and the controller operation is
                                                       temporarily unavailable. The new firmware is being loaded into
                                                       memory and the process takes a few seconds. Do not interrupt power
 (150 ms On, 150 ms Off, Continuous)                   to the device during this time.
 The Status LED is Always OFF                          The controller is operating normally.
 LED Blink Patterns - Repeat Every 2 Seconds (Highest Priority to Lowest Priority)
 Long Blink Continuous                                 The controller is not configured.
                                                       Appropriate action: Commission the controller.

 (1s On, 1s Off, Continuous)
 Long Long Long Blink                                  The controller is offline.
                                                       Appropriate action: Set the controller online.

 (800 ms On, 300 ms Off, 800 ms On, 300 ms Off,
 800 ms Off)
 Long Short Short Short Blink                          The controller is in bypass mode.
                                                       Appropriate Action: Set the controller online.
 Short Short Long Blink                                Poor-quality power; the device has browned-out: The voltage at the 24
                                                       VAC and 24 VCOM terminals has gone below the device’s acceptable
                                                       limit during powerup.
 Fast Blink 12x                                        Wink: The wink function identifies a device.

Repair Information
If the LN Series Controller fails to operate within its
specifications, replace the unit. For a replacement
controller, contact the nearest Johnson Controls®
representative.

10    LN Free Programmable PRG 600 Series Controllers Installation Instructions
Technical Specifications
LN-PRG6x0-2 (Part 1 of 2)
 Product Code                          LN-PRG600-2 and LN-PRG610-2
 Power Requirement                     Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
                                       Protection: 3.0A user-replaceable fuse
                                       Power Consumption: 22 VA typical plus all output loads
                                       Maximum Consumption: 65 VA
 Ambient Storage Conditions            Ambient Operating Temperature: 0 to 50°C, (32 to 122°F)
                                       Ambient Storage Temperature: -20 to 50°C, (-4 to 122°F)
                                       Ambient Relative Humidity: 0 to 90% noncondensing
 General                               Processor: STM32 (ARM Cortex™ M3) MCU, 32 bit
                                       Processor Speed: 72 MHz
                                       Memory: 1 MB Nonvolatile Flash (applications), 2 MB Nonvolatile Flash (storage)
                                                96 kB RAM
                                       Media Channel: TP/FT-10; 78 Kbps
                                       Communication: LonTalk® protocol
                                       Status Indicator: Green LED - power status and LAN TX, Orange LED - service
                                       and LAN RX
                                       Communication Jack: TP/FT-10; 78 Kbps, 1/8 in (3.5 mm)
                                       LONMARK® Interoperability: Version 3.4
                                       Device Class: Static Programmable Device
                                       LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1,
                                       Output Objects: Open - Loop Sensor #3, Real Time Clock: Real Time Keeper
                                       #3300, Scheduler: Scheduler #20020, Calendar: Calendar #20030,
                                       Programmable Device: Static Programmable Device #410
 Enclosure                             Material: FR/ABS
                                       Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
                                       Shipping Weight: 1.17 lb (0.53 kg)
 Inputs                                Input Types: universal software configurable
                                          Voltage: 0 to 10 VDC (40k ohm input impedance)
                                                    0 to 5 VDC (high input impedance)
                                          Current: 0 to 20 mA with 249 ohmjumper configurable internal resistor,
                                          Digital: dry contact
                                         Pulse: UI1 to UI4; 50 Hz maximum; Minimum 10 ms On/10 ms Off, dry contact
                                                   UI5 to UI6: 1 Hz maximum; Minimum 500 ms On/500 ms Off, dry contact
                                       Resistor Support: 0 to 350k ohms. All thermistor types that operate within this
                                          range are supported. The following temperature sensors are pre-configured:
                                            Thermistor:
                                               Type 2 and Type 3 10k ohm (10k ohm at 25°C [77°F])
                                            Platinum:
                                               PT1000 1k ohm (1k ohm at 0°C [32°F])
                                            Nickel:
                                               RTD Ni1000 (1k ohm at 0°C [32°F])
                                               RTD Ni1000 (1k ohm at 21°C [69.8°F])
                                            Input Resolution: 16-bit analog/digital converter
                                        Power Supply Output: 15VDC; maximum 320 mA (16 inputs x 20 mA each)

LN Free Programmable PRG 600 Series Controllers Installation Instructions                                           11
LN-PRG6x0-2 (Part 2 of 2)
 Outputs                                         Universal: 0-10 VDC linear, digital 0 to12 VDC (on/off), PWM, floating, or
                                                   0 to 20 mA (jumper configurable); software configurable. Built-in snubbing diode
                                                   to protect against back EMF, for example when used with a 12 VDC relay.
                                                   PWM control: adjustable period from 2 seconds to 15 minutes
                                                   Floating control:
                                                          minimum plus on/off: 500 ms
                                                       adjustable drive time period
                                                   Hands-off-Auto (HOA) Switch (when equipped): hand position potentiometer
                                                      range: 0 to 12.5 VDC
                                                         60 mA maximum at 12 VDC (60°C; 140°F)
                                                 Load Resistance: minimum resistance 200 ohms for 0 to 10 VDC and
                                                   0 to 12.5 VDC, maximum 500 ohm for 0 to 20 mA output
                                                 Auto reset fuse
                                                       60 mA at 60°C (140°F)
                                                     100 mA at 20°C (68°F)
                                                 Output Resolution: 10-bit digital/does analog converter
 Wireless Receiver1                              Communication: EnOcean® Wireless standard
                                                 Number of Wireless Inputs: 282
                                                 Supported Wireless Receivers: LN-WMOD315-0 and LN-WMOD868-0
                                                 Telephone Cord Cable: Connector: 4P4C modular jack, Length: 3 ft (1 m)
 Enclosure                                       Material: UL94-5VA
 Electromagnetic Compatibility                   CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial,
                                                             and light-industrial environments.
                                                 CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial,
                                                              and light-industrial environments.
 Compliance                         United       UL Listed, File E107041, CCN PAZX,
                                    States       Under UL 916, Energy Management Equipment
                                                 FCC Compliant to CFR 47, Part 15, Subpart B, Class A
                                    Canada       UL Listed, File E107041, CCN PAZX7,
                                                 Under CAN/CSA C22.2 No. 205, Signal Equipment
                                                 Industry Canada, ICES-003
                                    Europe       CE Mark – Johnson Controls, Inc., declares that the products are in compliance
                                                 with the essential requirements and other relevant provisions of the
                                                 EMC Directive 2004/108/EC.

1.   Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more
     than one wireless input from the controller.
2.   Some wireless modules may use more than one wireless input from the controller.

 The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
 specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from
 misapplication or misuse of its products.

                                                                                                                 Building Efficiency
                                                                                        507 E. Michigan Street, Milwaukee, WI 53202
                                            Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                   All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.