LN Free Programmable PRG 600 Series Controllers
Installation Instructions
LN-PRG600-2, LN-PRG610-2 Code No. LIT-12011691
Issued July 17, 2014
Applications North American Emissions Compliance
The LN Free Programmable PRG 600 Series Canada
Controllers are microprocessor-based free
programmable controllers designed to control various The term IC before the certification/registration
building automation systems, such as multi-zone air number only signifies that the Industry Canada
handing units and central plant applications. The technical specifications were met.
PRG 600 Series controllers use the LonTalk®
Industry Canada Statement
communication protocol.
Le terme « IC » précédant le numéro d'accréditation/
The PRG 600 Series controllers support up to 2 Input/
inscription signifie simplement que le produit est
Output extension modules that operate off of a
conforme aux spécifications techniques d'Industry
separate sub-bus, providing the PRG 600 Series
Canada.
controller with up to 40 universal inputs and
36 universal outputs.
United States
Follow these recommendations for proper installation
and subsequent operation of each controller: This equipment has been tested and found to
comply with the limits for a Class A digital device
• Inspect the controller for shipping damages. Do not pursuant to Part 15 of the FCC Rules. These limits
install damaged controllers. are designed to provide reasonable protection
• Keep the controller at room temperature for at least against harmful interference when this equipment is
24 hours prior to installation to allow any operated in a commercial environment. This
condensation that may have accumulated during equipment generates, uses, and can radiate radio
shipping to evaporate. frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
• Record the 12-digit Neuron® ID located on either harmful interference to radio communications.
end of the device (shown on the sticker below the Operation of this equipment in a residential area
barcode) for commissioning. may cause harmful interference, in which case the
Note: The controller’s plastic enclosure has a back users will be required to correct the interference at
plate that is separate from the front plate allowing the their own expense.
back plates to be shipped directly to the installation site
while all the engineering is done elsewhere. Installation
Observe these guidelines when installing an LN Free
• If the controller is used in a manner not specified
by Johnson Controls, the functionality and the Programmable PRG 600 Series Controller:
protection provided by the controller may become • Transport the controller in the original container to
impaired. minimize vibration and shock damage.
IMPORTANT: Prevent any static electric discharge • Verify that all parts shipped with the controller.
to the controller. Static discharge can damage the • Do not drop the controller or subject it to physical
controller and void the warranties. shock.
• Allow for proper clearance around the controller’s
enclosure, wiring terminals, and service pin to
provide easy access for hardware configuration
and maintenance.
LN Free Programmable PRG 600 Series Controllers Installation Instructions 1
Dimensions
Figure 1: LN PRG600 Series Controller Dimensions, mm (in.)
Mounting You can mount each controller on a DIN rail, in a panel,
or on a wall. The controllers are equipped with two
Observe these guidelines when mounting an LN Free
mounting holes 0.25 x 0.165 in. (6.35 x 4.191 mm).
Programmable PRG 600 Series Controller:
• Provide for sufficient space around the controller DIN Rail
for cable and wire connections, easy cover To mount the controller on a DIN rail:
removal, and good ventilation through the 1. Ensure the DIN rail is properly mounted on the
controller. wall.
• Ensure proper ventilation of each controller and 2. Clip the controller onto the DIN rail.
avoid areas where corroding; deteriorating; or
explosive vapors, fumes, or gases may be present. Wall Mount
To mount the controller on a wall:
• Orient each controller with the ventilation slots and
power supply/output terminal block connector 1. Press on the side clips to separate the controller’s
towards the top to permit proper heat dissipation. front and back plates.
• Do not mount the controller on surfaces prone to 2. Use the holes on the back plate to mark the wall
vibration, such as duct work, or in areas where location.
electromagnetic emissions from other devices or
3. Drill the holes.
wiring can interfere with controller communication.
4. Clean the surface and mount the controller using
the appropriate screws.
2 LN Free Programmable PRG 600 Series Controllers Installation Instructions
Wiring
CAUTION: Risk of Electric Shock.
Disconnect power supply before making
! electrical connections to avoid electric
shock.
MISE EN GARDE : Risque de décharge
électrique.
Débrancher l'alimentation avant de Figure 2: Power Wiring - AC
réaliser tout raccordement électrique afin
d'éviter tout risque de décharge IMPORTANT: Maintain consistent polarity when
électrique. you connect the controllers and devices to the
transformer. Connect the COM terminal of each
Follow these wiring recommendations:
controller and each peripheral to the same terminal
• Remove the front plate from the back plate to on the secondary side of the transformer. One
facilitate in the wiring process. Use a small flat terminal on the secondary side of the transformer
screwdriver to tighten the terminal connector must be connected to the building’s ground.
screws once the wires are inserted.
• Keep power cables apart from other types of wiring
to avoid ambient noise transmission to other wires
(for example, for power, 3-wire voltage, and current
inputs and outputs).
• Use wires or flat cables ranging from 22 to 14 AWG
(0.644 to 1.630 mm diameter) per pole. Power
cables must remain between 18 to 14 AWG
(1.024 to 1.630 mm) diameter.
• Do not connect the universal inputs, analog/digital
Figure 3: Power Wiring - DC
outputs or common terminals to earth or chassis
ground unless otherwise stated.
Input Wiring
• Keep all wires away from high speed data Each controller has physical connections for inputs that
transmission cables (for example, Ethernet cable). are software configurable from within the LN Graphical
• Keep input and output wires in conduits, trays, or Programming Interface (GPI) software. You can
close to the building frame whenever possible. configure each input in the software plug-in to ensure
proper input readings. The physical connections for
Power Wiring inputs are marked as UIx.
We recommend wiring only one controller per 24 VAC
Wiring Digital Inputs
transformer. When only one transformer is available,
determine the maximum number of controllers that can Use this input configuration to monitor digital dry
be supplied using the following method for calculating contacts, as well as pulsed contacts.
the required power transformer capacity:
1. Add up the maximum power consumption of all
controllers, including external loads, and multiply
this sum by 1.3.
2. If the resulting number is higher than 100 VA, use
Figure 4: Digital Input - Digital Dry Contact
multiple transformers.
(N.O. and N.C.)
Use an external fuse on the 24 VAC/DC side
(secondary side) of the transformer to protect all
controllers against power link spikes (Figure 2 and
LN Free Programmable PRG 600 Series Controllers Installation Instructions 3
Wiring Resistive Inputs Use the Figure 8 configuration for a 2-wire, 0 to 20 mA
Use this input configuration to monitor Resistance transducer powered by an external 24 AC/DC power
Temperature Detectors (RTD); thermistors, such as supply.
1,000 ohm RTDs to 10k ohm Type II and Type III
thermistors; and potentiometers, such as 10k ohm and
100k ohm.
Figure 5: Resistive Input - RTD/Thermistor Figure 8: Current Input - 2-Wire
Input Transducer, Externally Powered
Use the Figure 9 configuration for a 3-wire, 0 to 20 mA
transducer powered by an external 24 AC/DC power
supply.
Figure 6: Resistive Input - 10k ohm
Potentiometer Input
Wiring Current Inputs
Current inputs have a range of 0 to 20 mA. Set the
jumper to the 0 to 20 mA position for all current inputs.
This setting provides the required 249 ohm resistance Figure 9: Current Input - 3-Wire Transducer,
for the controller’s current inputs. Depending on the Externally Powered
transducer power requirements, you may use any of
the following input configurations. Use Figure 7 for the Use the Figure 10 configuration for a transducer
2-wire, 0 to 20 mA transducer powered by the powered by its own power source.
controller’s internal 15 VDC power supply.
Figure 7: Current Input - 2-Wire Transducer
Powered by the Controller
Figure 10: Current Input - 3-Wire Transducer,
Externally Powered
4 LN Free Programmable PRG 600 Series Controllers Installation Instructions
Wiring Voltage Inputs Connect the pulse input according to Figure 13 for a
Voltage inputs have a range of 0 to 10 VDC or pulse meter that can pull down a +5 VDC supply with a
0 to 5 VDC. Connect the voltage input according to 10k ohm pull-up resistor (internal supply type).
Figure 11 if you are using a 3-wire 0 to 10 V or 0 to 5 V
transducer.
Figure 11: Voltage Input - 3-Wire Transducer Figure 13: All Pulse Input Types - Internal
Supply, 2-wire Pulse Meter
Connect the voltage input according to Figure 12 if the When you use a pulse meter that requires more than
transducer is powered by its own power source. 5 VDC to operate, you must use a Fast Pulse Input
type (Table 1). An external power supply is required to
operate the pulse meter. You may use the controller’s
built-in power supply (Figure 14).
Figure 12: Voltage Input - Transducer with Own
Power Source
Wiring Pulse Inputs
The input must be wired according to the requirements
Figure 14: Fast Pulse Input Type - External
of the connected pulse meter (for example, fast pulse
Supply, 2-wire Pulse Meter, Built-in Power Used
or slow pulse and internal or external supply type).
Table 1 outlines the PRG 600 Series controller pulse
input support.
Table 1: Pulse Input Support
Controller Pulse Inputs
50 Hz: 10 ms 1 Hz: 500 ms
Minimum ON/ Minimum ON/
OFF (Fast OFF (Slow Pulse)
Pulse)
LN-PRG600-2 UI1 to UI4 UI5 to UI16 Figure 15: Fast Pulse Input Type - External
Supply, 2-wire Pulse Meter
LN-PRG610-2 UI1 to UI4 UI5 to UI16
Output Wiring
Configure the Pulse Input Types in the software to Each controller has physical connections for universal
verify the pulse meter is powered correctly. outputs. These outputs are all software configurable.
Table 2 shows the controller outputs.
Table 2: Controller Outputs
Controller Universal Jumper
Outputs 0–10 VDC/0–20 mA
LN-PRG600-2 12 Yes
LN-PRG610-2 12 Yes
LN Free Programmable PRG 600 Series Controllers Installation Instructions 5
Note: Before you connect output equipment to the Voltage Outputs
controller, refer to the installation instructions from the Connect the 0 to 10 VDC as shown in Figure 17.
equipment manufacturer.
Output Wiring Recommendations
Output wiring recommendations include:
• For a wire length less than 75 feet (23 m) long, use
either a shielded or unshielded 18 AWG wire.
• For a wire length up to 200 feet (61 m) long, use a
shielded 18 AWG wire. Figure 18: Voltage 0 to 10 VDC Universal
• The shield of the wire should be grounded on the Output
controller side and the shield length should be kept
as short as possible. If you are controlling an analog actuator, connect the
0 to 10 VDC output, along with an external 24 VAC
Wiring Universal Outputs (UOx) power source, to the analog actuator (Figure 19).
You can configure universal outputs to provide either a
linear signal ranging from 0 to 10 VDC or a 0 to 20 mA
signal or a discrete signal of 0 or 12 VDC. You can use
the discrete signal to generate a Pulse Wave
Modulation (PWM) or a simple two-state signal. The
outputs are protected by an auto-reset fuse.
Discrete Outputs
If a 12 VDC relay is being controlled, connect it to a
universal output according to Figure 16.
Figure 19: Voltage 0 to 10 VDC Universal
Output - Analog Actuator
Communications Wiring
The recommended cable type for LONWORKS®
communications is 22 AWG (0.65 mm), twisted pair,
unshielded wire. The LONWORKS communication wire
Figure 16: Discrete 0 or 12 VDC Universal is polarity insensitive and when laid out in a bus, star,
Output - Relay or free topology. For loop topology, take special care to
maintain the polarity when connecting the LONWORKS
Current Outputs
network to avoid a short circuit.
The 0 to 20 mA signal is configurable by jumper
(Figure 17). Note: We recommend you use the bus topology
network configuration for all LONWORKS communication
wiring. This configuration allows you to troubleshoot
the network easily.
Figure 17: 0 to 20 mA Universal Output and
Jumper Configuration
6 LN Free Programmable PRG 600 Series Controllers Installation Instructions
Connect both wires to the LON1 or LON2 terminals of Regardless of the mounting method, the wireless
the controller. When you insert multiple wires into the receiver should be 16 inches (41 cm) or more away
terminals, ensure you properly twist the wires together from the controller or any other network cables.
prior to inserting them into the terminal connectors.
Connecting the Wireless Receiver
LON Network Controller 1 Connect the wireless receiver to the controller with the
LON1 included telephone cable (4P4C modular connectors).
LON2 Locate the telephone socket inside the device
(Figure 21).
Controller 2
LON1
LON2
Figure 20: Communications Wiring
For more information and detailed explanations on
network topology and wire length restrictions, refer to
the LONWORKS LN-Series Network Communication
and Interface Guide (LIT-12011253) or Echleon
Corporation’s Junction Box and Wiring Guideline for
Twisted Pair LONWORKS® Networks.
IMPORTANT: Use the proper network terminators
for the network topology. Failure to use the correct
network terminators may result in communication
errors between controllers. Do not use multiple Figure 21: Telephone Socket
gauges of cable on the same communication bus. Location
Two network terminators are required for the bus Connecting to the Controller Wireless Port
topology network configuration. Place one network
The wireless-option controllers have a wireless port
terminator at each end of the bus topology channel.
where you connect the telephone cable. Locate the
One network terminator is required for the free wireless port on the bottom of the controller.
topology network configuration. You can put the
Maintenance
network terminator anywhere on the channel.
Wireless Installation CAUTION: Risk of Electric Shock.
Disconnect the power supply before
The LN Free Programmable PRG 600 Series
controllers can receive input signals from wireless
! making any electrical connections to
devices when connected to a wireless receiver and avoid electric shock.
programmed with LN GPI software. Compatible MISE EN GARDE : Risque de décharge
wireless devices include temperature sensors, duct électrique.
sensors, window/door contacts, and light switches. Débrancher l'alimentation avant de
For information on selecting mounting locations for the réaliser tout raccordement électrique afin
LN Series wireless controllers, refer to the LN Series d'éviter tout risque de décharge
Wireless Solution Guide Technical Bulletin électrique.
(LIT-12011628).
Each controller requires minimal maintenance, but it is
Mounting the Wireless Receiver important to:
You have three mounting options: on a wall or ceiling • clean the outside of the front plate an/or the inside
with double-sided tape, on a wall or ceiling with of the back plate with a dry cloth.
mounting screws, or on a metal enclosure using a
1/2 inch National Pipe Thread (NPT) hub. • verify the tension of all wires and cables each time
you service the controller.
7 LN Free Programmable PRG 600 Series Controllers Installation Instructions
Disposal
The Waste Electrical and Electronic Equipment
(WEEE) Directive sets regulations for the recycling and
disposal of products. The WEEE 2002/96/EG Directive
applies to stand-alone products that can function on
their own and are not a part of another system or piece
of equipment. For this reason, Johnson Controls®
products are exempt from the WEEE Directive.
Nevertheless, they are marked with the WEEE symbol,
indicating the devices are not disposed with municipal
waste.
Dispose of products at the end of their useful life
according to local regulations and the WEEE Directive.
Troubleshooting
Table 3 describes some troubleshooting scenarios.
Table 3: Troubleshooting (Part 1 of 3)
Problem Possible Solution
Controller is powered but does not turn on.
Fuse Is Blown Disconnect power from the controller and check the fuse integrity.
Reconnect power.
Power Supply Polarity Verify that consistent polarity is maintained between all controllers and
the transformer. Ensure that the COM terminal of each controller is
connected to the same terminal on the secondary side of the
transformer. See Figure 2 and Figure 3.
Controller cannot communicate on the LONWORKS network.
Absent or Incorrect Supply Voltage 1. Check power supply voltage between 24 VAC/DC ±15% and COM
pins, and ensure that it is between acceptable limits.
2. Check for tripped fuse or circuit breaker.
Overloaded Power Transformer Verify the transformer is powerful enough to supply all controllers.
Network Not Wired Properly Check that the wire connections are correct.
Absent or Incorrect Network Termination Check the network terminations.
8 LN Free Programmable PRG 600 Series Controllers Installation Instructions
Table 3: Troubleshooting (Part 2 of 3)
Problem Possible Solution
Controller communicates well over a short network but does not communicate on large network.
Network Length Check that the total wire length does not exceed the specifications of the
Junction Box and Wiring Guideline for Twisted Pair LONWORKS
Networks.
Wire Type Check that the wire type agrees with the specification of the LONWORKS
LN-Series Network Communications and Interface Guide (LIT-1201235)
or Junction Box and Wiring Guideline for Twisted Pair LONWORKS
Networks.
Network Wiring Problem Check that the wire connections are correct.
Absent or Incorrect Network Termination Check the termination(s). Incorrect or broken termination(s) make the
communication integrity dependent upon a controller's position on the
network.
Extra Capacitance Ensure no extra capacitance is connected to the network other than the
standard FTT circuit, and a maximum of a 3 meter stub (in bus topology).
Number of Devices on Network Segment The number of controllers on a channel should never exceed 64. Use a
Exceeded router or a repeater in accordance with LONWORKS LN-Series Network
Communications and Interface Guide (LIT-1201235) or Junction Box and
Wiring Guideline for Twisted Pair LONWORKS Networks.
Network Traffic Query node statistic to check errors.
Use a LONWORKS protocol analyzer to check network traffic.
Hardware input is not reading the correct value.
Input Wiring Problem Check that the wiring is correct according to this manual and according
to the peripheral device's manufacturer.
Open Circuit or Short Circuit Using a voltmeter, check the voltage on the input terminal. A short circuit
has a 0 V value and an open circuit has a 5 V value.
Configuration Problem Check the configuration of the input using the controller configuration
plug-in or wizard. Refer to the online help for more information.
Over Voltage or Over Current at an Input An over voltage or over current at one input can affect the reading of
other inputs. Observe the allowed voltage/current range limits for all
inputs.
Hardware output is not operating correctly.
Output Wiring Problem Check that the wiring is correct according to this manual and according
to the peripheral device's manufacturer.
Configuration Problem Using the controller configuration wizard (LN-GPI), check the
configuration of the input. Refer to the controller's user guide for more
information.
0 to 10 V Output, 24 VAC Powered Check the polarity of the 24 VAC power supply connected to the actuator
Actuator is Not Moving while connected to the controller. Reverse the 24 VAC wire if necessary.
Wireless devices not working correctly.
Device not associated to controller Using the device configuration wizard, check the configuration of the
input.
Power discharge Recharge the device with light (if solar powered) or replace the battery.
Ensure sufficient light intensity (200lx for 4 hours per day)
LN Free Programmable PRG 600 Series Controllers Installation Instructions 9
Table 3: Troubleshooting (Part 3 of 3)
Problem Possible Solution
Device too far from the Wireless Receiver Reposition the device to be within the range of the Wireless Receiver.
For information on typical transmission ranges, refer to the LN Series
Wireless Solution Technical Bulletin (LIT-12011628).
Configuration Problem Check the configuration of the input using the device configuration
plug-in or wizard.
Rx/Tx LEDs
Rx LED not Blinking Data is not being received from the LONWORKS data bus.
Tx LED not Blinking Data is not being transmitted onto the LONWORKS data bus.
Service Light LED Operation
Table 4: Service LED Operation Guide
Operation Service
Normal Operation
Fast Blink Continuous Initialization: The device is starting up.
Firmware upgrade in is progress and the controller operation is
temporarily unavailable. The new firmware is being loaded into
memory and the process takes a few seconds. Do not interrupt power
(150 ms On, 150 ms Off, Continuous) to the device during this time.
The Status LED is Always OFF The controller is operating normally.
LED Blink Patterns - Repeat Every 2 Seconds (Highest Priority to Lowest Priority)
Long Blink Continuous The controller is not configured.
Appropriate action: Commission the controller.
(1s On, 1s Off, Continuous)
Long Long Long Blink The controller is offline.
Appropriate action: Set the controller online.
(800 ms On, 300 ms Off, 800 ms On, 300 ms Off,
800 ms Off)
Long Short Short Short Blink The controller is in bypass mode.
Appropriate Action: Set the controller online.
Short Short Long Blink Poor-quality power; the device has browned-out: The voltage at the 24
VAC and 24 VCOM terminals has gone below the device’s acceptable
limit during powerup.
Fast Blink 12x Wink: The wink function identifies a device.
Repair Information
If the LN Series Controller fails to operate within its
specifications, replace the unit. For a replacement
controller, contact the nearest Johnson Controls®
representative.
10 LN Free Programmable PRG 600 Series Controllers Installation Instructions
Technical Specifications
LN-PRG6x0-2 (Part 1 of 2)
Product Code LN-PRG600-2 and LN-PRG610-2
Power Requirement Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
Protection: 3.0A user-replaceable fuse
Power Consumption: 22 VA typical plus all output loads
Maximum Consumption: 65 VA
Ambient Storage Conditions Ambient Operating Temperature: 0 to 50°C, (32 to 122°F)
Ambient Storage Temperature: -20 to 50°C, (-4 to 122°F)
Ambient Relative Humidity: 0 to 90% noncondensing
General Processor: STM32 (ARM Cortex™ M3) MCU, 32 bit
Processor Speed: 72 MHz
Memory: 1 MB Nonvolatile Flash (applications), 2 MB Nonvolatile Flash (storage)
96 kB RAM
Media Channel: TP/FT-10; 78 Kbps
Communication: LonTalk® protocol
Status Indicator: Green LED - power status and LAN TX, Orange LED - service
and LAN RX
Communication Jack: TP/FT-10; 78 Kbps, 1/8 in (3.5 mm)
LONMARK® Interoperability: Version 3.4
Device Class: Static Programmable Device
LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1,
Output Objects: Open - Loop Sensor #3, Real Time Clock: Real Time Keeper
#3300, Scheduler: Scheduler #20020, Calendar: Calendar #20030,
Programmable Device: Static Programmable Device #410
Enclosure Material: FR/ABS
Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
Shipping Weight: 1.17 lb (0.53 kg)
Inputs Input Types: universal software configurable
Voltage: 0 to 10 VDC (40k ohm input impedance)
0 to 5 VDC (high input impedance)
Current: 0 to 20 mA with 249 ohmjumper configurable internal resistor,
Digital: dry contact
Pulse: UI1 to UI4; 50 Hz maximum; Minimum 10 ms On/10 ms Off, dry contact
UI5 to UI6: 1 Hz maximum; Minimum 500 ms On/500 ms Off, dry contact
Resistor Support: 0 to 350k ohms. All thermistor types that operate within this
range are supported. The following temperature sensors are pre-configured:
Thermistor:
Type 2 and Type 3 10k ohm (10k ohm at 25°C [77°F])
Platinum:
PT1000 1k ohm (1k ohm at 0°C [32°F])
Nickel:
RTD Ni1000 (1k ohm at 0°C [32°F])
RTD Ni1000 (1k ohm at 21°C [69.8°F])
Input Resolution: 16-bit analog/digital converter
Power Supply Output: 15VDC; maximum 320 mA (16 inputs x 20 mA each)
LN Free Programmable PRG 600 Series Controllers Installation Instructions 11
LN-PRG6x0-2 (Part 2 of 2)
Outputs Universal: 0-10 VDC linear, digital 0 to12 VDC (on/off), PWM, floating, or
0 to 20 mA (jumper configurable); software configurable. Built-in snubbing diode
to protect against back EMF, for example when used with a 12 VDC relay.
PWM control: adjustable period from 2 seconds to 15 minutes
Floating control:
minimum plus on/off: 500 ms
adjustable drive time period
Hands-off-Auto (HOA) Switch (when equipped): hand position potentiometer
range: 0 to 12.5 VDC
60 mA maximum at 12 VDC (60°C; 140°F)
Load Resistance: minimum resistance 200 ohms for 0 to 10 VDC and
0 to 12.5 VDC, maximum 500 ohm for 0 to 20 mA output
Auto reset fuse
60 mA at 60°C (140°F)
100 mA at 20°C (68°F)
Output Resolution: 10-bit digital/does analog converter
Wireless Receiver1 Communication: EnOcean® Wireless standard
Number of Wireless Inputs: 282
Supported Wireless Receivers: LN-WMOD315-0 and LN-WMOD868-0
Telephone Cord Cable: Connector: 4P4C modular jack, Length: 3 ft (1 m)
Enclosure Material: UL94-5VA
Electromagnetic Compatibility CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial,
and light-industrial environments.
CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial,
and light-industrial environments.
Compliance United UL Listed, File E107041, CCN PAZX,
States Under UL 916, Energy Management Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
Canada UL Listed, File E107041, CCN PAZX7,
Under CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada, ICES-003
Europe CE Mark – Johnson Controls, Inc., declares that the products are in compliance
with the essential requirements and other relevant provisions of the
EMC Directive 2004/108/EC.
1. Available when an optional external Wireless Receiver is connected to the controller. Some wireless inputs may use more
than one wireless input from the controller.
2. Some wireless modules may use more than one wireless input from the controller.
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.
LN Free Programmable PRG 600 Series Controllers Installation Instructions 12