LN Application Specific, Remote I/O, and Free
Programmable Controllers
Installation Instructions                                                                            Code No. LIT-12011320
                                                                                                        Issued December 2017
LN-RTUL-1, LN-FCUL-1, LN-UVL-1, LN-HPUL-1, LN-IOxxx-1,
LN-PRG203-2, LN-PRG300-2, LN-PRG4x0-2, LN-PRG5x0-2

Application
Follow these recommendations for proper installation and subsequent operation of each controller:
•      Properly inspect the product for shipping damage. Do not install damaged controllers.
•      Record the 12-digit Neuron® ID located on either end of the device (shown on the sticker below the barcode)
       for commissioning.
•      Operate the controller under the following conditions:
       -   Ambient temperature:
       LN-PRG203-2, LN-PRG300-2, LN-PRG4x0-2, LN-RTUL-1, LN-FCUL-1, LN-UVL-1, LN-HPUL-1: 32 to 158°F
       (0 to 70°C), LN-IO301-1, LN-IO401-1 and LN-PRG5x0-2: 32 to 122°F (0 to 50°C)
       -   Relative humidity: 0 to 90%, noncondensing

    IMPORTANT: Prevent any static electric discharge to the controller. Static discharge can damage the controller
    and void the warranties.

North American Emissions Compliance
United States

    Compliance Statement (Part 15.19)
    This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
    This device may not cause harmful interference, and
    This device must accept any interference received, including interference that may cause undesired operation.
    Warning (Part 15.21)
    Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to
    operate the equipment.

Canada
    The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were
    met.
    Industry Canada Statement
    Le terme «IC» précédant le numéro d'accréditation/inscription signifie simplement que le produit est conforme aux
    spécifications techniques d'Industry Canada.

                         LN Application Specific, Remote I/O, and Free Programmable Controllers
                                                   Installation Instructions
                                                               1
Installation
Dimensions
      Figure 1:     LN-PRG4x0-2, LN-PRG5x0-2, LN-IO401-1, and LN-IO520-1 Dimensions, mm (in.)

                                                                                                   Fig: ln_prg4x0_prg5x0_io401_501_dim

        Figure 2:   LN-PRG203-2, LN-PRG300-2, LN-IO301-1, and Application Specific Controller
                                       Dimensions, mm (in.)

                                                                                                                                         Fig: ln_prg203_300_io301_app_specific_contr_dim

       LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                      2
Mounting
You can mount each controller on a DIN rail, on a wall, or in a panel. The controllers are equipped with two
mounting holes 0.25 x 0.165 in. (6.36 x 4.191 mm).
Location Considerations
Observe these guidelines when mounting an LN Application Specific or Remote I/O Module:
•   Provide for sufficient space around the device for cable and wire connections, access to service pin, hardware
    configuration, maintenance, easy cover removal, and good ventilation.
•   Ensure proper ventilation of each device and avoid areas where corroding, deteriorating, or explosive vapors,
    fumes, or gases may be present.
•   Orient each controller with the ventilation slots and power supply/output terminal block connector towards the
    top to permit proper heat dissipation.
•   Do not mount the controller on surfaces prone to vibration, such as duct work, or in areas where
    electromagnetic emissions from other devices or wiring can interfere with communication.
DIN Rail
To mount the controller on a DIN rail:
1. Ensure the DIN rail is properly mounted on the wall.
2. Clip the controller onto the DIN rail.
Wall Mount
To mount the device on a wall:
1. Press on the side clips to separate the device’s front and back plates.
2. Use the holes on the back plate to mark the wall location.
3. Drill the holes.
4. Clean the surface and mount the unit using the appropriate screws.

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                          3
Wiring

    Risk of Electric Shock.
    Disconnect the power supply before making electrical connections to avoid electric shock.

    Risque de décharge électrique.
    Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge
    électrique.

    IMPORTANT: All wiring must comply with electrical diagrams as well as national and local electrical codes.

Follow these wiring recommendations:
•      Remove the front plate from the back plate to facilitate in the wiring process. Use a small flat screwdriver to
       tighten the terminal connector screws once you have inserted the wires.
•      Keep power cables apart from other types of wiring to avoid ambient noise transmission to other wires (for
       example, for power, 3-wire voltage, and current inputs and outputs).
•      Use wires or flat cables ranging from 22 to 12 AWG (0.645 to 2.052 mm diameter) per pole. Power cables must
       remain between 18 to 14 AWG (1.024 to 1.628 mm) diameter.
•      Keep all wires away from high-speed data transmission cables (for example, Ethernet cable).
•      Keep input and output wires in conduits, trays, or close to the building frame whenever possible.
Power Wiring

    IMPORTANT: Voltage: 24 VAC/DC; +15%, Class 2. This is a Class 2 Product. Use a Class 2 transformer only
    (rated at 100 VA or less at 24 VAC) to power the device.

For more information and requirements for powering a device that uses a LONWORKS network for communications,
refer to the LONWORKS LN-Series Network Communication and Interface Guide Technical Bulletin (LIT-12011253).
We recommend wiring only one device per 24 VAC transformer. When only one transformer is available, determine
the maximum number of devices that can be supplied using the following method for calculating the required power
transformer capacity:
1. Add up the maximum power consumption of all controllers and multiply this sum by 1.3.
2. If the resulting number is higher than 100 VA, consider using multiple transformers.
Use an external fuse on the 24 VAC/DC side (secondary side) of the transformer to protect all units against power
link spikes (Figure 3).
Maintain consistent polarity when you connect the controllers (or modules) and devices to the transformer.

    IMPORTANT: Failure to maintain consistent polarity throughout the entire network will result in a short circuit
    and damage to the controller.

    IMPORTANT: The COM terminals of the controller are internally wired to the 24 V COM terminal of the power
    supply. Connecting a peripheral or another controller to the same transformer without maintaining polarity
    between these devices will cause a short circuit.

           LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                             4
Use an external fuse on the 24 VAC/DC side (secondary side) of the transformer to protect all controllers against
power link spikes.
                                      Figure 3: Power Wiring – AC

                                          Figure 4:    Power Wiring – DC

Input Wiring
The devices have physical connections for inputs (marked Ulx), which are software configurable from within the
device’s LNS® plug-in or wizard. Therefore, hardware configuration is not required.
Each input can be configured for digital, resistive, current, or voltage signals. You must configure the input types
properly in the software plug-in or wizard to ensure proper input readings.

 IMPORTANT: Before connecting any sensor to the device, refer to the installation guide of the equipment
 manufacturer.

Note: For a wire of less than 75 feet (23 m), use either a shielded or unshielded 19 AWG wire.
Note: For a wire from 75 feet (23 m) to 200 feet (61 m), we recommend a shielded 18 AWG wire.
Note: The wire should be shielded on the controller or module side, and the shield length should be kept as short
as possible.
Wiring Digital Inputs
Use the input configuration in Figure 5 to monitor digital dry contacts.
                                  Figure 5:    Digital Input – Digital Dry Contact
                                                  (N.O. and N.C.)

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                          5
Wiring Resistive Inputs
Use this input configuration to monitor 100k ohm RTDs, 10k ohm Type 2 and Type 3 thermistors, and
potentiometers (Figure 6 and Figure 7).
                                 Figure 6:   Resistive Input – RTD/Thermistor

                                     Figure 7:   Resistive Input – 10k Ohm

Note: The Application Specific Controllers do not support 100 or 1,000 ohm inputs.
Note: When using a 100 ohm input, the wire length should be kept short to avoid a possible temperature offset; for
example, an 18 AWG wire, 25 feet long (7.6 m) can create an offset of 2°F (1.1°C).

        LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                        6
Wiring Current Inputs
Current inputs have a range of 4 to 20 mA. Connect the current input according to Figure 8 if you are using a
2-wire, 4-20 mA transducer.
                                Figure 8: Current Input – 2-Wire Transducer

Connect the current input according to Figure 9 if you are using a 3-wire, 4-20 mA transducer.
                                 Figure 9:   Current Input – 3-wire Transducer

Connect the current input according to Figure 10 if you are using a transducer powered by its own power.
                                 Figure 10: Current Input – Transducer With
                                           Its Own Power Source

Wiring Voltage Inputs
Voltage inputs have a range of 0 to 10 VDC. Connect the voltage input according to Figure 11 if you are using a 3-
wire 0 to 10 V transducer.
                                           Figure 11: Voltage Input

Output Wiring
Each controller has physical connections for triac outputs and/or universal outputs, depending on the type and
model. The outputs are all software configurable. Table 1 shows the controller outputs.
Table 1: Controller Outputs (Part 1 of 2)
 Controller                        Triac Outputs            Universal Outputs        Jumper 0-10 VDC/4-20 mA
 LN-FCUL-1                                   5                        2
 LN-HPUL-1                                   5                        2
 LN-RTUL-1                                   5                        2
 LN-ULVL-1                                   5                        2

        LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                        7
Table 1: Controller Outputs (Part 2 of 2)
 Controller                          Triac Outputs             Universal Outputs         Jumper 0-10 VDC/4-20 mA
 LN-PRG203-2                                   5                         3
 LN-PRG300-2                                                             8
 LN-PRG400-2                                                             12                          X
 LN-PRG410-2                                                             12                          X
 LN-IO301-1                                    8
 LN-IO401-1                                    12
 LN-IO520-1

 IMPORTANT: Before connecting any sensor to the device, refer to the installation guide of the equipment
 manufacturer.

Note: For wire length less than 75 feet (23 m), use either a shielded or unshielded 19 AWG wire.
Note: For a wire up to 200 feet (61 m), we recommend a shielded 18 AWG wire.
Note: The wire should be shielded on the controller/module side, and the shield length should be kept as short as
possible.
Wiring Triac Outputs
Digital outputs are all made of triacs and voltage is no present on the output terminals; therefore, you need to add
an external power source, if necessary.
Note: You must add an external power source, typically 24 VAC.

 IMPORTANT: To measure the state of a digital output (triac), an external load must be connected.

If a 24 VAC relay is being controlled, connect the digital output according to Figure 12.
                                      Figure 12: Digital Triac Output – Relay

If a floating actuator is being controlled, connect the digital output according to Figure 13.
                                      Figure 13: Digital Triac Output – Floating

Wiring Universal Outputs (UOx)
Universal outputs can be configured to provide either a linear signal ranging from 0 to 12 VDC or a linear signal of
0 to 10 VDC. The discrete signal can be used to generate a PWM or a simple two-state signal. These outputs are
protected by an auto-reset fuse.
When controlling a relay with a universal output, a diode must be connected in parallel to protect the controller from
back-emf current that occurs when the relay is turned off.

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                           8
Wiring Discrete Outputs
If a 12 VDC relay is being controlled, connect it to a universal output according to Figure 14.
                                         Figure 14: Discrete 0 to 12 VDC

Wiring Voltage Inputs
Connect the 0 to 10 VDC output according to Figure 15.
                                         Figure 15: Voltage 0 to 10 VDC
                                                Universal Output

If an analog actuator is being controlled, connect the 0 to 10 VDC output, along with an external 24 VAC power
source, to the analog actuator according to Figure 16.
                                         Figure 16: Voltage 0 to 10 VDC
                                       Universal Output – Analog Actuator

Two network terminators are required for the bus topology network configuration. Place one network terminator at
each end of the bus topology channel.
One network terminator is required for the free topology network configuration. You can put the network terminator
anywhere on the channel.
Communications Wiring
The recommended cable type for LONWORKS® communications is 22 AWG (0.65 mm), twisted pair, UNSHIELDED
wire. The LONWORKS communication wire is polarity insensitive and can be laid out in a bus, star, or free topology.
For loop topology, take special care to maintain the polarity when connecting the LONWORKS network to avoid a
short circuit.
Note: We recommend you use the bus topology network configuration for all LONWORKS communication wiring.
This configuration allows you to troubleshoot the network easily.

        LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                          9
Connect both wires to the LON terminals (LON1 and LON2) of the controller (Figure 17). When you insert multiple
wires into the terminals, ensure you properly twist the wires together before you insert them into the terminal
connectors.
                                       Figure 17: Communications Wiring

For more information and detailed explanations on network topology and wire length restrictions, refer to the
LONWORKS LN-Series Network Communication and Interface Guide Technical Bulletin (LIT-12011253) or Echelon
Corporation’s Junction Box and Wiring Guideline for Twisted Pair LONWORKS® Networks.

 IMPORTANT: Use the proper network terminators for the network topology. Failure to use the correct network
 terminators may result in communication errors between units. Do not use multiple gauges of cable on the same
 communication bus.

LN Sensor Wiring
The controllers in this document are compatible with the LN Sensor line of standard room sensors. Refer to the LN
Series Sensor Installation Instructions (LIT-1201871) for wiring details.
Memory Erase Jumper
Each Application Specific Controller and Remote I/O Module features a memory erase jumper. Use the memory
erase jumper to erase the Neuron chip's memory. If an incorrect APB or NXE file is loaded into the device, the
Neuron chip's memory is corrupted and you cannot communicate with the device. Use the memory erase jumper to
correct this problem by resetting the Neuron chip's memory; the chip is then in an application-less state.
The memory erase jumper is labeled J2 on the Application Specific Controllers (Figure 19), J4 on the LN-IO301-1
Remote I/O Module (Figure 20), and J20 on the LN-IO401-1 and LN-IO520-1 Remote I/O Modules (Figure 18).
To erase the Neuron chip's memory using the memory erase jumper, do the following:
1. Disconnect the power to the device.
2. Place a jumper on the proper pins on the controller or module.
3. Reconnect the power to the device.
Note: The orange colored service LED blinks rapidly indicating that it is erasing the Neuron chip’s memory. When
the service LED stops blinking and remains solid, the erase procedure is complete.
Note: The erase procedure normally takes between 2 and 10 seconds to complete.
4. Disconnect the power to the device and remove the jumper.
5. Reconnect the power. The service LED blinks twice and becomes solid indicating the controller or module is
   application-less.
6. Download the correct APB file.

        LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                       10
                             Figure 18: Memory Erase Jumper

                        Figure 19: Memory Erase Jumper Location
                          (J2) on Application Specific Controllers

                      Figure 20: Memory Erase Jumper Location (J4)

LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                              11
Strain Relief and Terminal Block Cover
In certain jurisdictions, terminal block covers are required to meet local safety regulations. Strain reliefs and
terminal block covers are available for controllers housed in the large enclosures and are used to relieve tension on
the wiring and conceal the controllers' wire terminals. Strain reliefs and terminal block covers are optional and are
sold separately.
Prior to connecting all wires, it is recommended that you install the strain relief. Three screws are provided for its
installation under the bottom part of the enclosure. You can then use tie wraps to group wires together and attach
them securely to the strain relief in an effort to relieve undue tension. If necessary, clip the terminal block cover to
the strain relief as shown in Figure 21.
                                  Figure 21: Large Enclosure Strain Relief and
                                        Terminal Block Cover Installation

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                           12
Maintenance

    Risk of Electric Shock.
    Disconnect the power supply before making electrical connections to avoid electric shock.

    Risque de décharge électrique.
    Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge
    électrique.

Each controller requires minimal maintenance, but it is important to:
•      clean the outside of the front plate an/or the inside of the back plate, use a dry cloth.
•      verify the tension of all wires and cables each time you service the controller.
Disposal
The Waste Electrical and Electronic Equipment (WEEE) Directive sets regulations for the recycling and disposal of
products. The WEEE2002/96/EG Directive applies to stand-alone products that can function on their own and are
not a part of another system or piece of equipment.
For this reason, Johnson Controls® products are exempt from the WEEE Directive. Nevertheless, they are marked
with the WEEE symbol, indicating the devices are not disposed with municipal waste.
Dispose of products at the end of their useful life according to local regulations and the WEEE Directive.
Troubleshooting
Table 2 describes some troubleshooting scenarios.
Table 2: Troubleshooting (Part 1 of 2)
    Problem                                       Possible Solution
    Controller is powered but does not turn on.
    Fuse Is Blown                                 Disconnect power from the device and check the fuse integrity. Then wait a
                                                  few seconds to allow the auto-reset fuse to cool down. Reconnect power.
    Power Supply Polarity                         Verify that consistent polarity is maintained between all controllers and the
                                                  transformer. Ensure that the COM terminal of each controller is connected to
                                                  the same terminal on the secondary side of the transformer. See Figure 3.
    Device cannot communicate on a FTT network.
    Absent or Incorrect Supply Voltage            1. Check power supply voltage between 24 VAC/DC ±15% and COM pins,
                                                     and ensure that it is between acceptable limits.
                                                  2. Check for tripped fuse or circuit breaker.
    Overloaded Power Transformer                  Verify the transformer is powerful enough to supply all devices.
    Network Not Wired Properly                    Double-check the wire connections are correct.
    Absent or Incorrect Network Termination       Check the network terminations.
    Service Pin Not Working                       Use the memory erase jumper to reset the Neuron chip’s memory, then load
                                                  the proper APB or NXE into the controller using LN-Builder 3.4 or another
                                                  network management tool.
    Device communicates well over a short network but does not communicate on large network.
    Network Length                                Check that the total wire length does not exceed the specifications of the
                                                  Junction Box and Wiring Guideline for Twisted Pair LONWORKS Networks.

           LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                                13
Table 2: Troubleshooting (Part 2 of 2)
 Problem                                       Possible Solution
 Wire Type                                     Check that the wire type agrees with the specification of the LN-Series
                                               Network Communications and Interface Guide (LIT-1201253) or Junction Box
                                               and Wiring Guideline for Twisted Pair LONWORKS Networks.
 Network Wiring Problem                        Check that the wire connections are correct.
 Absent or Incorrect Network Termination       Check the termination(s). Incorrect or broken termination(s) make the
                                               communication integrity dependent upon a controller's position on the
                                               network.
 Extra Capacitance                             Ensure no extra capacitance is connected to the network other than the
                                               standard FTT circuit, and a maximum of a 3 meter stub (in bus topology).
 Number of Devices on Network Segment          The number of controllers on a channel should never exceed 64. Use a router
 Exceeded                                      or a repeater in accordance with LONWORKS LN-Series Network
                                               Communications and Interface Guide (LIT-1201253) or Junction Box and
                                               Wiring Guideline for Twisted Pair LONWORKS Networks.
 Network Traffic                               Query node statistic to check errors.
                                               Use a LONWORKS protocol analyzer to check network traffic.
 Hardware input is not reading the correct value.
 Input Wiring Problem                          Check that the wiring is correct according to this manual and according to the
                                               peripheral device's manufacturer.
 Open Circuit or Short Circuit                 Using a voltmeter, check the voltage on the input terminal. A short circuit has a
                                               0 V value and an open circuit shows approximately 5 V.
 Configuration Problem                         Check the configuration of the input using the device configuration plug-in or
                                               wizard. Refer to the device’s user guide for more information.
 Over-Voltage or Over-Current at an Input      An over-voltage or over-current at one input can affect the reading of other
                                               inputs. Respect the allowed voltage/current range limits of all inputs. See
                                               Technical Specifications.
 Hardware output is not operating correctly.
 Fuse Has Blown (auto-reset fuse)              Disconnect the power and output terminals. Wait a few seconds to allow the
                                               auto-reset fuse to cool down. Check the power supply and the output wiring.
                                               Reconnect the power.
 Output Wiring Problem                         Check that the wiring is correct according to this manual and according to the
                                               device's manufacturer.
 Configuration Problem                         Using the device configuration wizard (LN-GPI), check the configuration of the
                                               output. Refer to the device's user guide for more information.
 0 to 10 V Output, 24 VAC Powered              Check the polarity of the 24 VAC power supply connected to the actuator
 Actuator Is Not Moving                        while connected to the device. Reverse the 24 VAC wire if necessary.

        LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                             14
Service LED Operation Guide
Table 3: Service LED Operation Guide – Normal Operation
 Operation                                  Service
 Off                                        The device is in normal operation.
 On                                         The device is application-less.
                                            Appropriate action: reload the APB or NXE.
 Slow Blink                                 The device is not configured.
 (1 second On, 1 second Off)                Appropriate action: Commission the device.
 Fast Blink                                 Watchdog timeout. Application corrupted.
 (0.3 seconds On, 1 second Off)             Appropriate action: Use the memory erase jumper to reset the Neuron chip’s
                                            memory, then load the proper APB or NxE into the device using LN-Builder or
                                            another network management tool.

Repair Information
If the LN Series Application Specific Controller or Remote I/O Module fails to operate within its specifications,
replace the unit. For a replacement controller or module, contact the nearest Johnson Controls® representative.

        LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                         15
Technical Specifications
Table 4: LN Application Specific Controllers
 Product Codes                    LN-RTUL-1, LN-FCUL-1, LN-UVL-1, LN-HPUL-1
 Power Requirement                Voltage: 24 VAC, +15%, 50/60HZ, Class 2
                                  Protection: 1.35 A auto reset fuse
                                  Power Consumption: 6 VA
                                  Maximum Consumption: 15 VA
 Environmental                    Operating Temperature: 0 to 70ºC, (32 to 158ºF)
                                  Storage Temperature: -20 to 70ºC, (-4 to 158ºF)
                                  Relative Humidity: 0 to 90% noncondensing
 General                          Standard:
                                     LN-RTUL-1: Roof Top Unit Controller #8030
                                     LN-FCUL-1: Fan Coil Controller #8020
                                     LN-UVL-1: Unit Ventilator #8080
                                     LN-HPU-1: Heat Pump with Temperature Control #8051
                                  Processor: Neuron™ 3150®; 8 bits
                                  Processor Speed: 10 MHz
                                  Memory: Nonvolatile Flash 64k (APB application and configuration properties)
                                  Communication: LonTalk® protocol
                                  Media Channel: TP/FT-10; 78 Kbps
                                  Transceiver: FT-X1
                                  Status Indicator: Green LED – power status and LON TX, Orange LED – service
                                  and LON RX
                                  Communication Jack: LON audio jack mono 1/8 in (3.5 mm)
 Enclosure                        Material: ABS type PA-765A
                                  Dimensions (with screws): 5.7 x 4.7 x 2.0 in. (144.8 x 119.4 x 50.8 mm)
                                  Shipping Weight: 0.77 lbs. (0.35 kg)
 Inputs                           Quantity: 6
                                  Input Types: universal software configurable
                                     Voltage: 0 to 10 VDC , Accuracy +0.5%
                                     Current: 4 to 20 mA with a 249 ohm external resistor (wired in parallel), Accuracy
                                     +0.5%
                                     Digital: dry contact
                                  Resistor:
                                     RTD: 1k ohm (nickel and platinum), 100 ohm (platinum)
                                     Thermistor: Type 2 and Type 3 10k ohm, accuracy: +0.9°F, +5°C
                                     range: -40° to 257°F; resolution: 0.1°C; 0.18°F.
                                  Potentiometer: translation table configurable on several points; accuracy +0.5%
                                  Input Resolution: 12-bit analog/digital converter
 Outputs                          Quantity: 7
                                  5 Digital:
                                     Triac 1.0 A at 24 VAC
                                     External power supply
                                  2 Universal: 0 to 10 VDC (linear), digital 0 to 12 VDC (on/off) or PWM
                                     PWM output: adjustable period from 2 second to 15 minutes
                                     60 mA max. at 12 VDC (140°F; 60°C)
                                     Maximum load 200 ohms
                                     Auto-reset fuse: 60 mA at 140°F; 60°C; 100 mA at 68°F, 20°C
                                  Output Resolution: 8-bit digital/analog converter

          LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                          16
Table 4: LN Application Specific Controllers
 Electromagnetic Compatibility      CE Emission: (CDN and US)
                                    CE Immunity: Material
                                       EN61000-4-2: 1995, level 2 by contact
                                       EN61000-4-3: 1996, level 2
                                       EN61000-4-4: 1995, level 2
                                       EN61000-4-6: 1996, level 2
                                       ENV 5024: 1995, level 2
                                    FCC: This device complies with FCC rules part 15, subpart B, class B
 Compliance                         United States: UL916 Energy Management Equipment
                                    Material1: UL94-5VA
                                    Canada: UL916 Energy Management Equipment
                                    Material1:UL94-5VA
                                    Europe: CE Mark – Johnson Controls, Inc. declares that the products are in compliance
                                    with the essential requirements and other relevant provisions of EMC Directive 2004/
                                    108/EC.

1.   All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste
     Electrical and Electronic Equipment (WEEE) directive.

Table 5: LN Remote I/O Modules
 Product Codes                      LN-IO301-1, LN-IO401-1, LN-IO520-1
 Power Requirement                  Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
                                    Protection: 1.35 A auto-reset fuse
                                    Power Consumption: 6 VA typical
                                    Maximum Consumption: 15 VA
 Environmental                      Operating Temperature: 0 to 50°C, (32 to 122°F)
                                    Storage Temperature: -20 to 70°C, (-4 to 158°F)
                                    Relative Humidity: 0 to 90% noncondensing
 General                            Processor: Neuron® 3150™; 8 bits
                                    Processor Speed: 10 MHz
                                    Memory: 64k Nonvolatile Flash (APB application and configuration properties)
                                    Communication: LonTalk® protocol
                                    Transceiver: FT-X1
                                    Status Indicator: Green LED - power status and LON TX, Orange LED - service and LON
                                    RX
                                    Communication Jack: LON® mono audio jack 1/8 in. (3.5 mm)
 Enclosure                          Material: ABS PA-765A
                                    Dimensions (with screws):
                                       LN-IO301-1: 5.7 x 4.7 x 2.0 in. (144.8 x 119.4 x 50.8 mm)
                                       LN-IO401-1 and LN-IO520-1: 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
                                    Shipping Weight:
                                       LN-IO301-1:.77 lb (0.35 kg)
                                       LN-IO401-1 and LN-IO520-1: .86 lb (0.39kg)

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                            17
Table 5: LN Remote I/O Modules
Inputs                           Input Types: universal software configurable
                                     Voltage: 0 to 10 VDC , Accuracy +0.5%
                                     Current: 4 to 20 mA with a 249 ohm external resistor (wired in parallel)
                                     Digital: dry contact
                                 Resistor:
                                 Thermistor: Type 2 and Type 3 10k ohm, 10k ohm at 25°C; 77°F
                                     Range: -40° to 302°F; -40° to 150°C
                                 Platinum: Pt1000 (100 ohms at 32°F; 0°C)
                                     Range: -40° to 275°F; -40° to 135°C
                                 Potentiometer: Translation table configurable on several points
                                 Input Resolution: 16-bit analog/digital converter
Electromagnetic Compatibility    CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and
                                               light-industrial environments.
                                 CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
                                               light-industrial environments.
                                 IC: This Class (A) digital apparatus meets all requirements of the Canadian Interference
                                 Causing Equipment Regulations.
                                 FCC: This device complies with FCC rules part 15, subpart B, class B
Compliance                       United States: UL 916, Energy Management Equipment
                                 Material: UL94-5VA
                                 Canada: UL 916, Energy Management Equipment
                                 Material: UL94-5VA.
                                 Europe: CE Mark – Johnson Controls declares that the products are in compliance with
                                 the essential requirements and other relevant provisions of the EMC Directive 2004/108/
                                 EC.

Table 6: LN-PRG203-2 Programmable Controller (Part 1 of 2)
Product Code                  LN-PRG203-2
Power Requirement             Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
                              Protection: 1.85 A user-replaceable fuse
                              Power Consumption: 18 VA with 2 triac outputs ON and 2 outputs with
                              20 mA load at 12 VDC
                              Maximum Consumption: 25 VA
Environmental                 Operating Temperature: 0 to 70°C, (32 to 158°F)
                              Storage Temperature: -20 to 70°C, (-4 to 158°F)
                              Relative Humidity: 0 to 90% noncondensing
General                       Processor: Neuron® 3150™, 8 bits, 10 MHz
                              Processor Speed: 10 MHz
                              Memory: Nonvolatile Flash 64k (APB application); Nonvolatile Flash 128k (storage)
                              Media Channel: TP/FT-10; 78 Kbps
                              Communication: LonTalk® protocol
                              Status Indicator: Green LED – power status and LON TX, Orange LED – service and LON
                              RX
                              Communication Jack: LON® mono audio jack mono 1/8 in (3.5 mm)
                              LONMARK® Interoperability: Version 3.4
                              Device Class: Multi I/O Module
                              LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects: Open-
                              Loop Sensor #3
Enclosure                     Material: ABS type PA-765A
                              Dimensions (with screws): 5.7 x 4.7 x 2.0 in. (144.8 x 119.4 x 50.8 mm)
                              Shipping Weight: 0.97 lb (0.44 kg)

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                          18
Table 6: LN-PRG203-2 Programmable Controller (Part 2 of 2)
 Inputs                         Universal software configurable
                                Input Types:
                                    Digital: Dry Contact
                                    Pulse: Dry Contact; 500 milliseconds minimum ON/OF
                                    Voltage: 0 to 10 VDC,
                                    Current: 4 to 20 mA with 249 ohmsexternal resistor (wired in parallel)
                                Resistor Support:
                                Thermistor: Type 2 and Type 3 10k ohms (10k ohms at 25°C [77°F])
                                    Range: -40 to 150°C (-40 to 302°F)
                                Platinum:
                                    PT1000: 1k ohm (1k ohms at 0°C [32°F])
                                    Range: -40 to 150°C (-40 to 302°F)
                                    PT100: 100 ohms (100 ohms at 0°C [32°F])
                                    Range: -40 to 135°C (-40 to 275°F)
                                Nickel:
                                    RTD Ni1000 (1k ohm at 0°C [32°F])
                                    Range: -40 to 150°C (-40 to 302°F)
                                Potentiometer: Translation table configurable on several points
                                Input Resolution: 16-bit analog/digital converter
 Outputs                        Digital: 24 VAC Triac, digital (on/off), PWM, or floating
                                   software configurable
                                   0.5 A continuous
                                   1.0 A at 15% duty cycle for a 10-minute period
                                PWM control: adjustable period from 2 seconds to 15 minutes
                                Floating control: requires two consecutive output
                                   minimum plus on/off: 500 milliseconds
                                   adjustable drive time period
                                   External or internal power supply (jumper selectable)
                                Universal: 0-10 VDC, digital 0-12 VDC (on/off), PWM, or floating
                                PWM control: adjustable period from 2 seconds to 15 minutes
                                Floating control: requires two consecutive outputs
                                   minimum plus on/off: 500 milliseconds
                                   adjustable drive time period
                                60 mA maximum at 12 VDC (60°C [140°F])
                                minimum resistance 200 ohms
                                Auto reset fuse
                                   60 mA at 60°C (140°F)
                                   100 mA at 20°C (68°F)
                                Output Resolution: 10-bit digital/analog converter
 Electromagnetic                CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and light-
 Compatibility                              industrial environments (pending).
                                CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and light-
                                            industrial environments (pending).
                                FCC: This device complies with FCC rules part 15, subpart B, class B
 Compliance                     UL Listed: UL916 Energy management equipment
                                Material1: UL94-5VA
                                UL Listed: UL916 Energy management equipment
                                Material1: UL94-5VA

1.   All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste
     Electrical and Electronic Equipment (WEEE) directive.

          LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                             19
Table 7: LN-PRG300-2 Programmable Controller (Part 1 of 2)
Product Code                     LN-PRG300-2
Power Requirement                Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
                                 Protection: 1.85A auto-reset fuse
                                 Power Consumption: 18 VA, all outputs with 20 mA load at 12 VDC
                                 Maximum Consumption: 33 VA
Environmental                    Operating Temperature: 0 to 70°C, (32 to 158°F)
                                 Storage Temperature: -20 to 70°C, (-4 to 158°F)
                                 Relative Humidity: 0 to 90%
General                          Processor: Neuron 3150, 8 bits, 10 MHz
                                 Memory: Nonvolatile Flash 64k (APB application), Nonvolatile Flash 128k (storage)
                                 Media Channel: TP/FT-10; 78 Kbps
                                 Communication: LonTalk protocol
                                 Clock: Real-time clock chip, CR2032 lithium battery (for clock)
                                 Status Indicator: Green LED - power status and LON TX, Orange LED - service and
                                 LON RX
                                 Communication Jack: LON audio jack mono 1/8 in (3.5 mm)
                                 LONMARK Interoperability: Version 3.4
                                 Device Class: Multi I/O Module
                                 LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
                                 Open-Loop Sensor #3
Enclosure                        Material: ABS type PA-765A
                                 Dimensions (with screws): 5.7 x 4.7 x 2.0 in. (144.8 x 119.4 x 50.8 mm)
                                 Shipping Weight: 0.97 lb (0.44 kg)
Inputs                           Universal software configurable
                                 Input Types:
                                    Digital: Dry Contact
                                    Pulse: Dry Contact, 500ms minimum ON/OFF
                                   Analog Voltage: 0 to 10 VDC,
                                   Analog current: 4 to 20 mA with 249 ohmsexternal resistor (wired in parallel),
                                   Resistor Support:
                                 Thermistor: Type 2, Type 3 10k ohms (10k ohms at 25ºC [77ºF])
                                     Range: -40 to 150ºC, (-40 to 302ºF)
                                 Platinum:
                                     Pt1000: (1k ohm at 0ºC [32ºF])
                                     Range: -40 to 150ºC (-40 to 302ºF)
                                     PT100: 100 ohms (1k ohm at 0ºC [32ºF])
                                     Range: -40 to 135ºC (-40 to 275º)
                                 Nickel:
                                     Ni1000 (1k ohm at 0ºC [32ºF])
                                     Range: -40 to 150ºC (-40 to 302ºF)
                                 Potentiometer: Translation table configurable on several points
                                 Input Resolution: 16-bit analog/digital converter

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                         20
Table 7: LN-PRG300-2 Programmable Controller (Part 2 of 2)
 Outputs1                           Quantity: 8 (software configurable)
                                    0 to 10 VDC, digital 0 to12 VDC (on/off), PWM, or Floating
                                    PWM output: adjustable period from 2 seconds to 15 minutes
                                    Floating control: requires two consecutive outputs
                                        minimum pulse on/off: 500 millisecond
                                        adjustable drive time period
                                    60 mA maximum at 12 VDC (60°C [140°F])
                                    Minimum load: 200 ohms
                                    Auto reset fuse
                                        60 mA at 60ºC (140°F)
                                        100 mA at 20ºC (68°F)
                                    Output Resolution: 10-bit digital/analog converter
 Electromagnetic Compatibility      CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and
                                               light-industrial environments (pending).
                                    CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
                                               light-industrial environments (pending).
 Compliance                         United States: UL Listed: UL916 Energy management equipment
                                    Material2: UL94-5VA
                                    Canada: UL Listed: UL916 Energy management equipment
                                    Material2: UL94-5VA

1.   Floating available when programmed with LN GPI software.
2.   All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste
     Electrical and Electronic Equipment (WEEE) directive.

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                            21
Table 8: LN-PRG400-2 and LN-PRG410-2 Programmable Controllers (Part 1 of 2)
Product Codes                    LN-PRG400-2 and LN-PRG410-2
Power Requirement                Voltage: 24 VAC/DC; ±15%, 50/60 Hz, Class 2
                                 Protection: 3.0 A user-replaceable fuse
                                 Typical Consumption: 25 VA
                                 Maximum Consumption: 50 VA
                                 Power Supply: 15 VDC output used to power 4 to 20 mA inputs
Environmental                    Operating Temperature: 0 to 70°C, (32 to 158°F)
                                 Storage Temperature: -20 to 70°C, (-4 to 158°F)
                                 Relative Humidity: 0 to 90%
General                          Standard: LONMARK Functional Profile: SCC-VAV Controller #8502
                                 Processor: Neuron 3150, 8 bits, 10 MHz
                                 Memory: Nonvolatile Flash 64k (APB application), Nonvolatile Flash 128k (storage)
                                 Media Channel: TP/FT-10; 78 Kbps
                                 Communication: LonTalk protocol
                                 Clock: Real-time clock chip, CR2032 lithium battery (for clock)
                                 Status Indicator: Green LED - power status and LON TX, Orange LED - service and
                                 LON RX
                                 Communication Jack: LON audio jack mono 1/8 in (3.5 mm)
                                 LONMARK Interoperability: Version 3.4
                                 Device Class: Multi I/O Module
                                 LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
                                 Open-Loop Sensor #3
Enclosure                        Material: ABS type PA-765A
                                 Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
                                 Shipping Weight: 1.17 lb (0.53 kg)
Inputs                           Universal software configurable
                                 Input Types:
                                     Digital: Dry Contact
                                     Pulse: Dry Contact (500 milliseconds minimum ON/OFF
                                     Analog Voltage: 0 to 10 VDC
                                     Analog current: 4 to 20 mA with 249 ohmsexternal resistor (wired in parallel)
                                 Resistor Support:
                                 Thermistor: Type 2, Type 3 10k ohms (10k ohms at 25ºC [77ºF])
                                     Range: -40 to 150ºC (-40 to 302ºF)
                                 Platinum:
                                     Pt1000: (1k ohm at 0ºC [32ºF])
                                     Range: -40 to 150ºC (-40 to 302ºF)
                                     PT100: 100 ohms (1k ohm at 0ºC [32ºF])
                                     Range: -40 to 135ºC (-40 to 275ºF)
                                 Nickel: Ni1000 (1k ohm at 0ºC [32ºF])
                                     Range: -40 to 150ºC (-40 to 302ºF)
                                 Potentiometer: Translation table configurable on several points,
                                 Input Resolution: 16-bit analog/digital converter

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                          22
Table 8: LN-PRG400-2 and LN-PRG410-2 Programmable Controllers (Part 2 of 2)
 Outputs1                           Software and jumper configurable
                                    0 to 10 VDC, digital 0 to12 VDC (on/off), PWM, or Floating
                                    PWM output: adjustable period from 2 seconds to 15 minutes
                                    Floating control: requires two consecutive output
                                        minimum pulse on/off: 500 milliseconds
                                        adjustable drive time period
                                    60 mA maximum at 12 VDC (60ºC [140ºF])
                                    Minimum load 200 ohms
                                    Auto reset fuse
                                        60 mA at 60ºC (140ºF)
                                        100 mA at 20ºC (68ºF)
                                    Output Resolution: 10-bit digital/analog converter
                                    Power Supply Output: 15 VDC, maximum 240 mA
 Electromagnetic Compatibility      CE Emission: EN61000-6-3: 2007 Generic standards for residential, commercial, and
                                               light-industrial environments.
                                    CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
                                               light-industrial environments.
 Compliance                         United States: UL Listed: UL916 Energy management equipment
                                    Material2: UL94-5VA
                                    Canada: UL Listed: UL916 Energy management equipment
                                    Material2: UL94-5VA

1.   Floating available when programmed with LN GPI software.
2.   All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste
     Electrical and Electronic Equipment (WEEE) directive.

Table 9: LN-PRG500-2 and LN-PRG510-2 Controllers (Part 1 of 2)
 Product Codes                      LN-PRG500-2 and LN-PRG510-2
 Power Requirements                 Voltage: 24 VAC/DC; +/- 15%, 50/60 Hz, Class 2
                                    Protection: 3.0 A user-replaceable fuse
                                    Typical Consumption: 25 VA all outputs with 20mA load at 12 VDC and 15 VDC output
                                    80mA (4 x 20 mA)
                                    Maximum Consumption: 50 VA
 Environmental                      Operating Temperature: 0 to 70°C, (32 to 158°F)
                                    Storage Temperature: -20 to 70°C, (-4 to 158°F)
                                    Relative Humidity: 0 to 90%
 General                            Standard: LONMARK Functional Profile: SCC-VAV Controller #8502
                                    Processor: Neuron 3150, 8 bits, 10 MHz
                                    Memory: Nonvolatile Flash 64k (APB application), Nonvolatile Flash 64k (storage)
                                    Media Channel: TP/FT-10; 78 Kbps
                                    Communication: LonTalk protocol
                                    Transceiver: FTX-1
                                    LONMARK Interoperability: Version 3.4
                                    Device Class: Multi I/O Module
                                    LONMARK Functional Profile: Input Objects: Open-Loop Sensor #1, Output Objects:
                                    Open-Loop Sensor #3
 Enclosure                          Material: ABS type PA-765A
                                    Dimensions (with screws): 7.7 x 4.7 x 2.0 in. (195.6 x 119.4 x 50.8 mm)
                                    Shipping Weight: 1.17 lb (0.53 kg))

         LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions

                                                            23
Table 9: LN-PRG500-2 and LN-PRG510-2 Controllers (Part 2 of 2)
 Inputs                                   Universal software configurable
                                          Input Types:
                                              Digital: Dry Contact
                                              Pulse: Dry Contact
                                              Analog Voltage: 0 to 10 VDC, Accuracy: ±0.5%,
                                              Analog current: 4 to 20 mA with 249 ohmsexternal resistor (wired in parallel)
                                          Resistor Support:
                                          Thermistor: Type 2, Type 3 10k ohms (10k ohms at 25ºC [77ºF])
                                              Range: -40 to 150ºC (-40 to 302ºF)
                                          Platinum:
                                              Pt1000: (1k ohm at 0ºC [32ºF])
                                              Range: -40 to 150ºC (-40 to 302ºF)
                                              PT100: 100 ohms (1k ohm at 0ºC [32ºF])
                                              Range: -40 to 135ºC (-40 to 275ºF)
                                          Nickel:
                                              Ni1000 (1k ohm at 0ºC [32ºF])
                                              Range: -40 to 150ºC (-40 to 302ºF)
                                           Potentiometer: Translation table configurable on several points
                                           Input Resolution: 16-bit analog/digital converter
 Outputs                                  Universal 0 to10 VDC, digital 0 to12 VDC (on/off), 0-20 mA, PWM, or floating1
                                          PWM output: adjustable period from 2 seconds to 15 minutes
                                          Floating control: requires two consecutive output
                                             minimum pulse on/off: 500 milliseconds
                                             adjustable drive time period
                                          60 mA maximum at 12 VDC (60ºC; 140ºF)
                                          Minimum load 200 ohms
                                          Auto reset fuse
                                             60 mA at 60°C (140°F)
                                             100 mA at 20°C (68°F)
                                          Output Resolution: 10-bit digital/analog converter
                                          Power Supply Output: 15 VDC, maximum 240 mA
 Electromagnetic Compatibility            CE Emission: EN61000-6-3: 2007; Generic standards for residential, commercial, and
                                                     light-industrial environments.
                                          CE Immunity: EN61000-6-1: 2007; Generic standards for residential, commercial, and
                                                     light-industrial environments.
 Compliance                               United States: UL Listed: UL916 Energy management equipment
                                          Material: UL94-5VA
                                          Canada: UL Listed: UL916 Energy management equipment
                                          Material: UL94-5VA

1.   Available when programmed with LN GPI software.
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local J