LCS85 Turnkey User's Guide
MS-LCS8520-0                                                                                               Part No. 24-10526-11, Rev. G
                                                                                                                  Software Release 6.5
                                                                                                              Issued February 14, 2014
                                                                                                              Supersedes June 17, 2013

LCS85 Turnkey Introduction.....................................................................................................2
Naming Conventions.................................................................................................................2
LCS85 Hardware Platform.........................................................................................................2
LCS85 Ethernet Ports................................................................................................................2
Browser Access to the LCS85 Turnkey...................................................................................3
LCS85 Initial Configuration Values..........................................................................................3
Detailed Procedures..................................................................................................................4
   Starting the Computer for the First Time..........................................................................................4
   Logging in for the First Time.............................................................................................................4
   Setting the Time Zone, Date, and Time.............................................................................................4
   Checking the Default Gateway Settings...........................................................................................4
   Modifying the OS Hosts File..............................................................................................................6
   Installing Metasys System Software Patches..................................................................................7
Technical Specifications...........................................................................................................7
Appendix: Restoring an LCS85 Using a Recovery Image DVD.............................................9
   Restoring an LCS85............................................................................................................................9

                    LCS85 Turnkey User's Guide                                                                                                  1
LCS85 Turnkey Introduction
Welcome to your new LONWORKS® Control Server 85 (MS-LCS8520-0) Turnkey! Your turnkey has been pre-configured
with all prerequisite and Johnson Controls® software installed. The LCS85 has been named, has many recommended
performance settings enabled, and has been tested and verified for proper functionality prior to shipment.

Important: Keep all collateral materials shipped with your LCS85 in a safe and accessible place. Materials shipped
           with your LCS85 Turnkey are crucial when servicing and restoring the original LCS85 image.
Follow the instructions in the Detailed Procedures section before using your turnkey. If you should ever need to
restore your LCS85 to the original factory condition, see Appendix: Restoring an LCS85 Using a Recovery Image
DVD.
For information on integrating your LCS85 Turnkey into the LONWORKS network, refer to the LONWORKS Network
Integration with NAE and LCS Technical Bulletin (LIT-1201668).

Naming Conventions
Prior to shipment, all LCS85 Turnkeys are named LCSxxxxxxxxxxxx, where xxxxxxxxxxxx is the MAC address
of the enabled Ethernet card without hyphens. For example, if the LCS85 MAC address is 00-80-66-05-0F-FC, the
initial computer name is LCS008066050FFC.
If the name of your LCS85 does not meet your requirements, refer to the LCS85 Commissioning Guide (LIT-12011568)
for procedures on changing the name of your LCS85.

LCS85 Hardware Platform
LCS85 engines ship as a 1U rack-mount server-class computer configuration (Figure 1).
See the Technical Specifications section for more information on the LCS85 hardware platform.
The 1U rack-mount chassis is designed to mount in standard 1U server rack applications. Rail and bracket mount
accessories are available.
    Figure 1: Back of LCS85 1U Rack-Mount Server Chassis Physical Features, Connectors, and Ports

Table 1: Descriptions of LCS85 Connectors
Callout                Description
1                       Serial Port
2                       Video Port (An additional video port is located on the front of the server.)
3                       Ethernet Port 1 (1 Gbps)
4                       Ethernet Port 2 (1 Gbps, disabled)
5                       Two USB Ports (Two additional USB ports are located on the front of the server.)
6                       120 VAC Power

LCS85 Ethernet Ports
The LCS85 has two Ethernet ports. However, only one is used for network connections (Figure 1). The other port
has been disabled.

LCS85 Turnkey User's Guide                                                                                         2
Port 1 is a 1 GB Ethernet port and it is the only enabled network port on the LCS85 Turnkey. Use Port 1 only to
connect to the Building Automation System (BAS) or LONWORKS network. Also use Port 1 to connect to Metasys®
servers (Application and Data Servers/Extended Application and Data Servers [ADSs/ADXs]) and other Metasys
supervisory devices.

Browser Access to the LCS85 Turnkey
Starting at Release 6.0, you use the Launcher application instead of a web browser to access the LCS85 Turnkey.
If the Launcher is not already installed on your machine, you are prompted to install it when you attempt to log in
using a web browser. Refer to the Launcher Installation Instructions (LIT-12011783).
The Launcher is a software application installed on each client computer that lets you access any Metasys server
or supervisory engine on the building network, regardless of its software version. Its purpose is to remove the
dependency on the public Java® Runtime Environment (JRE) for the Site Management Portal UI at Release 6.0 or
later by placing a private edition of the JRE on the client computer. For details, refer to the Launcher Help
(LIT-12011742).
Note: We strongly advise that you do not browse to the Metasys Site Management Portal UI from a computer
      running a server-class operating system (OS). By default, Windows® Internet Explorer® Enhanced Security
      Configuration is enabled on server-class operating systems, and may block the Launcher download page
      from which you install the Launcher application for access to the Site Management Portal. Open the Site
      Management Portal UI from a computer that is not running a server-class OS.

LCS85 Initial Configuration Values
The LCS85 ships with several factory-set initial attribute values (Table 2).
Table 2: LCS85 Initial Configuration Values
Attribute/Field Name              LCS85 Initial Value
Computer Name                          LCSxxxxxxxxxxxx (where xxxxxxxxxxxx is the MAC address of the enabled Ethernet
                                       card without hyphens.)
DHCP Client                            Enabled
                                       Note:   When commissioning an LCS85 for an Ethernet LAN that supports Dynamic
                                               Host Configuration Protocol (DHCP) and Domain Name System (DNS), we
                                               recommend configuring DHCP to assign the same IP address to an LCS85
                                               when the IP address lease expires and after the LCS85 device resets. If a
                                               different IP address is issued to the LCS85, address binding to the LCS85 from
                                               other devices breaks.
                                       Note:   If you are using a static IP address, make sure you disable DHCP in the Metasys
                                               UI. You may need to check the default gateway setting in the Registry Editor if
                                               you encounter communication problems. See the Checking the Default Gateway
                                               Settings section for details.
Site Director                          A new LCS85 is shipped as a Site Director. If an LCS85 is not going to be the Site
                                       Director, you must demote it by entering the computer name or IP address of the
                                       designated Site Director in the Site Director attribute field on the Advanced Focus tab
                                       of the LCS85.
Initial Metasys UI Login User Name MetasysSysAgent (not case sensitive)
Initial Metasys UI Login Password      Contact your local Johnson Controls representative.
Initial Windows OS Login User          MetasysSysAgent or Administrator (not case sensitive)
       1
Name
Initial Windows OS Login Password Contact your local Johnson Controls representative.

1   The Windows OS has two administrator-level user accounts. For security reasons, we strongly recommend changing the
    Windows login password for both accounts at commissioning. You can disable the Administrator account, but do not disable
    the MetasysSysAgent account.

LCS85 Turnkey User's Guide                                                                                                       3
Detailed Procedures
Starting the Computer for the First Time
Enter the 25-character Microsoft® license product key during the Microsoft Windows Setup for your LCS85 Turnkey.
The key is located on a label affixed to the top of the LCS85 1U rack-mount model.

Logging in for the First Time
Important: Do not rename the LCS85 Turnkey computer when prompted to do so by Microsoft software during
           startup. Refer to the LCS85 Commissioning Guide (LIT-12011568) for instructions on renaming the
           LCS85 Turnkey computer. If you do rename the LCS85 when prompted, the LCS85 does not function
           properly, the rename procedure in this document fails, and you must restore the LCS85. See Appendix:
           Restoring an LCS85 Using a Recovery Image DVD.
All LCS85s ship with the same initial login user name and password. The initial Metasys UI user account login user
name is MetasysSysAgent and is not case sensitive. For the MetasysSysAgent default password, contact your
local Johnson Controls representative.
You must use the initial MetasysSysAgent user name and password to log in to any LCS85 the first time. For security
reasons, you must change the password at the first login, before the LCS85 goes online in a Metasys network. You
can also change your password at any time in the future.
When you change your account password for MetasysSysAgent user in the LCS85 Site Management Portal UI,
your Windows account password does not automatically change to match. If you want your Site Management Portal
UI and Windows passwords to match, you must change your Windows account password manually.
The Windows OS uses Windows Password Policy rules to establish criteria for the OS account password’s complexity
and duration. The MetasysSysAgent account login password must conform to the password policy rules established
in the LCS85 OS. If the MetasysSysAgent account password does not conform to the password policy, any attempt
to change the MetasysSysAgent password fails. Contact the Field Support Center if you cannot change the password.
The Windows OS has two administrator level user accounts: MetasysSysAgent and Administrator. For security
reasons, we strongly recommend changing the Windows login password for both accounts. You can disable the
Administrator account, but do not disable the MetasysSysAgent account. See Table 2.
When using an LCS85 that is in a Windows domain or on a network where the password policy is controlled, consult
the IT department to ensure that the MetasysSysAgent account password conforms to the network password policy
and remains in sync with the OS login password.
Any new Metasys user accounts you create for the LCS85 are unaffected by the Windows Password Policy rules.
Refer to the Security Administrator System Technical Bulletin (LIT-1201528) for information on creating new Metasys
user accounts and changing Metasys login passwords.
Note: When you change or add a login user name or password, record the new user name and password and store
      them in a safe location. You cannot access the Site Management Portal UI without a valid user name and
      password.

Setting the Time Zone, Date, and Time
The procedure you use to set the time zone, date, and time on an LCS85 depends on how the LCS85 fits into the
Metasys site hierarchy. Refer to Appendix: Time Zone, Date, and Time Management in the LCS85 Commissioning
Guide (LIT-12011568) for information and detailed procedures on setting time zone, date, and time on an LCS85
and on a Metasys network.

Checking the Default Gateway Settings
Important: This procedure applies to turnkeys with Metasys releases prior to Release 6.0.
All turnkeys ship with DHCP enabled. When you set your static IP address, you also need to check that your default
gateway settings remain in case of a power failure or when you restart your computer. If you lose your default
gateway settings, you may encounter communication problems with devices outside your current subnet.

LCS85 Turnkey User's Guide                                                                                       4
To prevent this issue, follow these steps to check your default gateway settings through the Registry Editor:
1. On the Start menu, type regedit in the Start Search field and press Enter. The Registry Editor appears.
2. Browse to the Interfaces folder using the following path: HKEY_LOCAL_MACHINE > SYSTEM >
   CurrentControlSet > services > Tcpip > Parameters > Interfaces.
3. Browse each interface and check the IPAddress entry to find the IP address that matches the static IP address
   of your turnkey (Figure 2).
   Note: If you do not know your static IP address, you can find it by entering ipconfig at the command prompt
         (Figure 3).
                             Figure 2: Matching Your Static IP Address in the Registry Editor

                       Figure 3: Finding Your Static IP Address Using the Command Prompt

4. In the same window where your IP address appears, double-click DefaultGateway (Figure 4). The Edit Multi-String
   window appears.

LCS85 Turnkey User's Guide                                                                                       5
                                      Figure 4: Default Gateway in Registry Editor

5. If your default gateway address appears below a blank line (Figure 5), delete this blank line to ensure your default
   gateway settings are preserved.
                                Figure 5: Extra Space Above Default Gateway Address

Modifying the OS Hosts File
You must modify the Microsoft Windows hosts file in order to access the Metasys Site Management Port UI. You
must also perform this procedure when you purchase a new turnkey.
1.   Go to Start > All Programs > Accessories. (If you are using Windows Server® 2012 R2 or Windows Server
     2012, type Notepad from the Start screen.)
2.   Right-click Notepad and select Run as administrator. Notepad opens.
3.   On the File menu, click Open.
4.   In the drop-down selection box in the lower-right corner of the Open dialog box, select All Files (*.*).
5.   Browse to C:\Windows\System32\drivers\etc.

LCS85 Turnkey User's Guide                                                                                           6
6. Select the hosts file.
7. Click Open.
8. Locate the line that contains 127.0.0.1.
9. Delete the # in front of 127.0.0.1.
10. On the File menu, click Save.

Installing Metasys System Software Patches
Be sure to install any Metasys software patches that were released after the image for your LCS85 Turnkey was
created. For example, a Release 6.5 LCS85 Turnkey solution does not have any Release 6.5 patches applied to it,
regardless of when you order it.
To install Metasys system software patches:
1. Browse to one of the following locations:
   Field Support Center (FSC) Product Quick Patches page at
   http://publish.johnsoncontrols.com/content/controls/us/eng/fsc/hf/Metasys_Quick_Patches.html
   For North American Authorized Building Controls Specialists (ABCS) Partners, go to the ABCS Exchange site
   under Metasys > Technical Support > Software Patches.
2. Search for patches that apply to the LCS85 for the Metasys software release installed on your LCS85 Turnkey
   solution.
3. Follow patch installation instructions to install the patch.

Technical Specifications
Table 3: MS-LCS8520-0
Computer Type                            Dell® PowerEdge® R420 or latest equivalent
Power Requirement                        100–240 VAC 50/60 Hz
Power Supply                             480 W
Ambient Operating Conditions             10 to 35°C (50 to 95°F); 20 to 80% RH, noncondensing (twmax=29C)
Ambient Storage Conditions               -40 to 65°C (-40 to 149°F); 5 to 95% RH, noncondensing (twmax=38C)
Data Protection                          Recommended UPS: APC® Smart-UPS SC 450 VA, 280 W, 120 VAC input/output,
                                         NEMA 5-15R output connections, OEM Part No. SC450RM1U
Processor                                Intel® Xeon® E5506, 2+ GHz, 4 MB Cache2 or comparable (subject to availability)
Memory                                   2 GB or more, 1066 MHz or higher, 2 x 1 GB, single ranked UDIMMs for 1
                                         processor
Hard Disk                                2 total (providing ample storage space, size subject to availability), 7.2k RPM
                                         SATA, 8.9 cm (3.5 in.) cabled
                                         3 Gbps, RAID 1 configuration with add-in SAS6/iR (SATA/SAS Controller) or
                                         higher
Internal Optical Drive                   DVD ROM, SATA
Operating System                         Windows Server® 2012 R2 Standard
Antivirus Software                       Symantec® Endpoint Protection, Small Business Edition (latest version)
Network and Serial Interfaces            2 RJ45 1 Gbps Ethernet Ports, Port 2 is disabled
                                         2 video ports; 1 front, 1 back
                                         1 9-pin Serial port
                                         4 USB ports (2 front, 2 back)
Dimensions                               4.3 x 43.4 x 62.7 cm (1.7 x 17.1 x 24.7 in.)
(Height x Width x Depth)
Mounting                                 Mount in an EIA-310D compatible server cabinet

LCS85 Turnkey User's Guide                                                                                                 7
Table 3: MS-LCS8520-0
Shipping Weight                           15.9 kg (35 lb)
Compliance                                Europe: CE Mark (Record Holder: http://www.dell.com/regulatory_compliance)

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable
for damages resulting from misapplication or misuse of its products.

LCS85 Turnkey User's Guide                                                                                             8
Appendix: Restoring an LCS85 Using a Recovery Image DVD
Use this procedure if you need to restore your LCS85 Turnkey to the condition in which you received it from the
factory. This procedure may be required in the case of an LCS85 software failure that prevents you from accessing
or operating the LCS85.

Important: Keep all collateral shipped with your LCS85 in a safe and accessible place. Materials shipped with your
           LCS85 Turnkey are crucial when servicing and restoring the original image.

Important: Restore the LCS85 only as a final course of action when you experience problems with the LCS85
           Turnkey, after you troubleshoot the system, and contact the Field Support Center (FSC). You lose all
           database information and settings if you follow this procedure. This procedure returns the LCS85 to
           the factory-original condition in which you received it.

Important: Recovery media is to be used only with the LCS85 Turnkey computer you purchased. Do not use
           recovery media on a non-Turnkey computer or on a different Turnkey computer.
To restore an LCS85, you need the following:
•    monitor, keyboard, and mouse
•    the LCS85 recovery image disk that shipped with your LCS85

Restoring an LCS85
1.   Obtain the 25-character Windows product key for the LCS85. The product key is located on a label on the top
     of the 1U rack-mount chassis.
2.   Connect the monitor, keyboard, and mouse to the LCS85, if not connected already.
3.   Disconnect the network cable from the LCS85, if it is connected.
4.   Place the recovery image DVD in the DVD drive.
5.   Restart the LCS85 computer. As the computer restarts, the operating system detects the bootable disk in the
     drive and displays Press any key to boot from CD or DVD.
6.   Press any key to begin the restoration process. If you did not press a key in time, restart the computer and try
     again.
     After a few moments, a Progress window appears and indicates Windows is loading files.
     Several minutes later, a warning message appears (Figure 6).
                                              Figure 6: Warning Message

7.   Click OK to begin the recovery process. After the system is reloaded and all files are restored, a Restore
     Complete message appears and the LCS85 computer restarts.

LCS85 Turnkey User's Guide                                                                                          9
                                         Figure 7: Restore Complete Message

8.   When the computer begins to restart, eject the disk from the drive. If the message Press any key to boot from
     CD or DVD appears again, you did not remove the disk in time. In this case, do not press any key while this
     message is displayed, or the restore process begins again. If the message appears, restart the computer again
     and repeat this step.
    When the restart completes, the LCS85 is in original factory condition.
9. Defragment the LCS85 hard drive to maximize server performance and protect your data. On the Start menu,
    click All Programs > Accessories > System Tools > Disk Defragmenter. (If you are using Windows Server 2012
    R2 or Windows Server 2012, type Defragment and Optimize Drives from the Start screen, then click Defragment
    and Optimize Drives in the Apps results.)
10. Connect Ethernet Port 1 on the LCS85 to the building network. This connection allows access to the BACnet®
    and LONWORKS networks.

     Important: Before attempting to access the Site Management Portal UI for the first time, the LCS85 must be
                connected to an active network at Ethernet Port 1 and restarted. Failure to follow this sequence
                prevents the LCS85 object from appearing in the Metasys UI navigation panel.
11. Restart the computer.
12. Browse to and log in to the LCS85 Site Management Portal UI.
     The initial login user name is MetasysSysAgent and is not case sensitive. For the MetasysSysAgent default
     password, contact your local Johnson Controls representative.
    Note: You must change the login account password for your LCS85. In some network scenarios, we recommend
           creating a new Metasys user account for the LCS85.
13. Make sure the required Computer Name (host name) value appears on the Network tab. Set the DHCP value
    to False if DHCP is not required on the network. Refer to the Establishing the LCS85 Network Parameters
    section in the LCS85 Commissioning Guide (LIT-12011568) for detailed procedures.
     Note: If you are using a static IP address, check your default gateway setting. See the Checking the Default
           Gateway Settings section for details.
14. Configure the time zone, date, and time settings in the LCS85 Metasys UI. Refer to the LCS85 Commissioning
    Guide (LIT-12011568) for detailed procedures for setting the time zone, time, and date on an LCS85.
     Note: Time Zone, Date, and Time must be set in the Site Management Portal UI. Do not use the Windows
           time dialog box to set the time zone, date, or time on the LCS85.
15. Configure the Site Director and Object Name for the LCS85 on the Focus tab. Refer to the Establishing Basic
    LCS85 Parameters in the Focus Screen section of the LCS85 Commissioning Guide (LIT-12011568) for detailed
    procedures.

LCS85 Turnkey User's Guide                                                                                     10
16. Access the System Configuration Tool (SCT) UI, and download the most recent archive database for the LCS85
    from the SCT. For information on downloading an archive database, refer to Database Uploading, Downloading,
    and Synchronization in the Metasys system Help (LIT-1201793).
     Note: All data recorded on the LCS85 since the archive database was last backed up is lost.
     The LCS85 is now restored and operational on the Metasys site.

                                                                                                               Building Efficiency
                                                                                      507 E. Michigan Street, Milwaukee, WI 53202
                                  Metasys®, Panoptix®, and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                     All other marks herein are the marks of their respective owners. © 2014 Johnson Controls, Inc.

Published in U.S.A.                                                                                      www.johnsoncontrols.com
LCS85 Turnkey User's Guide                                                                                                      11

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.