LCS85 Product Bulletin

                          MS-LCS85SW-x

Johnson Controls                                   LIT-12011549
www.johnsoncontrols.com                  2018-12-17 Release 10.0
                                                                      Contents
LonWorks Control Server (LCS) 85 Overview................................................................................ 3
Contents
           Features and Benefits........................................................................................................................... 3

LCS85 Networking............................................................................................................................ 4

           Object Support.......................................................................................................................................4

           Launcher Application............................................................................................................................ 4

           IP Ethernet Network..............................................................................................................................4

           Remote Site Communication............................................................................................................... 5

           ADS/ADX..................................................................................................................................................5

           Automation Level Communication......................................................................................................5

           LonWorks Network................................................................................................................................5

           BACnet Protocol..................................................................................................................................... 5

Flat LonWorks System......................................................................................................................5

Software for Efficient Building Operation..................................................................................... 6

           Conclusion.............................................................................................................................................. 7

Ordering Information...................................................................................................................... 8

LCS85 Technical Specifications..................................................................................................... 10

Points of single contact................................................................................................................. 11

North American Emissions Compliance...................................................................................... 11

           Canada.................................................................................................................................................. 11

           United States........................................................................................................................................11
LonWorks® Control Server (LCS) 85 Overview
The LonWorks® Control Server (LCS) 85 uses an open-architecture flat LonWorks system to monitor
and supervise HVAC equipment, lighting, security, fire, and access control. The LCS85 supports a
comprehensive set of supervisory features and functions for large facilities and technologically
advanced buildings and complexes. The LCS85 is a high-capacity server that allows the integration
of large LonWorks network systems. When configured as the Site Director, the LCS85 can support
up to four Metasys® network engines.
A single LCS85 within a building provides monitoring and control, alarm and event management,
data exchange, trending, energy management, scheduling, and data storage.
The LCS85 supports 10,000 objects, but is capable of supporting up to 25,000 objects when
enhanced with a 15,000-object upgrade.
The LCS85 has an embedded user interface that supports concurrently connected web browsers
with password access control and the security protection technology of the IT industry.
For details about LCS8520 hardware and software requirements, see LCS85 Technical Specifications.
For information about product ordering, see Ordering Information.

Features and Benefits
   CEA-852 Tunneling
        Extends the distance of hard-wired field controllers, and minimizes the cost of remote
        installations by eliminating the need of a local network engine.

   Communication Using Commonly Accepted IT Standards at the Automation and Enterprise
   Level
        Installs on the existing IT infrastructure within a building or enterprise and integrates the
        existing network using standard IT communication services over the company intranet, wide
        area network, or public Internet with firewall protection.

   Web-Based User Interface
        Provides user access to LCS85 system data from any supported web browser device
        connected to the network and eliminates need for separate web server.

   Site Director Function
        Provides user access to all data on one site through one device; the Site Director coordinates
        the display of data from multiple LCS85s for easy navigation through the entire site.

   Embedded Site Management Portal System Configuration Software
        Provides user with password-protected access to system configuration, monitoring,
        commanding, and diagnosis from any device with web browser software without the need
        for separate workstation software.

   Support for Web Services at the Automation Network Level
        Develops facility-specific advanced data interfaces and applications.

   Supervision of Field Controller LonWorks Networks
        Supports connectivity to open network standards for complete flexibility in selection of field
        devices. Supported protocols include LonWorks and BACnet/IP.

LCS85 Product Bulletin                                                                              3
     Trending, Totalization, and Alarming Functions Automatically Regenerated in the Metasys
     System
         Protects functionality using the data recording capabilities, fully integrates processing
         presentation, and provides storage of LonWorks network data in the web-enabled system.
     Scalable System Integration Solution for Integrating and Migrating LonWorks Networks
         Integrates LonWorks devices in one building, a network of small buildings, or multiple
         LonWorks networks in a large building complex, providing new technology while protecting
         existing investment.

     Support for up to 25,000 Objects
         Minimizes the quantity of required network engines and accommodates large LNS
         databases.

LCS85 Networking
The LCS85’s unique ability within a Metasys system is integrating LonWorks networks over IP. This
network integration allows you to build an extremely flexible network at the automation and
enterprise level of your system, as well as at the field controller and data acquisition levels.

Object Support
The LCS85 supports 10,000 objects on the LonWorks network, but is capable of supporting up
to 25,000 objects if you use MS-15KUPG-0 to enhance the LCS85 with a 15,000-object software
upgrade. If you upgrade your system, the maximum amount of permanent status objects is
11,000. Permanent status objects include COV Trends (not sample-based), Alarm Extensions, Global
Data Shares, and other objects involved in logic or other Metasys features. For a complete list of
permanent status objects, refer to the LonWorks® Network Integration with NAE and LCS Technical
Bulletin (LIT-1201668).

Launcher Application
The Launcher is a software application that lets you access any LCS85 server or network engine on
the building network, regardless of its software version. If the Launcher is not already installed on
your machine, you are prompted to install it when you browse to any Metasys server or network
engine on the building network. After you install the Launcher software, use it to launch the SMP
UI. Refer to the Launcher Tool Help (LIT-12011742).

IP Ethernet Network
The LCS85 connects directly to IP Ethernet networks running at 10, 100, or 1,000 Mbps. Multiple
LCS85s communicate with each other over the network, and one LCS85 can act as the Site Director.
Authorized users log in to the Site Director via a supported browser to access the entire Metasys
system for the site. Data transmission on the network uses standard IT protocols, services, and
formats. Networks in different buildings may be interconnected using standard WAN technologies
and network service providers. The speed of transmission depends on the technology used.

 4                                                                                LCS85 Product Bulletin
Remote Site Communication
Remote access to the LCS85 SMP UI can be established from any computer on the building
network, or set up over the Internet using an Internet service provider (ISP) line to the LCS85
Ethernet port. Local access is also possible directly from the LCS85 server.

ADS/ADX
The ADS/ADX (Application and Data Server/Extended Application and Data Server) is an optional
software package running on a computing platform that provides a location for long-term storage
of the system configuration database, trend logs, alarm logs, audit trails, and graphics.
An ADS/ADX can also be configured as the Site Director to allow more concurrent users and
coordinate access to all components on a site via a web browser connected over the network or
Internet. Refer to the Application and Data Server (ADS) and Extended Application and Data Server (ADX)
Product Bulletin (LIT-1201525) for more information about ADSs and ADXs.

Automation Level Communication
The LCS85 communicates internal system data using peer-to-peer messaging over the IP Ethernet
network. Each LCS85 shares data and has access to information on the other LCS85s connected on
the network, which enables coordination and control of the entire building management system.

LonWorks Network
The LCS85 supervises LonWorks devices using LonMark® guidelines. The LonWorks network
interface supports all LonMark certified devices, including Johnson Controls® devices, such as the
LN Series Controllers, the NexSys controller line, including the LonWorks programmable FSC.

BACnet Protocol
Although the primary function of the LCS85 is to supervise many LonWorks devices over an IP
network, it can also integrate devices through BACnet/IP communications. For example, a preferred
metering device that uses BACnet/IP could be used with the Demand Limiting Load Rolling (DLLR)
feature to shed appropriate loads on the LonWorks network.

Flat LonWorks System
The LCS85 integrates into the LonWorks network using an open-architecture flat LonWorks system.
In a basic flat LonWorks system, the network is managed by a single, LNS Computer running an
LNS-based network management tool, such as LN Builder or LonMaker.
The LCS85 communicates over the TCP/IP network with LonWorks IP routers using the CEA 852-A
protocol standard. In a flat LonWorks system, a Configuration Server is necessary to manage the
membership of the channel so that all devices can route traffic to one another.
     Note: The designated Configuration Server must be either a Loytec L-IP router or an Echelon
     Configuration Server. See Table 1 for ordering information.

The following example shows a complex flat LonWorks system setup with the Configuration Server
positioned at IP address 10.100.5.1.

LCS85 Product Bulletin                                                                              5
                            Figure 1: Flat LonWorks System

Refer to the LonWorks® Network Integration with NAE and LCS Technical Bulletin (LIT-1201668) for more
information on the LonWorks network and flat LonWorks system.

Software for Efficient Building Operation
The LCS85 supports virtual environments, including VMWare® and Microsoft® Hyper-V™. Refer to
the Network and IT Guidance Technical Bulletin (LIT-12011279) for more information.
The LCS85 installs with the latest version of the Metasys system software, which provides the
following features:
• Site Management Portal User Interface provides data and graphic screens to supported web
  browsers. Authorized users log in to the LCS85 using the Launcher application to access the
  SMP. This embedded user interface is ideal for smaller networks and remote locations where a
  dedicated computer platform to support a user interface is not required.

• System Security enables an LCS85 to recognize legitimate users with valid user IDs and
  passwords at the SMP UI. User access data is encrypted in the transmission and in the LCS85
  database. The system administrator manages user profiles, authorization levels, user ID,
  password, and specific LCS85 data access privileges in each user account.

• Basic Access allows access to a subset of the standard SMP capabilities based on their assigned
  permissions.

• RADIUS Server Accounts allow you to optionally authenticate non-local users through a Remote
  Authentication Dial-in User Services server.

• Monitoring and Control collects data from the field devices and then coordinates and sends the

 6                                                                               LCS85 Product Bulletin
   required commands to the controlled equipment at the required priority.

• Global Search allows you to search the Metasys system and manage lists of objects, which can be
  used by other features for commanding, trending, reporting, and object selection.

• Global Command allows you to send a single command to multiple objects, and view a log of the
  command results.

• Transaction Recording audits and logs all user actions performed through the LCS85.

• Alarm and Event Processing enables the LCS85 to send alarm and event messages to web
  browsers, pagers, email servers, Network Management Systems, and serial printers, as well as
  store and view alarm and event logs on the LCS85 and transfer it to an ADS/ADX or ODS.

• Historical Trend Data can be collected by the LCS85 for any monitored value at user-defined
  intervals, or trending can be based on COV. You can use trend logs to analyze building system
  performance and locate system problems. LCS85 trend logs can be transferred to the ADS/ADX
  or ODS at defined intervals or when the LCS85 logs are full.

• Totalization Data allows you to monitor energy (and other consumables) use and generate cost
  reports to support utility cost reductions, and also provides data for service, maintenance, and
  early identification of building system problems.

• Trend Studies allows you to view multiple trend extensions based on the selection of items.

• Scheduling allows you to define occupancy periods and start and stop times for mechanical
  or electrical equipment. Operating parameters can be set according to time of day, days of the
  week, holiday, or for calendar dates.

• Network-Wide System Interlocking enables the LCS85 to collect field controller data, make
  logical comparisons, and issue relevant commands to other field controllers anywhere on the
  network. Interlocking also enables data sharing between controllers.

• Optimal Start automatically determines the best time to start heating and cooling systems
  to ensure that the facility is ready for occupants. It adjusts to seasonal variations and reduces
  energy use.

• DLLR monitors energy meters for electricity, gas, steam, or water, and helps control energy
  consumption. Demand Limit helps manage utility demand charges. Load Rolling controls
  equipment operating levels to reduce total energy consumption. Comfort overrides prioritize
  equipment shedding.

Conclusion
The LCS85 affirms Johnson Controls position as a leader in the BAS industry and as an innovator of
solutions for the complete management of buildings. The integration of IT and Internet standards
into the LCS85 platform, as well as the use of open protocols for field networks, bring the benefits
of the global communications and control industries into one system. Web browser-based access
from any location is key to the effective use of the automation network.
The Metasys system continues to be the integrating network within buildings and has now
been extended to bridge the gap between traditional control systems and the business and
communication network systems of the enterprise.
The LCS85 and Metasys web-enabled network are wise investments that yield returns to the
building owner and operator far into the future.

LCS85 Product Bulletin                                                                                7
Ordering Information
Table 1 provides the product code numbers for the LCS85 and its accessories. A flat LonWorks
system requires a minimum of either one Loytec L-IP router designated as the Configuration
Server, or an Echelon® Configuration Server. If you upgrade the system using MS-15KUPG-0, the
maximum number of permanent status objects is 11,000. Refer to the LonWorks® Integration with
NAE and LCS Technical Bulletin (LIT-1201668) for a complete list of permanent status objects.
Table 1: LCS85 and LCS85 Accessory Ordering Information

Product Code Number                      Description
MS-LCS85SW-0                             License to enable the LCS85 software and the LonWorks
                                         software driver for new installations or projects
MS-LCS85SW-6                             License to enable the LCS85 software for upgrading
                                         existing LCS85s
MS-LCS85SW-SCS                           Software subscription for LCS85 software, one year
MS-LCS85SW-SC3                           Software subscription for LCS85 software, three years
MS-15KUPG-0                              Software upgrade license for support of additional 15,000
                                         objects
SC450RM1U (OEM Part No.)                 Recommended UPS for LCS85: APC Smart-UPS SC 450
                                         VA, 280 A 120 VAC input/output with NEMA 5-15R output
                                         connections
MS-EXPORT-0                              License to enable the Metasys Export Utility software for
                                         new installations or projects
MS-COPY-LCS85SW                          DVD copy of unlicensed LCS85 software

     Note: MS-EXPORT-0 is a stand-alone product. For more information, refer to the Metasys
     System Software Purchase Options Product Bulletin (LIT-12011703).

Table 2 lists part numbers for ordering Loytec L-IP routers. Loytec L-IP routers are not included in
the LCS85 product offering and are ordered separately. Loytec's Embedded IP-852 Configuration
Server is recommended, but not required. If more than one Loytec L-IP router is used, only
one needs to have the IP-852 Configuration Server enabled. If you do not use Loytec's IP-852
Configuration Server, then you must use Echelon's IP-852 Configuration Server. No other IP-852
Configuration Servers are approved for use with the LCS85.
Table 2: Loytec L-IP Routers Ordering Information

Product Code Number                      Description
LIP-3ECTB                                Router with 1 FTT10 channel and Embedded IP-852
                                         Configuration Server
LIP-33ECTB                               Router with 2 FTT10 channels and Embedded IP-852
                                         Configuration Server
LIP-3333ECTB                             Router with 4 FTT10 channels and Embedded IP-852
                                         Configuration Server

     Note: The LIP-3ECTB is the preferred Loytec L-IP router for use with the LCS85.

Table 3 lists ordering codes for other routers compatible with the LCS85. You can use these devices
to route the LonWorks field networks, but you cannot use them as the Configuration Server.
Contact your nearest Johnson Controls® representative to order.

 8                                                                                LCS85 Product Bulletin
Table 3: LCS85 Compatible Router Ordering Information

 Product Code Number                    Description
 Echelon Products

 LN-72101R-400
                  1                     i.LON SmartServer FT

 LN-72102R-400
                  1
                                        i.LON SmartServer FT with Modem

 LN-72101R-408                          i.LON SmartServer FT with IP-852 Routing

                                        LN-72101R-408
 LN-72102R-408                          i.LON SmartServer FT with IP-852 Routing and Modem
 LN-72101R-409
                  1
                                        i.LON SmartServer FT with Programmability

 LN-72102R-409
                  1
                                        i.LON SmartServer FT with Programmability and Modem

 LN-72101R-410                          i.LON SmartServer FT with IP-852 Routing and
                                        Programmability
 LN-72102R-410                          i.LON SmartServer FT with IP-852 Routing, Modem, and
                                        Programmability
 LN-72102-308                           i.LON 100 E3 FT with Modem and IP-852 Routing
 LN-72650R                              i.LON 600 and MPR-50 Multi-Port Router Bundle
 72601                                  i.LON 600 Server TP/FT-10CH90
 72603                                  i.LON 600 Server TP/FT-10CH24
 72160                                  Optional IP-852 Router Activation Key
 Adept Systems Products
 GR4A-EFNNI                                      2
                                        GRouter4 with Ethernet, FTT-10 Transceiver, No Internal FT
                                                 2
                                        Terminator, Screw Terminal Blocks
 GR4A-EFTNI                                      2
                                        GRouter4 with Ethernet, FTT-10 Transceiver, Internal FT
                                        Terminator, Screw Terminal Blocks
 GR4A-EFNPI                                      2
                                        GRouter4 with Ethernet, FTT-10 Transceiver, No Internal FT
                                        Terminator, Pluggable Terminal Blocks
 GR4A-EFTPI                                      2
                                        GRouter4 with Ethernet, FTT-10 Transceiver, Internal FT
                                        Terminator, Pluggable Terminal Blocks
 CNS Products
 CNSNeNode IV/1/1/1/1                   eNode™ LON/IP Router
                                                               2

1   The Optional IP-852 Router Activation Key (code no. 72160) is required for LCS85 server
    compatibility because these devices do not have IP-852 routing capability pre-installed. You
    must purchase code no. 72160 with this model.
2   Requires 5 VDC power supply and must have firmware version 4.10.038 or better.

LCS85 Product Bulletin                                                                             9
LCS85 Technical Specifications
Table 4: LCS85 Software System Recommendations for Installation/Upgrade

Recommended              Intel Xeon E5506, 2.13 GHz, 4 MB Cache
Computer Platform
                         2 x 160 GB 7.2K SATA, 8.9 cm (3.5 in.) Cabled

                         3 Gbps, RAID 1 configuration with add-in SAS6/iR (SATA/SAS Controller)
Recommended Memory       8 GB RAM minimum
Hard Disk                160 GB minimum
Supported Operating      • Windows® Server® 2016 (64-bit)
Systems and Software     • Windows® Server® 2012 R2 with Update 1 (64-bit)
                         • Windows® Server® 2012 (64-bit)
                             Note: Microsoft .NET Framework 3.5 Service Pack (SP) 1 and
                             Microsoft .NET Framework 4.6.1 are required for LCS85 software.
Internal Optical Drive   DVD ROM, SATA
Supported Web Browser    Windows® Internet Explorer® 11.0.9600.18816 Update version 11.0.47
Software for Metasys     or later
Site Management Portal
                             Note: In Internet Explorer 11, select the Use Microsoft
Client Computers
                             compatibility lists option, found under Tools > Compatibility View
                             Settings, to ensure that websites appear and function correctly.

                         Google® Chrome™ version 61 or later

                         Apple® Safari® 11 or later

                         Other browsers, such as Mozilla® Firefox®, may also be used but are
                         not fully supported.
Supported Virtual        Microsoft Hyper-V™, VMWare®
Environments
Network Communication Selectable Network Interface (if computer has multiple network cards,
                      during LCS85 installation, select the network card that was configured
                      for Metasys system use before installation)

                         Ethernet network interface card 10/100/1000 Mbps (100 Mbps or better
                         recommended)
Recommended Data         Uninterruptible power supply (UPS)
Protection
                         Smart-UPS SC 450VA, 280 W, 120 VAC input/output, NEMA 5-15R output
                         connections, OEM Part No. SC450RM1U

10                                                                           LCS85 Product Bulletin
Points of single contact
 APAC                                         Europe                     NA/SA
 JOHNSON CONTROLS                             JOHNSON CONTROLS           JOHNSON CONTROLS

 C/O CONTROLS PRODUCT MANAGEMENT              WESTENDHOF 3               507 E MICHIGAN ST

 NO. 32 CHANGJIJANG RD NEW DISTRICT           45143 ESSEN                MILWAUKEE WI 53202

 WUXI JIANGSU PROVINCE 214028                 GERMANY                    USA

 CHINA

North American Emissions Compliance

Canada

 This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing
 Equipment Regulations.

 Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le
 matériel brouilleur du Canada.

United States

 This equipment has been tested and found to comply with the limits for a Class A digital device
 pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
 against harmful interference when this equipment is operated in a commercial environment.
 This equipment generates, uses, and can radiate radio frequency energy and, if not installed
 and used in accordance with the instruction manual, may cause harmful interference to
 radio communications. Operation of this equipment in a residential area may cause harmful
 interference, in which case the users will be required to correct the interference at their own
 expense.

LCS85 Product Bulletin                                                                              11
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document
revision and are subject to change without notice.

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.