VG1000 Series Forged Brass Ball Valves Installation Instructions

Вид документаІнструкція
ВиробникJCI
МоделіVG1241, VG1245, VG1271, VG1275, VG1291, VG1295, VG1841, VG1845
Група обладнанняvalves
Мова документаанглійська
Розмір файлу0.3 МБ

Про документ

VG1000 Series forged brass ball valves regulate the flow of hot or chilled water (and on some models low-pressure steam) in response to a controller demand in HVAC systems. They are intended for use as an operating control only, with additional supervisory or safety devices designed into the system where failure could cause injury or property damage. Models are available in two-way and three-way configurations with NPT, sweat, or press end connections.

Ключові дані

ServiceHot Water, Chilled Water, 50/50 Glycol Solutions, and 15 psig (103 kPa) Saturated Steam for HVAC Systems
Maximum Closeoff Pressure200 psig (1,378 kPa)
Valve Body Pressure Rating580 psig (3,996 kPa) at 203°F (95°C) (PN40)
RangeabilityGreater than 500:1
Leakage0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
End ConnectionsNPT 1/2 to 2 in. (DN15 to DN50); Sweat and Press 1/2 to 1 in. (DN15 to DN25)
Body MaterialForged Brass

Застосування

  • Regulating flow of hot water, chilled water, and 50/50 glycol solutions in HVAC heating/ventilating/air-conditioning systems
  • Low-pressure steam service (VG12x5 Series): 15 psig (103 kPa) saturated steam at 250°F (121°C)
  • Two-way valve applications: Port A supply, Port B return; mount valve downstream from the coil
  • Three-way valve applications: Port A coil inlet, Port B bypass inlet, Port C common/return

Особливості

  • Forged brass body with chrome plated brass ball (x1 series) or 300 series stainless steel ball (x5 series)
  • Blowout-proof stem: nickel plated brass (x1) or 300 series stainless steel (x5)
  • Graphite-reinforced PTFE seats with EPDM O-ring backing; EPDM double O-ring stem seals
  • Flow-characterizing disk (Amodel® AS-1145HS polyphthalamide resin) located in Port A; Port A must be the inlet/coil connection
  • Press end connections compatible with RIDGID® press tools (ProPress® compatible); integral O-ring seal — never use sealant or pipe dope
  • Compatible with a wide range of Johnson Controls actuators (VA9104, VA9203, VA9208, M9102/M9104/M9106/M9109/M91xx) via direct mount or M9000-series linkage kits
  • Optional M9000-561 thermal barrier and M9000-330/340/341 weather shield enclosures
  • Equal percentage flow characteristics (two-way; three-way in-line port), linear on three-way angle/bypass port

Технічні дані

Parameter Value
Service Hot Water, Chilled Water, 50/50 Glycol Solutions, and 15 psig (103 kPa) Saturated Steam for HVAC Systems
Fluid temperature limits, Water VG12x1 and VG18x1 Series: 23 to 203°F (-5 to 95°C); VG12x5 and VG18x5 Series: -22 to 284°F (-30 to 140°C)
Fluid temperature limits, Steam VG12x5 Series: 15 psig (103 kPa) at 250°F (121°C); VG12x1 Series: Not Rated for Steam Service
Actuator maximum fluid operating temperature limit 212°F (100°C): VA9104, VA9203, VA9208, M9104 with M9000-551 linkage; 284°F (140°C): M9106 or M9109 with M9000-520 linkage, VA9104 / VA9203 / VA9208 with M9000-561 thermal barrier
Valve body pressure/temperature rating, Water VG1241, VG1245, VG1841, VG1845: 580 psig (3,996 kPa) at 203°F (95°C) (PN40); 464 psig (3,196 kPa) at 284°F (140°C) (PN40). VG1271, VG1275, VG1871, VG1875: 300 psig (2,067 kPa). VG1291, VG1295, VG1891, VG1895: 300 psig (2,067 kPa)
Steam rating 15 psig (103 kPa) Saturated Steam
Maximum closeoff pressure 200 psig (1,378 kPa)
Maximum recommended operating pressure drop 50 psi maximum differential pressure; 30 psi maximum for quiet service ball valves
Flow characteristics Two-way: equal percentage; Three-way: equal percentage (in-line/coil port), linear (angle/bypass port)
Rangeability Greater than 500:1
Minimum ambient operating temperature -4°F (-20°C) VA9104, M9104, M9106, M9109; -22°F (-30°C) VA9203; -40°F (-40°C) VA9208
Maximum ambient operating temperature (limited by actuator) 140°F (60°C) VA9104, M9104, VA9203, VA9208 (direct mount or with M9000-561 thermal barrier); 125°F (52°C) M9106 with M9000-5xx linkage; 122°F (50°C) M9100 with M9000-5xx linkage
Leakage 0.01% of maximum flow per ANSI/FCI 70-2, Class 4; 1% of maximum flow for three-way bypass port
End connections National Pipe Thread (NPT): 1/2 to 2 in. (DN15 to DN50); Sweat: 1/2 to 1 in. (DN15 to DN25); Press (ProPress® Compatible): 1/2 to 1 in. (DN15 to DN25)
Body material Forged Brass
Ball material VG12x1/VG18x1: Chrome Plated Brass; VG12x5/VG18x5: 300 Series Stainless Steel
Blowout-proof stem VG12x1/VG18x1: Nickel Plated Brass; VG12x5/VG18x5: 300 Series Stainless Steel
Seats Graphite-Reinforced Polytetrafluoroethylene (PTFE) with Ethylene Propylene Diene Monomer (EPDM) O-Ring Backing
Stem seals EPDM Double O-Rings
Characterizing disk Amodel® AS-1145HS Polyphthalamide Resin

Варіанти замовлення

Related installation instruction documents (actuators, linkages, accessories):

  • VA9104-xGA-2S / -3S Electric Non-Spring Return Actuators (Part No. 14-1336-15 / 14-1336-23)
  • M9102-AGA-2S/-3S and M9104-xGA-2S/-3S Electric Non-Spring Return Actuators (Part No. 34-636-1220 / 34-636-1433)
  • M9106-xGx-2 Series Electric Non-Spring Return Actuators (Part No. 34-636-1085)
  • M9109 Series Electric Non-Spring Return Actuators (Part No. 34-636-1190)
  • VA9203-AGx-2Z On/Off and Floating Point Spring Return Actuators (Part No. 14-1380-8)
  • VA9203-Bxx-2 On/Off Spring Return Actuators (Part No. 14-1380-16)
  • VA9203-GGx-2Z Proportional Spring Return Actuators (Part No. 14-1380-24)
  • VA9208-AGx-x On/Off and Floating Point Spring Return Actuators (Part No. 14-1379-5)
  • VA9208-Bxx-x On/Off Spring Return Actuators (Part No. 14-1379-13)
  • VA9208-GGx-x Proportional Spring Return Actuators (Part No. 14-1379-21)
  • M9108, M9116, M9124, M9132 Series Electric Non-Spring Return Actuators (Part No. 34-636-399)
  • M9210-AGx-3 Floating / M9210-Bxx-3 On/Off / M9210-GGx-3 Proportional Electric Spring Return Actuators (Part No. 34-636-1654 / 34-636-1638 / 34-636-1662)
  • M2000-560 Ball Valve Linkage Kit and M9000-561 Thermal Barrier (Part No. 34-636-2227)
  • M9000-330 and M9000-340 Weather Shield Enclosures (Part No. 14-1330-26); M9000-341 Weather Shield Enclosures (Part No. 34-636-2235)
  • M9000-51x Valve Linkage Kits (Part No. 14-1201-13); M9000-520 Linkage Kit (Part No. 14-1297-5); M9000-551 Linkage Kit (Part No. 34-636-1816)

Допуски та стандарти

  • ANSI/FCI 70-2, Class 4 leakage rating
  • VDI 2035 Standard recommended for proper water treatment
  • Lead-free RoHS compliance: 96.5% tin/3.5% silver solder recommended for sweat connections

Текст документа

VG1000 Series Forged Brass Ball Valves
Installation Instructions
                                                                                          Part No. 14-1201-5, Rev. R
                                                                                                   Issued June 9, 2011
                                                                                            Supersedes August 26, 2008

                                               Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications                                                  Installation
The VG1000 Series Ball Valves are designed to                 Install VG1000 Series Ball Valves with the actuator at
regulate the flow of hot or chilled water (and for some       or above the centerline of the horizontal piping, as
models, low pressure steam) in response to the                shown in Figure 1.
demand of a controller in Heating, Ventilating, and Air
Conditioning (HVAC) systems.                                   IMPORTANT: In steam applications, install the
                                                               valve with the stem horizontal to the piping. Failure
 IMPORTANT: Use the VG1000 Series Valves as an                 to follow these guidelines may shorten the life of the
 operating control. Where failure or malfunction of the        actuator.
 VG1000 Series Valve could lead to personal injury
 or property damage to the controlled equipment or            To minimize heat transfer in steam applications, wrap
 other property, additional precautions must be               the valve and piping with insulation. Allow sufficient
 designed into the system. Incorporate and maintain           clearance to remove the actuator (as illustrated in the
 other devices, such as supervisory or alarm systems          dimension drawings, Figure 6 through Figure 15).
 or safety or limit controls, intended to warn of or          When mounting the actuator in the field (before
 protect against failure or malfunction of the VG1000         installation), use an adjustable wrench to manually
 Series Valve.                                                rotate the valve stem several times. This rotation
                                                              breaks the torque that may have built up during
                                                              long-term storage.
                                                              For the valve to move in the proper direction, wire the
                                                              input lines to the electric actuator correctly.




                                                                                                                 FIG:mntpos




         Figure 1: Mounting Positions for Chilled Water and Condensing Atmosphere Applications




                                            VG1000 Series Forged Brass Ball Valves Installation Instructions                  1
                                                              •   VA9208-Bxx-x Series On/Off Spring Return Valve
    IMPORTANT: Take care to prevent foreign material
                                                                  Actuators Installation Instructions
    such as weld slag, thread burrs, metal chips, and
                                                                  (Part No. 14-1379-13)
    scale from entering the piping system. This debris
    can damage or severely impede the operation of the        •   VA9208-GGx-x Series Proportional Spring Return
    valve by embedding itself in the seats, scoring the           Valve Actuators Installation Instructions
    valve, and ultimately resulting in seat leakage. If the       (Part No. 14-1379-21)
    debris becomes embedded in the seats, subsequent
                                                              •   M9108, M9116, M9124, and M9132 Series Electric
    flushing and filtering of the piping system with the
                                                                  Non-Spring Return Actuators Installation
    valve installed does not remedy the problem.
                                                                  Instructions (Part No. 34-636-399)
For more detailed installation information about the          •   M9210-AGx-3 Floating Electric Spring Return
specific equipment used, refer to the appropriate                 Actuators Installation Instructions
document from the following list:                                 (Part No. 34-636-1654)
•     VA9104-xGA-2S Series Electric Non-Spring Return         •   M9210-Bxx-3 On/Off Electric Spring Return
      Valve Actuators Installation Instructions                   Actuators Installation Instructions
      (Part No. 14-1336-15)                                       (Part No. 34-636-1638)
•     VA9104-xGA-3S Series Electric Non-Spring Return         •   M9210-GGx-3 Proportional Electric Spring Return
      Valve Actuators Installation Instructions                   Actuators Installation Instructions
      (Part No. 14-1336-23)                                       (Part No. 34-636-1662)
•     M9102-AGA-2S and M9104-xGA-2S Series                    •   M2000-560 Ball Valve Linkage Kit and M9000-561
      Electric Non-Spring Return Actuators Installation           Thermal Barrier Installation Instructions
      Instructions (Part No. 34-636-1220)                         (Part No. 34-636-2227)
•     M9102-AGA-3S and M9104-xGA-3S Series                    •   M9000-330 and M9000-340 Series Weather Shield
      Electric Non-Spring Return Actuators Installation           Enclosures Installation Instructions
      Instructions (Part No. 34-636-1433)                         (Part No. 14-1330-26)
•     M9106-xGx-2 Series Electric Non-Spring Return           •   M9000-341 Series Weather Shield Enclosures
      Actuators Installation Instructions                         Installation Instructions (Part No. 34-636-2235)
      (Part No. 34-636-1085)
                                                              •   M9000-51x Series Valve Linkage Kits Installation
•     M9109 Series Electric Non-spring Return                     Instructions (Part No. 14-1201-13)
      Actuators Installation Instructions
      (Part No. 34-636-1190)                                  •   M9000-520 Ball Valve Linkage Kit Installation
                                                                  Instructions (Part No. 14-1297-5)
•     VA9203-AGx-2Z Series On/Off and Floating Point
      Electric Spring Return Valve Actuators Installation     •   M9000-551 Ball Valve Linkage Kit Installation
      Instructions (Part No. 14-1380-8)                           Instructions (Part No. 34-636-1816)

•     VA9203-Bxx-2 Series On/Off Spring Return Valve          Note: To avoid excessive wear or drive time on the
      Actuators Installation Instructions                     motor for VA9104, M9104, M9106, and M9109 AGx
      (Part No. 14-1380-16)                                   models, use a controller and/or software that provides
                                                              a time-out function to remove the signal at the end of
•     VA9203-GGx-2Z Series Proportional Spring Return         rotation (stall). The IGx and GGx models have an auto
      Valve Actuators Installation Instructions               shutoff to avoid excessive wear or drive time on the
      (Part No. 14-1380-24)                                   motor.
•     VA9208-AGx-x Series On/Off and Floating Point           On models with the flow-characterizing disk, the disk is
      Electric Spring Return Valve Actuators Installation     located in Port A. Port A must be the inlet. On
      Instructions (Part No. 14-1379-5)                       three-way models, use Port A as the coil inlet and
                                                              Port B as the bypass inlet.




2        VG1000 Series Forged Brass Ball Valves Installation Instructions
VG1841 and VG1845 Series Three-Way Ball Valves                                 Contact your local Johnson Controls® representative
have a different port configuration from VG1644 Series                         for compatibility concerns before using VG1000 Series
Three-Way valves. See Figure 2, Figure 3, and                                  Ball Valves to control the flow of fluids other than those
Figure 4 for details.                                                          outlined in the Technical Specifications table in this
                                                                               document.
                                                                               Press Valve Installation
                                                                               VG1000 press end connection valves are installed
                                      Port C
                                                                               using RIDGID® press tools. Always refer to the
          Port A
           Coil                      Common                                    operator’s manual supplied with the RIDGID press tool
                                                                               that is used to make the valve end connections. The
                                                                               manual should provide proper instructions for the safe
                                                                               operation of the tool, proper crimping procedures, and
                                             FIG:VGAtoC
                                                                               methods of inspecting the finished connection. If you
                    Port B Bypass                                              use a battery-operated press tool, ensure its proper
  Figure 2: VG1841 or VG1845 Series Three-Way                                  operation by fully charging the unit. To avoid damage to
     Ball Valve (Port A Connected to Port C)                                   the integral O-ring, never use sealant or pipe dope with
                                                                               a press connection. Always inspect the end
                                                                               connections of the valve before making the connection.
                                                                               The end connection should not be deformed, and the
                                                                               internal, integral O-ring must be in place for a proper
                                                                               seal.
          Port A                       Port C
           Coil                       Common                                   Sweat Valve Installation
                                                                               When soft soldering sweat ball valves, be sure to use a
                                                                               low temperature solder with a melting point that does
                                                                               not exceed 450°F (232°C). For lead-free RoHS
                                                  FIG:vgBtoC
                                                                               compliance, a 96.5% tin/3.5% silver solder is
                     Port B Bypass
                                                                               recommended. Never install the actuator on the valve
  Figure 3: VG1841 or VG1845 Series Three-Way                                  until you have completed the soldering operation and
     Ball Valve (Port B Connected to Port C)                                   the valve body has cooled. Before soldering, minimize
                                                                               the risk of damage to the ball seals by positioning the
                     Common                                                    ball so that Port A is fully open. When soldering, always
                       Port                                                    apply a wet rag around the valve’s neck and cover as
                                                                               much of the valve body with the rag as possible. Direct
                                                                               the tip of the flame away from the valve and always
                                                                               heat the copper tubing directly, but never the valve
                                                                               body. Solder Port A first, then the remaining ports.
    Normally                           Normally                                These steps provide maximum protection to the
    Open Port                          Closed Port
                                                               FIG:vg1644ccw
                                                                               internal valve components. See Figure 5 for details.
                                                                                               Use only low melting
                                                                                               temperature soft solder.
  Figure 4: Top View of VG1644 Series Three-Way
   Ball Valve (Actuator Fully Counterclockwise)
                                                                                                                          Place wet rag
                                                                                                                          around neck of valve.
 IMPORTANT: Protect the actuator from dripping
 water, condensation, and other moisture. Water or
 moisture could result in an electrical short, which
 may damage or affect the operation of the actuator.

 IMPORTANT: Do not cover the actuator with                                                                                                   FIG:sv_inst

 thermal insulating material. High ambient
 temperatures may damage the actuator, and a hot
 water pipe, steam pipe, or other heat source may                                        Figure 5: Sweat Valve Installation
 overheat it.



VG1000 Series Forged Brass Ball Valves Installation Instructions                                                                                           3
Dimensions                                                              See Table 2 for specific model dimensions for the
See Figure 6 for dimensions of the Non-Spring Return                    VA9104 Actuated VG1275 and VG1875 Series Sweat
VA9104 Actuated VG1241, VG1245, VG1841, and                             End and the VA9104 Actuated VG1295 and VG1895
VG1845 Series Ball Valve with M9000-551 Linkage.                        Series Press End Connection Ball Valves.
See Table 1 for specific model linkage dimensions.




                        Minimum Clearance Required
                                3-1/2 (89)

                  2-13/16                                                                      5-1/2
                    (71)                                                                       (140)




                                                 F
                                      A


                                           C                             B
      C

                                  B

                                                            E                          E                                  G

                                                                                                  D
                                                                                                                                        FIG:vg1kva04
              Two-Way Valve                          Three-Way Valve                   Two-Way Valve                  Three-Way Valve

     Figure 6: Non-Spring Return VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                                with M9000-551 Linkage Dimensions, in. (mm)

Table 1: VA9104 or M9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with
         M9000-551 Linkage Dimensions, in. (mm)
 Valve Size,      A                   B                 C               D                  E                  F            G
 in. (DN)1
 1/2 (DN15)       3-7/8 (98)          21/32 (17)        1-7/32 (31)     5-7/64 (129)       2-33/64 (64)       11/32 (9)   1-1/4 (32)
 3/4 (DN20)       3-7/8 (98)          21/32 (17)        1-7/32 (31)     5-7/32 (133)       2-51/64 (71)       11/32 (9)    1-13/32 (36)
 1 (DN25)         3-11/16 (100)       3/4 (19)          1-19/64 (33)    5-9/16 (141)       3-13/32 (87)       11/32 (9)    1-11/16 (43)

1.    On models with the flow-characterizing disk, the disk is located in Port A. Port A must be the inlet.

Table 2: VA9104 Actuated VG1275 and VG1875 Series Ball Valve with Sweat End Connections and VA9104
         Actuated VG1295 and VG1895 Series Ball Valves with Press End Connections Dimensions,
         in. (mm)
 Valve Size,        A                     B                      C                 D                      E                F
 in. (DN)1
 1/2 (DN15)         3-7/8 (98)            21/32 (17)             1-7/32 (31)       5-45/64 (145)          3-25/32 (96)     2-13/16 (55)
 3/4 (DN20)         3-7/8 (98)            21/32 (17)             1-7/32 (31)       5-57/64(150)           4-3/32 (104)     2-15/32 (62)
 1 (DN25)           3-11/16 (100)         3/4 (19)               1-19/64 (33)      5-1/8 (156)            3-13/32 (118)    2-27/32 (72)

1.    On models with the flow-characterizing disk, the disk is located in Port A. Port A must be the inlet.




4         VG1000 Series Forged Brass Ball Valves Installation Instructions
See Figure 7 and Table 3 for VA9104 Valve Actuator
dimensions with optional M9000-561 Thermal Barrier
installed.



                                     3-1/2 (89)
                                Clearance Required


               2-13/16                                5-1/2
                 (71)                                 (140)




                            A




                                                                                                   Port Marking
                                                                                                    Locations




                                                                                                                                FIG:M9104X_dims
                                                         D



     Figure 7: Field-Installed VA9104 Series Electric Actuator Dimensions with Optional M9000-561 Thermal
                                           Barrier Dimensions, in. (mm)

Table 3: VA9104 Actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valves with Optional
         Thermal Barrier Installed Dimensions, in. (mm)
 Valve Size,       A                   B             C              D                  E               F           G
 in. (DN)1
 1/2 (DN15)        5-11/32 (135)       21/32 (17)    1-7/32 (31)    5-7/64 (129)       2-33/64 (64)    11/32 (9)   1-1/4 (32)
 3/4 (DN20)        5-11/32 (135)       21/32 (17)    1-7/32 (31)    5-7/32 (133)       2-51/64 (71)    11/32 (9)   1-13/32 (36)
 1 (DN25)          5-27/64 (137)       3/4 (19)      1-19/64 (33)   5-9/16 (141)       3-13/32 (87)    11/32 (9)   1-11/16 (43)

1.    On models with the flow-characterizing disk, the disk is located in Port A. Port A must be the inlet.




VG1000 Series Forged Brass Ball Valves Installation Instructions                                                                                  5
See Figure 8 for dimensions of the VA9203 Actuated
VG1241, VG1245, VG1841, and VG1845 Series Ball
Valve with National Pipe Thread (NPT) end
connections. See Table 4 and Table 5 for specific
model linkage dimensions.




                                                             3-1/2 (89)
                                                        Clearance Required

                                        2-7/8
            3-1/4
            (82)
                                        (73)




                          A


                                                                                                            Port Marking
                                                                                                             Locations




                                                  D                                                                                         FIG:VA9203X_dims




                        Figure 8: VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series
                               Ball Valve with NPT End Connections Dimensions, in. (mm)

Table 4: VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with NPT End
         Connections Dimensions, in. (mm)
 Valve Size,        A               B             C                     D                    E                   F           G
 in. (DN)1
 1/2 (DN15)         4-1/4 (108)     21/32 (17)    1-7/32 (31)           6-23/32 (171)        2-33/64 (64)        11/32 (9)   1-1/4 (32)
 3/4 (DN20)         4-1/4 (108)     21/32 (17)    1-7/32 (31)           6-7/8 (175)          2-51/64 (71)        11/32 (9)   1-13/32 (36)
 1 (DN25)           4-9/32 (109)    3/4 (19)      1-19/64 (33)          7-7/64 (181)         3-13/32 (87)        11/32 (9)   1-45/64 (43)

1.   Port A must always be connected to the coil.

Table 5: VA9203 Actuated VG1271, VG1275, VG1871, and VG1875 Series Sweat Ball Valve and VA9203
         Actuated VG1291, VG1295, VG1891, and VG1895 Series Press Ball Valve Dimensions, in. (mm)
 Valve Size,                  A             B               C                      D               E                 F            G
 in. (DN)1
 1/2 (DN15)         4-5/8 (117)      21/32 (17)       1-7/32 (31)            7-13/64 (183)   3-25/32 (96)      11/32 (9)     1-1/4 (32)
 3/4 (DN20)         4-5/8 (117)      21/32 (17)       1-7/32 (31)            7-3/4 (197)     4-3/32 (104)      11/32 (9)     1-13/32 (36)
 1 (DN25)           4-11/16 (119)    3/4 (19)         1-19/64 (33)           8-3/16 (208)    4-41/64 (118)     11/32 (9)     1-45/64 (43)

1.   Port A must always be connected to the coil.




6      VG1000 Series Forged Brass Ball Valves Installation Instructions
See Figure 9 and Table 6 for VA9203 Valve Actuator
dimensions with optional M9000-561 Thermal Barrier
installed.




                                                         3-1/2 (89)
                                                    Clearance Required
            3-1/4                     2-7/8
            (82)                      (73)




                       A


                                                                                               Port Marking
                                                                                                Locations




                                                                                                                              FIG:VA9203X_dimsthbr

                                              D


     Figure 9: Spring Return VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                  with Optional M9000-561 Thermal Barrier Installed Dimensions, in. (mm)


Table 6: VA9203 Actuated VG1241, VG1245, VG1841, and VG1845 Series NPT Ball Valve with Optional
         Thermal Barrier Installed Dimensions, in. (mm)
 Valve Size                A              B                 C                  D              E               F           G
 in. (DN)1
 1/2 (DN15)         6 (152)          21/32 (17)       1-7/32 (31)        6-31/32 (177)   2-33/64 (64)    11/32 (9)   1-1/4 (32)
 3/4 (DN20)         6 (152)          21/32 (17)       1-7/32 (31)        7-1/8 (181)     2-51/64 (71)    11/32 (9)   1-13/32 (36)
 1 (DN25)           6-1/16 (154)     3/4 (19)         1-19/64 (33)       7-31/64 (190)   3-13/32 (87)    11/32 (9)   1-45/64 (43)

1.   Port A must always be connected to the coil.




VG1000 Series Forged Brass Ball Valves Installation Instructions                                                                                     7
See Figure 10 and Table 7 for VA9208 Actuated
VG1241, VG1245, VG1841, and VG1845 Valve
Actuator dimensions.




                                                        3-1/2 (89)
       3-29/32                 2-7/8               Clearance Required
         (99)                  (73)




                                                                                              Port Marking
                                                                                               Locations




                                                                                                                                   FIG:VA9208X_dims




     Figure 10: Spring Return VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                                          Dimensions, in. (mm)

Table 7:     VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve Dimensions, in. (mm)
 Valve Size       Valve          A           B               C                D              E               F           G
 in. (DN)         Style1
 1-1/4               All     7-11/16      1-1/32        1-23/32         7-5/32 (182)    3-15/16 (100)   11/32 (9)   1-31/32 (50)
 (DN32)                      (195)        (26)          (44)
 1-1/2               All     7-7/8        1-9/64        1-57/64         7-3/8 (187)     4-21/64 (110)   11/32 (9)   2-11/64 (55)
 (DN40)                      (200)        (29)          (48)
 2 (DN50)          2-way     8-1/32       1-15/32       2-1/8 (54)      7-19/32 (193)   4-27/32 (123)   11/32 (9)   2-27/64 (62)
                             (204)        (37)
                   3-way                                                7-7/8 (200)

1.    Port A must always be connected to the coil (see Figure 10).




8       VG1000 Series Forged Brass Ball Valves Installation Instructions
See Figure 11 and Table 8 for VA9208 Actuated
VG1241, VG1245, VG1841, and VG1845 Valve
Actuator dimensions with optional M9000-561 Thermal
Barrier installed.


                                                                 3-1/2 (89)
                   3-29/32                                  Clearance Required
                     (99)




      A
                                                                                         F



                                                                                                           Port Marking
                                                                                                            Locations
                                                                   C                 C




            B


                                                                                                 E                         G         B
                                                            D


     Figure 11: Spring Return VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve
                  with Optional M9000-561 Thermal Barrier Installed Dimensions, in. (mm)

Table 8: VA9208 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with Optional
         M9000-561 Thermal Barrier Installed Dimensions, in. (mm)
 Valve          Valve             A               B                    C                 D                E                 F            G
 Size in.       Style
 (DN)1
 1-1/4           All         9-17/64 (235)   1-1/32 (26)        1-23/32 (44)     7-1/4 (184)         3-15/16 (100)        11/32   1-31/32 (50)
 (DN32)                                                                                                                   (9)
 1-1/2           All         9-15/16 (240)   1-9/64 (29)        1-57/64 (48)     7-7/16 (189)        4-21/64 (110)        11/32   2-11/64 (55)
 (DN40)                                                                                                                   (9)
 2 (DN50)       2-way        9-31/32 (244)   1-15/32 (37)       2-1/8 (54)       7-11/16 (195)       4-27/32 (123)        11/32   N/A
                                                                                                                          (9)
                3-way                                                            7-7/8 (200)                                      2-27/64 (62)

1.   Port A must always be connected to the coil (Figure 11).




VG1000 Series Forged Brass Ball Valves Installation Instructions                                                                                 9
Linkage Kits
See Figure 12 and Table 9 for dimensions of the
Non-Spring Return M9106 or M9109 Actuated
VG1241, VG1245, VG1841, and VG1845 Series Ball
Valve with M9000-520 Linkage.




                      Minimum Clearance Required
                           3-1/2 in. (89 mm)



                 4-7/32
                 (107)

                                                                                           7-27/32
                3-29/32                                                                     (199)
                 (100)




                                    A

                                               F




                                         C                               B
     C

                                B

                                                          E                                              G
                                                                                     E

                                                                                                                                 FIG:vg1km69
                                                                                                  D
             Two-Way Valve                         Three-Way Valve            Two-Way Valve           Three-Way Valve

Figure 12: Non-Spring Return M9106 or M9109 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball
                          Valve with M9000-520 Linkage Dimensions, in. (mm)

Table 9: M9106 and M9109 Actuated VG1241, VG1245, VG1841, and VG1845 Series Ball Valve with
         M9000-520 Linkage Dimensions, in. (mm)
 Valve Size,      A                 B                C               D                E                  F              G
 in. (DN)1
 1/2 (DN15)       6-19/64 (160)     21/32 (17)       1-7/32 (31)     6-49/64 (172)    2-33/64 (64)       11/32 (9)      1-1/4 (32)
 3/4 (DN20)       6-19/64 (160)     21/32 (17)       1-7/32 (31)     6-29/32 (175)    2-51/64 (71)       11/32 (9)      1-13/32 (36)
 1 (DN 25)        6-3/8 (162)       3/4 (19)         1-19/64 (33)    7-13/64 (183)    3-13/32 (87)       11/32 (9)      1-11/16 (43)
 1-1/4 (DN32)     6-13/16 (173)     1-1/32 (26)      1-23/32 (44)    7-15/32 (190)    3-15/16 (100)      11/32 (9)      2 (51)
 1-1/2 (DN40)     6-31/32 (177)     1-9/64 (29)      1-57/64 (48)    7-43/64 (195)    4-21/64 (110)      11/32 (9)      2-1/8 (54)
 2 (DN50)         7-11/64 (182)     1-15/32 (37)     2-1/16 (53)     7-59/64 (201)    4-27/32 (123)      11/32 (9)      2-9/16 (65)

1.   On models with the flow-characterizing disk, the disk is located in Port A. Port A must be the inlet.



10       VG1000 Series Forged Brass Ball Valves Installation Instructions
Weather Shields                                           See Figure 14 for dimensions of the Spring Return
See Figure 13 for dimensions of the Non-Spring Return     VA9208 Series Actuated VG1241, VG1245, VG1841,
M91xx Series Actuated VG1241, VG1245, VG1841,             and VG1845 Series Ball Valve with M9000-341
and VG1845 Series Ball Valve with M9000-330               Weather Shield Kit. See Table 8 for specific model
Weather Shield Kit.                                       linkage dimensions.

                                       9-17/32
                                        (242)                                        4-23/32
                                                                                      (120)
                              7-3/32
                              (181)




                                                                       A




                                                                                                                     FIG:m91xx_m9000-330ws




                 Figure 13: Non-Spring Return M91xx Series Actuated VG1241, VG1245, VG1841,
                    and VG1845 Series Ball Valve with M9000-516 Linkage and Field-Installed
                                M9000-330 Weather Shield Dimensions, in. (mm)




                                                                   B




                                 A




                                                                                                FIG: VA9208_whshld
                     D


                 Figure 14: Spring Return VA9208 Series Actuated VG1241, VG1245, VG1841,
                  and VG1845 Series Ball Valve Field-Installed M9000-341 Weather Shield Kit
                                            Dimensions, in. (mm)




VG1000 Series Forged Brass Ball Valves Installation Instructions                                                                             11
Table 10: Weather Shield Enclosure Dimensions, in. (mm)
 Dimension              M9000-321
 A                      9-29/64 (240)
 B                      4-47/64 (120)
 C                      3-15/16 (100)
 D                      1-27/32 (47)

Piping
                                                                         VG18xx Three-Way Valve




                                                             Port A                        Port C          Return


                                                                            Port B




                                                                                                           Supply


                                          Typical Three-Way Ball Valve Application



                                                                        VG12xx Two-Way Valve




                                                               Port A                    Port B            Return




                                                                                                           Supply



                                           Typical Two-Way Ball Valve Application
                                                                                                                    FIG:vg1000pip
                    Note: Mount the valve downstream from the coil to minimize heat transfer to the actuator.
                                       Figure 15: Typical VG1000 Piping




12   VG1000 Series Forged Brass Ball Valves Installation Instructions
Wiring                                                         Troubleshooting
Be sure to wire the input lines to the electric actuator       Servicing the Actuator or Piping System
correctly for the valve to move in the proper direction.
                                                               When servicing the electric actuator or the piping
                                                               system:
 IMPORTANT: Use copper conductors only. Make
 all wiring connections in accordance with local,              •     disconnect the power supply to the actuator.
 national, and regional regulations. Do not exceed
                                                               •     relieve the pressure in the piping system.
 the actuator’s electrical ratings.
                                                                   IMPORTANT: Do not attempt to manually rotate the
             WARNING: Risk of Electric Shock.                      drive shaft while the actuator is installed without first
             Disconnect the power supply before
     !       making electrical connections. Contact
                                                                   releasing the actuator gears. Manually rotating the
                                                                   drive shaft without releasing the actuator gears may
             with components carrying hazardous                    result in permanent damage to the actuator.
             voltage can cause electric shock and
             may result in severe personal injury or           Repair Information
             death.
                                                               If the VG1000 Series Forged Brass Ball Valve fails to
                                                               operate within its specifications, replace the unit. For a
             CAUTION: Risk of Property Damage.                 replacement valve, contact the nearest
             Do not apply power to the system before
     !       checking all wiring connections. Short
                                                               Johnson Controls® representative.

             circuited or improperly connected wires
             may result in permanent damage to the
             equipment.

Technical Specifications
VG1000 Series Forged Brass Ball Valves (Part 1 of 2)
 Service1                                                  Hot Water, Chilled Water, 50/50 Glycol Solutions, and
                                                           15 psig (103 kPa) Saturated Steam for HVAC Systems
 Fluid Temperature Limits           Water                  VG12x1 and VG18x1 Series: 23 to 203°F (-5 to 95°C)
                                                           VG12x5 and VG18x5 Series: -22 to 284°F (-30 to 140°C)
                                    Steam                  VG12x5 Series: 15 psig (103 kPa) at 250°F (121°C)
                                                           VG12x1 Series: Not Rated for Steam Service
 Actuator Maximum Fluid             212°F (100°C)          VA9104 Series Non-Spring Return Actuator
 Operating Temperature Limit
                                                           VA9203 Series Spring Return Actuators
                                                           VA9208 Series Spring Return Actuators
                                                           M9104 with M9000-551 Linkage
                                    284°F (140°C)          M9106 or M9109 with M9000-520 Linkage
                                                           VA9104 with M9000-561 Thermal Barrier
                                                           VA9203 or VA9208 with M9000-561 Thermal Barrier
 Valve Body Pressure/               Water                  VG1241, VG1245, VG1841, and VG1845 Series:
 Temperature Rating                                        580 psig (3,996 kPa) at 203°F (95°C) (PN40)
                                                           464 psig (3,196 kPa) at 284°F (140°C) (PN40)
                                                           VG1271, VG1275, VG1871, and VG1875 Series:
                                                           300 psig (2,067 kPa)
                                                           VG1291, VG1295, VG1891, and VG1895 Series:
                                                           300 psig (2,067 kPa)
                                    Steam                  15 psig (103 kPa) Saturated Steam
 Maximum Closeoff Pressure                                 200 psig (1,378 kPa)
 Maximum Recommended Operating Pressure Drop               50 psi Maximum Differential Pressure and 30 psi Maximum for
                                                           Quiet Service Ball Valves




VG1000 Series Forged Brass Ball Valves Installation Instructions                                                           13
VG1000 Series Forged Brass Ball Valves (Part 2 of 2)
 Flow Characteristics                      Two-Way                    Equal Percentage
                                           Three-Way                  Equal Percentage Flow Characteristics of In-line Port (Coil) and
                                                                      Linear Flow Characteristics of Angle Port (Bypass)
 Rangeability2                                                        Greater than 500:1
 Minimum Ambient Operating                 -4°F (-20°C)               VA9104 and M9104 Series Non-Spring Return Actuator
 Temperature
                                           -4°F (-20°C)               M9106 and M9109 Series Non-Spring Return Actuators
                                           -22°F (-30°C)              VA9203 Series Spring Return Actuators
                                           -40°F (-40°C)              VA9208 Series Spring Return Actuators
 Maximum Ambient                           Direct Mount or            140°F (60°C) VA9104 Series Non-Spring Return Actuators
 Operating Temperature                     with M9000-561
 (Limited by the Actuator)3                Thermal Barrier
                                           M9000-551 Linkage          140°F (60°C) M9104 Series Non-Spring Return Actuators
                                           Direct Mount or            140°F (60°C) VA9203 and VA9208 Series Non-Spring Return
                                           with M9000-561             Actuators
                                           Thermal Barrier
                                           M9000-5xx Series           125°F (52°C) M9106 Series Non-Spring Return Actuators
                                           Linkage                    122°F (50°C) M9100 Series Non-Spring Return Actuators
 Leakage                                                              0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
                                                                      1% of Maximum Flow for Three-Way Bypass Port
 End Connections                                                      National Pipe Thread (NPT): 1/2 to 2 in. (DN15 to DN50)
                                                                      Sweat: 1/2 to 1 in. (DN15 to DN25)
                                                                      Press (ProPress® Compatible): 1/2 to 1 in. (DN15 to DN25)
 Materials                                 Body                       Forged Brass
                                           Ball                       VG12x1 and VG18x1 Series: Chrome Plated Brass
                                                                      VG12x5 and VG18x5 Series: 300 Series Stainless Steel
                                           Blowout-Proof              VG12x1 and VG18x1 Series: Nickel Plated Brass
                                           Stem                       VG12x5 and VG18x5 Series: 300 Series Stainless Steel
                                           Seats                      Graphite-Reinforced Polytetrafluoroethylene (PTFE) with
                                                                      Ethylene Propylene Diene Monomer (EPDM) O-Ring Backing
                                           Stem Seals                 EPDM Double O-Rings
                                           Characterizing Disk        Amodel® AS-1145HS Polyphthalamide Resin

1.   Proper water treatment is recommended; refer to the VDI 2035 Standard.
2.   Rangeability is defined as the ratio of maximum controllable flow to minimum controllable flow.
3.   In steam applications, install the valve with the stem horizontal to the piping and wrap the valve and piping with insulation.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.




                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                    All other marks herein are the marks of their respective owners. © 2011 Johnson Controls, Inc.