The VA-720x Series synchronous motor driven actuator provides floating or proportional control of valves with up to 19 mm stroke in heating, ventilation and air conditioning applications. This compact, non-spring return actuator has a 1000 N nominal force and responds to a variety of input signals. It can be field mounted or ordered factory coupled to VG7000, VG8000, VG9000 and VGS8000 Series valves.
Ключові дані
| Actuator force | 1000 N +30% / -20% |
|---|---|
| Stroke | 20 mm maximum; 8, 10, 13, 19 mm selectable |
| Supply voltage | 24 V ±15%, 50…60 Hz |
| Control signal | Floating or proportional (0…10 VDC or 0(4)…20 mA) |
| Nominal speed at 50 Hz (60 Hz) | 4 (3.2) s/mm |
| Enclosure protection | IP 42 (EN 60529) |
| Ambient operating condition | -5 to +55 °C, non condensing |
| Net weight | 1.0 kg |
Застосування
- Floating or proportional control of valves in HVAC applications
- Factory-fitted combinations with VG7000 Series Cast Bronze Valves
- Combinations with VG8000 Series PN16 and PN25 Flanged Valves
- Combinations with VG9000 Series PN6 and PN10 Flanged Valves
- Combinations with VGS8000 Series Male Threaded Valves
- Sequential operation of several actuators from one 0…10 V controller output (minimum adjustable span 2 V enables up to 5 sequenced devices)
Особливості
- 1000 N force output compact unit — covers a wide range of applications with one actuator
- Magnetic clutch provides constant output force for positive close-off of valves and protects motor in stall conditions
- "Signal fail" safe position: safety position after control signal failure; up/down selectable in-situ
- Selectable stroke via jumpers: 8 mm, 10 mm, 13 mm, 19 mm
- Direct/reverse action selectable via jumper
- Voltage/current input signal selection via jumper
Технічні дані
| Parameter | Value |
|---|---|
| Models | Floating: VA-7200-xx01; Proportional: VA-72x2-xx01 |
| Type of motor | Synchronous / reversible |
| Supply voltage (50/60 Hz) | 24 V ± 15%, 50…60 Hz |
| Actual power | 5 W |
| Apparent power | 5.6 VA at 50 Hz / 6.7 VA at 60 Hz |
| Electronic positioner ratings | 2 VA |
| Positioner input impedance | 100 kΩ (0…10 VDC); 500 Ω (0…20 mA) |
| Actuator force | 1000 N +30% -20% |
| Stroke | 20 mm maximum; 8, 10, 13, 19 mm selectable |
| Nominal speed at 50 Hz (60 Hz) | 4 (3.2) s/mm |
| Enclosure protection | IP 42 (EN 60529) |
| Enclosure material | Self extinguishing VO-UL 94 ABS + PC |
| Hand wheel material | Self extinguishing nylon PA |
| Yoke material | Die cast aluminium |
| Ambient operating condition | -5 to +55 °C, non condensing |
| Ambient storage condition | -20 to +65 °C, non condensing |
| Electrical connections | 2.5 mm² (floating), 1.5 mm² (proportional) |
| Net weight | 1.0 kg |
Варіанти замовлення
For VG7000 Series Valves:
- VA-7200-1001 — Floating control, 24 VAC supply
- VA-7202-1001 — Proportional control (0…10 VDC / 0(4)…20 mA), 24 VAC supply
For VG8000, VG9000 and VGS8000 Series Valves:
- VA-7200-8201 — Floating control, 24 VAC supply
- VA-7202-8201 — Proportional control (0…10 VDC / 0(4)…20 mA), 24 VAC supply
Factory-fitted valve-actuator combination: add "+M" to the end of the actuator ordering code (e.g. VG7203AT + VA-7202-1001+M).
Factory settings: 19 mm stroke, 0…10 V input signal, direct action, fail-safe position "fully up", starting point 1 V, span 8 V.
Допуски та стандарти
- EMC directive 89/336 EEC: EN 61000-6-2, EN 61000-6-3
Позиції каталогу з цим документом
Текст документа
European Electronic Controls Catalogue
Catalogue Section E
Product Bulletin VA-7200
Issue Date 1005
VA-7200
Electric Valve Actuator
I ntroduction
The VA-720x Series synchronous motor driven
actuator provides floating or proportional control of
valves, with up to 19mm stroke in heating,
ventilation and air conditioning applications.
This compact, non-spring return actuator has a
1000N nominal force and responds to a variety of
input signals.
The VA-7200 Series can be easily field mounted
or ordered factory coupled to VG7000, VG8000,
VG9000 and VGS8000 Series valves in
accordance with the specified maximum close-off
pressure ratings (see pertinent valve bulletins).
VA-7200
Features and Benefits
1000N Force Output compact unit Covers a wide range of applications with one actuator
Magnetic clutch Provides constant output force for positive close-off of
valves, and protects motor in stall conditions
“Signal fail” safe position Valve safety position after control signal failure, the
safety position, up / down, is selectable in-situ
© 2005 Johnson Controls, Inc. E11
Order No. 10.736 E
VA-7200 2
O rdering data
For VG7000 Series Valves
O rdering procedure
The actuator can be ordered as a separate unit or
a factory fitted valve-actuator combination. Should
Item Code Control, Power Supply the latter be requested, please just add “+M” to the
end of the actuator ordering code.
VA-7200-1001 Floating control, 24 VAC supply
For example:
VA-7202-1001 Proportional control (0…10 VDC /
0(4)…20 mA), 24 VAC supply Item 1 VG7203AT (valve body)
For VG8000, VG9000 and VGS8000 Series Valves Item 2 VA-7202-1001 (actuator)
Alternatively, to order a factory fitted combination.
Item Code Control, Power Supply Item 1 VG7203AT (valve body)
VA-7200-8201 Floating control, 24 VAC supply Item 2 VA-7202-1001+M (actuator)
VA-7202-8201 Proportional control (0…10 VDC /
0(4)…20 mA), 24 VAC supply
A ctuator / valve combinations M ounting instructions
The VA-7200 can be combined with the following When mounting the actuator on a valve, please
valve ranges: follow the instructions below:
• VG7000 Series Cast Bronze Valves • It is recommended that the valves be mounted
upright in an easily accessible location. When
• VG8000 Series PN16 and PN25 Flanged mounted horizontally, the yoke should be fitted
Valves such that the stanchions are aligned vertically,
• VG9000 Series PN6 and PN10 Flanged one above the other.
Valves
• VGS8000 Series Male Threaded Valves OK
For complete ordering information, please refer to 90° Max
the relevant product bulletin
OK
O peration
Floating control models
Connections Actuator Stem “Signal fail”
safe position
1-2 extends N/A
1-3 retracts N/A
Proportional control models • The actuator must be protected against
(0…10 V or 0…20 mA) dripping water, which could enter the housing
and damage the mechanism or motor.
Jumper Input control Actuator “Signal fail”
function signal Stem safe position • Do not cover with insulating material.
Direct increases extends selectable • Sufficient clearance must be allowed for
action decreases retracts selectable actuator removal (refer to the dimension
Reverse increases retracts selectable drawings).
action decreases extends selectable • The valve must be installed so that the plug
“Signal Fail” safe position (only for Voltage input) seats against the flow, as indicated by the
arrows on the valve.
A signal failure on proportional models will cause
the actuator to automatically move the stem to a
(via jumper) pre-selected position (100% extended
or 100% retracted).
E11
VA-7200 3
W iring instructions WARNING
• All wiring must be in accordance with local Shock Hazard
regulations and national electrical codes and
should be carried out by authorised personnel Disconnect the power supply before wiring
only. connections are made to prevent personal injury.
• Make sure that the line power supply is in Equipment Damage Hazard
accordance with the power supply specified on Make and check all wiring connections before
the device. applying power to the system. Short circuited or
• See also the instructions in paragraph improperly connected wires may result in
“Application”. permanent damage to the unit.
Wiring Diagrams:
Floating model 24 VAC
VA-7200-xx01
Proportional model
VA-7202-xx01
E11
VA-7200 4
A djustments for proportional models
The adjustment procedure varies depending on
2. Set the direct / reverse action jumper (J1) so
that the valve stem travels in the desired
whether voltage or current control is used, taking direction (as per changes in control signal)
this into account, to adjust please carry out the • DA (J1 top jumper) stem extends on signal
following instructions: increase.
1. Set the stroke jumper to match the valve • RA (J1 bottom jumper) stem retracts on
stroke, this setting is approximate. Jumper signal increase.
location is as depicted below:
3. Select voltage (V) or current (mA) input signal
Stroke selection jumpers (J5): to match the controller output (if the input
Jumper 8: 8mm signal selection jumper is removed the
Jumper 10: 10mm actuator defaults to voltage input).
Jumper 13: 13mm
Jumper 19: 19mm Note: When mA input is selected, multiply
the “start” and “span” scales by two.
Stroke fine adjustment Starting point Span value 4. Set the signal fail default position to “fully up”,
or “fully down”, if the actuator control signal is
J5 8 4 6
STROKE
lost i.e. an open connection, the actuator will
10 2 64 8
default to this pre-designated position.
13
19 Note: When mA input is selected, the
0 8 2 10 actuator will default to the “low” input signal
START SPAN position.
Action selection
DA 5. Adjust the potentiometers to the nominal
V A values. Set the stroke fine adjustment to
J3 J1 RA
J2 midpoint. Set the starting point (offset) to the
J7 “low” input signal using the scale printed on
DOWN UP the PCB as a reference. Set the span value to
1 2 3 4 Failsafe input signal the “high” input signal minus the offset; see
table below. Use the scales for reference.
0/10 VDC
0/20 mA 6. Apply the voltage specified by application
24 LED (RA / DA) requirements to drive the actuator to
Com the “fully up” position using the following table.
24 Com (If mA input is selected, multiply all values by
two).
Calibration values
VA-72x2 PCB Components Actual Reference
Minimum Maximum Minimum Maximum
The V / A jumper (J3) allows selection of the input 0 10 1 9
signal type as follows: 0 5 1 4
5 10 6 9
Volts
mA Note: Using the calibration values (± 0.5 V) will
ensure proper close-off throughout the life of
the valve (takes seat wear into account).
When the voltage input range (J3) is set the If the application requires values other
DOWN / UP jumper (J2) allows selection of the than those given, use the
actuator “failsafe” stem position as follows: minimum actual value + 1 V and the
maximum actual value - 1 V
DOWN to determine the reference values.
• DA: “fully up” (min. voltage)
UP
• RA: “fully up” (max. voltage)
When the actuator is in operation the LED
will illuminate.
Note: Disconnecting J7 from PCB, the power
supply is interrupted. Therefore the plug must be
in place for actuator operation.
E11
VA-7200 5
12. If the “fully down” position cannot be achieved,
7. Slowly turn the starting point potentiometer
return the stroke potentiometer to the nominal
clockwise until the valve stem reaches stroke
position and then slowly turn the span
limit, when the valve stem is in the “fully up”
potentiometer anti-clockwise until “fully down”
position (the LED will be illuminated and there
is achieved. Repeat step 11.
should be no gear movement).
13. Adjust the voltage to drive the actuator to “fully
8. Slowly turn the starting point potentiometer
up” position. Verify starting point adjustment.
anti-clockwise, stop when the LED flashes or
goes out. 14. Check for proper operation using the min. and
max. operating voltages. Allow the actuator to
Note: The actuator electronics contain a
complete several operating cycles.
time-out feature. If calibration takes longer
than 3…10 minutes, the LED will extinguish, Note: The LED will remain illuminated for
falsely indicating a satisfactory condition. 3…10 minutes after the actuator has
Should this occur, cycle the power to the completed its operation cycle.
actuator and readjust the starting point.
15. Refit the cover and secure the screws.
9. Apply the input voltage requirements specified The unit is now ready for operation.
by the application (RA / DA) to drive the valve
stem to the “fully down” position as per chart in Factory Settings
step 6.
The VA-7200 is delivered with the following factory
10. To ensure that the valve stem is in the “fully settings:
down” position, slowly turn the stroke 19 mm stroke
potentiometer clockwise until the valve stem 0…10 V input input signal
reaches stroke limit (the LED will be on and Direct action
there should be no gear movement). Fail safe position “fully up”
Starting point 1 V
11. Slowly turn the stroke potentiometer anti-
Span 8V
clockwise, until the LED extinguishes.
The sequencing and action of the actuator are
A pplications individually adjustable on each positioner. Each
positioner has its own adjustment for starting point
Actuators with built-in positioner for controllers between 0…10 V and span between 2…10 V.
with 0…10V output is sequential operation. Using the minimum adjustable span of 2 V
therefore enables a maximum of 5 sequenced
devices; further sequencing can be accomplished
To further actuators
24V
24VAC Com Com 0...10V by using additional controller outputs. Each
0...10 V
positioner can be switched for direct or reverse
0...10 V Com action.
24 VAC Com
24 VAC
1 2 3 4 1 2 3 4 1 2 3 4
Y1 Y2 Y3
The controller output 0…10 V can operate several
actuators with built-in electronic positioner. The Starting Span Starting + Span Positioner
Point Point Action
electrical wiring for parallel and sequenced
operation is identical. 1V 8V 9V DA
* * Factory
1V 3,5V 4,5V DA calibration
5,5V 3,5V 9V RA
Example of adjustments
E11
VA-7200 6
D imensions (in mm)
0
0 106
1
0
2
1
8 8
7 7
Lock screw Lock screw
VA-7200 for VG7000 Valve Series VA-7200 for VG8000, VG9000 and VGS8000
(section) Valve Series
E11
VA-7200 7
S pecifications
Models: Floating Proportional
0…10 VDC or 0…20 mA
Type of motor: Synchronous / reversible
Supply voltage (50/60 Hz): 24 V ± 15% 24 V ± 15%
50…60 Hz 50…60 Hz
Motor ratings:
Actual power 5W
Apparent power 5.6 VA at 50 Hz 6.7 VA at 60 Hz
Electronic positioner ratings: 2 VA
100 kΩ input impedance
- (0…10 VDC)
500 Ω input impedance
(0…20 mA)
Actuator force: 1000 N + 30% - 20%
Stroke: 20 mm maximum; 8, 10, 13, 19 mm selectable
Nominal speed at 50 Hz (60 Hz): 4 (3.2) s / mm
Enclosure protection: IP 42 (EN 60529)
Materials:
Enclosure: Self extinguishing VO-UL 94 ABS + PC
Hand wheel: Self extinguishing nylon PA
Yoke: Die cast aluminium
Ambient Operating condition: -5 to +55, °C, non condensing
Ambient Storage condition: -20 to +65 °C, non condensing
Electrical connections: 2.5 mm2 2.5 mm2 1.5 mm2
Net weight: 1.0 kg
Compliance: EMC directive 89/336 EEC: EN 61000-6-2, EN 61000-6-3
The performance specifications are nominal and conform to acceptable industrial standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
Johnson Controls International, Inc.
Headquarters: Milwaukee, Wisconsin, USA
European Customer Service Center: Westendhof 3, D-45143 Essen, Germany
European Factories: Essen (Germany), Leeuwarden (The Netherlands) and Lomagna (Italy)
Branch Offices Principal European Cities.
E11